  • CITY OF CHICAGO

    DEPARTMENT OF WATER MANAGEMENT

    STANDARD DETAILS FOR

    WATER MAIN INSTALLATIONS

    PREPARED BY: BUREAU OF ENGINEERING SERVICES

    April, 2009

    City of Chicago Department of Water Management Richard M. Daley John F. Spatz, Jr. Mayor Commissioner

  • This page intentionally left blank.

  • 1

    TABLE OF CONTENTS

    GENERAL DETAILS G-1 PROJECT SIGN G-3 SAMPLE SYBOLOGY LEGEND G-4 (1 OF 2) LEGEND - SYMBOLS G-4 (2 OF 2) LEGEND LINE STYLES

    WATER MAIN DETAILS D-2 FIRE HYDRANT SETTING DETAIL D-3 FIRE HYDRANT INSTALLATION DETAIL FOR VAULTED SIDEWALKS D-5 FIRE HYDRANT DRAIN DETAIL D-6 FIRE HYDRANT SUMP FOR RELOCATED HYDRANTS D-7 COLOR CODE FOR FIRE HYDRANTS D-8 WATER MAIN TRENCH DETAILS D-9 WATER MAIN TRENCH INSULATION DETAIL D-10 WATER MAIN POLYETHYLENE WRAP DETAIL D-11 THRUST RESTRAINT CONCRETE THRUST BLOCK DETAILS D-12 THRUST RESTRAINT RESTRAINED JOINT PIPE D-13 PRECAST VALVE BASIN FOR PIPES UP TO 16-INCH DIAMETER D-14 BRICK MASONRY VALVE BASIN D-16 TYPICAL 1-INCH TO 2-INCH WATER SERVICE D-18 CASING PIPE UNDER RAILROAD TRACK DETAIL D-19 (1 OF 2) WATER MAINS CROSSING OVER SEWERS AND HOUSE DRAINS D-19 (2 OF 2) WATER MAINS CROSSING UNDER SEWERS AND HOUSE DRAINS D-20 (1 OF 2) GENERAL NOTES WATER MAIN CONTRACTS D-20 (2 OF 2) GENERAL NOTES WATER MAIN CONTRACTS CONT D-23 NEW COPPER 1-INCH WATER SERVICE STANDARD METER VAULT D-24 NEW COPPER 1.5 N. & 2 IN. WATER SERVICE STANDARD METER VAULT D-25 3 INCH, 4 INCH, 6 INCH, 8 INCH & 12 INCH METER VAULTS D-26 12 INCH METER VAULT WITH CHECK VALVE D-27 TYPICAL METER INSTALLATION FOR 1 INCH WATER SERVICE WITH

    LAWN HYDRANT AND BACKFLOW PREVENTOR D-28 ELECTRICAL CONTINUITY BRACKET FOR TRANSITION COUPLING D-30 TYPICAL SERVICE RECONNECTION 3 INCH AND LARGER USING MJ

    RESILIENT WEDGE VALVE D-31 SERVICE PIPE INSULATION

  • 2

    FEEDER MAIN DETAILS FM-1 INSPECTION MANHOLE FM-4 PITOMETER TAP BASIN PRECAST CONCRETE FM-5 FIRE HYDRANT SETTING 16 INCH & LARGER WATER FM-13 BUTTERFLY VALVE FM-14 TORQUE OVERLOAD PROTECTOR FM-15 BUTTERFLY VALVE BASIN PRECAST CONCRETE FM-16 (1 OF 2) BUTTERFLY VALVE BASIN MASONRY PLAN FM-16 (2 OF 2) BUTTERFLY VALVE BASIN MASONRY SECTIONAL VIEW FM-18 (1 OF 2) TYPICAL BLOW-OFF FIRE CISTERN MASONRY PLAN FM-18 (2 OF 2) TYPICAL BLOW-OFF FIRE CISTERN MASONRY SECTIONAL VIEW FM-19 TYPICAL BLOW-OFF FIRE CISTERN PRECAST CONCRETE

  • For information about this project,please call (312) 747-3570.

    BUILDING CHICAGO TOGETHER

    RICHARD M. DALEY, MAYOR

    NOTES:

    2-

    0"

    2-0"

    CL

    1/2 " PLYWOOD FOR CONSTRUCTIONSIGN MOUNTED TO STAND

    6"6"

    3-0"

    4-

    0"

    3-

    0" 4" x 4" WOOD POSTS

    ANCHORED INTO GROUND AND BRACEDAS REQUIRED OR AS CALLED FOR IN

    SPECIFICATIONS

    18"18"

    4" 4"

    3-0"

    FROM THE TIME CONSTRUCTION BEGINS TO THE TIME THAT PAVEMENT IS RESTORED.

    "WATER" OR"SEWER" ASAPPROPRIATE

    DEPARTMENT OF WATERMANAGEMENT

    1. TWO SIGNS (ONE ON EACH END OF EACH PIPE PROJECT) MUST BE DISPLAYED

    2. THE LOCATION OF THE SIGN WILL BE DETERMINED FOR THE RESIDENT ENGINEER.

    3. AFTER THE COMPLETION OF THE CONTRACT THE SIGN WILL BE PROPERTY OF THE

    CITY OF CHICAGO AND MUST BE DELIVERED TO THE APPROPRIATE DISTRICT YARD

    UNLESS ORDERED TO DISCARD BY THE COMMISSIONER.

    REV:04.07 PROJECT SIGN G -1

  • REV:04.07 G -3 SAMPLE SYMBOLOGY LEGEND

  • NE

    W R

    ED

    UC

    ER

    NE

    W W

    ED

    GE

    VA

    LV

    EN

    EW

    TA

    PP

    ING

    CO

    NN

    EC

    TIO

    N

    NE

    W 1

    /4 W

    AT

    ER

    MA

    IN B

    EN

    D

    NE

    W

    1/8

    W

    AT

    ER

    MA

    IN B

    ED

    NE

    W 1

    /16

    WA

    TE

    R

    MA

    IN B

    EN

    D

    N

    EW

    WA

    TE

    R

    MA

    IN T

    EE

    NE

    W W

    AT

    ER

    MA

    IN

    CA

    P O

    R P

    LU

    G

    NE

    W F

    IRE

    HY

    DR

    AN

    T

    NE

    W W

    AT

    ER

    VA

    LV

    E

    PR

    OP

    OS

    ED

    WA

    TE

    R

    MA

    IN T

    AP

    PR

    OP

    OS

    ED

    WA

    TE

    R M

    AIN

    SL

    EE

    VE

    PR

    OP

    OS

    ED

    WA

    TE

    R

    BU

    FF

    AL

    O B

    OX

    PIP

    E B

    RE

    AK

    SY

    MB

    OL

    NO

    RT

    H A

    RR

    OW

    HA

    ND

    ICA

    PP

    ED

    SY

    MB

    OL

    PR

    OP

    OS

    ED

    WA

    TE

    R M

    AIN

    INS

    PE

    CT

    ION

    MA

    NH

    OL

    E

    EX

    IST

    ST

    OR

    M

    WA

    TE

    R C

    AT

    CH

    BA

    SIN

    E

    XIS

    T S

    TO

    RM

    WA

    TE

    R I

    NL

    ET

    100.5

    EX

    IST

    ST

    RE

    ET

    EL

    EV

    AT

    ION

    EX

    IST

    ST

    OR

    M W

    AT

    ER

    MA

    NH

    OL

    E

    EX

    IST

    CO

    MB

    INE

    D

    SE

    WE

    R M

    AN

    HO

    LE

    EX

    IST

    SA

    NIT

    AR

    Y

    SE

    WE

    R M

    AN

    HO

    LE

    PR

    OP

    OS

    ED

    SE

    WE

    R M

    AN

    HO

    LE

    PR

    OP

    OS

    ED

    ST

    OR

    M

    WA

    TE

    R C

    AT

    CH

    BA

    SIN

    EX

    IST

    TE

    LE

    PH

    ON

    E

    MA

    NH

    OL

    E

    EX

    IST

    TE

    LE

    PH

    ON

    E

    PE

    DE

    ST

    AL

    EX

    IST

    TE

    LE

    PH

    ON

    E

    PO

    LE

    E

    XIS

    T T

    RE

    E

    DE

    CID

    UO

    US

    E

    XIS

    T T

    RE

    E

    CO

    NIF

    ER

    OU

    S

    EX

    IST

    ING

    BU

    SH

    EX

    IST

    TR

    EE

    ST

    UM

    P

    EX

    IST

    MA

    RS

    H S

    YM

    BO

    L E

    XIS

    T T

    RA

    FF

    IC

    SIG

    NA

    L M

    AN

    HO

    LE

    EX

    IST

    TR

    AF

    FIC

    SIG

    NA

    L

    EX

    IST

    TR

    AF

    FIC

    SIG

    N

    T E

    XIS

    T T

    RA

    FF

    IC

    CO

    NT

    RO

    L B

    OX

    EX

    IST

    EL

    EC

    TR

    IC

    MA

    NH

    OL

    E

    EX

    IST

    ING

    CO

    M E

    D

    MA

    NH

    OL

    E

    EX

    IST

    LIG

    HT

    PO

    LE

    EX

    IST

    . S

    TR

    EE

    T

    LIG

    HT

    CO

    NT

    RO

    L B

    OX

    SE

    XIS

    T C

    AR

    RIA

    GE

    LIG

    HT

    EX

    IST

    RA

    ILR

    OA

    D

    SIG

    NA

    L

    RA

    ILR

    OA

    D T

    RA

    CK

    PR

    OF

    ILE

    RA

    ILR

    OA

    D

    CO

    MM

    UN

    ICA

    TIO

    N

    E

    XIS

    T U

    NK

    NO

    WN

    MA

    NH

    OL

    E

    EX

    IST

    UT

    ILIT

    Y P

    OL

    EE

    XIS

    T F

    LA

    G P

    OL

    EE

    XIS

    T G

    UY

    WIR

    E

    FF

    IRE

    AL

    AR

    M B

    OX

    GU

    AR

    DR

    AIL

    CO

    NC

    RE

    TE

    HO

    RIZ

    ON

    TA

    L

    TH

    RU

    ST

    BL

    OC

    K

    BR

    IDG

    E C

    OL

    UM

    NM

    ON

    ITO

    RIN

    G W

    EL

    LE

    XIS

    T B

    OL

    LA

    RD

    SO

    IL B

    OR

    ING

    EX

    IST

    MA

    IL B

    OX

    SU

    RV

    EY

    ED

    CH

    ISL

    ED

    CR

    OS

    S

    EX

    IST

    SU

    RV

    EY

    IRO

    N P

    IPE

    EX

    IST

    PR

    OP

    ER

    TY

    CO

    RN

    ER

    SU

    RV

    EY

    TR

    AV

    ER

    SE

    PO

    INT

    EX

    IST

    CO

    NC

    I.D

    .

    MO

    NU

    ME

    NT

    SU

    RV

    EY

    CO

    NC

    RE

    TE

    MO

    NU

    ME

    NT

    EX

    IST

    RIG

    HT

    OF

    WA

    Y M

    AR

    KE

    R

    EX

    IST

    CA

    BL

    E T

    .V.

    MA

    NH

    OL

    E

    EX

    IST

    CA

    BL

    E T

    .V.

    PE

    DE

    ST

    AL

    EX

    IST

    GA

    S

    VA

    LV

    E

    CO

    NC

    RE

    TE

    BL

    OC

    K

    EX

    IST

    GA

    S

    MA

    NH

    OL

    E

    NE

    W 1

    /32

    WA

    TE

    R

    MA

    IN B

    EN

    D

    PR

    OP

    OS

    ED

    WA

    TE

    R M

    ET

    ER

    RA

    MP

    DIS

    AB

    LE

    D

    E

    XIS

    T W

    AT

    ER

    VA

    LV

    E B

    OX

    EX

    IST

    WA

    TE

    R

    BU

    FF

    AL

    O B

    OX

    EX

    IST

    WA

    TE

    R

    ME

    TE

    R

    EX

    IST

    FIR

    E

    HY

    DR

    AN

    T

    EX

    IST

    ST

    AN

    D P

    IPE

    EX

    IST

    WA

    TE

    R

    WE

    DG

    E V

    AL

    VE

    EX

    IST

    TA

    PP

    ING

    CO

    NN

    EC

    TIO

    N

    EX

    IST

    1/4

    W

    AT

    ER

    MA

    IN B

    EN

    D

    EX

    IST

    1/8

    W

    AT

    ER

    MA

    IN B

    EN

    D

    EX

    IST

    1/1

    6 W

    AT

    ER

    MA

    IN B

    EN

    D

    EX

    IST

    WA

    TE

    R

    MA

    IN T

    EE

    EX

    IST

    WA

    TE

    R M

    AIN

    RE

    DU

    CE

    R

    EX

    IST

    WA

    TE

    R

    MA

    IN T

    AP

    EX

    IST

    WA

    TE

    R M

    AIN

    BL

    OW

    OF

    F

    EX

    IST

    FIR

    E

    CIS

    TE

    RN

    EX

    IST

    WA

    TE

    R M

    AIN

    INS

    PE

    CT

    ION

    MA

    NH

    OL

    E

    EX

    IST

    WA

    TE

    R M

    AIN

    PIT

    OM

    ET

    ER

    TA

    P

    EX

    IST

    WA

    TE

    R M

    AIN

    B

    UT

    TE

    RF

    LY

    VA

    LV

    E

    EX

    IST

    FE

    ED

    ER

    MA

    IN 4

    5 D

    EG

    BE

    ND

    RE

    ST

    RA

    INE

    D J

    OIN

    T P

    IPE

    EX

    IST

    ING

    WA

    TE

    R

    MA

    IN C

    AP

    OR

    PL

    UG

    EX

    IST

    ING

    FL

    AR

    ED

    EN

    D

    NO

    .

    PR

    ES

    SU

    RE

    VA

    LV

    E

    (RIG

    HT

    - L

    EF

    T)

    NO

    .

    PR

    ES

    SU

    RE

    VA

    LV

    E

    (UP

    - D

    OW

    N)

    WE

    XIS

    T M

    AN

    HO

    LE

    WIT

    H W

    AT

    ER

    VA

    LV

    E

    PR

    ES

    SU

    RE

    GA

    GE

    PIP

    E R

    ISE

    R D

    OW

    NP

    IPE

    RIS

    ER

    UP

    EX

    IST

    1/3

    2 W

    AT

    ER

    MA

    IN B

    EN

    D

    EX

    IST

    WA

    TE

    R

    CR

    OS

    S

    I

    EX

    IST

    IN

    SP

    EC

    TIO

    N

    MA

    NH

    OL

    E-F

    EE

    DE

    R

    REV:06.07 G -4 LEGEND - SYMBOLSSHT. 1 OF 2

    EX

    IST

    ING

    WA

    TE

    R S

    YM

    BO

    LS

    PR

    OP

    OS

    ED

    WA

    TE

    R S

    YM

    BO

    LS

    SU

    RV

    EY

    SY

    MB

    OL

    S

    RA

    ILR

    OA

    D S

    YM

    BO

    LS

    TR

    AF

    FIC

    SY

    MB

    OL

    S

    SE

    WE

    R S

    YM

    BO

    LS

    VE

    GE

    TA

    TIO

    N S

    YM

    BO

    LS

    TE

    LE

    PH

    ON

    E S

    YM

    BO

    LS

    GA

    S S

    YM

    BO

    LS

    CA

    BL

    E T

    .V. S

    YM

    BO

    LS

    EL

    EC

    TR

    ICA

    L S

    YM

    BO

    LS

    MIS

    CE

    LL

    AN

    EO

    US

    SY

    MB

    OL

    S

    WA

    TE

    R S

    ER

    VIC

    ES

    CU

    T-O

    FF

    EA

    RT

    H H

    AT

    CH

    CO

    NC

    RE

    TE

    HA

    TC

    HC

    ON

    CR

    ET

    E H

    AT

    CH

    GR

    AV

    EL

    HA

    TC

    H

  • Proposed-C

    urb

    Ex

    isti

    ng

    -W

    ate

    r M

    ain

    Ex

    isti

    ng

    -W

    ate

    r S

    erv

    ices

    Exis

    ting-T

    ele

    phone

    Proposed-S

    idew

    alk

    Pro

    po

    sed

    -W

    ate

    r M

    ain

    Pro

    po

    sed

    -P

    av

    em

    en

    t

    Ex

    isti

    ng

    -C

    ity

    Press E

    lectr

    ical

    Ex

    isti

    ng

    -C

    urb

    Exis

    ting-F

    ence

    Exis

    ting-S

    idew

    alk

    Exis

    ting-E

    dge o

    f P

    avem

    ent

    Abandoned-W

    ate

    r M

    ain

    Ex

    istin

    g-C

    ity

    Ele

    ctr

    ic

    Exis

    ting-C

    om

    Ed

    Exis

    ting-H

    edge L

    ine

    Ex

    isti

    ng

    -Wo

    od

    s T

    ree L

    ine

    Ex

    isti

    ng

    RO

    W

    Ex

    isti

    ng

    RO

    W (

    Vacate

    d)

    Exis

    ting R

    OW

    (E

    levate

    d)

    Ex

    isti

    ng

    -E

    asem

    en

    t

    Pro

    po

    sed

    -RO

    W

    Ex

    isti

    ng

    -Cit

    y L

    imit

    s B

    ou

    nd

    ary

    Lin

    e

    Exis

    ting-C

    hic

    ago P

    ark

    Dis

    tric

    t L

    ine

    Exis

    ting-C

    able

    TV

    Exis

    ting-D

    itches-C

    reeks-

    Edge o

    f W

    ate

    r

    Exis

    ting-E

    mbankm

    ents

    -

    Dead E

    nds-R

    eta

    inin

    g W

    all

    s

    Exis

    ting-C

    TA

    Buri

    ed E

    lectr

    ic C

    able

    s

    Exis

    ting-R

    ail

    roads

    Exis

    ting-S

    team

    and C

    ooli

    ng P

    ipes

    Pro

    po

    sed

    -D

    itch

    es-C

    reek

    s-

    Edge o

    f W

    ate

    rP

    ro

    po

    sed

    -S

    ew

    er

    Ex

    isti

    ng

    -S

    ed

    imen

    t F

    orce M

    ain

    Pro

    po

    sed

    -S

    ed

    imen

    t F

    orce M

    ain

    Pro

    po

    sed

    -S

    ew

    er L

    ate

    ral

    Ex

    isti

    ng

    -B

    urie

    d S

    treet

    Car T

    rack

    s

    Ex

    isti

    ng

    -S

    ew

    er

    SY

    MB

    OL

    DE

    SC

    RIP

    TIO

    NS

    YM

    BO

    LD

    ES

    CR

    IPT

    ION

    Abandoned-S

    ew

    er

    Abandoned-G

    as

    Exis

    ting-G

    as

    SHT. 2 OF 2

    REV:06.07 G -4 LEGEND - LINE STYLES

    Pro

    po

    sed

    -N

    ew

    Wate

    r S

    erv

    ices

    B-B

    ox

    to

    Pro

    perty

    Pro

    po

    sed

    -W

    ate

    r M

    ain

    (By

    Oth

    ers

    )

    Pro

    po

    sed

    -N

    ew

    Wate

    r S

    erv

    ices

    WM

    to

    B-B

    ox

  • JOINT OF SIDEWALK

    STONE ABOVE TO COME

    OVER CENTER OF WALL

    BLOCKING

    CONCRETE

    PIER

    BR

    ICK

    OR

    CO

    NC

    RE

    TE

    WA

    LL

    WA

    TE

    RP

    RO

    OF

    ING

    SIDEWALK

    CURB

    PAVEMENT

    BL

    OC

    KIN

    G

    TO BE FILLED WITH SAND

    AFTER HYDRANT IS SET

    CURB

    ABOVE

    WATERPROOFING

    WATERPROOFING

    PIER

    SECTION VIEW

    1/4 " EXPANSION JOINT

    FILL WITH TAR

    8"

    PLAN VIEW

    REINFORCED CONCRETE

    SUPPORT BRACKET(S)TO SUIT CONDITIONS

    1" FLEXIBLE COPPER

    TUBING TO DRAIN

    2 OR 2.5 ALONGI.D.O.T. ROADWAYS

    6-

    9"

    3-6"

    8"

    3-6"

    8"

    3-

    6"

    8"

    8"

    1" SOFT COPPER WATER

    SERVICE TUBING TO

    STANDARD HYDRANT

    DRAIN.

    TOP FLANGE

    REV:07.07

    FIRE HYDRANT INSTALLATION DETAIL

    FOR VAULTED SIDEWALKS D -3

    THIS DETAIL IS PROVIDED FOR

    REFERENCE PURPOSES ONLY

    AND IS NOT A C.D.W.M.

    WATER MAIN STANDARD

  • PROP. CURB & GUTTER

    EXIST. CURB & GUTTER

    PROP. CURB & GUTTER

    A

    A

    SEE TILE DRAIN DETAIL

    VIEW "A-A"

    1 1/2

    4 x 4 x 3 SUMP

    6"

    6"

    MECHANICAL JOINT

    IF TRANSITION SLEEVE REQDPROVIDE CONCRETE THRUST

    BLOCK ON HYDRANT

    NOTE:

    WATER TABLE MUST BE BELOW

    BOTTOM OF DRAIN SUMP.

    2-0" CITY ROADWAYS

    2-6" I.D.O.T. ROADWAYS

    3" OF

    BITUMINOUS

    CONCRETE

    3/4 "

    STRAIGHT

    METER COUPLING

    HYDRANT

    BRANCH

    EXIST. CURB

    & GUTTER

    HYDRANT BRANCH

    8" MIN.

    9"

    2

    2

    3

    4

    REV:04.07

    FIRE HYDRANT SUMP DRAIN

    FOR RELOCATED HYDRANTS D -6

  • B B B B B

    Y Y Y Y Y

    Y R R R R

    Y R W R R

    W W W W W

    B

    Y

    Y

    R

    W

    B

    Y

    W

    W

    W

    B B

    Y Y

    R W

    W W

    W W W W W W

    W W W R

    W W R R

    UNCIRCULATED WATER MAINS-DEAD END

    CIRCULATED WATER MAINS

    6 O

    R 8

    IN

    CH

    (15

    0 O

    R 2

    00m

    m)

    WA

    TE

    R M

    AIN

    WATER MAINS LARGER THAN 16-INCH

    12-14-16-INCH WATER MAINS

    8-INCH WATER MAINS

    6-INCH WATER MAINS

    4-INCH WATER MAINS

    12 I

    NC

    H O

    R L

    AR

    GE

    R W

    AT

    ER

    MA

    IN

    W.M. LARGER THAN 16-INCH

    12-16-INCH W.M.

    8-INCH W.M.

    6-INCH W.M.

    4-INCH W.M.

    8-INCH W.M.

    6-INCH W.M.

    4-INCH W.M.

    OR

    LESS

    OR

    LESS

    OR

    LESS

    OR

    LESS

    90

    300

    300

    300

    300

    90

    90

    300

    300

    300

    90

    300

    300

    300

    B-BLUE FLANGE Y-YELLOW FLANGE R-RED FLANGE W-WHITE FLANGE

    ALL PUBLIC FIRE HYDRANTS ARE TO BE PAINTED RED EXCEPT FOR THE

    TOP FLANGES WHICH MUST BE COLOR CODED.

    REV:04.07 COLOR CODE FOR FIRE HYDRANTS D -7

  • EXISTING SURFACE

    WATER MAIN

    PR

    OV

    IDE

    IN

    SU

    LA

    TIO

    N W

    HE

    N D

    EP

    TH

    OF

    CO

    VE

    R I

    S L

    ES

    S T

    HA

    N

    5 F

    EE

    T

    4"

    6" (

    MIN

    .)

    6"

    D+3

    EXTEND INSULATION BOARD

    DOWN SIDES TO 6" BELOW

    WATER MAIN OR SERVICE.

    6"

    1-6"(MIN.)

    D

    PIPE BEDDING

    MATERIAL

    REV:04.07 WATER MAIN TRENCH INSULATION DETAIL D -9

    BACKFILL MATERIAL

    FINE SAND (FA7)

    MIN. 2 WIDE BY 4"

    THICK INSULATION BOARD (USE2-2" THICK BOARDS).MASTIC AT ALL JOINTS

    NOTES:

    1. INSULATION BOARD TO BE CLOSED CELL, EXTRUDED POLYSTYRENE

    FOAM MEETING ASTM 578, TYPE VI, 40 PSI COMPRESSING STRENGTH (ASTM D1621) 0.1% MAX. WATER ABSORPTION (ASTM C272).

    2. BACKFILL MATERIAL AROUND INSULATION MUST BE FINE SAND FREE FROM ROOTS,

    ORGANIC MATTER, OR OTHER INJURIOUS MATERIALS.

    3. OVERLAP ALL INSULATION BOARD JOINTS.

  • 4 MIL POLYETHYLENE WRAP12"

    MIN.

    12"

    MIN.

    2" ADHESIVE TAPE 2" ADHESIVE TAPE

    2" ADHESIVE TAPE

    WATER MAIN PIPE

    D.I.P. WITH PUSH-ONJOINTS (IN.)

    PIPE DIAMETER(IN.)

    4

    6

    8

    12

    16

    24

    14

    17

    21

    29

    37

    53

    16

    20

    24

    30

    37

    53

    NOTES:

    1. USE ONE LENGTH OF POLYETHYLENE TUBE WRAP

    FOR EACH LENGTH OF PIPE, OVERLAPPED

    AT PIPE JOINTS AND FOLD EXCESS OVER

    TOP OF TUBE FOR SLACK REDUCTION.

    2. USE CHART "A" TO SELECT SIZE OF WRAP.

    REV:04.07

    WATER MAIN

    POLYETHYLENE WRAP DETAIL D -10

    CHART "A" POLYWRAP FLAT TUBE WIDTHS

    D.I.P. WITHMECHANICAL JOINTS (IN.)

  • HORIZONTAL THRUST BLOCK DETAILS

    W

    2 MINIMUM

    DEAD END THRUST BLOCK BEND THRUST BLOCK

    2 MIN.

    H

    BEND THRUST BLOCK

    2 MIN.

    W

    H

    DEAD END THRUST BLOCK

    H

    TRENCH

    NOTES:

    2

    MIN

    .

    W

    12"

    12"

    VERTICAL THRUST BLOCK DETAILS

    REV:04.07

    THRUST RESTRAINT

    CONCRETE THRUST BLOCK DETAILS D -11

    D DD

    2 MIN.2 MIN.2 MIN.

    HORIZONTAL

    1/4 BEND

    D

    1

    1

    H

    2.5

    5.5

    3.5

    W

    2.5

    4.5

    3.5

    CY

    2

    1

    .5

    DEAD END & TEE

    D

    1

    1

    H

    6.5

    W CY

    4

    3

    5

    4

    3

    2.5

    1.5

    PIPE

    SIZE

    INCH DIA.

    16

    12

    8

    HORIZONTAL

    1/8 BEND

    D

    1

    1

    H

    4.5

    W CY

    3

    2

    3

    2

    1.5

    .75

    4

    .3.5 .5.5 .5

    HORIZONTAL

    1/16 BEND

    D

    1

    1

    H

    1.5

    3.5

    2.5

    W

    1.5

    3.5

    2.5

    CY

    1

    .5

    D

    1

    1

    H

    2.5

    W CY

    2 2

    PIPE

    SIZE

    INCH DIA.

    16

    12

    8

    HORIZONTAL

    1/32 BEND

    .5 .5.25 1.5

    2.5

    1.5

    .6

    .4

    .25

    TABLE 1

    D

    7

    5

    H W CY

    11

    7

    D

    2

    2

    H

    4.5

    W CY

    3 3

    PIPE

    SIZE

    INCH DIA.

    16

    12

    8 23.5

    1

    TABLE 2

    VERTICAL

    1/8 BEND

    VERTICAL

    1/8 BEND BOTTOM

    4.5

    6

    6

    4

    6

    5

    4 2

    4

    2

    2.25

    .5

    D IS THE DIMENSION INTO UNDISTURBED GROUND IN FEET

    H IS HEIGHT OF THRUST BLOCK IN FEET

    W IS WIDTH OF THRUST BLOCK IN FEET

    ALL DIMENSIONS ARE MINIMUM.

    THRUST BLOCKS IN LOOSE FILL OR SAND AREAS ARE

    NOT INCLUDED IN THESE TABLES AND WILL REQUIREADDITIONAL ANALYSIS.

    CONCRETE BLOCKSIZE PER TABLE 2

    W

    D

    EPOXY COATED #5 REBARS(ASTM A615 GRADE 60) (TYP.)

    H

    PLAN VIEW PLAN VIEW PLAN VIEW

    PROFILEPROFILE

    TEE THRUST BLOCK

    PROFILE

    TEE THRUST BLOCK

    PROFILE

    CONCRETE BLOCK SIZEPER TABLE 1

    1. FULL CONCRETE THRUST BLOCKS AS SHOWN ARE REQUIRED WHEN THRUST RESTRAIN IS NOT PROVIDED BY OTHER MEANS SUCH AS RESTRAINED JOINT PIPE.

    2. WHEN THRUST RESTRAINT GLANDS ARE INSTALLED FOR THE CONNECTIONS, CONCRETE THRUST BLOCKS SHALL BE PROVIDED UP TO THE THE DOTTED LINE AS SHOWN.

    3. ALL BOLTS, NUTS, THRUST RESTRAINT GLANDS AND FITTINGS SHALL BE WRAPPED WITH POLYETHYLENE TUBING TO PREVENT CORROSION AND CONCRETE ADHESION.

    4. CONCRETE FOR THRUST BLOCKS MUST NOT CONTAIN FLY ASH.

    PLAN VIEW

    UNDISTURBED SOIL

  • TEE

    LB

    20 20

    PIP

    E S

    IZE

    24"

    16"

    8" 26

    12"

    L2

    L1

    1/8 VERTICAL BENDS

    37

    67

    67

    L1 L2

    26

    11

    20

    20P

    IPE

    SIZ

    E

    24"

    16"

    12"

    8"

    1/32 1/16 1/8

    3 6 12

    1/4

    29

    4 8 17 41

    7 30 73

    7 30 73

    15

    15

    DISTANCE OF RESTRAINEDJOINTS REQUIRED

    EITHER SIDE OF BENDS

    REV:04.07

    THRUST RESTRAINT

    RESTRAINED JOINT PIPE DETAILS D -12

    LBTEE SIZE

    0

    42

    277

    BEND SIZES

    LL

    L

    HORIZONTAL TEES - LENGTH OF RESTRAINED JOINTS

    1/8 VERTICAL BENDS - LENGTH OF RESTRAINED JOINTS

    NOTE:

    1. MINIMUM LENGTHS OF PIPE REQUIRED TO RESTRAIN FITTINGS SHOWN.

    2. LENGTHS BASED ON POLY-WRAPPED PIPE.

    8" x 8" :(8", 12", 16" OR 24") x 12"

    16" x 16"

    36" x 24"

    HORIZONTAL BENDS - LENGTH OF RESTRAINED JOINTS

    33

  • PU

    1" TEST TAP 1" TEST TAP

    MJ VALVE

    GRADE

    GATE VALVE

    26"

    24"

    2"

    SIDE VIEW SEAL AROUND PIPE

    5 DIA.

    8" 8"

    VA

    RIE

    S

    8"

    LIFTING

    LUGLIFTING

    LUG

    FILL SPACE AROUND

    PIPE W/BRICK

    AND MORTAR

    COMPACTED

    GRANDULAR BEDDING

    FOR RESTRICTED HEADROOM,

    USE ALTERNATE DESIGN W/

    PRE CAST FLAT SLAB TOP.

    POURED CONCRETE OR

    CONCRETE BLOCK

    SUPPORT UNDER MAIN #4 EPOXY COATED REBARS

    4" C/C BOTH WAYS

    STANDARD FRAME AND

    LID SET IN MORTAR BEDDESIGN SLAB FOR H20LOADING CONDITIONS.

    PRECAST REINFORCEDCONCRETE MANHOLECONCENTRIC CONE

    B

    A

    WATERPIPE

    MORTARJOINT

    DE

    PT

    H V

    AR

    IES

    8"

    6"

    32"

    ADJUSTING RING(S)WITH MORTAR JOINT

    BETWEEN RINGS

    SEAL JOINTS WITH

    MASTIC SEALANT

    WHEN MULTIPLE RISER

    SECTIONS ARE USED

    1" THICK

    EXPANSION

    MATERIAL

    6 3/4 "

    B

    A

    OPTIONAL SPLIT BOTTOM

    NOMINAL

    PIPE SIZES

    OPENING DIMENSIONS

    A B

    8"

    12"

    16"

    11.0"

    15.5"

    19.5"

    12.5"

    16.5"

    21.0"

    REV:06.07

    PRECAST VALVE BASIN

    FOR PIPES UP TO 16" DIA. D -13

  • PU

    NOTES:

    VA

    RIA

    BL

    E

    LUG LUG

    GRADE

    1" EXPANSION MATERIAL

    1" CORPORATION (2 REQD)OPENINGS TO BE TAPPED DRY.

    (NOT REQUIRED ON SIDECONNECTIONS, SERVICE

    CONNECTIONS OR

    FIRE HYDRANT BRANCHES)

    SIDE VIEW AROUND PIPE

    WATER PIPE

    MORTAR

    JOINT

    MAXIMUM CORBEL= 1 1/2 "

    GATE

    VALVE

    FILL SPACE AROUND

    PIPE W/ BRICK

    AND MORTAR

    COMPACTED

    GRANULAR BEDDING

    POURED CONCRETE OR

    CONCRETE BLOCK SUPPORT

    UNDER MAIN

    36"

    MA

    X.

    CORBELLED

    2"

    #4 EPOXY COATED REBARS

    4" C/C BOTH WAYS

    5-0" DIA.

    24"

    26"

    8"

    8"

    6"

    6"

    7-0"

    STANDARD FRAME AND LID

    1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING

    2. USE PRECAST CONCRETE BASE OR PROVIDE 6" (MIN.) THICK CONCRETE BASE POURED IN PLACE WITH #4 EPOXY COATED REBARS 4" C/C BOTH WAYS.

    3. CUT LIFTING LUGS AFTER PLACING THE PRE-CAST SLAB IN POSITION.

    4. ALL JOINTS AND BRICK MASONRY SHALL BE PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT MORTAR.

    5. PRECAST CONCRETE TOP SLAB TO BE USED WHERE HEAD ROOM IS RESTRICTED.

    REV:04.07 BRICK MASONRY VALVE BASIN D -14

    FOR RESTRICTED HEADROOM

    USE ALTERNATE DESIGN W/ PRE

    CAST FLAT SLAB TOP. DESIGN SLAB

    FOR H20 LOADING CONDITIONS.

  • SHUT-OFF BOXCORPORATION COCK

    WEIGHTWEIGHTSIZE

    In. Lb. Lb.

    1.0

    1.5

    2.0

    3.00 7.25

    10.00

    16.50

    PR

    OP

    ER

    TY

    LIN

    E

    7.25

    7.25

    STREET PAVEMENT

    CONCRETE CURB

    CORPORATION COCK

    DIRECT CONNECTION

    WATER MAIN

    5-6"

    MIN

    .

    ROUNDWAY

    (CURB STOP)

    VARIABLE

    GRADE

    12"x 12"x 2"

    PRE-CAST

    CONCRETE BLOCK

    REV:04.07 TYPICAL 1" TO 2" WATER SERVICE D -16

    SHUT-OFF BOX

  • N.T.S.

    RECEIVING PITJACKING PIT

    ROAD ROAD

    A

    A

    PROPOSED STEEL

    CASING PIPE

    CASING END SEAL

    (SEE NOTE 1)

    L

    CASING END SEAL

    (SEE NOTE 1)

    10 10

    SEE PLAN FOR LENGTH

    C RAILROAD TRACK OR OUTER MOST

    TRACK UNDER MULTIPLE TRACKS

    (SEE PLANS FOR NUMBER OF TRACKS)

    5.5

    20 SPUR TRACK

    30 MAIN TRACK

    OR PER PERMIT

    (MIN

    . O

    R

    PE

    R P

    ER

    MIT

    )

    PROPOSED D.I. RESTRAINED

    JOINT WATER PIPE

    WITH SPACERS

    PROPOSED D.I. RESTRAINED

    JOINT WATER PIPE

    WITH SPACERS

    REV:07.07 CASING PIPE UNDER RAILROAD TRACK DETAIL D -18

    SECTION A-A

    WATER MAIN

    STAINLESS STEEL

    CASING SPACER

    NON-CONDUCTIVE

    PLASTIC RUNNER

    CASING PIPE

    PROFILE

    NOTES:

    1. END SEAL - BRICK AND MORTAR OR SELF CURING RUBBER SEAL.

    2. LENGTH OF CASING PIPES UNDER METRA TRACKS SHALL BE EXTENDED

    TO METRA R.O.W. LINES AND JACKING AND RECEIVING PITS ARE

    NOT TO BE LOCATED WITHIN TRACK R.O.W.

    THIS DETAIL IS PROVIDED FOR

    REFERENCE PURPOSES ONLY

    AND IS NOT A C.D.W.M.

    WATER MAIN STANDARD

  • 10.

    LOCATION OF UTILITIES AND PROPERTY LINES ARE FROM

    THE BEST INFORMATION AVAILABLE. EXACT LOCATION AND

    1.

    6.

    11.

    VICINITY. THE CONTRACTOR MUST COMPLY WITH

    7.

    8.

    9.

    COMPLETENESS ARE NOT GUARANTEED.

    WITH THE UTILITY OWNERS PRIOR TO DOING ANY WORK IN THE

    2. THE CONTRACTOR MUST VERIFY THE LOCATION OF UNDERGROUND UTILITIES

    3.

    4. IF ANY PUBLIC OR PRIVATE UTILITIES CROSS THE WATER

    MAIN TRENCH AND MUST REMAIN IN PLACE, THE CONTRACTOR

    MUST PROTECT SAID UTILITY IN CONFORMANCE WITH THE

    SPECIFICATIONS OR AS DIRECTED BY THE COMMISSIONER.

    WATER MAIN AND FITTINGS LOCATIONS SHOWN ON THE DRAWINGS FOR THE

    NEW WATER MAINS AND APPURTENANCES MAY BE CHANGED BY THE COMMISSIONER

    DUE TO FIELD CONDITIONS. NO ADDITIONAL COMPENSATION WILL BE ALLOWED

    FOR SUCH CHANGES, UNLESS PREVIOUSLY APPROVED BY THE COMMISSIONER.

    REQUIREMENTS OF UTILITY OWNERS REGARDING NOTICEOF WORK AND PROTECTION OF UTILITIES. THE CONTRACTOR MUST

    COMPLY WITH THE CITY OF CHICAGO, DEPARTMENT OF TRANSPORTATION

    DAMAGE PREVENTION PROTOCOL CITY INFRASTRUCTURE DEPARTMENTS.

    ALL UTILITIES MUST BE NOTIFIED AT LEAST 48 HOURS

    BEFORE CONSTRUCTION. (CALL DIGGER 312-744-7000).

    FITTINGS AND THEIR LOCATIONS INDICATED ON THE DRAWINGS

    ARE TENTATIVE. THE CONTRACTOR MUST COMPLETE THE

    INSTALLATION WITH THE NECESSARY FITTINGS DICTATED BY

    FIELD CONDITIONS. NO ADDITIONAL PAYMENT WILL BE MADE

    FOR DEVIATIONS FROM THE INDICATED FITTINGS.

    WORK INDICATED ON THE PLANS AND NOT REFERENCED

    TO A BID ITEM IS CONSIDERED INCIDENTAL TO THE WORK

    TO WHICH IT APPLIES AND NO ADDITIONAL COMPENSATION

    WILL BE ALLOWED.

    5. PROVIDE EROSION CONTROL IN ACCORDANCE WITH THE SPECIFICATIONS.

    GENERAL NOTES

    IN INSTANCES WHERE CHLORINATION IS TO BE DONE

    AGAINST ANY EXISTING VALVE, AT THE TIME THAT THE

    EXISTING WATER MAIN IS BREACHED FOR FINAL CONNECTION, THE

    CONTRACTOR IS TO VERIFY THAT THE EXISTING VALVES

    ARE IN GOOD OPERATING CONDITION AND DO NOT LEAK. ANY

    LEAKING VALVE SHOULD BE BROUGHT TO THE COMMISSIONERS

    ATTENTION AND BE REPAIRED OR REPLACED PRIOR TO MAKING PIPE

    CONNECTIONS TO THE EXISTING WATER MAIN. THE VALVE SHOULD

    REMAIN IN THE CLOSED POSITION UNTIL THE NEW WATER MAIN IS

    APPROVED FOR SERVICE.

    REV:04.07 D -20

    GENERAL NOTES

    WATER MAIN CONTRACTSSHT. 1 OF 2

    TEST PITS MUST BE EXCAVATED IN ADVANCE OF PIPELINE

    CONSTRUCTION IN ORDER TO CONFIRM DEPTH AND LOCATION

    OF EXISTING UTILITIES AND WHEN DIRECTED BY THE DEPARTMENT

    MANAGER. NO ADDITIONAL PAYMENT WILL BE MADE FOR TEST PIT

    EXCAVATION.

    THE CONTRACTOR MUST PROVIDE THRUST RESTRAINTS IN ACCORDANCE

    WITH THE SPECIFICATIONS. THE CONTRACTOR MUST FURNISH AND INSTALL

    MECHANICAL JOINT THRUST RESTRAINT GLANDS AT ALL FITTINGS AND

    MECHANICAL JOINTS.

    THE CONTRACTOR MUST VERIFY THE OPERATION OF EVERY VALVE

    NECESSARY FOR THE REQUIRED WATER MAIN SHUT DOWN FOR EACHPIPE SECTION. FOR VALVES OR WATER MAINS UNDER 16-INCHES IN DIAMETER,

    THE WORK MUST BE DONE UNDER THE DIRECT SUPERVISION OF A DEPARTMENT

    REPRESENTATIVE AT LEAST 2 WEEKS PRIOR TO THE START

    OF THE JOB. A 24 HOUR ADVANCE NOTICE MUST BE GIVEN TO ALL

    CONSUMERS EFFECTED AND THE BUREAU OF OPERATIONS AND DISTRIBUTION.

    THE OPERATION OF ALL VALVES 16-INCHES IN DIAMETER AND LARGER

    MUST BE PERFORMED BY CITY FORCES PURSUANT TO A 72 HOUR

    ADVANCE NOTIFICATION TO THE DEPARTMENT. ANY VALVE

    FOUND NOT OPERABLE WILL BE REPAIRED OR REPLACED BY

    THE DEPARTMENT UNLESS DIRECTED OTHERWISE BY THE COMMISSIONER.

  • 12.

    14.

    15.

    16.

    17.

    18.

    19.

    13. ALL VALVE BASINS MUST BE CONSTRUCTED OF PRE-CAST

    REINFORCED CONCRETE UNLESS DIRECTED OTHERWISE

    BY THE COMMISSIONER.

    HOUSE DRAINS ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR

    MUST LOCATE ALL HOUSE DRAINS WITHIN THE AREA OF EXCAVATION

    AND MAKE ADJUSTMENTS AND/OR REPAIRS.

    20. ABANDON EXISTING WATER MAINS IN ACCORDANCE WITH THE SPECIFICATIONS.

    ALL OPENINGS IN EXISITNG WATER MAINS MUST BE PLUGGED OR

    CAPPED WITH DUCTILE IRON FITTINGS UNTIL THE MAIN IS ABANDONED.

    IF A STANDARD MECHANICAL JOINT SLEEVE DOES NOT FIT TO MAKE

    CONNECTION OF THE NEW PIPE TO THE EXISTING PIPE, A TRANSITION

    SLEEVE MUST BE USED. NO GRINDING OF THE EXISTING PIPE IS

    PERMITTED.

    NOTES INDICATING S.N.L., E.W.L., ETC., MEAN SOUTH OF THE NORTH

    PROPERTY LINE, EAST OF THE WEST PROPERTY LINE, ETC. AND ARE MEASURED

    FROM THE NEAREST STREET.

    BURIED STREET CAR TRACKS ARE SHOWN FOR INFORMATIONAL PURPOSES ONLY.

    EXACT LOCATIONS AND DIMENSIONS ARE UNKNOWN UNLESS NOTED OTHERWISE.

    CAUTION SHOULD BE EXERCISED WHEN EXCAVATING IN THE STREETS CONTAINING

    BURIED STREET CAR TRACKS. BURIED TRACKS AND CABLES MAY BE USED FOR

    ELECTRICAL GROUNDING BY THE CHICAGO TRANSIT AUTHORITY OR MEMBERS

    OF THE CHICAGO AREA JOINT ELECTROLYSIS COMMITTEE STANDARDS. ELECTRICAL

    CONDUCTIVITY MUST BE MAINTAINED.

    THE DEPARTMENT WILL PROVIDE THE NECESSARY I.E.P.A. WATER MAIN

    CONSTRUCTION PERMITS FOR THIS CONTRACT.

    21. SWAB PIPE AND FITTINGS THAT WILL NOT BE PRESSURE TESTED OR CHLORINATED WITHCHLORINE SOLUTION DURING INSTALLATION AND USE EXTRA PRECAUTION TO PREVENT SOILAND DEBRIS FROM ENTERING THE PIPE. INCORPORATE UNTESTED PIPE INTO THE FLUSHINGROUTINE WHEN POSSIBLE. WHEN CONNECTING NEW PIPE TO THE EXISTING WATER SYSTEM,USE OPERATING PRESSURE TO VISUALLY INSPECT FOR LEAKS. WHEN FEASIBLE, PERFORMINSPECTION PRIOR TO BACKFILLING. COMPLY WITH ALL STANDARDS AND REQUIREMENTS OFTHE BUREAU OF WATER QUALITY (312) 744-8190.

    REV:04.07 D -20

    GENERAL NOTES

    WATER MAIN CONTRACTSSHT. 2 OF 2

    GENERAL NOTES (CONTINUED)

    WORK WITHIN STATE ROUTES ARE NOTED ON THE DRAWINGS AND WILL REQUIREI.D.O.T., REGION 1, UTILITY PERMITS. THE CONTRACTOR IS RESPONSIBLE FOR

    SECURING ALL PERMITS, INITIATED BY THE DEPARTMENT AND OBTAINING

    PERFORMANCE BONDS. ALL WORK MUST BE IN ACCORDANCE WITH I.D.O.T. PERMIT

    REQUIREMENTS. QUESTIONS SHOULD BE DIRECTED TO: I.D.O.T REGION ONE UTILITIESCOORDINATOR AT (847) 705-4258.

  • INSIDE VAULT

    GRADE

    FLOW

    FRAME AND LID (NEENAH R1911C)

    K

    A

    B

    F G

    H

    C

    D

    E

    C C

    B

    J

    I

    NOTE:

    1 1/2 " AND 2" METER VAULT CALL

    FOR 39" COVER. SEE NEXT PAGE.

    A

    B

    C

    D

    E

    F

    G

    H

    I

    J

    METER

    SHUT-OFF BOX

    MALE I.P.S. TO FLARED ADAPTER

    K EXTRA HEAVY SALT GLAZED VITRIFIED CLAY TILE PIPE

    FEMALE FLARED FITTING

    FULL PORT CONTROL VALVE

    1" TYPE K COPPER PIPE

    1" x 3/4 " BRASS BUSHING

    3/4 " BENT METER COUPLING

    1" ROUNDWAY

    5"

    1-

    6"

    58"

    24"

    5-

    0" M

    IN.

    1" METER VAULT

    VAULT CODE 11-8-200

    G

    H

    C

    D

    E

    REV:04.07

    NEW COPPER 1" WATER SERVICE

    STANDARD METER VAULT D -23

  • INSI

    DE V

    AULT

    BAS

    E FO

    UNDA

    TION

    I

    B

    A

    F

    G

    H

    J

    K

    J

    M

    J C

    G

    N

    H G

    D

    F G

    E

    J

    I

    J

    K

    J

    M

    FLOW

    FLOW

    J

    K

    J

    I

    H

    G

    G

    G

    F

    E

    G

    H

    I

    J

    K

    C

    A

    M

    J M

    J

    B

    J

    N

    GRADE GRADE

    GRADE

    A

    B

    C

    D

    E

    F

    G

    H

    I

    PRECAST CONCRETE TOP

    F.M. FLARED FITTING

    SOLID CONCRETE BLOCK OR PRECAST CONCRETE

    J

    K

    M

    N

    ROUNDWAY

    SHUT-OFF BOX

    TYPE K COPPER

    MALE I.P.T. TO FLARED

    FULL PORT CONTROL VALVE

    BRASS UNION

    METER

    BRASS NIP.

    BRASS ELL.

    COVER 25 1/4 "x 25 1/4 "(NEENAH, R6662JP OR EQUAL) CENTERED OVER METER

    54"

    30"

    54"

    5"

    5"

    5"

    10 1/4 "

    39"

    33 1/2 "

    10 1/4 "

    54"

    5-

    0"

    15"

    54"

    REV:04.07

    NEW COPPER 1 1/2 " & 2" WATER SERVICES

    STANDARD METER VAULT D -24

  • SUMP

    FLOW FLOW

    METERSTRAINER

    D

    A B C E

    SUMP PIT

    VAULT COVERS

    F

    HG

    C

    E D FA D

    A B C D E F G

    1-0" 1-2" 2-6" 1-2" 1-0"

    H

    6-0"8-0"SPOOL PIECE

    VARIES

    14 MAXIUM IF

    CONCRETE COLLAR IS USED

    1" TAPS REQUIRED UPSTREAM AND DOWNSTREAM. ALL PIPES AND FITTINGS SHALL BE FLANGEDAND SHALL CONFORM TO U.S.A. STANDARD A21.51-1965 (A.W.W.A.C. 151-65) AND SHALL HAVE ON OUTSIDEBITUMINOUS COATING OF EITHER COAL TAR OR ASPHALT BASE AND A CEMENT MORTAR LINING

    CONFORMING TO U.S.A. STANDARD A21.4-64 (A.W.W.A.C. 104-53).

    ALL METER VAULT COVERS AND LIDS SHALL BE HEAVY DUTY. 2 PIECE SHALL BE PLACED DIRECTLY ABOVE

    THE COMPOUND METER BYPASS. NO CENTER BRACE SHALL BE PERMITTED IN COVER FRAME. VAULT COVER

    SHALL MEASURE 49 1/2 " x 31 1/2 " AND COMPLY TO R6663NP NEENAH OR EQUAL.FOR METER READER ACCESS A 1-11" COVER MUST BE INSTALLED IN CORNER OF VAULT ACCESS

    COVER TO CONFORM TO R1889 NEENAH OR EQUAL. LADDER TO BE DIRECTLY UNDERCOVER.

    FOR BLOCK CONSTRUCTION ON IRON RUNG LADDER ANCHORED TO WALL WITH STEPS 16" MAX.

    ON CENTER. FOR PRE-CAST VAULTS USE CAST IRON STEPS R1980-T. BOLTING TO BE INSTALLED IN VERTICAL

    AT 16" CENTERS. A SUMP PIT SHALL BE INSTALLED NEAR BUT NOT UNDER LADDER. NO MECHANICAL

    JOINT FITTING ALLOWED IN VAULT. BLOCK SUMP TO BE LOCATED NEAR ACCESS LADDER, BUT NOT UNDER

    LADDER. METER AND VAULTS ETC. TO BE CENTERED IN VAULT.

    SIZE

    3"

    4"

    6"

    8"

    12"

    1-0"

    1-0"

    1-0"

    1-0"

    1-2"

    1-2"

    1-2"

    1-2"

    2-6"

    2-6"

    2-6"

    2-6"

    1-2"

    1-2"

    1-2"

    1-2"

    SPOOL PIECE

    VARIESSPOOL PIECE

    VARIESSPOOL PIECE

    VARIESSPOOL PIECE

    VARIES

    1-0"

    1-0"

    1-0"

    1-0"

    8-0" 6-0"

    6-0"

    6-0"

    6-0"

    10-0"

    10-0"

    10-0"

    5-

    0"

    18"

    8"

    9"

    8"

    REV:04.07 3", 4", 6", 8" & 12" METER VAULTS D -25

    SLEEVE W/LINK-SEAL

    (TYP.)

  • TAP

    SUMP

    SUMP PIT

    1. ALL CONCRETE STRUCTURES SHALL BE WATER TIGHT, THE CONTRACTOR WILL BE REQUIRED TO TAKE SUCH MEANS NECESSARY TO CORRECT ANY AND ALL LEAKAGE THRU FLOORS OR WALLS OF STRUCTURE, WITHOUT ADDITIONAL COMPENSATION.

    3. METER AND PIPING TO BE SET BEFORE INSTALLING ROOF SLAB.

    4. ALL METER VAULTS SHALL BE FURNISHED WITH GALVANIZED OR ALUMINUM LADDERS. ALL OPENINGS IN METER VAULTS SHALL BE SEALED WITH NO SHRINK GROUT.

    GRADE

    24" ROUND COVER OVER LADDERNEENAH R1900 C OR EQUAL

    24"x 48"SPLIT COVER

    NEENAH R1877 E1 OR EQUAL

    12" VALVE

    12" D.I. PIPE12"

    CHECK VALVE12"

    STRAINER

    12"METER

    12"VALVE

    12" FLANGE TO MJ BELL ADAPTER 12" FLANGE TO MJ PE ADAPTER

    2. WALLS MAY BE CONSTRUCTED OF 8" CONCRETE BLOCK ON A CONCRETE FLOOR SLABS MAY BE PRECAST CONCRETE-OR THEY BE PRECAST CONCRETE REINFORCED AS REQUIRED.

    24"

    NOTES:

    12-0"

    2-

    6"

    2-

    6"

    5-

    0"

    9"

    7-

    3"

    12-0"

    9"

    2-

    0"

    6"

    6-

    0"

    2-

    0"

    9"

    REV:04.07 12" METER VAULT WITH CHECK VALVE D -26

    REMOVEABLEROOF SLAB

    SECTION VIEW IN GROUND

    PLAN VIEW IN GROUND

    PLAN VIEW ABOVE SURFACE

    LINK-SEAL 16" SLEEVEPOURED IN WALLOF VAULT (TYP.)

  • REDUCED PRESSURE ZONE (RPZ)BACKFLOW PREVENTOR

    K

    E

    D

    C

    G

    H

    C

    E

    D

    C WATER MAIN

    B

    I

    TILE ORAPPROVEDCONCRETEPIPE

    GRADE

    B

    F

    RISER

    24"

    CURB AND GUTTER

    COMMON BRICK

    J

    5-

    0" M

    IN.

    A

    BACKFLOW PREVENTOR ENCLOSURE

    SHUTOFF WATER AT ROUNDWAY 1

    2

    3

    4

    5

    6

    7

    REMOVE AND STORE RPZ AND KEEP FROM FREEZING.

    OPEN LAWN HYDRANT AND LOOSEN METER NUT ON HOUSE SIDE OF METER

    BLOWOUT WATER LINES FROM RPZ TO METER AND FROM RPZ TO LAWN HYDRANT.

    IN SPRING REINSTALL RPZ AND ALSO HAVE RPZ TESTED BY LICENSED PERSONEL

    WITH A PERMIT FROM WATER DEPT. IN CITY HALL.

    EACH RPZ MUST BE IDENTIFIED OR NUMBERED SO THAT RPZ WILL BE

    REINSTALLED IN THE SAME LOCATION AT ALL TIMES.

    EACH LAWN HYDT. (HOSE CONNECTION) MUST BE MARKED

    "NON POTABLE WATER DO NOT DRINK".

    TO PROTECT WATER SYSTEM FROM FREEZING

    DEPTH

    OFBURY

    5 MIN.

    GROUND DRAINMUST BE PLUGGED

    3/4 " I.P.S.

    2" PIPE CASING

    SUPPLY LINE

    2 3/

    4 "

    FLOW

    STREET

    BUFFALO BOX

    INSIDEVAULT

    ROUNDWAYCOMMON BRICK

    C

    NON POTABLEWATER STAMP

    ON LID

    A

    B

    C

    D

    E

    F

    G

    H

    I

    J

    K

    FRAME AND LID (NEENAH R1911C)

    MALE I.P.S. TO FLARED ADAPTER

    1" TYPE K COPPER PIPE

    FEMALE FLARED FITTING

    1"x 3/4 " BRASS BUSHING

    3/4 " BENT METER COUPLING

    METER

    FULL PORT CONTROL VALVE

    1" ROUNDWAY

    SHUT-OFF BOX

    EXTRA HEAVY SALT GLAZED VITRIFIED CLAY TILE PIPE

    STREET

    CURBAND

    GUTTER

    LAWNHYDRANT

    CORPORATIONCOCK

    18

    "

    MIN

    .

    RE

    V:0

    4.0

    7

    TY

    PIC

    AL

    ME

    TE

    R IN

    ST

    AL

    LA

    TIO

    N F

    OR

    1" W

    AT

    ER

    SE

    RV

    ICE

    WIT

    H L

    AW

    N H

    YD

    RA

    NT

    AN

    D

    BL

    AC

    KF

    LO

    W P

    RE

    VE

    NT

    OR

    D

    -27

  • M.J. PLUG

    PROPOSED WATER MAIN

    EXISTING WATER MAIN

    M.J. RESILIENT WEDGE VALVE

    TO BE BURIED (SIDEWAYS)

    PROPOSED WATER MAIN

    EXISTING WATER MAIN

    EXISTING

    SERVICE

    CUT, CAP & BRACE

    THE EXIST. SERVICE

    EXISTING

    SERVICE

    1/8 2BMJ BENDS

    MJ SLEEVE

    MJ RESILIENT WEDGE VALVE

    TO BE BURIED (SIDEWAYS)

    3BMJ TEE

    3BMJ TEE

    INSTALLATION

    RECONNECTION

    I.

    II.

    NOTE:

    MINIMUM 4" TEE TO BE USED

    FOR 3" SERVICE CONNECTION.

    REV:04.07

    TYPICAL SERVICE RECONNECTION 3" AND

    LARGER USING M.J. RESILIENT WEDGE VALVE D -30

    SET: 1-4" 3BMJ TEE

    1-8" MJ RESILIENT WEDGE VALVE

    2-12" MJ RESTRAINT GLANDS

    2-8" MJ RESTRAINT GLANDS

    3 OF 8" D.I.W.P.

    TEMPORARILY PLUG AND BRACE THE VALVE

    WITH:1-8" MJ PLUG

    AFTER THE NEW WATER MAIN IS APPROVED,

    CUT, CAP AND BRACE THE EXISTING 8" SERVICE

    WITH:1-8" MJ CAP

    1-8" MJ RESTRAINT GLAND

    REMOVE TEMPORARY PLUG OF NOTE ABOVE AND CONNECT

    8" SERVICE TO THE MJ RESILIENT WEDGE VALVE

    WITH:2-8"x 1/8 2BMJ BENDS

    1-8" MJ SLEEVE

    7-8" MJ RESTRAINT GLANDS

    8 OF 8" D.I.W.P.

    SWAB THE NEW PIPE WITH HTH CHLORINE DURING THE

    INSTALLATION. BURY THE MJ RESILIENT WEDGE VALVE.

    NOTE:

    MECHANICAL JOINT THRUST

    RESTRAINT GLANDS OR APPROVED

    EQUIPMENT FITTINGS TO BEUSED WITH ALL MJ FITTINGS.

  • SERVICE

    FINISHED GRADE

    SERVICE PIPE INSULATION DETAILS

    SIDE VIEW

    TOP VIEW

    WATER MAIN

    MIN. 2 WIDE BY

    4" THICK INSULATION

    BOARD

    4"

    6"

    6"

    5-

    0"

    4"

    4"

    2-

    0"

    REV:04.07 SERVICE PIPE INSULATION DETAILS D -31

    NOTES:

    1. BACK FILL MATERIAL AROUND INSULATION SHALL BE FINE SAND (FA7), FREE FROM ROOTS, ORGANIC MATTER, LEAVES OR OTHER INJURIOUS MATERIALS.

    2. OVERLAP ALL INSULATION BOARD JOINTS.

    3. INSULATION BOARD TO BE CLOSED CELL, EXTRUDED POLYSTYRENE FOAM

    MEETING ASTM 578, TYPE VI, 40 PSI COMPRESSING STRENGTH (ASTM D1621) 0.1% MAX. WATER ABSORPTION (ASTM C272).

  • EXISTING GRADE

    SECTIONAL VIEW

    PLAN

    CL

    VA

    RIA

    BL

    E

    7"

    8" PRECAST CONCRETE BASE

    (MAX.)1-6"

    6" COMPACTEDBEDDING MATERIALS

    CL

    MA

    NH

    OL

    E T

    OH

    AV

    E F

    LA

    TS

    LA

    B T

    OP

    CREATE SUMP ATBOTTOM OF MANHOLEBY SLOPING FLOOR @1"/ft. SLOPE

    FOR FRAME/GRATE

    NEW INSPECTION

    MANHOLE

    FEEDER MAIN

    PLACE CONCRETE FILL TOSLOPE BOTTOM OFMANHOLE TO PROVIDESUMP AREA.

    SLOPE

    3

    (MIN.)

    5-0"

    5-0"

    (MIN

    .)

    VA

    RIA

    BL

    E0

    TO

    3

    (SE

    E T

    OP

    SL

    AB

    DE

    TA

    IL)

    ACCESS HOLE

    EXISTING

    PRECAST TOP

    SLAB SEE DETAIL

    EXPANSION

    MATERIAL

    SEAL AREA AROUND PIPE

    WITH BRICK AND MORTAR

    (SEE VALVE BASIN DETAIL)

    PRECAST HOLE/ARCH

    FOR TEE (IFREQUIRED TOENLARGE USE

    CONCRETE SAW)

    NOTE:

    ALL OPENINGS IN BASIN SHALL BE SEALED WITH

    "NO SHRINK" GROUT.

    36"

    CL

    CL

    6.7 TYP.

    REDUCE IF REQUIRED TO CLEAR UTILITIES

    REV:04.07 INSPECTION MANHOLE FM -1

    SEE INSPECTION MANHOLE

    FRAME AND LID DETAIL

  • PU

    NOTE:

    3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.

    CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    4. PRECAST CONCRETE TOP SLAB TO BE USED WHERE

    HEAD ROOM IS REQUIRED.

    5. THE LOCATION OF MANHOLE TO BE DETERMINED ON INDIVIDUAL BASIS.

    SECTIONAL VIEW

    CL

    CL

    2. USE PRECAST CONCRETE BASE OR PROVIDE

    6" THICK IDOT CLASS SI CONCRETE BASE

    POURED IN PLACE WITH #4 EPOXY COATED REBARS

    4" C/C BOTH WAYS.

    1. PROVIDE 6" THICK COMPACTED CA-16 BEDDING

    6"

    6"

    VA

    RIA

    BLE

    36"

    34"

    36"

    8" MIN

    .

    SCALE: N.T.S.

    2" TEST TAP

    REV:07.07

    PITOMETER TAP BASIN

    PRECAST CONCRETE FM -4

    PIPE O.D.

    2-3" MIN

    6. OPENING ON TOP SLAB TO BE CENTERED OVER

    TEST TAP.

    *

    *

    *

    5-0" (30" DIA. PIPE)6-0" (36" DIA. PIPE)7-0" (42" & 48" DIA. PIPE)

    USE CITY OF CHICAGO INSPECTION

    MANHOLE FRAME AND LID

    PRECAST CONCRETE

    ADJUSTING RINGS

    GRADE

    PIPE DIA.

    (SEE PLAN)

    LUG LUG

    FILL

    CA-16

    GRADE

    6" MIN.

    6" MIN.

  • TAGS

    SPURGEAR

    F = NO. AND SIZE OF BOLTS,STRADDLE CENTERLINE.

    P N

    H

    Y

    1. BUTTERFLY VALVES SHALL BE MANUFACTURED IN ACCORDANCE WITH AWWA SPECIFICATION C-504-87, CLASS 150B, SHORT BODY VALVE WITH MECHANICAL JOINT ACCESSORIES.

    2. OPERATORS ARE EQUIPPED WITH OPEN/CLOSE INDICATING ARROW. ASSEMBLY OPEN CLOCKWISE.

    2 1/2 " SQ. NUTCOUNTER CLOCKWISE TO CLOSEUNLESS OTHERWISE SPECIFIED

    A B C D E F G X VALVE SIZE

    16

    20

    24

    28

    32

    24-INCH

    30-INCH

    36-INCH

    42-INCH

    48-INCH

    18 5/8 "

    21 1/2 "

    25 7/16 "

    29 7/8 "

    34 1/16 "

    18 5/8 "

    24 3/8 "

    28 1/4 "

    32 7/8 "

    37 1/8 "

    31 9/16 "

    39"

    45 7/8 "

    53"

    59 7/8 "

    13 1/4 "

    18"

    22"

    22"

    24"

    1 5/8 "

    1 13/16 "

    2"

    2"

    2"

    3/4 "

    1"

    1"

    1 1/4 "

    1 1/4 "

    30"

    36 7/8 "

    43 3/4 "

    50 5/8 "

    57 1/2 "

    6 3/8 "

    10"

    14"

    14"

    16"

    OPERATOR SIZE J L M N P Q Y VALVE

    T-425

    T-425

    75

    127

    7 3/8 "

    8"

    6"

    6 5/8 "

    7 1/8 "

    7 1/8 "

    6 7/8 "

    6 7/8 "

    9 1/2 "

    9 1/2 "

    6 5/8 "

    6 5/8 "

    24"

    24"

    36"

    48"

    NO.OF

    TURNS

    NOTE:

    4 7/8 "

    REV:07.07 BUTTERFLY VALVE FM -13

    D

    E (TYP.)

    X = LAYING LENGTH

    INSTALLATION DIAGRAM

    J A B

    4" MAX.

    3 1/2 " SPACE REQUIRED FORTHRUST BEARING COVER REMOVAL

    G =

    BO

    LT

    CIR

    CL

    E

    C =

    FL

    AN

    GE

    O.D

    .

  • OPENOPEN

    PAINT: TWO PART EPOXY PRIME COAT

    WITH TWO PART POLYURETHANE

    TOP COAT COLOR-U.S. PAINT

    #G9028 "SUN YELLOW"

    SEALANT: POLYURETHANE

    ADJUSTING SCREW: ALLOY STEEL

    ANSI B18.6

    NUT: CAST IRON ASTM A48

    SPRING GUIDE: ALLOY STEEL

    AISI 41L40

    BEARING BALL: MFGS. STD.

    SPRING: CRV SPRING STEEL DIM 2093

    GASKETS: CELLULOSE FIBER-STYRENE

    BUTADIENE

    DRIVE PLATE: CARBON STEEL AISI 1045

    DRIVE ROLLER: ALLOY STEEL

    AISI 41L40

    RETAINER: CAST IRON ASTM A48

    SPLINE HD SCREW: ALLOY STEEL

    ANSI B18.3 ENI PLATED

    WASHER: MOLYDISULFIDE FILLED NYLON

    SEAL RING: NITRILE BUTADIENE

    DETENT PIECE: SAE 123C CAST IRON

    SOCKET HD SCREW: ALLOY STEEL

    ANSI B18.3 ENI PLATED

    SOCKET: CAST IRON ASTM A48

    SQ HD SET SCREW: ALLOY STEEL

    1/2 " x 1" ANSI B18.6 ENI PLATED

    2 7/16 "

    3"

    9 1/8

    "

    2 9/16

    "

    2 1/2 "

    4 1/2 "

    2 5/8 "

    REV:04.07 TORQUE OVERLOAD PROTECTOR FM -14

  • FILL CA-16

    LUG

    LUGLUG

    GRADE

    VALVE BUTTON

    WATER MAIN

    +

    VALVE BUTTON

    MASONRY SUPPORT

    MJ BUTTERFLY VALVE

    CL

    CL

    PRECAST CONCRETE

    FILL CA-16

    MASONRY SUPPORT

    UNDER GEAR BOX

    VA

    RIA

    BL

    E

    NOTES:

    5. THE LOCATION OF MANHOLE TO BE DETERMINED ON INDIVIDUAL BASIS.

    1. PRECAST CONCRETE TOP SLAB TO BE USED WHERE

    HEAD ROOM IS REQUIRED.

    3. PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.

    CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    CL

    CL

    CL

    CL CL

    CL

    CL

    CL

    CLCL

    USE CITY OF CHICAGOSTANDARD FRAME WEIGHT 395 lbs.

    AND STANDARD LID WEIGHT 152 lbs.

    2. PRECAST 6" THICK CONCRETE SLAB WITH #4 EPOXY

    COATED REBARS 4" C/C BOTHWAYS.

    4. PROVIDE 24-INCH DIAMETER OPENING IN THE

    CENTER OR AS REQUIRED.

    26"

    23"

    21"

    24"

    5"

    6"

    5"

    5

    6"

    6"

    REV:07.07

    BUTTERFLY VALVE BASIN

    PRECAST CONCRETE FM -15

    6. PROVIDE 6" THICK COMPACTED

    CA-16 BEDDING.

  • MJ BUTTERFLY

    VALVE

    >

    >

    > >

    >

    >

    >

    >

    >

    >

    PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.

    CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    ALL JOINTS AND BRICK MASONRY SHALL BE

    PLASTERED INSIDE AND OUTSIDE WITH 1:2

    MORTAR TO MAKE THE STRUCTURE WATER TIGHT.

    PRECAST CONCRETE TOP SLAB TO BE USED WHERE

    HEAD ROOM IS REQUIRED.

    1.

    2.

    3.

    4.

    5.

    NOTES:

    VALVE BUTTON

    PROVIDE 6" THICK COMPACTED CA-16 BEDDING.

    USE PRECAST CONCRETE BASE OR PROVIDE 6"

    THICK I.D.O.T. CLASS SI CONCRETE BASE POURED

    IN PLACE WITH #4 EPOXY COATED REBARS 4"

    C/C BOTH WAYS.

    8"

    3-6"

    3-6"

    7-0"

    REV:04.07

    BUTTERFLY VALVE BASIN - MASONRY

    PLAN FM -16 SHT. 1 OF 2

  • LUG LUG

    VALVE BUTTON WATER MAIN

    PU

    GRADE

    FILL CA-16

    FILL CA-16

    1.

    2.

    3.

    4.

    5.

    NOTES:

    MASONRY SUPPORTUNDER GEAR BOX

    CL

    CL

    CL

    CL

    CL

    MJ BUTTERFLYVALVE

    USE CITY OF CHICAGOSTANDARD FRAME WEIGHT 395 LBS.AND STANDARD LID WEIGHT 152 LBS.

    MAXIMUM CORBEL= 1 1/2 "

    36" MAX.TOP OF BASIN TO BECORBELED AS SHOWN

    PROVIDE 6" THICK COMPACTED CA-16 BEDDING

    USE PRECAST CONCRETE BASE OR PROVIDE

    6" THICK I.D.O.T. CLASS SI CONCRETE BASE

    POURED IN PLACE WITH #4 EPOXY COATED REBARS

    4" C/C BOTH WAYS.

    PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.

    CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    ALL JOINTS AND BRICK MASONRY SHALL BE

    PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT

    MORTAR TO MAKE THE STRUCTURE WATER TIGHT.

    PRECAST CONCRETE TOP SLAB TO BE USED WHERE

    HEAD ROOM IS REQUIRED.

    6"

    6"

    VA

    RIA

    BLE

    24"

    26"

    5 DIA.

    8"

    7

    REV:04.07

    BUTTERFLY VALVE BASIN - MASONRY

    SECTIONAL VIEW FM -16 SHT. 2 OF 2

  • >>

    CONCRETE ORBRICK MASONRY

    THRUST BLOCK

    HANDLE

    NOTES:

    5-0" DIA.

    6-4" DIA.

    7-0" DIA.

    8" MJ VALVE

    8" D.I.W.P.

    8"x 8" MJ TEEVERTICAL

    16" D.I.W.P.SUMP DRAIN

    2-1" DIA. HOLES

    1/2 " THICKSTEEL PLATE SUMP COVER

    PROVIDE 1/2 " THICK STEEL PLATE

    SUMP COVER 20" x 20"

    TRIM THE CORNERS AND BLUNT

    THE SHARP EDGES.

    MAKE 2- 1" DIA. HOLES

    FOR #4 BENT BAR HANDLE.

    6"

    PROVIDE 6" THICK COMPACTED CA-16 BEDDING

    USE PRECAST CONCRETE BASE OR PROVIDE6" THICK IDOT CLASS SI CONCRETE BASEPOURED IN PLACE WITH #4 EPOXY COATED REBARS4" C/C BOTH WAYS.

    PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    1.

    2.

    3.

    4.

    5.

    6.

    7.

    ALL JOINTS AND BRICK MASONRY SHALL BEPLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENTMORTAR TO MAKE THE STRUCTURE WATER TIGHT.

    PRECAST CONCRETE TOP SLAB TO BE USED WHEREHEAD ROOM IS REQUIRED.

    PROVIDE 2" SLOPE TOWARDS THE SUMP.

    PROVIDE 1/2 " THICK STEEL PLATE SUMP COVER.

    CENTER LINE

    8"

    4"

    9

    1-9"

    8"

    8"

    4"

    8"

    18

    "

    REV:04.07

    TYPICAL BLOW-OFF/FIRE CISTERN-MASONRY

    PLAN FM -18 SHT. 1 OF 2

  • PU

    GRADE

    1" EXPANSION MATERIAL

    MAXIMUM CORBEL= 1 1/2 "

    SLOPE

    FILL CA 16

    FILL CA 16

    SLOPE

    WATERMAIN

    45

    8" MJ VALVE

    3BMJ TEE

    1.

    2.

    3.

    4.

    5.

    NOTES:

    PROVIDE 6" THICK COMPACTED CA 16 BEDDING

    USE PRECAST CONCRETE BASE OR PROVIDE

    6" THICK IDOT CLASS SI CONCRETE BASE

    POURED IN PLACE WITH #4 EPOXY COATED REBARS

    4" C/C BOTH WAYS.

    PROVIDE FOUR #4 REBAR LUGS FOR HANDLING.

    CUT THE LUGS AFTER PLACING THE SLAB IN POSITION.

    ALL JOINTS AND BRICK MASONRY SHALL BE

    PLASTERED INSIDE AND OUTSIDE WITH 1:2 CEMENT

    MORTAR TO MAKE THE STRUCTURE WATER TIGHT.

    PRECAST CONCRETE TOP SLAB TO BE USED WHERE

    HEAD ROOM IS REQUIRED.

    >>

    >

    24"

    26"

    36" MAXIMUM

    TOP OF BASIN TO BE

    CORBELED AS SHOWN

    >

    USE CITY OF CHICAGO

    STANDARD FRAME WEIGHT 395 LBS.

    AND STANDARD LID WEIGHT 152 LBS.

    >

    5 DIA.

    CONCRETE OR

    BRICK MASONRY

    THRUST BLOCK

    REMOVE THE MJ PLUG

    TO DRAIN WATER

    FROM THE PIPE

    8"X8" MJ TEE

    VERTICAL

    W/MJ PLUG

    M.J.

    PLUG

    3

    MIN

    IMU

    M

    8"x 1/8 1BMJ BEND

    16"

    7

    24

    "

    CONCRETE

    BOTTOMCONCRETE OR

    BRICK MASONRY

    SUPPORT

    16" D.I.W.P.SUMP DRAIN

    3"

    3"

    6"

    6"

    VA

    RIA

    BL

    E

    REV:04.07

    TYPICAL BLOW-OFF/FIRE CISTERN-MASONRY

    SECTIONAL VIEW FM -18 SHT. 2 OF 2

  • PRECAST CONCRETE

    LUG

    GRADE

    FILL CA-16

    MASONRY SUPPORT

    WATER MAIN

    3BMJ TEE

    SECTIONAL VIEW

    PLAN

    8" MJ VALVE

    8" MJ CAP

    8" D.I. PIPE

    8"x 8"3BMJ TEE

    8" MJ PLUG

    6" THICK

    COMPACTED CA-16 BEDDING.

    8" D.I. PIPE

    8"x 1/8 1BMJ BEND

    USE CITY OF CHICAGOSTANDARD FRAME WEIGHT 395 Lbs.

    AND STANDARD LID WEIGHT 152 Lbs.

    45%%d

    26"

    23"

    21"

    24"

    5-0"

    5"

    5"

    TY

    PE

    "X

    " L

    AD

    DE

    R R

    UN

    GS

    16"

    O.C

    .

    6"

    6"

    VA

    RIA

    BL

    E

    6"

    REV:04.07

    TYPICAL BLOW-OFF/FIRE CISTERN

    PRECAST CONCRETE FM -19

    NOTE: INSTALL MEGALUGS ON ALL MECHANICAL JOINTS.

  • This page intentionally left blank.