4
Blindtext SlimVent. Plate and cased axial fans SPW & SCW. Metal impeller with a slim motor profile. – Simplified range. – Metal impellers. – Available off the shelf. – Thermal protection of motor. – Compact motor design. – Speed controllable. so refreshing 26.11.04 / K. Neumann
Transcript
Page 1: SPW SCW GB 1204 · 3 SlimVent plate and cased axial fans SPW & SCW 26.11.04 / K. Neumann ∆p stat. Pa ρ= 1.20 kg/m3 315 355 400 2) Cased fans on this size below 30 Pa have an increased

Blindtext

SlimVent.Plate and cased axial fans SPW & SCW.Metal impeller with a slim motor profile.

– Simplified range.– Metal impellers.– Available off the shelf.– Thermal protection of motor.– Compact motor design.– Speed controllable.

so refreshing26.11.04 / K. Neumann

Page 2: SPW SCW GB 1204 · 3 SlimVent plate and cased axial fans SPW & SCW 26.11.04 / K. Neumann ∆p stat. Pa ρ= 1.20 kg/m3 315 355 400 2) Cased fans on this size below 30 Pa have an increased

26.11.04 / K. Neumann

SlimVent plate and cased axial fans SPW & SCW

2

■ Specification SPW

■■ CasingManufactured in mild steel andcoated in epoxy paint – colourRAL 9010 white.

■■ ImpellerAll models have dynamicallybalanced metal impellers for highefficiency and low noise levels.The blades are manufactured inmild steel for sizes up to 500mm and in cast aluminium forsizes 560 and 630. The hub iscast aluminium and suitable for– 30 °C to + 70 °C. The finish forsizes up to 450 is black paint,with sizes 500 to 630 in naturalaluminium.

■■ MotorExternal rotor motor with a die-cast aluminium casing, protectedto IP 54. Thermal contacts formotor protection and radiosuppression. Sealed for life ballbearings lubricated for tempera-tures from – 30 °C up to + 70 °C.

■■ Motor protectionAll models are fitted with thermalcontacts as standard whichshould be connected to a motorprotection unit (see below).The automatic resetting thermalcontacts can be used wired in

series with the motor windingsexcept the 630 size where theymust be wired into a suitableprotection unit to be effective.

■■ Electrical connectionThe plate fans have theterminals in the terminal boxfitted to the rear of the motor.

■■ GuardSPW models have motor sidewire guard fitted as standard toEN 294. Coated in epoxy paint –colour black.

■■ Speed control All models are speed controllablewith matched 5 step auto trans-former and electronic speedcontrollers listed in thetable below.

■■ InstallationCompact fan design for easyinstallation able to be installedat any angle or position.

■■ DimensionsAll dimensions shown in thetable are in millimeters.

■■ Sound levelsThe sound levels are ’A’ scaleweighted levels LWA and LPW.

■ Specification SCW

■■ CasingManufactured in mild steel andcoated in epoxy paint – colourRAL 7032 (mushroom) grey.

■■ ImpellerAll models have dynamicallybalanced metal impellers for highefficiency and low noise levels.The blades are manufactured inmild steel for sizes up to 500mm and in cast aluminium forsizes 560 and 630. The hub iscast aluminium and suitable for– 30 °C to + 70 °C. The finish forsizes up to 450 is black paint,with sizes 500 to 630 in naturalaluminium.

■■ MotorExternal rotor motor with a die-cast aluminium casing, protectedto IP 54. Thermal contacts formotor protection and radiosuppression. Sealed for life ballbearings lubricated for tempera-tures from – 30 °C up to + 70 °C.

■■ Motor protectionAll models are fitted with thermalcontacts as standard whichshould be connected to a motorprotection unit (see below).The automatic resetting thermalcontacts can be used wired in

series with the motor windingsexcept the 630 size where theymust be wired into a suitableprotection unit to be effective.

■■ Electrical connectionThe cased fans have theterminals in the IP 55 terminalbox fitted on the casing.

■■ GuardSCW models are supplied with-out guard. Guards are availlableas an accessory to fix on the fanflange.

■■ Speed control All models are speed controllablewith matched 5 step auto trans-former and electronic speedcontrollers listed in the tablebelow.

■■ InstallationCompact fan design for easyinstallation able to be installedat any angle or position.

■■ DimensionsAll dimensions shown in thetable are in millimeters.

■■ Sound levelsThe sound levels are ’A’ scaleweighted levels LWA and LPW.

SPW SCW

Size Model Number Motor Amps Wiring Maximum air Protection Speed controller Speed controller Starter with fullPlate Cased of poles Watts Diagram flow temp. to 5 step transformer electronic motor protection

mm Type Ref. No. Type Ref. No. kW A No. + °C IP Type Ref. No. Type Ref. No. Type Ref. No.

315 SPW 315/4 7849 SCW 315/4 7856 4 0.14 0.65 848 70 54 TSW 1.5 1495 ESA 1 0238 MW 1579

355 SPW 355/4 7850 SCW 355/4 7857 4 0.22 0.95 848 70 54 TSW 1.5 1495 ESA 1 0238 MW 1579

400 SPW 400/4 7851 SCW 400/4 7858 4 0.32 1.40 848 50 54 TSW 1.5 1495 ESA 3 IND 7806 MW 1579

450 SPW 450/4 7852 SCW 450/4 7859 4 0.34 1.48 848 55 54 TSW 3.0 1496 ESA 3 IND 7806 MW 1579

500 SPW 500/4 7853 SCW 500/4 7860 4 0.67 3.30 848 60 54 TSW 5.0 1497 ESA 6 IND 7807 MW 1579

560 SPW 560/4 7854 SCW 560/4 7861 4 1.35 6.00 848 60 54 TSW 7.5 1596 ESA 10 IND 7808 MW 1579

630 SPW 630/41) 7855 SCW 630/41) 7862 4 2.50 10.5 848 40 54 TSW 121) 1493 — — MW 1579

■ Technical Data

1) The 630 mm fans must be wired to a Helios MW unit to provide thermal motor protection.

Page 3: SPW SCW GB 1204 · 3 SlimVent plate and cased axial fans SPW & SCW 26.11.04 / K. Neumann ∆p stat. Pa ρ= 1.20 kg/m3 315 355 400 2) Cased fans on this size below 30 Pa have an increased

3

SlimVent plate and cased axial fans SPW & SCW

26.11.04 / K. Neumann

∆pstat.Pa

ρ = 1.20 kg/m3

315

355

400

2) Cased fans on this size below 30 Pa have an increased noise level and care should be taken when selecting for these pressures.

V· m3/h

315 to 400

Sound pressure at 4 mSound power levels

Dimensions in mm

SPW

Dimensions in mm

SCW

Size A B C D E F G H [KG]

315 317 345 82 85.5 3.5 430 380 9 5.5

355 358 386 86 77 20 485 435 9 7.0

400 403 488 88 96 0 540 490 9 9.0

450 452 548 100 96 10.5 575 535 11 10.0

500 504 538 150 30.5 37 655 615 11 20.0

560 560 694 120 35 56 725 675 11 30.0

630 636 680 150 45 75 805 750 11 35.0

Size A B C D E F G H [KG]

315 317 382 0 130 221 356 8 7.0 5.0

355 358 421 6.0 135 240 395 12 7.0 6.5

400 403 466 7.5 155 262 438 12 7.0 8.5

450 452 515 0 160 287 487 12 7.0 9.0

500 504 567 7.0 165 312 541 12 7.0 18.0

560 562 635 0 210 343 605 16 11.5 28.0

630 635 709 13.0 220 380 674 16 11.5 33.0

■ Dimensions SCW

■ Dimensions SPW

Size Model Air volume flow m3/s against static pressure PaPlate Cased

mm 0 20 40 50 60 80 100 120 140 160 180 200 220

315 SPW 315/4 SCW 315/4 0.7502) 0.6882) 0.611 0.554 0.511

355 SPW 355/4 SCW 355/4 1.0282) 0.9582) 0.875 0.833 0.783

400 SPW 400/4 SCW 400/4 1.375 1.292 1.208 1.153 1.097 0.958 0.799

450 SPW 450/4 SCW 450/4 1.509 1.426 1.341 1.290 1.239 1.111 0.958 0.792

500 SPW 500/4 SCW 500/4 2.264 2.161 2.044 1.992 1.931 1.806 1.653 1.444 1.111

560 SPW 560/4 SCW 560/4 3.819 3.078 3.583 3.514 3.444 3.306 3.161 2.979 2.778 2.500

630 SPW 630/4 SCW 630/4 5.261 5.139 5.014 4.949 4.883 4.722 4.556 4.344 4.111 3.833 3.611 3.361 3.089

■ Selection Table

∆pstat.Pa

ρ = 1.20 kg/m3

V· m3/h

450 to 630

500

560

630

450

LWA FrequencyDia. Hz Total 63 125 250 500 1k 2k 4k315 Air noise dB(A) 68 38 50 53 58 62 62 53355 Air noise dB(A) 71 41 53 56 61 65 65 56400 Air noise dB(A) 70 40 52 55 60 64 64 55450 Air noise dB(A) 70 40 52 55 60 64 64 55500 Air noise dB(A) 75 45 57 60 65 69 69 60560 Air noise dB(A) 83 53 65 68 73 77 77 68630 Air noise dB(A) 88 58 70 73 78 82 82 73

LPA FrequencyDia. Hz Total 63 125 250 500 1k 2k 4k315 Air noise dB(A) 48 18 30 33 38 42 42 33355 Air noise dB(A) 51 21 33 36 41 45 45 36400 Air noise dB(A) 50 20 32 35 40 44 44 35450 Air noise dB(A) 50 20 32 35 40 44 44 35500 Air noise dB(A) 55 25 37 30 45 49 49 40560 Air noise dB(A) 63 23 45 48 53 57 57 48630 Air noise dB(A) 68 38 50 53 58 62 62 53

Page 4: SPW SCW GB 1204 · 3 SlimVent plate and cased axial fans SPW & SCW 26.11.04 / K. Neumann ∆p stat. Pa ρ= 1.20 kg/m3 315 355 400 2) Cased fans on this size below 30 Pa have an increased

ESA 1

Electronic speed controllerESA..IND for surface mountingWhite polymer casing with a bluealuminium anodised face and anilluminated on off switch.Fully variable speed control 10-100 % with built in fuse and anadjustable lowest speed.

Supply 230 V / 1 ph. / 50 HzProtection IP 65

FMFR

5 Step transformer speedcontroller TSW for surfacemountingFive step auto transformer speedcontroller with outputs of 80 / 100 /130 / 170 and 230 volts for 5 fanspeeds (performances). RobustISO casing made from light grey,impact resistant polymers.Supply 230 V / 1 ph. / 50 HzProtection IP 54.

Note: Ducting systemAll HELIOS components fit standard nominal duct dia-meters. The ducting used maybe rigid or flexible and madefrom aluminium, galvanisedsteel or plastic.

RDS

Mounting feet MKTo fix Axial cased fans to ceiling,wall or floor. Made from hot dippedgalvanised steel. Fixing holes fit casing flanges. Supplied as a set including a pairof feet, nuts and bolts.

MK

Flange FRSpigotted flange made of galvani-sed steel. Dimensions and holes tomatch the fans and accessories toDIN 24155, Pt 2.

Anti vibration mounts SDD 1.5for compression.To reduce noise and vibrationtransmission of fans installed onhorizontal surfaces.Easy installation in combinationwith feet MK (accessory).The SDD 1.5 is suitable for the complete range of SCW casedfans from 315 to 630 mm.Anti vibration mounts with rubberelements are suitable for use in am-bient temperatures up to + 60 °C.

Electronic speed controllerESA 1White polymer casing.Operation display via illuminatedring in control knob.Infinitely variable speed control 10-100 % with built in fuse and anadjustable lowest speed.

Supply 230 V / 1 ph. / 50 HzProtection IP 40

Wiring Diagram No. SS-556.1

Circular silencer RDSfor direct connection to cased(SCW) axial fansCasing made of galvanised sheetsteel, acoustically lined with highquality mineral wool covered witha cloth on the face to preventerosion. Supplied with tappedholes in the flanges to match thefan and matching flange hole drillings.

Helios Ventilation Systems Ltd. • 5 Crown Gate • Wyncolls Road • Severalls Industrial Park • Colchester • Essex • CO4 9HZTelephone: 01206 228500 • Telefax: 01206 228501 • E-mail: [email protected] • www.heliosfans.co.uk

Published by ©: Helios Ventilation Systems Ltd. We reserve the rights for alterations without prior notice. Document no. 90 505 / 12.04

SDD 1.5

Type Ref. No.

MK 315-355 1448

MK 400-450 1449

MK 500-560 1450

MK 630 1333

Type Ref. No.

FR 315 1204

FR 355 1205

FR 400 1206

FR 450 1207

FR 500 1208

FR 560 1209

FR 630 1211

Type Ref. No.

FM 315 1674

FM 355 1675

FM 400 1676

FM 450 1677

FM 500 1678

FM 560 1679

FM 630 1680

Type Max. fan Bolt Fixing mmwt. kg size hole centers

SDD 1.5 50 M8 9 65

Flexible sleeve FM (shown withflanges) consists of a silicon freepolymer fabric cloth (max. temp+ 80 °C). Flexible connector to befitted on to FR flanges between fanand ducting to reduce vibrationtransmission. Dimensions to DIN24155, Pt. 2.

TSW

Type Ref. I max. Dim. in mmNo. A W H D

ESA 1 0238 1.0 80 80 65

Wiring Diagram No. SS-710

Type Ref. I max. Dim. in mmNo. A W H D

ESA 3 IND 7806 3.0 111 99 59

ESA 6 IND 7807 6.0 145 97 64

ESA 10 IND 7808 10.0 104 146 83

ESA..IND

Wiring Diagram No. SS-437.1

Type Ref. I max. Dim. in mmNo. A W H D

TSW 1.5 1495 1.5 154 200 79

TSW 3.0 1496 3.0 154 200 148

TSW 5.0 1497 5.0 200 254 167

TSW 7.5 1596 7.5 200 254 167

TSW 10 1498 10.0 200 254 167

TSW 12 1493 12.0 236 316 188

Type Ref. Nom. mmNo. dia. long O/D

RSD 315/800 8744 315 800 504

RSD 355/800 8747 355 800 564

RSD 400/800 8750 400 800 564

RSD 450/800 8756 450 800 634

RSD 500/600 8755 500 600 714

RSD 560/600 8758 560 600 804

RSD 630/600 8744 630 800 900


Recommended