CDP-STAT-01 Fuel Cell Stationary Systems Deployed by Year
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
50
100
150
200
250
300
Proj
ect C
ount
Cumulative Deployment Count by Year*
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
100
200
300
400
Total = 397 unitsFuel Cell CHP = 118 unitsFuel Cell Electric = 279 units
Proj
ect C
ount
Tot
al
Fuel Cell CHPFuel Cell ElectricTotal
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
50
100
150
Cap
acity
[MW
]
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
50
100
150
200
Total = 161 MWFuel Cell CHP = 35 MWFuel Cell Electric = 126 MW
Tota
l Cap
acity
[MW
]
Cumulative Capacity by Year
Fuel Cell CHPFuel Cell ElectricTotal
NREL cdp_stat_01Created: Apr-21-15 11:09 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.
3
CDP-STAT-02 Stationary Fuel Cell System Count by Status
9%
21%
3%
15%
52%
Stationary Fuel Cell Deployment Count By Status*
Order of Project Phases: [1] Includes CA SGIP projects in Reservation Request Form (RRF) phases.[2] Includes CA SGIP projects in Proof of Project Milestone (PPM) phases.[3] Projects are in operation and pending confirmation of incentive claims, including CA SGIP Incentive Claim Form (ICF) phases.[4] Includes projects that are receiving perfomance based incentives, includes CA SGIP Performance Based Incentives (PBI) In Progress.[5] Includes installed projects with unknown operation status, includes CA SGIP Payment Completed and Payment Recalled status.
Application Review [1]Project Execution Review [2]Incentive Claim Review [3]Project In Operation [4]Project Completed [5]
NREL cdp_stat_02Created: Apr-21-15 11:09 AM | Data Range: 2001Q2-2014Q4
70% of projects havebeen installed [3-5].
*Data from the CA SGIP.
4
CDP-STAT-03 California SGIP Deployment Map
CA Stationary Fuel Cell Installations [1] (2001 - 2014)
Application Review [1]Project Execution Review [2]Incentive Claim Review [3]Project In Operation [4]Project Completed [5]
NREL cdp_stat_03Created: Apr-21-15 11:09 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.
Order of Project Phases: [1] Includes CA SGIP projects in Reservation Request Form (RRF) phases.[2] Includes CA SGIP projects in Proof of Project Milestone (PPM) phases.[3] Projects are in operation and pending confirmation of incentive claims, including CA SGIP Incentive Claim Form (ICF) phases.[4] Includes projects that are receiving perfomance based incentives, includes CA SGIP Performance Based Incentives (PBI) In Progress.[5] Includes installed projects with unknown operation status, includes CA SGIP Payment Completed and Payment Recalled status.
5
CDP-STAT-04 Stationary Fuel Cell System Count and Capacity by Fuel Type
4%9%
9%
79%
Site Count by Fuel Type*
Biomass [1]
Digester Gas [1]
Landfill Gas [1]
Natural Gas
3%
17%
11%
69%
Installed Capacity by Fuel Type
NREL cdp_stat_04Created: Apr-21-15 11:12 AM | Data Range: 2001Q2-2014Q4
Includes Status Categories:Application Review [2]Project Execution Review [3]Incentive Claim Review [4]Project In Operation [5]Project Completed [6]
Total Capacity: 161 MWTotal Sites: 397
Installations by Fuel Type(All Fuel Cell Systems)
[1] The renewable fuels exclude those defined as conventional in Section 2805 of the California Public Utilities Code and are categorizedhere as gas derived from biomass, digester gas, or landfill gas.Definition of Included Status: [2] Includes CA SGIP projects in Reservation Request Form (RRF) phases.[3] Includes CA SGIP projects in Proof of Project Milestone (PPM) phases.[4] Projects are in operation and pending confirmation of incentive claims, including CA SGIP Incentive Claim Form (ICF) phases.[5] Includes projects that are receiving perfomance based incentives, includes CA SGIP Performance Based Incentives (PBI) In Progress.[6] Includes installed projects with unknown operation status, includes CA SGIP Payment Completed and Payment Recalled status.
*Data from the CA SGIP.
6
CDP-STAT-05 Fuel Type Capacity
Biomass Digester Gas Landfill Gas Natural Gas200
300
400
500
600
700
800
900
1000
Inst
alle
d C
apac
ity (k
W)
Stationary Fuel Cell - Installation Capacity Statistics by Fuel Type[1]*
NREL cdp_stat_05Created: Apr-21-15 11:13 AM | Data Range: 2001Q2-2014Q4
75% Percentile
Median
25% Percentile
Mean
Insufficientdata toprotect
anonymity
[1] The renewable fuels exclude those defined as conventional in Section 2805 of the California PublicUtilities Code and are categorized here as gas derived from biomass, digester gas, or landfill gas.
*Data from the CA SGIP.
7
CDP-STAT-06 Fuel Cell Stationary Capacity and Average Prices
0 200 400 600 800 1000 1200 1400 >1400(max 4200)0
10
20
30
40Stationary Fuel Cell - Distribution of Capacity and Average Eligible Cost $2010/kW*
Capacity (kW)
% o
f sys
tem
s
0 200 400 600 800 1000 1200 1400 >1400(max 4200)0
2,000
4,000
6,000
8,000
10,000
12,000
Ave
rage
$/k
W(A
djus
ted
to 2
010
dolla
rs)
$/kW w/o Incentive$/kW w/ Incentive2020 DOE Target†
0 200 400 600 800 1000 1200 1400 >1400(max 4200)0
10
20
30
Capacity (kW)
% o
f sys
tem
s
Detailed Capacity Distribution
0 10 20 30 40 50 60 70 80 90100110
Num
ber o
f sys
tem
s
0 10 20 30 40 500
20406080
Capacity (kW)%
of s
yste
ms
<=50
kW
NREL cdp_stat_06Created: Apr-21-15 11:13 AM | Data Range: 2001Q2-2014Q4
†installed cost for the year 2020, operatingon natural gas. May not include all costsreported in CA SGIP.
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
8
CDP-STAT-07 Distribution of Stationary Fuel Cell Install Price with and without Incentives
0
20
40
60
0
1000
20
00
3000
40
00
5000
60
00
7000
80
00
9000
1000
011
000
1200
013
000
1400
015
000
1600
017
000
1800
019
000
2000
021
000
proj
ect c
ount
Price without incentives [$2010/kW]
Stationary Fuel Cell - Installed Eligible Cost Per kW*Adjusted To 2010 Dollars
Avg** = $10,429 $/kW
CurrentDOE 2020 Target†Mean without Incentives 1 ($2,506)
0
20
40
60
0
1000
20
00
3000
40
00
5000
60
00
7000
80
00
9000
1000
011
000
1200
013
000
1400
015
000
1600
017
000
1800
019
000
2000
021
000
proj
ect c
ount
Price with incentives [$2010/kW]
Avg** = $6,929 $/kW
CurrentDOE 2020 Target†Mean with Incentives 1 ($2,736)
NREL cdp_stat_07Created: Apr-21-15 11:13 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
**Data bins with less than 2projects filtered.†installed cost for the year 2020,operating on natural gas. May notinclude all costs reported in CA SGIP.
9
CDP-STAT-08 Stationary Fuel Cell Install Price Over Time with and without Incentives
2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
5
10
15
Ave
rage
$20
10/W
of In
stal
led
Cap
acity
Stationary Fuel Cell - Average Eligible Cost $2010/W Trend for Overall Deployments*
Without IncentiveWith IncentiveDOE 2020 Target†
0
5
10
15
200220
0320
0420
0520
0620
0720
0820
0920
1020
1120
1220
1320
14
Capacity < 500 kW
Ave
rage
$20
10/W
of In
stal
led
Cap
acity
0
5
10
15
200220
0320
0420
0520
0620
0720
0820
0920
1020
1120
1220
1320
14
500 kW <= Capacity < 1000 kW
0
5
10
15
200220
0320
0420
0520
0620
0720
0820
0920
1020
1120
1220
1320
14
Capacity >= 1000 kW
NREL cdp_stat_08Created: Apr-21-15 11:35 AM | Data Range: 2001Q2-2014Q4
Note: Data points are omitted where only onesystem would be represented in a given year.†installed cost for the year 2020, operating on naturalgas. May not include all costs reported in CA SGIP.
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-GenerationEquipment, Waste Heat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection,Warranty, Maintenance Contract, Metering, Monitoring & Data Acquisition System, Emission Control EquipmentCapital, Gasline Installation, Fuel Gas Clean-up Equipment, Electricity Storage Devices, Bond to CertifyRenewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering, etc.), Thermal Load, & Other Eligible Costs
10
CDP-STAT-09 Stationary Fuel Cell Install Price by Fuel Type with and without Incentives
Biomass Digester Gas Landfill Gas Natural Gas
4000
6000
8000
10000
12000
$201
0/kW
of In
stal
led
Cap
acity
Stationary Fuel Cell - Eligible Cost $2010/kW of Installed Capacity by Fuel Type*
Avg. Without IncentiveAvg. With Incentive
NREL cdp_stat_09Created: Apr-21-15 11:15 AM | Data Range: 2001Q2-2014Q4
75% Percentile
Median
25% Percentile
Mean
Note: Refer to CA SGIPHandbook for on-site vsdirected digester gas (biogas)qualifications.
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
11
CDP-STAT-10 Installed Capacity and Fuel Type
0 200 400 600 800 1000 >10000
10
20
30
40
50
60
70
System Size (kW)
Tota
l Ins
talle
d C
apac
ity (M
W)
Stationary Fuel Cell - Installed Capacity And Fuel Type*
BiomassDigester GasLandfill GasNatural Gas
NREL cdp_stat_10Created: Apr-21-15 11:15 AM | Data Range: 2001Q2-2014Q4
Note: Refer to CA SGIP Handbookfor on-site vs directed digester gas(biogas) qualifications.
*Data from the CA SGIP.
12
CDP-STAT-11 Total Incentive Spending ($2010) per kW by Year
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
20
40
60
80
100
120
140
160
180
Cum
ulat
ive
Cap
acity
[MW
]
Year1500
2000
2500
3000
3500
4000
4500
5000
5500
Ince
ntiv
e Sp
endi
ng ($
2010
) Per
kW
Inst
alle
d
Stationary Fuel Cell - Total Incentive ($2010) per kW by Year*
NREL cdp_stat_11Created: Apr-21-15 11:16 AM | Data Range: 2001Q2-2014Q4
In 2014 incentive rates for emerging technologies(including fuel cells) and biogas will decline 10% and allother technologies 5% annually. (2014 SGIP Handbook)
*Data from the CA SGIP.
13
CDP-STAT-12 Average System Size Installed Per Year (kW)
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
100
200
300
400
500
600
700
800
Ave
rage
Sys
tem
Siz
e In
stal
led
Per Y
ear (
kW)
Year
Stationary Fuel Cell - Average System Size Installed Per Year (kW)*
Overall Average Capacity = 460 kW
NREL cdp_stat_12Created: Apr-21-15 11:16 AM | Data Range: 2001Q2-2014Q4 *Data from the CA SGIP.
14
CDP-STAT-13 Installed Annual Capacity by Fuel Type
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
10
20
30
40
50
60
Year
Tota
l Ann
ual I
nsta
lled
Cap
acity
(MW
)
Stationary Fuel Cell - Installed Fuel Type By Year*
BiomassDigester GasLandfill GasNatural Gas
NREL cdp_stat_13Created: Apr-21-15 11:16 AM | Data Range: 2001Q2-2014Q4 Note: Refer to CA SGIP Handbook for on-site vs
directed digester gas (biogas) qualifications.
*Data from the CA SGIP.
15
CDP-STAT-14 Distribution of Capacity by Equipment Type
0 200 400 600 800 1000 1200 1400 1600 1800 2000 >20000
50
100
150
200
250Distribution of Capacity by Equipment Type*
Capacity (kW)
Tota
l # o
f Sys
tem
s
Fuel Cell CHPFuel Cell ElectricGas TurbineInternal CombustionMicroturbine
NREL cdp_stat_14Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
(max 9200)*Data from the CA SGIP.
16
CDP-STAT-15 Average Eligible Cost by Equipment Type, including Other Distributed Generation
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
5
10
15
Ave
rage
$20
10/W
of In
stal
led
Cap
acity
Average Eligible Cost $2010/W Trend for Overall Deployments*Without Incentives
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
5
10
15
Ave
rage
$20
10/W
of In
stal
led
Cap
acity
Average Eligible Cost $2010/W Trend for Overall Deployments*With Incentives
Fuel Cell CHPFuel Cell ElectricGas TurbineInternal CombustionMicroturbine
Fuel Cell CHPFuel Cell ElectricGas TurbineInternal CombustionMicroturbine
NREL cdp_stat_15Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4 *Data from the CA SGIP.
Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, Waste HeatRecovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract, Metering, Monitoring& Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-up Equipment, Electricity StorageDevices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering, etc.), Thermal Load, & Other Eligible Costs
17
CDP-STAT-16 Average Eligible Cost for Biogas Sources
0 200 400 600 800 1000 >10000
2000
4000
6000
8000
10000
12000
Stationary Fuel Cell - Average Eligible Cost $2010/kW Biogas Source*Without Incentives
System Size (kW)
$201
0/kW
of In
stal
led
Cap
acity
Directed**Onsite**
0 200 400 600 800 1000 >10000
2000
4000
6000
8000
Stationary Fuel Cell - Average Eligible Cost $2010/kW Biogas Source*With Incentives
System Size (kW)
$201
0/kW
of In
stal
led
Cap
acity
Directed**Onsite**
NREL cdp_stat_16Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
(max 4200)
(max 4200)
** Refer to CA SGIP Handbook for on-site vsdirected digester gas (biogas) qualifications.
*Data from the CA SGIP.
Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-GenerationEquipment, Waste Heat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty,Maintenance Contract, Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital,Gasline Installation, Fuel Gas Clean-up Equipment, Electricity Storage Devices, Bond to Certify Renewable Fuel,Sales Tax, Fuel Supply (digesters, gas gathering, etc.), Thermal Load, & Other Eligible Costs
18
CDP-STAT-17 Mean Time Between Stoppage (for any reason) for Units <100 kW
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 140000
5
10
15
20
25
30
35
% o
f Uni
ts
Mean Time (hr) between Stoppages
Stationary Fuel Cell - Mean Time Between Stoppage (hours)*
NREL cdp_stat_17Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
Overall Mean = 2407 hours
* Voluntarily supplied data
Units <100 kW
19
CDP-STAT-18 Mean Unit Lifetime Electrical Efficiency (%HHV) for Units <100 kW
10 15 20 25 30 35 40 45 50 55 600
5
10
15
20
25
30
35
40
45
% o
f Uni
ts
Mean Unit Electrical Efficiency (% HHV)
Stationary Fuel Cell - Unit Lifetime Mean Electrical Efficiency (HHV)*†
NREL cdp_stat_18Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
Overall Mean = 28 %
Units <100 kW
* Voluntarily supplied data†Includes startup, shutdown, transient andpartial power operation
20
CDP-STAT-19 Mean Unit Lifetime Availability for Units <100 kW
40 45 50 55 60 65 70 75 80 85 90 95 1000
5
10
15
20
25
30
35
40
% o
f Uni
ts
Mean Unit Availability (%)
Stationary Fuel Cell - Unit Mean Availability*
NREL cdp_stat_19Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
Overall Mean = 92 %
* Voluntarily supplied data
Units <100 kW
21
CDP-STAT-20 Installations By Fuel Type (CHP Fuel Cells)
8%
4%
87%
Site Count by Fuel Type*
Digester Gas [1]
Landfill Gas [1]
Natural Gas
30%
10%
60%
Installed Capacity by Fuel Type
NREL cdp_stat_20Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
Includes Status Categories:Application Review [2]Project Execution Review [3]Incentive Claim Review [4]Project In Operation [5]Project Completed [6]
Total Capacity: 35 MWTotal Sites: 118
Installations by Fuel Type(CHP Fuel Cell Systems)
[1] The renewable fuels exclude those defined as conventional in Section 2805 of the California Public Utilities Code and are categorizedhere as gas derived from biomass, digester gas, or landfill gas.Definition of Included Status: [2] Includes CA SGIP projects in Reservation Request Form (RRF) phases.[3] Includes CA SGIP projects in Proof of Project Milestone (PPM) phases.[4] Projects are in operation and pending confirmation of incentive claims, including CA SGIP Incentive Claim Form (ICF) phases.[5] Includes projects that are receiving perfomance based incentives, includes CA SGIP Performance Based Incentives (PBI) In Progress.[6] Includes installed projects with unknown operation status, includes CA SGIP Payment Completed and Payment Recalled status.
*Data from the CA SGIP.
22
CDP-STAT-21 Installation Capacity by Fuel Type (CHP Fuel Cells)
Digester Gas Landfill Gas Natural Gas0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
Inst
alle
d C
apac
ity (k
W)
Installation Capacity Statistics by Fuel Type[1] (CHP Fuel Cell)*
NREL cdp_stat_21Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
75% Percentile
Median
25% Percentile
Mean
Insufficientdata toprotect
anonymity
[1] The renewable fuels exclude those defined as conventional in Section 2805 of the California PublicUtilities Code and are categorized here as gas derived from biomass, digester gas, or landfill gas.
*Data from the CA SGIP.
23
CDP-STAT-22 Distribution of Capacity and Eligible Cost (CHP Fuel Cells)
0 200 400 600 800 1000 1200 1400 >1400(max 2800)0
10
20
30
40
50
60
70Distribution of Capacity and Average Eligible Cost $2010/kW (CHP Fuel Cell)*
Capacity (kW)
% o
f sys
tem
s
0 200 400 600 800 1000 1200 1400 >1400(max 2800)0
2,000
4,000
6,000
8,000
10,000
12,000
Ave
rage
$/k
W(A
djus
ted
to 2
010
dolla
rs)
$/kW w/o Incentive$/kW w/ Incentive2020 DOE Target†
0 200 400 600 800 1000 1200 1400 >1400(max 2800)0
10
20
30
40
50
Capacity (kW)
% o
f sys
tem
s
Detailed Capacity Distribution
01020304050
Num
ber o
f sys
tem
s
0 10 20 30 40 500
20406080
Capacity (kW)%
of s
yste
ms
<=50
kW
NREL cdp_stat_22Created: Apr-21-15 11:17 AM | Data Range: 2001Q2-2014Q4
†installed cost for the year 2020, operatingon natural gas. May not include all costsreported in CA SGIP.
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
24
CDP-STAT-23 Distribution of Eligible Cost with and without Incentives (CHP Fuel Cells)
0
10
20
30
0
1000
20
00
3000
40
00
5000
60
00
7000
80
00
9000
1000
011
000
1200
013
000
1400
015
000
1600
017
000
1800
019
000
2000
021
000
proj
ect c
ount
Price without incentives [$2010/kW]
Installed Eligible Cost Per kW (CHP Fuel Cell)*Adjusted To 2010 Dollars
Avg** = $10,408 $/kW
CurrentDOE 2020 Target†Mean without Incentives 1 ($3,065)
0
10
20
30
40
0
1000
20
00
3000
40
00
5000
60
00
7000
80
00
9000
1000
011
000
1200
013
000
1400
015
000
1600
017
000
1800
019
000
2000
021
000
proj
ect c
ount
Price with incentives [$2010/kW]
Avg** = $7,545 $/kW
CurrentDOE 2020 Target†Mean with Incentives 1 ($3,224)
NREL cdp_stat_23Created: Apr-21-15 11:18 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
**Data bins with less than 2projects filtered.†installed cost for the year 2020,operating on natural gas. May notinclude all costs reported in CA SGIP.
25
CDP-STAT-24 Eligible Cost By Fuel Type with and without Incentives (CHP Fuel Cells)
Digester Gas Landfill Gas Natural Gas
2000
4000
6000
8000
10000
12000
$201
0/kW
of In
stal
led
Cap
acity
Eligible Cost $2010/kW of Installed Capacity by Fuel Type (CHP Fuel Cell)*
Avg. Without IncentiveAvg. With Incentive
NREL cdp_stat_24Created: Apr-21-15 11:19 AM | Data Range: 2001Q2-2014Q4
75% Percentile
Median
25% Percentile
Mean
Note: Refer to CA SGIPHandbook for on-site vsdirected digester gas (biogas)qualifications.
*Data from the CA SGIP.Eligible Costs May Include: Planning & Feasibility Study, Engineering & Design, Permitting, Self-Generation Equipment, WasteHeat Recovery Costs, Construction & Installation Costs, Gas & Electric Interconnection, Warranty, Maintenance Contract,Metering, Monitoring & Data Acquisition System, Emission Control Equipment Capital, Gasline Installation, Fuel Gas Clean-upEquipment, Electricity Storage Devices, Bond to Certify Renewable Fuel, Sales Tax, Fuel Supply (digesters, gas gathering,etc.), Thermal Load, & Other Eligible Costs
26
CDP-STAT-25 Cumulative Deployment Count by Category and Year
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
50
100
150
200
250
300
Proj
ect C
ount
Cumulative Deployment Count by Category and Year*
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
500
1000
1500
2000
Total = 1947 unitsFuel Cell CHP = 118 unitsFuel Cell Electric = 279 unitsGas Turbine = 15 unitsInternal Combustion = 279 unitsMicroturbine = 159 unitsPressure Reduction Turbine = 3 units
Proj
ect C
ount
Tot
al
Fuel Cell CHPFuel Cell ElectricGas TurbineInternal CombustionMicroturbinePressure Reduction TurbineTotal
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
50
100
150
200
Cap
acity
[MW
]
2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 20140
100
200
300
400
500
600
Total = 534 MWFuel Cell CHP = 35 MWFuel Cell Electric = 126 MWGas Turbine = 53 MWInternal Combustion = 178 MWMicroturbine = 38 MWPressure Reduction Turbine = 1 MW
Tota
l Cap
acity
[MW
]
Cumulative Capacity by Category and Year
Fuel Cell CHPFuel Cell ElectricGas TurbineInternal CombustionMicroturbinePressure Reduction TurbineTotal
NREL cdp_stat_25Created: Apr-21-15 11:19 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.
27
CDP-STAT-26 Installed Eligible Cost per kW By Capacity
0
10
20
30
Average Prices No Incentive, Incentive0-50 kW = $11,275/kW, $8,782/kWAverage Prices No Incentive, Incentive
51-200 kW = $10,927/kW, $6,715/kW
Average Prices No Incentive, Incentive
201-400 kW = $10,022/kW, $6,220/kW
Average Prices No Incentive, Incentive
401+ kW = $9,537/kW, $5,620/kWData points with less than 2 projects filtered.
0 10
00 20
00 30
00 40
00 50
00 60
00 70
00 80
00 90
00
1000
011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
000
proj
ect c
ount
Price [$2010/kW] No Incentive
Stationary Fuel Cell - Installed Eligible Cost Per kW By Capacity*Adjusted To 2010 Dollars
0-50kW
51-200 kW
201-400 kW
>400 kW
DOE 2020 Target†
0
10
20
30
0 10
00 20
00 30
00 40
00 50
00 60
00 70
00 80
00 90
00
1000
011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
000
proj
ect c
ount
Price [$2010/kW] With IncentiveNREL cdp_stat_26Created: Apr-21-15 11:27 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.
Eligible Costs May Include: Planning & Feasibility Study,Engineering & Design, Permitting, Self-GenerationEquipment, Waste Heat Recovery Costs, Construction &Installation Costs, Gas & Electric Interconnection, Warranty,Maintenance Contract, Metering, Monitoring & DataAcquisition System, Emission Control Equipment Capital,Gasline Installation, Fuel Gas Clean-up Equipment,Electricity Storage Devices, Bond to Certify RenewableFuel, Sales Tax, Fuel Supply (digesters, gas gathering, etc.),Thermal Load, & Other Eligible Costs
†installed cost for the year 2020, operating on naturalgas. May not include all costs reported in CA SGIP.
28
CDP-STAT-27 Installed Eligible Cost per kW By Capacity (CHP Fuel Cell)
0
10
20
30
Average Prices No Incentive, Incentive0-50 kW = $11,303/kW, $8,809/kWAverage Prices No Incentive, Incentive
51-200 kW = $NaN/kW, $NaN/kW
Average Prices No Incentive, Incentive
201-400 kW = $9,165/kW, $5,316/kW
Average Prices No Incentive, Incentive
401+ kW = $7,608/kW, $3,706/kWData points with less than 2 projects filtered.
0 10
00 20
00 30
00 40
00 50
00 60
00 70
00 80
00 90
00
1000
011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
000
proj
ect c
ount
Price [$2010/kW] No Incentive
Installed Eligible Cost Per kW By Capacity (CHP Fuel Cell)*Adjusted To 2010 Dollars
0-50kW
51-200 kW
201-400 kW
>400 kW
DOE 2020 Target†
0
10
20
30
0 10
00 20
00 30
00 40
00 50
00 60
00 70
00 80
00 90
00
1000
011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
000
proj
ect c
ount
Price [$2010/kW] With IncentiveNREL cdp_stat_27Created: Apr-21-15 11:27 AM | Data Range: 2001Q2-2014Q4
*Data from the CA SGIP.
Eligible Costs May Include: Planning & Feasibility Study,Engineering & Design, Permitting, Self-GenerationEquipment, Waste Heat Recovery Costs, Construction &Installation Costs, Gas & Electric Interconnection, Warranty,Maintenance Contract, Metering, Monitoring & DataAcquisition System, Emission Control Equipment Capital,Gasline Installation, Fuel Gas Clean-up Equipment,Electricity Storage Devices, Bond to Certify RenewableFuel, Sales Tax, Fuel Supply (digesters, gas gathering, etc.),Thermal Load, & Other Eligible Costs
†installed cost for the year 2020, operating on naturalgas. May not include all costs reported in CA SGIP.
29
CDP-STAT-28 Range of Installed Eligible Cost per kW Biogas Sources by Capacity
0 200 400 600 800 1000 >10000
3000
6000
9000
12000
15000
18000
System Size (kW)
$201
0/kW
of In
stal
led
Cap
acity
Stationary Fuel Cell - Range of Installed Eligible Cost Per kW Biogas Sources by Capacity*
Biogas Sources with Incentive 25th/75th percentileBiogas Sources without Incentive 25th/75th percentileMean with IncentiveMedian with IncentiveMean without IncentiveMedian without Incentive
NREL cdp_stat_28Created: Apr-21-15 11:19 AM | Data Range: 2001Q2-2014Q4
Insufficientdata toprotect
anonymity
Insufficientdata toprotect
anonymity
*Data from the CA SGIP.
30
CDP-STAT-29 U.S. Deployment Map of Stationary Fuel Cells
USA Stationary Fuel Cell Installations (2001 - 2015)
NREL cdp_stat_29Created: Apr-24-15 11:26 AM | Data Range: 2001Q2-2014Q4
Total Count of Sites in Continental US: 447
Includes CA SGIP data as well as sites supplying voluntary data.
31
CDP-STAT-30 Cumulative Fuel Cell Output of Voluntarily Supplied Data for Units >100 kW
2008Q1 2009Q1 2010Q1 2011Q1 2012Q1 2013Q1 2014Q1 2015Q10
0.5
1
1.5
2
2.5
3
3.5
4
4.5x 105
Calendar
Fuel
Cel
l Cum
ulat
ive
Ener
gy (M
Wh)
Stationary Fuel Cell - Cumulative Fuel Cell Energy Output*
Total MWh: 472,989
NREL cdp_stat_30Created: Apr-24-15 11:46 AM | Data Range: 2001Q2-2014Q4
* Voluntarily supplieddata for units > 100 kW
Units >100 kW
32
CDP-STAT-31 Histogram of Load Fractions for Base Load Units >100 kW
0 10 20 30 40 50 60 70 80 90 100 110 120 Inf0
5
10
15
20
25
30
35
40
45
Load Fraction (%) [2]
Ope
ratio
n Ti
me
(%)
Stationary Fuel Cell - Histogram of Load Fractions (Base Load Units) [1]
NREL cdp_stat_31Created: Apr-24-15 11:37 AM | Data Range: 2001Q2-2014Q4 [1] Voluntarily supplied data for units > 100 kW, fuel cells running as building base load generation
[2] Load fraction is the ratio of electrical output per rated capacity of the fuel cell unit.
Units >100 kW
33
CDP-STAT-32 Histogram of Load Fractions for Load Following Units >100 kW
0 10 20 30 40 50 60 70 80 90 100 110 120 Inf0
5
10
15
20
25
30
Load Fraction (%) [2]
Ope
ratio
n Ti
me
(%)
Stationary Fuel Cell - Histogram of Load Fractions (Load Following Units) [1]
NREL cdp_stat_32Created: Apr-24-15 11:37 AM | Data Range: 2001Q2-2014Q4 [1] Voluntarily supplied data for units > 100 kW, fuel cells running as building load following generation
[2] Load fraction is the ratio of electrical output per rated capacity of the fuel cell unit.
Units >100 kW
34
CDP-STAT-33 Electrical Efficiency by Load Fraction for Units >100 kW
20
25
30
35
40
45
50 75 90 100 110Load Fraction (%) [2]
Mea
n El
ectr
ical
Effi
cien
cy H
HV
(%) [
3]
Stationary Fuel Cell - Electrical Efficiency by Load Fraction [1]
Median25/75th percentileMeanDOE Target Efficiency 2015 (HHV)
NREL cdp_stat_33Created: Apr-24-15 1:19 PM | Data Range: 2001Q2-2014Q4
Units >100 kW
[1] Voluntarily supplied data for units > 100 kW[2] Load fraction is the ratio of electrical output per rated capacity of the fuel cell unit. Efficiency data points for each load fraction are +/- 2% of the target load fraction.[3] Mean efficiencies by unit are calculated as the percentage of electrical power output to higher heating value of fuel input. The natural gas higher heating value used is48.956 MJ/kg and the lower heating value used is 44.294 MJ/kg.