Study Committee B2Technical Advisory Group B2-AG-06
Ci T t i lCigre Tutorial
BangkokBangkok 28 February, 2011
Cigre TutorialCigre Tutorial
Fittings for Optical Cables –Selection, Test and Assessment,
SCB2, WG11, TF3 reports – Fittings for Optical Cable on Overhead LinesCable on Overhead Lines
Results of Questionnaire – Electra 165Results of Questionnaire Electra 165Guide to Selection & Use – Electra 176 Guide to Testing Procedures for OPGW & OPPC gfittings – Electra 188 Guide to Testing Procedures for ADSS & OPAC fittings
Electra 191– Electra 191
Study Committee B2 - Technical Advisory Group B2-AG-06
T d D fi iti O ti l C blTypes and Definitions - Optical Cable on Overhead Lines
OPGW – Optical Ground WireADSS – All Dielectric Self Supporting cable pp gOPAC – Optical cable wrapped, lashed or clipped to ground wire or conductor (Attached)OPPC – Optical Phase Conductor (OPCON)
Study Committee B2 - Technical Advisory Group B2-AG-06
Typical Optical Ground Wire (OPGW) Installation
OPGWTypical OPGW Cable Construction
Aluminium Spacer
Buffer Tube
Optical Fibres
Aluminium Clad Steel Wire
Aluminium Barrier Tape
Study Committee B2 - Technical Advisory Group B2-AG-06
Typical All Dielectric Self Supporting (ADSS) installation
Typical ADSS Cable ConstructionBuffer Tube
Aramid Yarn Layer
Central Member
Optical Fibres
Outer Sheath
Inner Sheath
ADSS Cable
Study Committee B2 - Technical Advisory Group B2-AG-06
Typical OPAC Optical Cable (attached) Installation
EarthwireTape or Spiral Clip
Lashed CableLashed CableTypical Lashed Cable Construction
Buffer Tube
Optical Fibres
St th M b
Outer Sheath
Strength Members
Study Committee B2 - Technical Advisory Group B2-AG-06
Questionnaire - Fittings for Optical Cable on Overhead LinesOverhead Lines
Circulated via SCB2 National members66 replies received from Utilities in Australia (4), Asia66 replies received from Utilities in Australia (4), Asia (4), Europe (37), North America (17) & South America (4)Drawings of typical fittings included in QuestionnaireDrawings of typical fittings included in QuestionnaireQuestionnaire did not address Optical Phase Conductor (OPPC)
Study Committee B2 - Technical Advisory Group B2-AG-06
Typical Suspension Clamps for Optical Cable on Overhead Lines
Bolted
Armour Grip (AG)
Study Committee B2 - Technical Advisory Group B2-AG-06
Armour Grip (AG)
Typical Tension Clamps for Optical Cable on Overhead Lines
Helicale ca
ConicalBolted
Study Committee B2 - Technical Advisory Group B2-AG-06
Typical Vibration Dampers for Optical Cable on Overhead Lines
Stockbridge
BretelleImpact
Study Committee B2 - Technical Advisory Group B2-AG-06
Results of Questionnaire - Fittings for Optical Cable on Overhead Lines
5060
40
50Bolted suspensionAG suspension
2030 AG suspension
Bolted deadendConical deadend
010
OPGW OPAC ADSS
Conical deadendHelical deadend
Study Committee B2 - Technical Advisory Group B2-AG-06
Results of Questionnaire - Fittings for Optical Cable onResults of Questionnaire - Fittings for Optical Cable on Overhead Lines
40
30 StockbridgeImpact damper
10
20 Impact damperBretelleOther
0OPGW OPAC ADSS
OtherNone
Study Committee B2 - Technical Advisory Group B2-AG-06
R l f Q i i OPAC O i l C blResults of Questionnaire - OPAC Optical Cable on Overhead Lines
WRAPPEDWRAPPED57%LASHED 29%CLIPPED 14%14%
Study Committee B2 - Technical Advisory Group B2-AG-06
Results of Questionnaire – Operating Experience
30
40
20
30 OPAC
ADSS
10 OPGW
0No
problemMinor
problemcable
Minorproblemfittings
Majorproblem
cable
Majorproblemfittings
Study Committee B2 - Technical Advisory Group B2-AG-06
Results of Questionnaire - Test Standard, Fittings for Optical Cable
20
15
20NoneSuppliers Standard
10In-house StandardNational Standard
0
5
Study Committee B2 - Technical Advisory Group B2-AG-06
0OPGW Attached ADSS
Fittings for Optical Cable on Overhead Lines
Results of Questionnaire was published in Electra No 165Task Force continued work - Guide to Selection & Use of Fittings for optical cable on overhead lines
Study Committee B2 - Technical Advisory Group B2-AG-06
Selection and Use - Fittings for Optical Cable on Overhead Lines
Fittings for OPGW -Suspension clampsTension (dead end) clamps
Fittings for ADSS -Suspension clampsTension (dead end) clampsTension (dead-end) clamps
Aeolian vibration dampers Anti-galloping devicesAircraft Warning Markers
Tension (dead-end) clampsAeolian vibration dampers Anti-galloping devicesDownlead clampsAircraft Warning Markers
Grounding connectorsJumper connectorsDownlead clamps
Downlead clamps
Fittings for OPAC –R ti fitti lDownlead clamps Routing fittings only
Study Committee B2 - Technical Advisory Group B2-AG-06
Selection and Use - Fittings for Optical Cable on Overhead Lines
TYPE USE FITTINGOPGW Longer spans Helical dead-end
All voltagesNew build lines
AG SuspensionStockbridge damper
ADSS Shorter spans Helical deadendADSS Shorter spans< 150 kVExisting lines
Helical deadendAG SuspensionImpact damper
OPAC All earthwires Routing fittings only
Study Committee B2 - Technical Advisory Group B2-AG-06
Fittings for Optical Cable on Overhead Lines
Guide to Selection and Use was published in Electra No 176in Electra No 176Task Force continued work - Guide to Testing Procedures, Fittings for OPGW,Testing Procedures, Fittings for OPGW, OPPC, OPAC and ADSS optical cable
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Terms and DefinitionsMFL – Mechanical Failure LoadRTS – Rated Tensile StrengthSMWT* – Specified Maximum Working Tension Also known as gMAT* – Max Allowable Tension or MRCL* – Max Rated Cable LoadEDT – Every Day Tension nm – nanometre (optical wavelength) dB/k d ib l/k ( ti l l )dB/km – decibel/km (optical loss)
* Max tensile load that may be applied to cable in service with an optical attenuation increase < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Procedures - Fittings for OPGW on Overhead LinesLines
TENSION FITTINGTensile load*
SUSPENSION FITTINGVertical load/turning angle*
Aeolian vibration fatigue*Galloping fatigue*Fault current
Aeolian vibration fatigue*Galloping fatigue*Fault current Unbalanced load to IEC 61284
* Increase in optical atten ation hen loaded p to SMWT < 0 05 dB/km at* Increase in optical attenuation when loaded up to SMWT < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Optical SchematicMonitoring optical signal by concatenating fibres in one continuous loop
Study Committee B2 - Technical Advisory Group B2-AG-06
Tension Test
Load cable to a minimum of 50% RTS while monitoring optical signal losswhile monitoring optical signal loss.
8m
Study Committee B2 - Technical Advisory Group B2-AG-06
Aeolian Vibration TestVibrate cable at resonant frequency between 20-70 Hz at an anti-node loop velocity of 500mm/s for 100,000,000 cycles while monitoring optical signal losscycles while monitoring optical signal loss
Study Committee B2 - Technical Advisory Group B2-AG-06
Turning Angle TestTension cable to Specified Maximum Working Tension (SMWT) at maximum angle while monitoring optical signal losssignal loss
Study Committee B2 - Technical Advisory Group B2-AG-06
T t P d Fitti f OPGW O h dTest Procedures - Fittings for OPGW on Overhead Lines
VIBRATION DAMPER ANTI-GALLOPING DEVICEVIBRATION DAMPERApplication test*Reference to IEC 61897 for Stockbridge dampers
ANTI-GALLOPING DEVICEApplication test*Required to limit galloping
Damper should control vibration to Anti-node velocity < 500 mm/sec
AIRCRAFT WARNING DEVICEApplication test*
DOWNLEAD CLAMPGROUND CONNECTORS DOWNLEAD CLAMPApplication test*
GROUND CONNECTORSApplication test*
* Increase in optical attenuation when loaded up to SMWT < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Procedures - Fittings for OPPC on Overhead Lines
TENSION FITTINGAs OPGW plus
Corona and RIV
SUSPENSION FITTINGAs OPGW plus
Corona and RIV
VIBRATION DAMPERAs OPGW plus
Corona and RIV
ANTI GALLOPING DEVICEAs OPGW plus
Corona and RIV
JUMPER CONNECTORSAs OPGW plus
Corona and RIV
DOWNLEAD CLAMPAs OPGW plus
Corona and RIVCorona and RIV Corona and RIV
PHASE TO EARTH INSULATOR
Study Committee B2 - Technical Advisory Group B2-AG-06
PHASE TO EARTH INSULATOR
Fittings for Optical Cable on Overhead Lines
Guide to Testing Procedures of Fittings for OPGW & OPPC was published in Electra No 188OPPC was published in Electra No 188Guide to Testing Procedures of Fittings for OPAC & ADSS optical cable was published in Electra No 191
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Procedures - Fittings for ADSS cable on Overhead LinesOverhead Lines
TENSION FITTINGUltimate Tensile load
SUSPENSION FITTINGVertical load/turning angle*
Optical tensile load*Elevated temperature*Aeolian vibration fatigue*
Vertical load/turning angleAeolian vibration fatigue*Galloping fatigue*Unbalanced loadg
Galloping fatigue*Unbalanced load
> SMWT-EDT < SMWT-EDT2
* Increase in optical attenuation when loaded up to SMWT < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Elevated Temperature TestRaise cable temperature to 70°C and load to Every D T i (EDT) f 24Day Tension (EDT) for 24 hours
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Procedures - Fittings for ADSS cable on Overhead Lines
VIBRATION DAMPERApplication test*Reference to IEC 61897 for
ANTI-GALLOPING DEVICEApplication test*Required to limit galloping
Stockbridge dampersRequirement for performance Standard for Impact dampers on ADSS cables
q g p g
ARC SUPPRESSION DEVICERequired to withstand vibration and galloping testADSS cables test
DOWNLEAD CLAMPApplication test*
* Increase in optical attenuation when loaded up to SMWT < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Test Procedures - Fittings for OPAC cable on Overhead LinesOverhead Lines
Routing effectivenessClamping*Abrasion (vibration & combined cyclic motion)*Abrasion (vibration & combined cyclic motion)Fault conditionsWeathering, ageing and pollution resistanceMechanical loading*Mechanical loadingMovement controlElectrical tests
* Increase in optical attenuation when loaded upto SMWT < 0 05 dB/km at Increase in optical attenuation when loaded upto SMWT < 0.05 dB/km at 1550 nm
Study Committee B2 - Technical Advisory Group B2-AG-06
Related Standards on Testing of Fibre Optic Cable and FittingsFittings
IEEE 1138 – OPGWIEEE 1222 – ADSSIEEE 1591 – Fittings for Optical CablesIEEE 1591 – Fittings for Optical CablesBS EN 187200 Optical cables to be used along electrical power lines (OCEPL)IEC 61284* Overhead Lines FittingsIEC 61284* Overhead Lines FittingsIEC 61897* Stockbridge type Aeolian vibration dampers* For standard , non-fibre fittings
Study Committee B2 - Technical Advisory Group B2-AG-06
AcknowledgementsSpecial recognition to Tom Smart, TF Convenor TF3 members during period of optical fibre reports - H Argasinska, A Berg, U Cosmai, K Halsen, D Havard, D Hearnshaw, R Kleveborn, S Mikkelsen M Mito F Morentin M Muggiasca J Schmidt M St LouisMikkelsen, M Mito, F Morentin, M Muggiasca, J Schmidt, M St-Louis, D Sunkle, R Sutehall, W TroppauerFrom - Cable and Fitting manufacturers, Consultants and UtilitiesSpecial Contributors – T Alderton, G Diana & M Ervik CIGRE reviewers – K Papailiou and F TavanoWG11 Convenors – D Havard and K Papailiou
Study Committee B2 - Technical Advisory Group B2-AG-06