STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory Department of Civil Engineering University of Engineering and Technology Lahore, 54890 Pakistan. Ph: 92-42-99029202 I/C Testing Laboratoires UET Lahore, Pakistan. Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples To, M/S Powertech Pakistan (Pvt) Limited Lahore (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # PT/Hroon.Com.P.Tech Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615 Sr. No. Weight Diameter/ Size (mm) Area (in 2 ) Yield load Breaking Load Yield Stress (psi) Ultimate Stress (psi) Elongation % Elongation Remarks (lbs/ft) Nominal Actual Nominal Actual (kg) (kg) Nominal Actual Nominal Actual (inch) 1 0.370 10 9.45 0.11 0.109 3000 4900 60200 60780 98200 99300 1.20 15.0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Note: only one sample for tensile and one sample for bend test Bend Test 10mm Dia Bar Bend Test Through 180º is Satisfactory
Transcript
Page 1: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, M/S Powertech Pakistan (Pvt) Limited Lahore (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # PT/Hroon.Com.P.Tech Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (mm)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.370 10 9.45 0.11 0.109 3000 4900 60200 60780 98200 99300 1.20 15.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile and one sample for bend test

Bend Test 10mm Dia Bar Bend Test Through 180º is Satisfactory

Page 2: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Operations Manager Velosi Integrity & Safety Pakistan Pvt. Ltd Lahore (Mughal Engineering) Reference # CED/TFL 30214 (Dr. Nauman) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 22-03-2018 Tension Test Report (Page – 1/1) Date of Test 03-04-2018 Gauge length 2 inches Description Welded Plate Tensile and Bend Test

Sr. N

o.

Des

igna

tion

Size

of S

trip

X S

ectio

n A

rea

Yie

ld lo

ad

Bre

akin

g L

oad

Yie

ld S

tres

s

Ulti

mat

e St

ress

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(mm) (mm2) (kN) (kN) (MPa) (MPa) (inch)

1 Welded Plate 24.95x5.95 148.45 -------- 78.20 -------- 526.77 0.45 22.50 Failure at the location other than weld

2 Welded Plate 24.40x5.90 143.96 -------- 77.40 -------- 537.65 0.40 20.00 Failure at the location other than weld

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

Only two samples for tensile and four samples for bend test

Bend Test Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Page 3: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, General Manager National Power Construction Corporation (Pvt) Limited Civil Works, Erection, Stringing, Testing & Commissioning of 500kV Transmission Lines Reference # CED/TFL 30215 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # NPCC/ADB-108-2017/E-83 Dated: 21-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght

Diameter/ size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.363 3 0.369 0.11 0.107 3400 5050 68200 70260 101200 104400 1.10 13.8

2 5.251 11 1.402 1.56 1.544 59200 76800 83700 84540 108600 109700 1.30 16.3

3 5.296 11 1.408 1.56 1.557 53200 69000 75200 75320 97500 97700 1.30 16.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only three samples for tensile and three samples for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory #11 Bar Bend Test Through 180º is Satisfactory #11 Bar Bend Test Through 180º is Failed

Witness by Zaigham Sohail (J.E. NESPAK)

Page 4: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer AZ Engineering Associates Sialkot Fly over at Sublime Chowk on Sialkot Wazirabad Road (Dist. Sialkot) (AFCO) Reference # CED/TFL 30216 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # RE/SKT-95 Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght

Diameter/ Size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.378 3 0.376 0.11 0.111 3100 5300 62200 61520 106200 105200 1.00 12.5

2 0.393 3 0.383 0.11 0.115 3300 5600 66200 63010 112300 107000 1.20 15.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and one sample for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory

Page 5: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer NESPAK M.Garh – D.G Khan Road (WMI) Reference # CED/TFL 30217(Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 3949/HA/02/56 Dated: 19-03-2018 Tension Test Report (Page – 1/4) Date of Test 27-03-2018 Gauge length 640 mm Description Steel Strand Tensile Test as per ASTM A-416-94a

Sr. N

o. Nominal

Diameter Nominal Weight

Measured weight

Yield strength clause (6.3)

Breaking strength clause

(6.2) You

ng’s

M

odul

us o

f E

last

icity

% E

long

atio

n

Rem

arks

/ C

oil N

o.

(mm) (kg/km) (kg/km) (kg) (kN) (kg) (kN) E, GPa

1 15.24 (0.6") 1102.0 1118.0 25000 245.25 27500 269.8 199 >3.50 5421

2 15.24 (0.6") 1102.0 1118.0 24500 240.35 27500 269.8 198 >3.50 5424

3 15.24 (0.6") 1102.0 1118.0 24900 244.27 27800 272.7 199 >3.50 5427

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

Only three samples for Test

Note: 1. Modulus of Elasticity is based on nominal steel area of the steel strand vide clause 13.3 of ASTM – A416a 2. Load versus percentage strain graphs are attached

Page 6: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer NESPAK M.Garh – D.G Khan Road Reference # CED/TFL 30217(Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 3949/HA/02/56 Dated: 19-03-2018 Graph (Page – 2/4)

Page 7: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer NESPAK M.Garh – D.G Khan Road Reference # CED/TFL 30217(Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 3949/HA/02/56 Dated: 19-03-2018 Graph (Page – 3/4)

Page 8: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer NESPAK M.Garh – D.G Khan Road Reference # CED/TFL 30217(Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 3949/HA/02/56 Dated: 19-03-2018 Graph (Page – 4/4)

Page 9: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Highway Sub Division Rajanpur (Annual Development Programme for The Year 2017-2018 – Construction of Pile Foundation Bridge at River Creek Malik Bahar Length: 570 Rft District Rajanpur) Reference # CED/TFL 30218 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 622/RP Dated: 22-01-2018 Tension Test Report (Page -1/2) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.409 3/8 0.391 0.11 0.120 3200 4950 64200 58670 99200 90800 1.70 21.3

2 0.411 3/8 0.392 0.11 0.121 3150 4950 63200 57540 99200 90500 1.60 20.0

3 4.102 10/8 1.239 1.27 1.206 49000 59400 85100 89570 103100 108600 1.40 17.5

4 4.099 10/8 1.239 1.27 1.205 48200 59200 83700 88180 102800 108400 1.40 17.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile and one sample for bend test

Bend Test 3/8" Dia Bar Bend Test Through 180º is Satisfactory 10/8" Dia Bar Bend Test Through 180º is Satisfactory

Page 10: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Highway Sub Division Rajanpur (Annual Development Programme for The Year 2017-2018 – Construction of Pile Foundation Bridge at Mulana Abdul Wahab Length: 510 Rft District Rajanpur) Reference # CED/TFL 30218 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 623/RP Dated: 23-01-2018 Tension Test Report (Page -2/2) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.408 3/8 0.391 0.11 0.120 3200 4950 64200 58880 99200 91100 1.60 20.0

2 0.412 3/8 0.393 0.11 0.121 3150 5000 63200 57330 100200 91000 1.40 17.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and one sample for bend test

Bend Test 3/8" Dia Bar Bend Test Through 180º is Satisfactory

Page 11: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, M/S KSS Engineering (Pvt) Limited Karach (CMPAK Project Site ID: 41847, 41855, 42056, 42276, 42309, 42342) Reference # CED/TFL 30220 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # KSS/Steel/200318/01 Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (mm)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.370 10 9.46 0.11 0.109 3000 4900 60200 60760 98200 99300 1.10 13.8

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile and one sample for bend test

Bend Test 10mm Dia Bar Bend Test Through 180º is Satisfactory

Page 12: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, M/S Maftel Networks Lahore (Project/Site ID: 41956, 41825, 41957) Reference # CED/TFL 30221 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 16-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (mm)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.371 10 9.47 0.11 0.109 3100 4850 62200 62570 97200 97900 1.30 16.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile test

Bend Test

Page 13: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Operations Manager Velosi Integrity & Safety Pakistan Pvt. Ltd Lahore (JESR-Al-Madina) Reference # CED/TFL 30222 (Dr. Nauman) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 22-03-2018 Tension Test Report (Page – 1/1) Date of Test 03-04-2018 Gauge length 2 inches Description Welded Plate Tensile and Bend Test

Sr. N

o.

Des

igna

tion

Size

of S

trip

X S

ectio

n A

rea

Yie

ld lo

ad

Bre

akin

g L

oad

Yie

ld S

tres

s

Ulti

mat

e St

ress

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(mm) (mm2) (kN) (kN) (MPa) (MPa) (inch)

1 Welded Plate 24.50x4.80 117.60 -------- 63.50 -------- 539.97 0.40 20.00 Failure at the location other than weld

2 Welded Plate 24.30x4.90 119.07 -------- 64.50 -------- 541.70 0.55 27.50 Failure at the location other than weld

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

Only two samples for tensile and four samples for bend test

Bend Test Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Page 14: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Operations Manager Velosi Integrity & Safety Pakistan Pvt. Ltd Lahore (Qadri Engineering) Reference # CED/TFL 30223 (Dr. Nauman) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 22-03-2018 Tension Test Report (Page – 1/1) Date of Test 03-04-2018 Gauge length 2 inches Description Welded Plate Tensile and Bend Test

Sr. N

o.

Des

igna

tion

Size

of S

trip

X S

ectio

n A

rea

Yie

ld lo

ad

Bre

akin

g L

oad

Yie

ld S

tres

s

Ulti

mat

e St

ress

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(mm) (mm2) (kN) (kN) (MPa) (MPa) (inch)

1 Welded Plate 25.00x6.15 153.75 -------- 82.20 -------- 534.63 0.35 17.50 Failure at the location other than weld

2 Welded Plate 24.25x5.95 144.29 -------- 78.50 -------- 544.05 0.25 12.50 Failure at the location other than weld

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

- - - - - - - - - - -

Only two samples for tensile and four samples for bend test

Bend Test Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Root) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Strip taken from Welded Plate (Face) Bend Test Through 180º is Satisfactory

Page 15: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division C.M Sectt; Lahore Construction of 02-Nos Class Rooms in Govt Primary School Kot Wadhawa Singh NA-129, Lahore . Reference # CED/TFL 30224 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # SDO/CMS/314 Dated: 10-02-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.408 3/8 0.391 0.11 0.120 2650 4050 53100 48660 81200 74400 1.40 17.5

2 0.377 3/8 0.375 0.11 0.111 2500 3900 50100 49770 78200 77700 1.30 16.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and two samples for bend test

Bend Test 3/8" Dia Bar Bend Test Through 180º is Satisfactory 3/8" Dia Bar Bend Test Through 180º is Satisfactory

Page 16: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, M/S Defence Housing Authority. Lahore Cantt (Infra Dev Works (Pkg II & III) DHA Ph-VIII)(M/s NLC) Reference # CED/TFL 30225 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 408/241/E/Lab/115/7088 Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght

Diameter/ size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.379 3 0.377 0.11 0.111 3600 4700 72200 71230 94200 93000 1.00 12.5

S.J

Stee

l

2 0.375 3 0.375 0.11 0.110 3700 4800 74200 73980 96200 96000 0.90 11.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and one sample for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory

Page 17: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, M/S Shahzad & Co Sheikhupura Reference # CED/TFL 30226-229 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 22-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (mm)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.382 10 9.61 0.11 0.112 3850 4900 77200 75520 98200 96200 0.80 10.0

2 0.383 10 9.62 0.11 0.113 4100 5100 82200 80290 102200 99900 0.80 10.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 18: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division No. 2 Lahore Construction of Dangerous Class Room Blocks at Government Girls Middle School at Begum Pura, Lahore Reference # CED/TFL 30227 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 423/2nd Dated: 16-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.364 3/8 0.369 0.11 0.107 3000 3700 60200 61880 74200 76400 1.50 18.8

2 0.364 3/8 0.369 0.11 0.107 2250 2850 45100 46290 57200 58700 1.70 21.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 19: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Site Incharge Akhuwat University, Kasur Akhuwat University Mustafa abad Faculty & Boys Hostel and Academic Block Construction Reference # CED/TFL 30230 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # Nil Dated: 12-02-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght

Diameter/ size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.380 3 0.377 0.11 0.112 4400 5200 88200 86890 104200 102700 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile and one sample for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory

Page 20: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Execuitve Engineer Highway Division Chiniot (Widening/Improvement of Road from District Boundary Chiniot near Kallar wala to Nalka Adda via Mouza Sulman, Rehmanabad, Length 27.50 km (Phase-1, km No. 0.00 to 2.50, Length 2.50 km), District Chiniot Reference # CED/TFL 30231 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 639/C Dated: 14-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.376 3/8 0.375 0.11 0.110 3700 4750 74200 73810 95200 94800 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only one sample for tensile and one sample for bend test

Bend Test 3/8" Dia Bar Bend Test Through 180º is Satisfactory

Page 21: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Assistant Director (Engg) Model Town Zone WASA (GDA) Gujranwala Sewerage/Drainage at Jinnah Road, Raja Colony, Gulzar Colony, Khokharki, Satelite Town, Pasrur Road, Model Town, Islamabad, Kotly Rustam, Hafizabad Road, Garjakh and Allied Areas Gujranwala (Group-III) Reference # CED/TFL 30232 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # WASA/ADE/MTZ/32 Dated: 19-02-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.145 3/16 0.233 ----- 0.043 1100 1400 ----- 56890 ----- 72500 1.50 18.8

2 0.215 1/4 0.284 ----- 0.063 2250 3100 ----- 78390 ----- 108100 1.20 15.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and two samples for bend test

Bend Test 3/16" Dia Bar Bend Test Through 180º is Satisfactory 1/4" Dia Bar Bend Test Through 180º is Satisfactory

Page 22: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 18 Ex-HQ 30 Corps (HQ Arty 30 corps/HQ Long Corps) at Gwa Cantt)(M/s Siddique Iqbal & Co) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1965/7/E-6 Dated: 22-03-2018 Tension Test Report (Page -1/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.402 3/8 0.388 0.11 0.118 3200 5300 64200 59720 106200 99000 1.40 17.5

2 0.395 3/8 0.384 0.11 0.116 3100 5100 62200 58890 102200 96900 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 23: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 20 Ex-HQ 30 Corps (HQ Sig 30 Corps /HQ Log 30 Corps ) at Gwa Cantt) (M/s H & S Construction Company) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1963/6/E-6 Dated: 22-03-2018 Tension Test Report (Page -2/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.373 3/8 0.374 0.11 0.110 3950 5000 79200 79320 100200 100400 1.00 12.5

2 0.374 3/8 0.374 0.11 0.110 4150 5100 83200 83280 102200 102400 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 24: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 17 Ex-HQ 30 Corps (HQ Arty 30 corps/ HQ Log 30 Corps) at Gwa Cantt)(M/s Siddique Iqbal & Co) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1966/8/E-6 Dated: 22-03-2018 Tension Test Report (Page -3/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.340 3/8 0.357 0.11 0.100 2300 3300 46100 50710 66200 72800 1.20 15.0

2 0.346 3/8 0.360 0.11 0.102 2600 3800 52100 56340 76200 82400 1.40 17.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 25: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 05 Ex-HQ 30 Corps (HQ 2 Arty) at Gwa Cantt)(M/s Malik Builders & Co) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1961/7/E-6 Dated: 22-03-2018 Tension Test Report (Page -4/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.378 3/8 0.376 0.11 0.111 4200 5100 84200 83330 102200 101200 1.00 12.5

2 0.375 3/8 0.375 0.11 0.110 3800 4900 76200 75960 98200 98000 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 26: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 04 Ex-HQ 30 Corps (HQ 2Arty) at Gwa Cantt)(M/s Malik Builders & Co) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1968/8/E-6 Dated: 22-03-2018 Tension Test Report (Page -5/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.375 3/8 0.374 0.11 0.110 3800 4800 76200 76070 96200 96100 1.10 13.8

2 0.376 3/8 0.375 0.11 0.110 3900 4900 78200 77830 98200 97800 1.00 12.5

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 27: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Gujranwala Cantt (Const of 8x NCsE Block No. 24 Ex-HQ 30 Corps (11 Army Avn) at Gwa Cantt)(M/s A.Q Enterprises) Reference # CED/TFL 30233 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 6180/1967/8/E-6 Dated: 22-03-2018 Tension Test Report (Page -6/6) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.379 3/8 0.377 0.11 0.112 3900 4950 78200 77090 99200 97900 1.00 12.5

2 0.375 3/8 0.375 0.11 0.110 3800 4800 76200 75980 96200 96000 1.30 16.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 28: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer NESPAK Orange Metro Line Project Lahore Package 3 (Dera Gujjran) Reference # CED/TFL 30234 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 3765/03/OLMTP/MMK/157 Dated: 22-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Plain Steel Bar Tensile and Bend Test

Sr. N

o.

Wei

ght

Diameter/ size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.411 3 0.392 ------ 0.121 3400 4600 ------ 61970 . 83900 1.40 17.5

2 0.413 3 0.393 ------ 0.121 3000 4550 ------ 54470 ------ 82600 1.50 18.8

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and one sample for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory

Page 29: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Garrison Engineer (Army)-II Sialkot Cantt (Const of 8x Sldrs Flat Block No. 1 at AD Line SIK Cantt) Reference # CED/TFL 30235 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 2026/161/E-6 Dated: 21-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.374 3/8 0.374 0.11 0.110 2050 2800 41100 41110 56200 56200 1.90 23.8

2 0.374 3/8 0.374 0.11 0.110 2050 2800 41100 41130 56200 56200 1.90 23.8

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile and one sample for bend test

Bend Test 3/8" Dia Bar Bend Test Through 180º is Satisfactory

Page 30: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division Narowal Construction of Government Shelterless Primary School Nagray District Narowal Re-Construction of Govt Girls Primary School Sadiqabad District Narowal Reference # CED/TFL 30236 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 1440/NL Dated: 13-03-2018 Tension Test Report (Page -1/2) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.380 3/8 0.377 0.11 0.112 4100 5000 82200 80920 100200 98700 0.90 11.3

2 0.380 3/8 0.377 0.11 0.112 4200 5050 84200 82860 101200 99700 0.90 11.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 31: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division Narowal Construction of Government Shelterless Primary School Langiya District Narowal Reference # CED/TFL 30236 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 1439/NL Dated: 13-03-2018 Tension Test Report (Page -2/2) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.377 3/8 0.376 0.11 0.111 4300 5150 86200 85570 103200 102500 0.90 11.3

2 0.380 3/8 0.377 0.11 0.112 4200 5150 84200 82900 103200 101700 0.90 11.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 32: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division Shakararh Re-Construction of Dangerous School Building Govt Girls Primary School Bhajna Tehsil Shakargarh Reference # CED/TFL 30237 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 812/Sg Dated: 20-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.382 3/8 0.378 0.11 0.112 4300 5250 86200 84460 105200 103200 1.00 12.5

2 0.382 3/8 0.378 0.11 0.112 4300 5200 86200 84460 104200 102200 0.80 10.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 33: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Resident Engineer Dar Engineering Punjab Agriculture Food and Durg Authority’s Science Enclave, Lahore Pakistan Reference # CED/TFL 30238 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # DB-78/DAR/RE/ME/2018/0043 Dated: 22-03-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile and Bend Test as per ASTM-A615

Sr. N

o.

Wei

ght

Diameter/ size

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

(#

)

Act

ual

(inch

)

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.369 3 0.372 0.11 0.108 3600 4800 72200 73180 96200 97600 1.00 12.5

M-0

2

2 0.376 3 0.375 0.11 0.110 3800 5100 76200 75860 102200 101800 0.90 11.3

3 0.373 3 0.374 0.11 0.110 3700 4900 74200 74350 98200 98500 0.75 9.4

M-0

9

4 0.372 3 0.373 0.11 0.109 3750 4900 75200 75520 98200 98700 0.90 11.3

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only four samples for tensile and two samples for bend test

Bend Test #3 Bar Bend Test Through 180º is Satisfactory #3 Bar Bend Test Through 180º is Satisfactory

Page 34: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Sub Divisional Officer Buildings Sub Division No. 2 Lahore Construction of Multipurpose Hall and 12-Nos Class Rooms at First & Third Floor at Govt, Girls High School Charrar Lahore Cantt N.A 125. Reference # CED/TFL 30228 (Dr. Qasim Khan) Dated: 22-03-2018 Reference of the request letter # 361-B/2nd Dated: 21-02-2018 Tension Test Report (Page -1/1) Date of Test 26-03-2018 Gauge length 8 inches Description Deformed Steel Bar Tensile Test as per ASTM-A615

Sr. N

o.

Wei

ght Diameter/

Size (inch)

Area (in2)

Yie

ld lo

ad

Bre

akin

g L

oad Yield Stress

(psi) Ultimate Stress

(psi)

Elo

ngat

ion

% E

long

atio

n

Rem

arks

(lbs/

ft)

Nom

inal

Act

ual

Nom

inal

Act

ual

(kg) (kg)

Nom

inal

Act

ual

Nom

inal

Act

ual

(inch

)

1 0.352 3/8 0.363 0.11 0.103 2400 3250 48100 51130 65200 69300 1.70 21.3

2 0.375 3/8 0.375 0.11 0.110 2300 3200 46100 46020 64200 64100 1.60 20.0

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

- - - - - - - - - - - - - -

Note: only two samples for tensile test

Bend Test

Page 35: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Chief Resident Engineer Osmani & Co. (Pvt) Ltd Swat Motorway Project Reference # CED/TFL 30239 (Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 100/CRE/SMP/2018 Dated: 21-03-2018 Tension Test Report (Page – 1/4) Date of Test 27-03-2018 Gauge length 640 mm Description Steel Strand Tensile Test as per ASTM A-416-94a

Sr. N

o. Nominal

Diameter Nominal Weight

Measured weight

Yield strength clause (6.3)

Breaking strength clause

(6.2) You

ng’s

M

odul

us o

f E

last

icity

% E

long

atio

n

Rem

arks

/ C

oil N

o.

(mm) (kg/km) (kg/km) (kg) (kN) (kg) (kN) E, GPa

1 12.70 (1/2”) 775.0 783.0 17800 174.62 20400 200.1 199 >3.50 236

2 12.70 (1/2”) 775.0 782.0 18000 176.58 19500 191.3 199 >3.50 242

3 12.70 (1/2”) 775.0 782.0 17800 174.62 19600 192.3 199 >3.50 249

- - - - - - - - - -

- - - - - - - - - -

- - - - - - - - - -

Only three samples for Test

Note: 1. Modulus of Elasticity is based on nominal steel area of the steel strand vide clause 13.3 of ASTM – A416a 2. Load versus percentage strain graphs are attached

Page 36: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Chief Resident Engineer Osmani & Co. (Pvt) Ltd Swat Motorway Project Reference # CED/TFL 30239 (Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 100/CRE/SMP/2018 Dated: 21-03-2018 Graph (Page – 2/4)

Page 37: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Chief Resident Engineer Osmani & Co. (Pvt) Ltd Swat Motorway Project Reference # CED/TFL 30239 (Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 100/CRE/SMP/2018 Dated: 21-03-2018 Graph (Page – 3/4)

Page 38: STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory ... · (Usf Small lot Khyber Project - Ufone Site ID: 5506) Reference # CED/TFL 30213 (Dr. Qasim Khan) Dated: 22-03-2018 Reference

STRUCTURAL ENGINEERING DIVISION Test Floor Laboratory

Department of Civil Engineering University of Engineering and Technology Lahore, 54890

Pakistan. Ph: 92-42-99029202

I/C Testing Laboratoires UET Lahore, Pakistan.

Note: 1- You can See your reports On Internet in the following web site http://www.uet.edu.pk/faculties/facultiesinfo/civil/index.html?RID=testing_reports 2. The above results pertain to sample /samples supplied to this laboratory. 3- Sealed sample / Unsealed sample / Marked sample/Signed Samples

To, Chief Resident Engineer Osmani & Co. (Pvt) Ltd Swat Motorway Project Reference # CED/TFL 30239 (Dr. M Rizwan Riaz) Dated: 22-03-2018 Reference of the request letter # 100/CRE/SMP/2018 Dated: 21-03-2018 Graph (Page – 4/4)


Recommended