117700
STYLE 3350 TUCKAWAY™ ELECTRIC MONITORINSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS
The following is intended to provide the basic instructions for installation, operation and maintenance of the TuckAway electric monitor, and to assist in attaining the best possible performance from the unit. Read and understand these operating instructions before use.
TOOLS REQUIRED •UtilityKnife •Mediumflatscrewdriver •MediumPhillipsscrewdriver •Smallflatscrewdriver •SmallPhillipsscrewdriver • 1/2 inch hex head wrench •Electrician’spliers(multipurpose,strippingandcrimping)
PRODUCT RATINGSMaximumMotorCurrentDraw: 12 volt versions 14.0 amps each for elevation and rotation motors 3.0 amps for nozzle pattern motor 24 volt versions 7.5 amps each for elevation and rotation motors 1.5 amps for nozzle pattern motor
NormalOperatingCurrent: (Dependingonoperatingconditions–pressure,flow,etc.) 12 volt versions 3.0 to 10.0 amps each for elevation, rotation, and stow motors 0.7 amps for nozzle pattern motor 24 volt versions 2 - 5 amps each for elevation and rotation motors 0.4 amps for nozzle pattern motor
MinimumVoltage:(Truckenginemustbeoperatingforpropervoltagerequirement.) All12voltmotors:11.5voltswhileoperating All24voltmotors:23voltswhileoperating
MaximumFlow:1000gpm(3800lpm)
MaximumPressure:200psi(14bar)
PRODUCT WARNINGSWARNING: Forfirefightinguseonlybytrainedfirefighters.WARNING: Chargetheunitslowly.Rapidchargingmaycauseapressuresurgethathasthepotentialtocausean
injury, or damage the monitor. WARNING: DONOTstowordeploytheTuckAwaymonitorwhileflowing.Pressingthestowordeploybuttons
causesthenozzletomoveautomaticallyandthewaterstreammaycausedamagetoequipmentor injury to personnel could result.
WARNING: Aimtheunitinasafedirectionbeforepumpingwaterthroughit.(i.e.Awayfrompowerlines)WARNING: Although the logic circuit board includes a water-resistant coating, it is important to keep water out
ofthecontrolandlogicboxes.Prolongedexposuretowaterwillcausedamage.Whenthecoverof the control or logic box is removed, check that the O-ring under the cover is intact and free of dirt and debris.
WARNING: TheTuckAwaymonitorusescurrentlimitingforboththemonitorandnozzle.Useonlyappropriate AkronBrassCompanynozzles.
WARNING: Donotusetheelectriccontrolswhentheoverridecranksarebeingusedorareinpositionforuse.WARNING: Replace the identification tags if they should become worn or damaged.WARNING: DONOTexceedthemaximumpressureorflowratingsofthemonitor.Exceedingtheseratingsmay
lead to an injury or may cause damage to the monitor.WARNING: DONOTinstallshutoffsontheoutletoftheTuckAwayelectricmonitor.Shutoffsincreasethe
potential for pressure surges due to water hammer, which have the potential to cause an injury or damage the monitor.
WARNING: Ifnotequippedwithanautomaticdrainvalve,draintheTuckAwaymonitorafterusetoprevent “freeze damage”.
WARNING: Ensurethethreadonthenozzleswivelmatchesthethreadonthemonitoroutlet.Donotover tighten the nozzle onto the unit.
WARNING: The TuckAway monitor, nozzle, logic box, control box, tether controller, and field adjustable stops are madeforoptimalperformance.Donotalterinanymanner.
WARNING: EnsurethattheTuckAwayisreturnedtothestowpositionafteruse.WARNING: TheTuckAwaymonitorwasdesignedforusewiththeAkromaticnozzle.Useofanyothernozzle
could affect the speed or operation of the unit and should be tested before being put into service.WARNING: Maketheconnectionofthevehicleandauxiliarybatterythefinalstep.
MECHANICAL MONITOR ATTACHMENTWARNING: NSUFFICIENTSTRUCTURALSUPPORTCANLEADTOFAILURE,WHICHHASPOTENTIALTOCAUSE
ANINJURY.THEREFORE,ADDITIONALSTRUCTURALSUPPORTATTHEINLETFLANGEORATTHE INLETELBOW(Figure1)MAYBEREQUIRED.(ContactAkronBrassCustomerServiceforassistance.)
The TuckAway monitor is to be mounted on the waterway with eight 5/8” bolts and nuts of grade five minimum and suitable washers with a minimum of six threads engagement. The bolts must be tightened in a criss-cross pattern progressively increasing tightening torquetoamaximumof100lb.ft.dry.
ROTATIONAL STOPSThe rotational stops set the boundaries for the area that the monitor is allowed to travel. The monitor is shipped with a stop in location2whichgivesa90°clockwiseand90°counter-clockwiserotation(SeeFigure2).The45°clockwiseand45°counter-clockwiserotation is achieved by adding stops in location 1 & 3 and a plug in location 2. Both the plugs and the stops have a 1/2” hex head. Refer toFigure2todeterminewhichstoplocationisneededforthedesiredrotation.AlsosetDIPSwitch4ONif±45°rotation is desired.
VERTICAL STOPThe vertical stop will limit the elevation of the outlet. The monitor is shipped with a vertical elevation of 30° above horizontal. The monitor can be changed to 90° above horizontal by replacing the stop with the 3/4” hex head plug in the 30° stop location (SeeFigure2).
MECHANICAL ATTACHMENT OF CONTROLLER AND LOGIC BOXA.CONTROLLERANDTETHERCONNECTORATTACHMENT
MountingholedimensionsaregiveninFigure3.Thecontrollerandtetherconnectorshouldbeinstalledpriortoelectricalconnection to the logic box.
B.LOGICBOXATTACHMENTThe TuckAway logic box must be mounted close enough to the monitor to allow the wiring harness to reach the monitor. The logicboxoveralldimensionsandmountingholedimensionsaregiveninFigure4.
2
11
Figure 4
TOVEH
ICLEBAT
TERY
(POW
ER&G
ROUN
D)
20-
10CAB
LETO
VEH
ICLEM
ULTIPL
EXSY
STEM
BATT
ERY(+1
2V)
GROUN
D
16-10
CAB
LEX66
"
WIRIN
GHA
RNES
S
LOGI
CBO
X
5 3/
4
4.62
5
8.312
10
Figure 3
Figure 3a
BEFOREUSEREADOPERATINGINSTRUCTIONS
RAISE
FOG LEFT LOWER
RIGHTSSDEPLOY
STOW
96"
6"
VIEWA-A
MOUNTINGDIMENSIONS
13/8
16 29/32
6.402 1/4
2.025
37/64
#10SOCKETHEADCAPSCREWMOUNTINGHOLESSIZEDTOFIT
.375
3 11/64
2 17/64
A
A
3 7/64
WHILEFLOWINGWATERDONOTDEPRESSSTOWORDEPLOY
VIEWA-A
FOG
SS
LEFT
RIGHT
RAISE
LOWER
COMMON
BROWNBLACK
BLUE
GREENYELLOW
RED
WHITE
96INCHES
#20-7CABLE
6
TYP4
CLEARANCEFORCONNECTORFLANGE
1 9/32
1 9/32
`1HOLE
PANELMOUNTINGDIMENSIONS
#4-40UNCTAPPEDHOLE
.969
.969
GB
CD
E
FA
3
ELECTRICAL INSTALLATION INSTRUCTIONSA. CONTROLLERORTETHERCONNECTORELECTRICALATTACHMENT
These instructions are for attaching the controller or the tether connector to the logic box. The controller and tether connector aresuppliedwith8ft.ofcable.
STEP 1 Determinethelengthofcableneededtoreachthelogicbox,add6”andthencuttheremainderoff.
STEP 2 Removethecablegripnutfortheappropriatecablefromthelogicbox,DONOTREMOVETHECABLEGRIP.Thread cable grip nut on the cable with the threads facing out. On the same end of the cable, remove 6 inches of theoutercasingofthecableandstripback3/8”fromeachofthewires(SeeFigure3).
STEP 3 Loosenthe4logicboxcoverscrewsandsetthelogicboxcoveraside.Threadthewiresthroughthe“controlboxhole”inthelogicbox(seeFigure4).Pullenoughcablethroughthecablegriptoensureagoodfit.Tightenthecablegripnutandattachtheindividualwirestotheproperterminals(seewiringdiagram,Figure5).Note:Thecontrollerandthetetherconnectorcanbeattachedtoeitherterminal:Master(TB2)orSlave(TB3).TheoneattachedtotheMaster(TB2)terminalwillhavetheoverridingcapabilities.AdjusttheDIPswitchsettingsasneeded.(Refertothedescriptionbelow).Reattachthelogicboxcoverandsecurewiththe4screws.
B.DIPSWITCHSETTINGSTheDIPswitchesarelocatedinthelogicboxonthecircuitboard.
Theswitchesarefactorysetat:
Switch1- Allowsthenozzletoautomaticallyreturntothestowedpositionifthenozzledriftsduetovibrationsfromdriving on the road.
Switch2- AllowstheStowandDeployswitchtobeamomentaryoramaintainswitch.
ON-RequiresJOG(maintain)toStoworDeploy(NoLearnModeifDIP2isON) OFF-MomentaryswitchtostarttheStoworDeploysequence(factoryset)
Switch3- Allowstherotation,leftandright,tobelimitedto45°or90°(measuredfromcenter)intheelevationrangefromtheinitialDeployedposition(45°belowhorizontal)to90°belowhorizontal.(SeeFigure2)
ON-Stopsat45°rotationleftandright(factoryset).Tolimitthenozzlefromstriking theladder.(WilloverrideSwitch4-OFF) OFF-Allows90°rotationleftandright
Switch4- Allowstherotation,leftandright,tobelimitedto45°or90°(measuredfromcenter)intheentireelevationrangefromtheinitialDeployedpositiontotheupperlimitdependingonDIPSwitch3.(SeeFigure2)
ON-Stopsat45°rotationleftandright(alsochangestops,seeRotationalStops) (willoverrideSwitch3-OFF) OFF-Allows90°rotationleftandright(factoryset)
Switch5- AllowsthenozzletoreturntostraightstreamduringtheStowsequence.
ON-ReturnsthenozzletostraightstreamduringtheStowsequence OFF-Leavesnozzlepatternsetwherelastused(factoryset)
Switch6- AllowstheusertobeabletooperatethemonitorintheStowedposition.
ON-Allfunctionsareactiveatalltimes,Stowedornot OFF-AllfunctionaredisableduntilDeployed(factoryset)
1 2 3 4 5 6 7 8On • • • •Off • • • •
4
Switch7- AllowstheusertochoosebetweentheLearnedpositionsortheDefaultpositions. ON-DeployandStowattheLearnedposition(factoryset) OFF-DeployandStowinthedefaultpositiononlySwitch8- AllowstheusertoturntheLearnmodeONorOFF. ON-EnablesLearnmodeprogramming(factoryset) OFF-DisabletheLearnmode,theusercannotreprogramanewsetting
C.MONITOR,VEHICLEBATTERY,ORCABINDICATORLIGHTELECTRICALATTACHMENTTheseinstructionsareforattachmentofthemonitorwiringharness(TB4,TB5),thevehiclebattery(TB1),andthecabindicatorlight(TB6)tothelogicbox.WARNING: Therecommendedwiresizeforthevehiclebatterypowerlead(TB1)is10AWGwire.Ifsmaller
diameterwiringisused,nolessthan12AWG,aminimum11.5voltsisneededatthepowerleads(TB1)whenunderaload(operating).
STEP 4 Removethecablegripnutfortheappropriatecablefromthelogicbox(seeFigure4),DONOTREMOVETHECABLEGRIP.Threadthecablegripnutonthecorrectcablewiththethreadsfacingout.
STEP 5 Loosenthe4logicboxcoverscrewsandsetthelogicboxcoveraside.Threadthecablethroughthecorrectlogicboxcablegrip(seeFigure4).Pullenoughcablethroughthecablegriptoensureagoodfit.Tightenthecablegripnutandattachtheindividualwirestotheproperterminals(seewiringdiagram,Figure5).Reattachthelogicboxcoverandsecurewiththe4screws.
OPERATING INSTRUCTIONSA.STARTUP
1. Uponinitialinstallationofalogicboxoraftermaintenance(disassembly/reassembly)oftheunit,themechanicalunitmayNOTbesyncronizedwiththelogicbox(i.e.theelectronicsmaypointleftwhilethemechanicalunitpointsright).
2. HoldeithertheLEFTorRIGHTswitchONuntiltheendoftravelisreached.ContinueholdingtheswitchONwhilemomentarilyturningtheDEPLOYswitchON,thenreleasingtheDEPLOYswitch.ReleasetheLEFTorRIGHTswitch.
3. ThenholdtheDOWNswitchONuntiltheendoftravelisreached.IftheunitwillnotmoveDOWN,usetheUPswitch instead, until the end of travel is reached. In either case, continue holding the switch ON at the end of travelwhilemomentarilyturningtheDEPLOYswitchON,thenreleasingtheDEPLOYswitch.ReleasetheDOWNorUPswitch.
4. Theunitwillnowbesyncronizedandwillallowfullmotioninalldirections(assetviatheDIPswitches).
B. PANELCONTROLLEROPERATIONThe panel controller is used to control the monitor and nozzle.1. Todeploythemonitorforuse: LiftthesafetycoverontheSTOW/DEPLOYswitchandpushthetoggleswitchupandrelease.2. Tostowthemonitorafteruse: LiftthesafetycoverontheSTOW/DEPLOYswitchandpushthetoggleswitchdownandrelease.3. Tochangethehorizontalmonitorpositiontowardtherightorleft: Pressthepropertoggleswitchtoward“RIGHT”or“LEFT”respectively,aslabeledonthecontroller,untilthe
desired position is reached.4. Tochangetheverticalmonitornozzlepositionupwardordownward: Pressthepropertoggleswitchtoward“RAISE”or“LOWER”respectively,aslabeledonthecontroller,untilthe
desired position is reached.
9
Figure 2
AKRON
90°Upper Limits
30°Upper Limits
30°
30° Stop
90° Stop (permanent)
90° Stop (permanent)
SIDE VIEW - DEPLOYED
90° Below Horizontal
45°
Initial Deployed Position
90°
90°
1
2
3
Plug
Plug
Stop
BOTTOM VIEW
90° ROTATION(Factory Set)
45°
45°1
2
3
StopPlug
Stop
45° ROTATION
8
Figure 1
2
6 5/16
127/8373/8
24 1/2
47/8
811/16
24 1/2
27 1/2
81/4
31
21/2NHTHREAD
4"150LBFLANGE
3/8-16THREADX5/8DEEPFORADDITIONALSUPPORT
24 1/2 27 1/2
373/8
24 1/2
81/4
811/16
3
2
163/8
26
4 1/2
87/8
27 1/2
24 1/2
TOP VIEW - DEPLOYED
TOP VIEW - STOWED
SIDE VIEW - DEPLOYED
SIDE VIEW - STOWED
5
5. Tochangethenozzlepatterntowardthestraightstreamorfogposition: Pressthepropertoggleswitchtoward“STRAIGHT”or“FOG”respectively,aslabeledonthecontroller,untilthedesired
nozzle position is reached.
C.EMERGENCYSTOPDURINGDEPLOYORSTOWIfitisnecessarytoimmediatelystoptheTuckAwaymonitorduringthedeployorstowsequence,activateanyswitchonthecontrolpanelandtheunitwillstopmoving.Tocompletethestowordeploysequenceafteranemergencystop,activateandreleasethestow/deploytoggleswitch.Thiswillautomaticallycontinuethestow/deploysequence.Besuretocompletelystowordeploy the monitor before flowing water.
D.MANUALOVERRIDECONTROLSThe manual override control is to be used only when the power to the monitor is off. A single override crank with a 1/4” hex drive is provided and attached to the monitor for use on both the horizontal and vertical override controls. To use the manual override, insert the hex drive end of the override crank into the hexagon shaped hole on the shaft end opposite the motor. Rotate the override crank in the desired direction to aim the monitor. The crank is not intended for use while flowing water, but rather to stow a non-working monitor for transport to repair facilities.
WARNING: Whentheoverridecrankisnolongerinuse,putitbackinthestorageposition.Donotusethe electric controls when the override crank is being used or is in position for use.
E.LEARNMODE(DIPSwitch7and8mustbeON) ThelearnmodeallowstheoperatortoteachthemonitoranewfinalpositionatStoworDeploy.
TolearnanewDeployposition:
Startwiththeunitinthestowedposition.HoldtheDeployswitchON.Whenitreachesthedefaultdeployedposition,the monitorwillstop,continuetoholdtheDeployswitchwhileusingtheup/downandleft/rightswitchestopositiontheunitatthe desireddeployedposition.ReleasetheDeployswitchlastandthiswillbethenewlearnedposition.
NOTE:IfyoureleasetheDeployswitchandtrytoactivatetheDeployswitchagain,themonitorwillstop(E-Stop)andflashcode 3(SeeErrorcodes).
TolearnanewStowposition:
Startwiththeunitsomewhereinthedeployedstate.HoldtheStowswitchON.Whenitreachesthedefaultstowposition.the monitorwillstop,continuetoholdtheStowswitchwhileusingtheup/downandleft/rightswitchestopositiontheunitatthe desiredstowedposition.ReleasetheStowswitchlastandthiswillbethenewlearnedposition.
NOTE:IfyoureleasetheStowswitchandtrytoactivatethestowswitchagain,themonitorwillstop(E-Stop)andflashcode3 (SeeErrorcodes).
WARNING: The nozzle position may need to be reprogrammed in the event of variable loads on the motor. Possibleloadsituationsincludeextremetemperatures,changingnozzles,wearandtear,etc.
MAINTENANCE INSTRUCTIONSYourTuckAwaymonitorandnozzleshouldbeinspectedpriortoandaftereachusetoensureitisingoodoperatingcondition.Periodically,anunanticipatedincidentmayoccurwheretheunitismisusedinamannerthatisinconsistentwithstandardoperatingpractices.Apartiallistofpotentialmisusesincludes: •Operatingabovethemaximumratedpressureorflow. •Prolongedexposuretotemperaturesabove130°F,orbelow-25°F. •Operatinginacorrosiveenvironment. •HavingtheTuckAwaynozzlehitafixedobjectduringoperationortransportation. •Othermisusethatmightbeuniquetoyourspecificenvironment.
6
Also,therearemany“telltale”signsthatindicaterepairisinorder,suchas: •Controlsthatareeitherinoperableordifficulttooperate. •Excessivewear •Poordischargeperformance •Waterleaks.If any of the above situations are encountered, the TuckAway monitor should be taken out of service, repaired, and tested by a qualifiedtechnicianbeforeplacingbackinservice.
A. MOTORREPLACEMENT
Toreplacethehorizontal,verticalmotors:
1. Disconnectpowerfromtheunit.
2. Loosenandremovethe4socketscrewsfromthegearboxhousing
3. Slowlyremovethemotorassemblyandgearboxhousingfromtheunit.
Important: Make sure the internal gear remains in place, (hold with a screwdriver), to avoid gear alignment problems.
4. Loosenandremovethe4socketheadcapscrewsfromtheinsideofthegearboxhousingthatholdthehousingandthemotor assembly together.
5. Remove the gearbox housing from the motor assembly.
6. Replace both O-ring seals on the gearbox housing.
7. Attach the new motor assembly to the gearbox housing, making sure all 4 screws are tight.
8. Installthemotorandgearboxhousingassemblytotheunitmakingsureall4socketscrewsaretight.Itmaybenecessarytorotatethemotorslightlytogetthemotorgeartolineupwiththegearsinsidethegearbox.Hint:Usetheoverridecrank manual.
9. Restore power to the unit.
10. Test the operation of the unit.
CallAkronBrassTechnicalServiceifanyproblemsareencountered.
B. FAULTCODESYourTuckAwaymonitorcomeswithabuiltindiagnostictool.OnthecontrolpanelisasmallLEDindicator.TheprimaryfunctionoftheLEDindicatoristoindicatewhetherthemonitorisstowedordeployed.TheLEDindicatoralsofunctionsasaFaultIndicator.
Deployed: Thelightwillrepeatedlyflashtwiceastheunitisdeploying.Whenthefullydeployedpositionisreachedthe light will stop flashing and remain on. NOTE:Assoonasthedeploysequencebegins,thelightinthecabwillturnon.
Stowed: WhenthefullystowedpositionisreachedtheLEDindicatorwillgoout. NOTE:Thelightinthecabwillalsogooutwhenfullystowed.
Fault Code 1: Faultcode1isrepresentedwhenthelightflashescontinually.IftheEEPROMonthecircuitboardisfaulty,Fault1willoccur.
Correction: The circuit board must be replaced
Fault Code 2: Faultcode2isnormalduringthedeploysequenceandisrepresentedwhenthelightrepeatedlyflashestwice.Code2isnotafault,butoccurswhenthedeploybuttonispressedandautomaticallyendswhenthe fully deployed position is reached. Operation of any switch while flashing twice will cause the monitor togointoE-stopmode.
Fault Code 3: Faultcode3isrepresentedwhenthelightrepeatedlyflashes3times.Thisfaultcodeindicatesanemergencystop(E-stop)occurredduringstowordeploy.IfanyswitchispushedduringthestowordeploysequenceallmovementwillstopandFault3willflash.
Correction: Activiate the deploy or stow switch. This will continue the sequence until the light stays on constantly at full deployment or turns off at stow. Be sure to completely stow or deploy the monitor before flowing water.
7
Fault Code 4: FaultCode4isrepresentedwhenthelightflashesfourtimes.ThisindicatesthemonitorwaspreventedfromcompletingtheDeploysequenceintheverticaldirection.
Correction: This can be cancelled out by removing any obstructions and completing the sequence by activating the Stow or Deploy switch.
Fault Code 5: FaultCode5isrepresentedwhenthelightflashesfivetimes.ThisindicatesthemonitorwaspreventedfromcompletingtheDeploysequenceinthehorizontaldirection.
Correction: This can be cancelled out by removing any obstructions and completing the sequence by activating the Stow or Deploy switch.
Fault Code 6: FaultCode6isrepresentedwhenthelightflashessixtimes.ThisindicatesthemonitorwaspreventedfromcompletingtheStowsequenceintheverticaldirection.
Correction: This can be cancelled out by removing any obstructions and completing the sequence by activating the Stow or Deploy switch.
Fault Code 7: FaultCode7isrepresentedwhenthelightflashesseventimes.ThisindicatesthemonitorwaspreventedfromcompletingtheStowsequenceinthehorizontaldirection.
Correction: This can be cancelled out by removing any obstructions and completing the sequence by activating the Stow or Deploy switch.
WARRANTY AND DISCLAIMER: We warrant Akron Brass products for a period of five (5) years after purchase against defects in materials or workmanship. Akron Brass will repair or replace product which fails to satisfy this warranty. Repair or replacement shall be at the discretion of Akron Brass. Products must be promptly returned to Akron Brass for warranty service.
We will not be responsible for: wear and tear; any improper installation, use, maintenance or storage; negligence of the owner or user; repair or modification after delivery; damage; failure to follow our instructions or recommendations; or anything else beyond our control. WE MAKE NO WARRANTIES, EXPRESS OR IMPLIED, OTHER THAN THOSE INCLUDED IN THIS WARRANTY STATEMENT, AND WE DISCLAIM ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Further, we will not be responsible for any consequential, incidental or indirect damages (including, but not limited to, any loss of profits) from any cause whatsoever. No person has authority to change this warranty.
REvISED: 8/11
PHONE:330.264.5678or800.228.1161IFAX:330.264.2944or800.531.7335Iakronbrass.com
ISO 9001 REGISTERED COMPANY ©AkronBrassCompany.2011Allrightsreserved.NoportionofthiscanbereproducedwithouttheexpresswrittenconsentofAkronBrassCompany.
Figure 5
+12/24VOLT
+12/24VOLT
GROUNDGROUND
INDLIGHTINDLIGHT
MASTER
SLAVE
WHT
TANYELGRNBLUREDBLKORGPURGRY
WHT
RIGHTMOTOR
UPMOTOR
RED/BLKGRN/BLKWHT/BLK
ORGBLUBLKREDGRNWHT TAN
YELGRNBLUREDBLKORGPURGRY
LIMSTOW LIMHOME
SSMOTORFOGMOTOR
DOWNMOTORLEFTMOTOR
TOCONTROLBOXORJOYSTICK
TOCONTROLBOXORJOYSTICK
20-10CABLE16-10CABLE
20-10CABLE
5/16
5/16
3
3 1
47/8
7
TB2
1
SLAVE
MASTER
TOMONITOR
+12/24VOLTLED2
FOGSTREAMUPDOWNLEFTRIGHTSTOWDEPLOY
+12/24VOLT
LED1
FOG
STREAM
UP
DOWN
LEFT
RIGHT
STOW
DEPLOY
UP=ON
8
1
UP
DOWNDOWNDOWN
DOWN
UPUP
UP
DIPFUNCTIONS
OperateinStowedPositionReturntoSSduringStow
LimitedRotationatAllElevationsLimitedRotationatLowElevation
JogToStoworDeployEnableDriftCorrection
UsetheLearnedPositionsEnableLEARNMode
isstowed,closed(on)allothertimes.open(off)onlywhenthemonitorcontacts rated 1 amp at 24 vdc max,Note:INDLIGHTisasetofSPDT
theINDLIGHTCustomermustsupplypowerto
ClosedOpen
CABLETOCABLIGHTCIRCUIT
+12/24VOLTAUXBATTERY(OPTIONAL)
+12/24VOLTVEHICLEBATTERY TOVEHICLEBATTERY–VEHICLEGROUND
AUXGROUND
Blac
k
Green
Whit
e
4
1 TB3 TB1
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
128
27
26
25
24
23
22
21
20
19
18
17
16
14
13
12
11
10
9
8
7
6
5
4
3
2
1
15
28
2815
1514
14
1
1
STYLE3350
876876
FactoryS
ettin
gs