PERFORMANCE SUMMARY • UMA # 38 Untitled • SOTANO OFICINAS MANTO Tuesday, January 21, 2003 Page 1 of 159 Version 3.70 - Released 5/13/2002 - VA01 CS² Air Handler Model # AHD2 FS 040 V M Insulation (entire unit) 2.00# Quantity 1 Wall thickness 2" (5.08 cm) Environment Indoor Sealed panels Positive pressure only Notes - Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which is based on ARI Standard-430. - See individual coil ratings for ARI certification information. - ETL listed & UL 1995 Approved. A. Section 16C Combination filter/mixing box section Inlet location(s) Top and back Access panels One Top dampers Standard Panel hand Left Back dampers Standard Liners Solid Filter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.10 B. Section 18 Internal face & bypass short coil section Coil size Small Liners Solid Drain pan Standard Pressure drop (in w.g.) 0.61 Maximum bypass air flow (ft³/min) 2,191 Refer to attached pages for coil performance. C. Shipping split D. Section 3 Vertical draw-thru fan section Fan type Forward curved (alternate) Total static @ Actual (in w.g.) 1.71 Internal isolation Spring Brake power @ Actual (HP) 1.53 Arrangement #3 Rotations per minute 1,553 Motor type High Eff. TEFC Altitude (ft) 0 Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0 Motor power (HP) 2.00 Coil size Large Motor hand Left Drain pan Standard Drive 150% HP Adjustable Access panels One Air flow (ft³/min) 2,280 Panel hand Left External static @ Actual (in w.g.) 1.00 Liners Solid Internal static @ Actual (in w.g.) 0.71
Transcript
Page 1: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 38

Untitled • SOTANO OFICINAS MANTO

Tuesday, January 21, 2003 Page 1 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.10

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.61Maximum bypass air flow (ft³/min) 2,191

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (alternate) Total static @ Actual (in w.g.) 1.71Internal isolation Spring Brake power @ Actual (HP) 1.53Arrangement #3 Rotations per minute 1,553Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 2.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,280 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.71

Page 2: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 38

Untitled • SOTANO OFICINAS MANTO

Tuesday, January 21, 2003 Page 2 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 6 C - 14T x 44 LH Q 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

B. Fin material - 0.008 Polycoat

A,B

#1102.665.3

2,2800

3340.47

77.2 / 65.850.6 / 50.4

Actual

Water17.02.6

44.056.15.7

5 / 1422.344.06.8

6 / 127

Air handler1@1 1/21@1 1/2

MPT

Page 3: Submit Tal Mater No in f David

FAN CURVE • UMA # 38

Untitled • SOTANO OFICINAS MANTO

Tuesday, January 21, 2003 Page 3 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,280Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 1.71Style Draw-thru Rotations per minute 1,553Inlet vanes No Brake power @ Altitude (HP) 1.53Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

1,600 2,000 2,400 2,800 3,200 3,600 4,000 4,400

2.00

3.60

1.75

3.20

1.50

2.80

1.25

2.40

1.00

2.00

0.75

1.60

0.50

1.20

0.25

0.80

Page 4: Submit Tal Mater No in f David

DRAWING • UMA # 38

Untitled • SOTANO OFICINAS MANTO

Tuesday, January 21, 2003 Page 4 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/7

75 lb

Con

tact

fact

ory

for f

an d

imen

sion

als.

37.5

in/1

,057

lb

38.5 in

78.0 in

54.0

in3.

0 in

3.0

in

60.0

in60

.0 in

Page 5: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 37

Untitled • SOTANO COMEDOR

Tuesday, January 21, 2003 Page 5 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.11

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.89Maximum bypass air flow (ft³/min) 2,191

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (alternate) Total static @ Actual (in w.g.) 2.00Internal isolation Spring Brake power @ Actual (HP) 2.01Arrangement #3 Rotations per minute 1,688Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,520 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.00

Page 6: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 37

Untitled • SOTANO COMEDOR

Tuesday, January 21, 2003 Page 6 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 8 C - 14T x 44 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1184.291.4

2,5200

3700.71

82.3 / 72.048.4 / 48.3

Actual

Water35.54.3

44.054.413.6

5 / 1422.344.06.8

8 / 129

Air handler1@1 1/21@1 1/2

MPT

Page 7: Submit Tal Mater No in f David

FAN CURVE • UMA # 37

Untitled • SOTANO COMEDOR

Tuesday, January 21, 2003 Page 7 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,520Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 2.00Style Draw-thru Rotations per minute 1,688Inlet vanes No Brake power @ Altitude (HP) 2.01Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

1,600 2,000 2,400 2,800 3,200 3,600 4,000 4,400

2.25

4.00

2.00

3.60

1.75

3.20

1.50

2.80

1.25

2.40

1.00

2.00

0.75

1.60

0.50

1.20

Page 8: Submit Tal Mater No in f David

DRAWING • UMA # 37

Untitled • SOTANO COMEDOR

Tuesday, January 21, 2003 Page 8 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/8

45 lb

Con

tact

fact

ory

for f

an d

imen

sion

als.

37.5

in/1

,084

lb

38.5 in

78.0 in

54.0

in3.

0 in

3.0

in

60.0

in60

.0 in

Page 9: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 36

Untitled • SOTANO OFICINAS DIETISTA

Tuesday, January 21, 2003 Page 9 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 048 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.15

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.12Maximum bypass air flow (ft³/min) 2,689

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.27Internal isolation Spring Brake power @ Actual (HP) 3.15Arrangement #3 Rotations per minute 1,259Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 4,040 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.27

Page 10: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 36

Untitled • SOTANO OFICINAS DIETISTA

Tuesday, January 21, 2003 Page 10 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 C - 14T x 54 LH Q 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

B. Fin material - 0.008 Polycoat

A,B

#1149.3105.5

4,0400

4830.82

76.4 / 64.752.2 / 52.2

Actual

Water26.12.8

44.055.55.1

5 / 1422.354.08.4

6 / 1210

Air handler1@1 1/21@1 1/2

MPT

Page 11: Submit Tal Mater No in f David

FAN CURVE • UMA # 36

Untitled • SOTANO OFICINAS DIETISTA

Tuesday, January 21, 2003 Page 11 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 048 V M Air flow (ft³/min) 4,040Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 2.27Style Draw-thru Rotations per minute 1,259Inlet vanes No Brake power @ Altitude (HP) 3.15Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

2,400 3,200 4,000 4,800 5,600 6,400 7,200 8,000

2.40

7.20

2.20

6.40

2.00

5.60

1.80

4.80

1.60

4.00

1.40

3.20

1.20

2.40

1.00

1.60

Page 12: Submit Tal Mater No in f David

DRAWING • UMA # 36

Untitled • SOTANO OFICINAS DIETISTA

Tuesday, January 21, 2003 Page 12 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

48 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/8

71 lb

12.4

in13

.6 in

37.5

in/1

,204

lb

38.5 in

80.0 in

64.0

in3.

0 in

3.0

in

70.0

in

26.6

in15

.8 in

70.0

in

Page 13: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 35

Untitled • P.BAJA AUTOPSIA

Tuesday, January 21, 2003 Page 13 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 080 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.98Maximum bypass air flow (ft³/min) 5,146

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.12Internal isolation Spring (standard) Brake power @ Actual (HP) 4.34Arrangement #3 Rotations per minute 1,014Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 5,979 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.12

Page 14: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 35

Untitled • P.BAJA AUTOPSIA

Tuesday, January 21, 2003 Page 14 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 C - 18T x 62 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1231.8152.9

5,9790

4840.68

77.4 / 66.053.7 / 52.9

Actual

Water45.43.3

44.054.25.5

5 / 1828.762.012.4

5 / 1215

Air handler1@1 1/21@1 1/2

MPT

Page 15: Submit Tal Mater No in f David

FAN CURVE • UMA # 35

Untitled • P.BAJA AUTOPSIA

Tuesday, January 21, 2003 Page 15 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 080 V M Air flow (ft³/min) 5,979Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.12Style Draw-thru Rotations per minute 1,014Inlet vanes No Brake power @ Altitude (HP) 4.34Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,000 4,800 5,600 6,400 7,200 8,000 8,800 9,600

2.50

10.8

0

2.25

9.60

2.00

8.40

1.75

7.20

1.50

6.00

1.25

4.80

1.00

3.60

0.75

2.40

Page 16: Submit Tal Mater No in f David

DRAWING • UMA # 35

Untitled • P.BAJA AUTOPSIA

Tuesday, January 21, 2003 Page 16 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

80 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.26.5 in

21.0 in

2.0

in21

.0 in

69.0

in/1

,190

lb

51.0 in15.8

in16

.0 in

43.5

in/1

,834

lb

51.0 in

90.5 in

72.0

in3.

0 in

3.0

in

78.0

in

37.0

in18

.8 in

78.0

in

Page 17: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 34

Untitled • P.BAJA CIRCULA Y ESPERA

Tuesday, January 21, 2003 Page 17 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 180 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13

B. Shipping split

C. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.87Maximum bypass air flow (ft³/min) 11,422

Refer to attached pages for coil performance.

D. Shipping split

E. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.99Internal isolation Spring (standard) Brake power @ Actual (HP) 7.91Arrangement #3 Rotations per minute 659Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive Fixed Access panels OneAir flow (ft³/min) 11,820 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.99

Page 18: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 34

Untitled • P.BAJA CIRCULA Y ESPERA

Tuesday, January 21, 2003 Page 18 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W F 6 C - 30T x 86 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1650.1373.2

11,8200

4140.65

80.2 / 68.950.8 / 50.8

Actual

Water120.0

4.344.054.811.4

5 / 3047.886.028.6

6 / 1230

Air handler1@2 1@2 MPT

Page 19: Submit Tal Mater No in f David

FAN CURVE • UMA # 34

Untitled • P.BAJA CIRCULA Y ESPERA

Tuesday, January 21, 2003 Page 19 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 180 V M Air flow (ft³/min) 11,820Fan type Forward curved (standard/22-22) Static pressure @ Altitude (in w.g.) 1.99Style Draw-thru Rotations per minute 659Inlet vanes No Brake power @ Altitude (HP) 7.91Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000

2.25

20.0

0

2.00

18.0

0

1.75

16.0

0

1.50

14.0

0

1.25

12.0

0

1.00

10.0

0

0.75

8.00

0.50

6.00

Page 20: Submit Tal Mater No in f David

DRAWING • UMA # 34

Untitled • P.BAJA CIRCULA Y ESPERA

Tuesday, January 21, 2003 Page 20 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

80 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

10.0

in/6

13 lb

32.0

in/1

,546

lb74.0 in17

.8 in

27.4

in

61.8

in/4

,026

lb

74.0 in

146.5 in

104.

0 in

45.4

in27

.4 in

104.

0 in

Page 21: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 33

Untitled • P.BAJA LABORATORIO

Tuesday, January 21, 2003 Page 21 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 100 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.97Maximum bypass air flow (ft³/min) 6,176

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.11Internal isolation Spring (standard) Brake power @ Actual (HP) 5.27Arrangement #3 Rotations per minute 864Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,259 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.11

Page 22: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 33

Untitled • P.BAJA LABORATORIO

Tuesday, January 21, 2003 Page 22 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 C - 22T x 62 LH Q 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

B. Fin material - 0.008 Polycoat

A,B

#1288.0189.9

7,2590

4810.67

77.8 / 66.553.5 / 53.4

Actual

Water54.33.3

44.054.65.5

5 / 2235.162.015.1

5 / 1218

Air handler1@1 1/21@1 1/2

MPT

Page 23: Submit Tal Mater No in f David

FAN CURVE • UMA # 33

Untitled • P.BAJA LABORATORIO

Tuesday, January 21, 2003 Page 23 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 100 V M Air flow (ft³/min) 7,259Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 2.11Style Draw-thru Rotations per minute 864Inlet vanes No Brake power @ Altitude (HP) 5.27Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,500 6,000 7,500 9,000 10,500 12,000 13,500 15,000

2.40

13.5

0

2.20

12.0

0

2.00

10.5

0

1.80

9.00

1.60

7.50

1.40

6.00

1.20

4.50

1.00

3.00

Page 24: Submit Tal Mater No in f David

DRAWING • UMA # 33

Untitled • P.BAJA LABORATORIO

Tuesday, January 21, 2003 Page 24 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

00 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.28.0 in

26.5 in

2.0

in26

.5 in

73.0

in/1

,334

lb

58.0 in16.4

in19

.0 in

51.0

in/2

,420

lb

58.0 in

114.5 in

72.0

in3.

0 in

3.0

in

78.0

in

36.0

in22

.0 in

78.0

in

Page 25: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 32

Untitled • P.BAJA DIAGNOSTICO

Tuesday, January 21, 2003 Page 25 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 080 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Throw away Pressure drop (in w.g.) 0.11

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.90Maximum bypass air flow (ft³/min) 5,146

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.01Internal isolation Spring (standard) Brake power @ Actual (HP) 3.82Arrangement #3 Rotations per minute 982Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 5,660 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.01

Page 26: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 32

Untitled • P.BAJA DIAGNOSTICO

Tuesday, January 21, 2003 Page 26 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 18T x 62 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1208.4147.6

5,6600

4580.63

76.0 / 64.251.9 / 51.4

Actual

Water38.14.6

44.054.916.1

5 / 1828.762.012.4

5 / 129

Air handler1@1 1/21@1 1/2

MPT

Page 27: Submit Tal Mater No in f David

FAN CURVE • UMA # 32

Untitled • P.BAJA DIAGNOSTICO

Tuesday, January 21, 2003 Page 27 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 080 V M Air flow (ft³/min) 5,660Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.01Style Draw-thru Rotations per minute 982Inlet vanes No Brake power @ Altitude (HP) 3.82Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,000 4,800 5,600 6,400 7,200 8,000 8,800 9,600

2.20

9.00

2.00

8.00

1.80

7.00

1.60

6.00

1.40

5.00

1.20

4.00

1.00

3.00

0.80

2.00

Page 28: Submit Tal Mater No in f David

DRAWING • UMA # 32

Untitled • P.BAJA DIAGNOSTICO

Tuesday, January 21, 2003 Page 28 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

80 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.26.5 in

21.0 in

2.0

in21

.0 in

69.0

in/1

,190

lb

51.0 in15.8

in16

.0 in

43.5

in/1

,834

lb

51.0 in

90.5 in

72.0

in3.

0 in

3.0

in

78.0

in

37.0

in18

.8 in

78.0

in

Page 29: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 31

Untitled • P.BAJA URGENCIA

Tuesday, January 21, 2003 Page 29 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 240 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.11

B. Shipping split

C. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.73Maximum bypass air flow (ft³/min) 14,078

Refer to attached pages for coil performance.

D. Shipping split

E. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.94Internal isolation Spring (standard) Brake power @ Actual (HP) 8.79Arrangement #3 Rotations per minute 553Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 15.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 14,849 Panel hand LeftExternal static @ Actual (in w.g.) 1.10 Liners SolidInternal static @ Actual (in w.g.) 0.84

Page 30: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 31

Untitled • P.BAJA URGENCIA

Tuesday, January 21, 2003 Page 30 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W F 6 C - 34T x 106 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1757.9448.4

14,8490

3720.55

78.6 / 67.550.5 / 50.5

Actual

Water126.3

4.044.056.011.6

5 / 3454.2

106.039.9

6 / 1234

Air handler1@2 1@2 MPT

Page 31: Submit Tal Mater No in f David

FAN CURVE • UMA # 31

Untitled • P.BAJA URGENCIA

Tuesday, January 21, 2003 Page 31 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 240 V M Air flow (ft³/min) 14,849Fan type Forward curved (standard/25-25) Static pressure @ Altitude (in w.g.) 1.94Style Draw-thru Rotations per minute 553Inlet vanes No Brake power @ Altitude (HP) 8.79Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000

2.20

25.0

0

2.00

22.5

0

1.80

20.0

0

1.60

17.5

0

1.40

15.0

0

1.20

12.5

0

1.00

10.0

0

0.80

7.50

Page 32: Submit Tal Mater No in f David

DRAWING • UMA # 31

Untitled • P.BAJA URGENCIA

Tuesday, January 21, 2003 Page 32 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 2

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

40.0 in

38.0 in

2.0

in38

.0 in

49.0

in/1

,103

lb34

.0 in

/1,9

73 lb

82.5 in18.4

in31

.3 in

70.0

in/4

,845

lb

82.5 in

162.5 in

116.

0 in

3.0

in3.

0 in

122.

0 in

45.4

in31

.3 in

122.

0 in

Page 33: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 30

Untitled • P.BAJA QQUIROFANO 1-4

Tuesday, January 21, 2003 Page 33 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 064 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.17

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.68

Refer to attached pages for coil performance.

D. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.03Internal isolation Spring (standard) Total static @ Actual (in w.g.) 3.53Arrangement #3 Brake power @ Actual (HP) 6.88Motor type High Eff. TEFC Rotations per minute 1,288Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 5,900 Liners SolidExternal static @ Actual (in w.g.) 2.50

E. Shipping split

Page 34: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 30

Untitled • P.BAJA QQUIROFANO 1-4

Tuesday, January 21, 2003 Page 34 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.19

G. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 35: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 30

Untitled • P.BAJA QQUIROFANO 1-4

Tuesday, January 21, 2003 Page 35 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 8 A - 21T x 60 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1239.2158.6

5,9000

4230.68

74.8 / 64.050.0 / 50.0

Actual

Water47.63.7

44.054.112.8

5 / 2133.560.013.98 / 8

14Air handler

1@1 1/21@1 1/2

MPT

Page 36: Submit Tal Mater No in f David

FAN CURVE • UMA # 30

Untitled • P.BAJA QQUIROFANO 1-4

Tuesday, January 21, 2003 Page 36 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 064 H M Air flow (ft³/min) 5,900Fan type Forward curved (standard/15-11) Static pressure @ Altitude (in w.g.) 3.53Style Blow-thru Rotations per minute 1,288Inlet vanes No Brake power @ Altitude (HP) 6.87Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000

4.00

18.0

0

3.60

16.0

0

3.20

14.0

0

2.80

12.0

0

2.40

10.0

0

2.00

8.00

1.60

6.00

1.20

4.00

Page 37: Submit Tal Mater No in f David

DRAWING • UMA # 30

Untitled • P.BAJA QQUIROFANO 1-4

Tuesday, January 21, 2003 Page 37 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

64 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

20.5 in21.0 in

2.0

in21

.0 in

134.

5 in

/2,3

57 lb

52.0

in/5

63 lb

45.0 in

45.0 in

70.0

in3.

0 in

3.0

in

76.0

in76

.0 in

Page 38: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 29

Untitled • P.BAJA RECOBRO

Tuesday, January 21, 2003 Page 38 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.81Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.94Internal isolation Spring (standard) Brake power @ Actual (HP) 9.08Arrangement #3 Rotations per minute 785Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 10,170 Panel hand LeftExternal static @ Actual (in w.g.) 2.00 Liners SolidInternal static @ Actual (in w.g.) 0.94

Page 39: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 29

Untitled • P.BAJA RECOBRO

Tuesday, January 21, 2003 Page 39 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1396.9267.9

10,1700

4320.57

77.1 / 65.652.7 / 52.6

Actual

Water72.03.4

44.055.06.7

5 / 2844.676.023.6

5 / 1223

Air handler1@1 1/21@1 1/2

MPT

Page 40: Submit Tal Mater No in f David

FAN CURVE • UMA # 29

Untitled • P.BAJA RECOBRO

Tuesday, January 21, 2003 Page 40 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 10,170Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 2.94Style Draw-thru Rotations per minute 785Inlet vanes No Brake power @ Altitude (HP) 9.08Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

9,000 10,500 12,000 13,500 15,000 16,500 18,000 19,500

3.00

25.0

0

2.70

22.5

0

2.40

20.0

0

2.10

17.5

0

1.80

15.0

0

1.50

12.5

0

1.20

10.0

0

0.90

7.50

Page 41: Submit Tal Mater No in f David

DRAWING • UMA # 29

Untitled • P.BAJA RECOBRO

Tuesday, January 21, 2003 Page 41 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.42.0 in

26.5 in

2.0

in26

.5 in

77.0

in/1

,967

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,162

lb

72.0 in

142.5 in

88.0

in3.

0 in

3.0

in

94.0

in

39.0

in20

.4 in

94.0

in

Page 42: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 28

Untitled • P.BAJA QUIROFANO ORTOP.

Tuesday, January 21, 2003 Page 42 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.24

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.15

Refer to attached pages for coil performance.

D. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.64Internal isolation Spring Total static @ Actual (in w.g.) 4.14Arrangement #3 Brake power @ Actual (HP) 5.16Motor type High Eff. TEFC Rotations per minute 1,664Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 4,120 Liners SolidExternal static @ Actual (in w.g.) 2.50

E. Shipping split

Page 43: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 28

Untitled • P.BAJA QUIROFANO ORTOP.

Tuesday, January 21, 2003 Page 43 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.26

G. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 44: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 28

Untitled • P.BAJA QUIROFANO ORTOP.

Tuesday, January 21, 2003 Page 44 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 8 C - 17T x 44 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1173.4114.3

4,1200

4981.15

74.5 / 63.848.9 / 48.8

Actual

Water32.64.4

44.054.619.0

5 / 1727.144.08.3

8 / 128

Air handler1@1 1/21@1 1/2

MPT

Page 45: Submit Tal Mater No in f David

FAN CURVE • UMA # 28

Untitled • P.BAJA QUIROFANO ORTOP.

Tuesday, January 21, 2003 Page 45 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 H M Air flow (ft³/min) 4,120Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 4.14Style Blow-thru Rotations per minute 1,664Inlet vanes No Brake power @ Altitude (HP) 5.16Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

3,200 4,000 4,800 5,600 6,400 7,200 8,000 8,800

4.50

15.0

0

4.20

13.5

0

3.90

12.0

0

3.60

10.5

0

3.30

9.00

3.00

7.50

2.70

6.00

2.40

4.50

Page 46: Submit Tal Mater No in f David

DRAWING • UMA # 28

Untitled • P.BAJA QUIROFANO ORTOP.

Tuesday, January 21, 2003 Page 46 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

23.5 in15.0 in

1.0

in15

.0 in

124.

5 in

/1,9

60 lb

52.0

in/4

79 lb

42.0 in

42.0 in

54.0

in3.

0 in

3.0

in

60.0

in60

.0 in

Page 47: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 27

Untitled • P.BAJA QUIROF. 5

Tuesday, January 21, 2003 Page 47 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 048 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.18

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.86

Refer to attached pages for coil performance.

D. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.25Internal isolation Spring Total static @ Actual (in w.g.) 3.75Arrangement #3 Brake power @ Actual (HP) 5.46Motor type High Eff. TEFC Rotations per minute 1,595Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 4,550 Liners SolidExternal static @ Actual (in w.g.) 2.50

E. Shipping split

Page 48: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 27

Untitled • P.BAJA QUIROF. 5

Tuesday, January 21, 2003 Page 48 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.21

G. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 49: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 27

Untitled • P.BAJA QUIROF. 5

Tuesday, January 21, 2003 Page 49 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 8 B - 17T x 54 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1203.2128.9

4,5500

4480.86

75.5 / 64.949.3 / 49.3

Actual

Water39.63.9

44.054.313.2

5 / 1727.154.010.2

8 / 1011

Air handler1@1 1/21@1 1/2

MPT

Page 50: Submit Tal Mater No in f David

FAN CURVE • UMA # 27

Untitled • P.BAJA QUIROF. 5

Tuesday, January 21, 2003 Page 50 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 048 H M Air flow (ft³/min) 4,550Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 3.75Style Blow-thru Rotations per minute 1,595Inlet vanes No Brake power @ Altitude (HP) 5.46Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

3,200 4,000 4,800 5,600 6,400 7,200 8,000 8,800

4.00

18.0

0

3.60

16.0

0

3.20

14.0

0

2.80

12.0

0

2.40

10.0

0

2.00

8.00

1.60

6.00

1.20

4.00

Page 51: Submit Tal Mater No in f David

DRAWING • UMA # 27

Untitled • P.BAJA QUIROF. 5

Tuesday, January 21, 2003 Page 51 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

48 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

25.5 in15.0 in

1.0

in15

.0 in

124.

5 in

/2,0

74 lb

52.0

in/5

34 lb

44.0 in

44.0 in

64.0

in3.

0 in

3.0

in

70.0

in70

.0 in

Page 52: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 26

Untitled • P.BAJA ESTERILIZACION

Tuesday, January 21, 2003 Page 52 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 2,191

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.98Internal isolation Spring Brake power @ Actual (HP) 1.83Arrangement #3 Rotations per minute 1,153Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 3,000 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.98

Page 53: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 26

Untitled • P.BAJA ESTERILIZACION

Tuesday, January 21, 2003 Page 53 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 14T x 44 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1128.782.5

3,0000

4400.59

77.7 / 66.452.2 / 52.1

Actual

Water25.74.0

44.054.010.0

5 / 1422.344.06.8

5 / 127

Air handler1@1 1/21@1 1/2

MPT

Page 54: Submit Tal Mater No in f David

FAN CURVE • UMA # 26

Untitled • P.BAJA ESTERILIZACION

Tuesday, January 21, 2003 Page 54 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 V M Air flow (ft³/min) 3,000Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 1.98Style Draw-thru Rotations per minute 1,153Inlet vanes No Brake power @ Altitude (HP) 1.83Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000

2.10

5.00

1.95

4.50

1.80

4.00

1.65

3.50

1.50

3.00

1.35

2.50

1.20

2.00

1.05

1.50

Page 55: Submit Tal Mater No in f David

DRAWING • UMA # 26

Untitled • P.BAJA ESTERILIZACION

Tuesday, January 21, 2003 Page 55 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/7

40 lb

12.4

in13

.6 in

37.5

in/1

,084

lb

38.5 in

78.0 in

54.0

in3.

0 in

3.0

in

60.0

in

25.6

in15

.8 in

60.0

in

Page 56: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 25

Untitled • P.BAJA LABOR EXPULSION

Tuesday, January 21, 2003 Page 56 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 AF 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Shipping split

D. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.96Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

E. Shipping split

Page 57: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 25

Untitled • P.BAJA LABOR EXPULSION

Tuesday, January 21, 2003 Page 57 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 3 Vertical draw-thru fan section

Fan type Airfoil (standard) Total static @ Actual (in w.g.) 3.59Internal isolation Spring (standard) Brake power @ Actual (HP) 7.54Arrangement #3 Rotations per minute 1,894Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,590 Panel hand LeftExternal static @ Actual (in w.g.) 2.50 Liners SolidInternal static @ Actual (in w.g.) 1.09

Page 58: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 25

Untitled • P.BAJA LABOR EXPULSION

Tuesday, January 21, 2003 Page 58 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section D - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1331.2225.0

8,5900

4640.68

76.7 / 65.252.4 / 52.3

Actual

Water58.43.9

44.055.411.6

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 59: Submit Tal Mater No in f David

FAN CURVE • UMA # 25

Untitled • P.BAJA LABOR EXPULSION

Tuesday, January 21, 2003 Page 59 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 AF 120 V M Air flow (ft³/min) 8,590Fan type Airfoil (standard/201) Static pressure @ Altitude (in w.g.) 3.59Style Draw-thru Rotations per minute 1,894Inlet vanes No Brake power @ Altitude (HP) 7.54Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,400 7,200 8,000 8,800 9,600 10,400 11,200 12,000

5.00

7.80

4.50

7.65

4.00

7.50

3.50

7.35

3.00

7.20

2.50

7.05

2.00

6.90

1.50

6.75

Page 60: Submit Tal Mater No in f David

DRAWING • UMA # 25

Untitled • P.BAJA LABOR EXPULSION

Tuesday, January 21, 2003 Page 60 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

AF

120

V M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

28.0 in

26.5 in

2.0

in26

.5 in

73.0

in/1

,048

lb32

.0 in

/951

lb

58.0 in22.9

in22

.3 in

51.0

in/3

,079

lb

58.0 in

114.5 in

88.0

in3.

0 in

3.0

in

94.0

in

42.0

in27

.0 in

94.0

in

Page 61: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 24

Untitled • P.BAJA SEMI. INTENS.

Tuesday, January 21, 2003 Page 61 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.17

D. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.45

Refer to attached pages for coil performance.

E. Shipping split

Page 62: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 24

Untitled • P.BAJA SEMI. INTENS.

Tuesday, January 21, 2003 Page 62 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (alternate) Internal static @ Actual (in w.g.) 0.91Internal isolation Spring Total static @ Actual (in w.g.) 3.41Arrangement #3 Brake power @ Actual (HP) 3.93Motor type High Eff. TEFC Rotations per minute 2,170Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 5.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 3,050 Liners SolidExternal static @ Actual (in w.g.) 2.50

G. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.14

H. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 63: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 24

Untitled • P.BAJA SEMI. INTENS.

Tuesday, January 21, 2003 Page 63 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 17T x 44 LH 1 Section D - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1113.679.8

3,0500

3680.45

76.7 / 64.852.5 / 52.2

Actual

Water20.22.7

44.055.35.2

5 / 1727.144.08.3

5 / 128

Air handler1@1 1/21@1 1/2

MPT

Page 64: Submit Tal Mater No in f David

FAN CURVE • UMA # 24

Untitled • P.BAJA SEMI. INTENS.

Tuesday, January 21, 2003 Page 64 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 H M Air flow (ft³/min) 3,050Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 3.41Style Blow-thru Rotations per minute 2,170Inlet vanes No Brake power @ Altitude (HP) 3.93Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500

4.00

9.00

3.50

8.00

3.00

7.00

2.50

6.00

2.00

5.00

1.50

4.00

1.00

3.00

0.50

2.00

Page 65: Submit Tal Mater No in f David

DRAWING • UMA # 24

Untitled • P.BAJA SEMI. INTENS.

Tuesday, January 21, 2003 Page 65 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

23.5 in

15.0 in

1.0

in15

.0 in

107.

0 in

/1,1

35 lb

89.5

in/1

,194

lb

42.0 in

42.0 in

54.0

in3.

0 in

3.0

in

60.0

in60

.0 in

Page 66: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 23

Untitled • P.BAJA QUEMADOS

Tuesday, January 21, 2003 Page 66 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 022 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.20

D. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.51

Refer to attached pages for coil performance.

E. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (alternate) Internal static @ Actual (in w.g.) 1.02Internal isolation Spring Total static @ Actual (in w.g.) 3.52Arrangement #3 Brake power @ Actual (HP) 2.32Motor type High Eff. TEFC Rotations per minute 2,110Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 3.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 1,830 Liners SolidExternal static @ Actual (in w.g.) 2.50

Page 67: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 23

Untitled • P.BAJA QUEMADOS

Tuesday, January 21, 2003 Page 67 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Shipping split

G. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.16

H. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 68: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 23

Untitled • P.BAJA QUEMADOS

Tuesday, January 21, 2003 Page 68 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 13T x 32 LH 1 Section D - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#159.445.7

1,8300

3970.51

76.4 / 64.053.3 / 53.0

Actual

Water11.12.0

44.054.72.5

5 / 1320.732.04.6

5 / 126

Air handler1@1 1/21@1 1/2

MPT

Page 69: Submit Tal Mater No in f David

FAN CURVE • UMA # 23

Untitled • P.BAJA QUEMADOS

Tuesday, January 21, 2003 Page 69 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 022 H M Air flow (ft³/min) 1,830Fan type Forward curved (alternate/9-6) Static pressure @ Altitude (in w.g.) 3.52Style Blow-thru Rotations per minute 2,110Inlet vanes No Brake power @ Altitude (HP) 2.32Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

1,500 1,800 2,100 2,400 2,700 3,000 3,300 3,600

4.00

6.00

3.60

5.40

3.20

4.80

2.80

4.20

2.40

3.60

2.00

3.00

1.60

2.40

1.20

1.80

Page 70: Submit Tal Mater No in f David

DRAWING • UMA # 23

Untitled • P.BAJA QUEMADOS

Tuesday, January 21, 2003 Page 70 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

22 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

15.5 in

15.0 in

1.0

in15

.0 in

128.

0 in

/1,2

75 lb

46.0

in/3

43 lb

34.0 in

34.0 in

42.0

in3.

0 in

3.0

in

48.0

in48

.0 in

Page 71: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 22

Untitled • P.BAJA INTENS.

Tuesday, January 21, 2003 Page 71 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 048 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.21

B. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

C. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.31

D. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.70

Refer to attached pages for coil performance.

E. Shipping split

Page 72: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 22

Untitled • P.BAJA INTENS.

Tuesday, January 21, 2003 Page 72 of 159 Version 3.70 - Released 5/13/2002 - VA01

F. Section 2 Horizontal blow-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.47Internal isolation Spring Total static @ Actual (in w.g.) 3.97Arrangement #3 Brake power @ Actual (HP) 6.54Motor type High Eff. TEFC Rotations per minute 1,650Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 4,991 Liners SolidExternal static @ Actual (in w.g.) 2.50

G. Section 27 Diffuser section

Liners Solid Pressure drop (in w.g.) 0.25

H. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One

Page 73: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 22

Untitled • P.BAJA INTENS.

Tuesday, January 21, 2003 Page 73 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 17T x 54 LH 1 Section D - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1195.8130.6

4,9910

4910.70

77.3 / 65.953.0 / 52.9

Actual

Water35.94.9

44.054.916.3

5 / 1727.154.010.2

5 / 128

Air handler1@1 1/21@1 1/2

MPT

Page 74: Submit Tal Mater No in f David

FAN CURVE • UMA # 22

Untitled • P.BAJA INTENS.

Tuesday, January 21, 2003 Page 74 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 048 H M Air flow (ft³/min) 4,991Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 3.97Style Blow-thru Rotations per minute 1,650Inlet vanes No Brake power @ Altitude (HP) 6.54Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000

4.40

18.0

0

4.00

16.0

0

3.60

14.0

0

3.20

12.0

0

2.80

10.0

0

2.40

8.00

2.00

6.00

1.60

4.00

Page 75: Submit Tal Mater No in f David

DRAWING • UMA # 22

Untitled • P.BAJA INTENS.

Tuesday, January 21, 2003 Page 75 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

48 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

25.5 in

15.0 in

1.0

in15

.0 in

107.

0 in

/1,2

65 lb

89.5

in/1

,345

lb

44.0 in

44.0 in

64.0

in3.

0 in

3.0

in

70.0

in70

.0 in

Page 76: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 21

Untitled • P.BAJA MED.FIS. Y REHAB.

Tuesday, January 21, 2003 Page 76 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.16

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.05Maximum bypass air flow (ft³/min) 2,191

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.21Internal isolation Spring Brake power @ Actual (HP) 2.33Arrangement #3 Rotations per minute 1,223Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 3,350 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.22

Page 77: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 21

Untitled • P.BAJA MED.FIS. Y REHAB.

Tuesday, January 21, 2003 Page 77 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 6 B - 14T x 44 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1134.689.1

3,3500

4910.74

76.8 / 65.552.2 / 51.9

Actual

Water26.64.1

44.054.112.7

5 / 1422.344.06.8

6 / 107

Air handler1@1 1/21@1 1/2

MPT

Page 78: Submit Tal Mater No in f David

FAN CURVE • UMA # 21

Untitled • P.BAJA MED.FIS. Y REHAB.

Tuesday, January 21, 2003 Page 78 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 V M Air flow (ft³/min) 3,350Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 2.21Style Draw-thru Rotations per minute 1,223Inlet vanes No Brake power @ Altitude (HP) 2.33Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

2,400 3,000 3,600 4,200 4,800 5,400 6,000 6,600

2.25

6.00

2.10

5.40

1.95

4.80

1.80

4.20

1.65

3.60

1.50

3.00

1.35

2.40

1.20

1.80

Page 79: Submit Tal Mater No in f David

DRAWING • UMA # 21

Untitled • P.BAJA MED.FIS. Y REHAB.

Tuesday, January 21, 2003 Page 79 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/7

61 lb

12.4

in13

.6 in

37.5

in/1

,084

lb

38.5 in

78.0 in

54.0

in3.

0 in

3.0

in

60.0

in

25.6

in15

.8 in

60.0

in

Page 80: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 20

Untitled • P.BAJA ADMIN.

Tuesday, January 21, 2003 Page 80 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.16

B. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.19

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.49

Refer to attached pages for coil performance.

D. Shipping split

E. Section 1 Horizontal draw-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 0.84Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.84Arrangement #3 Brake power @ Actual (HP) 8.60Motor type High Eff. TEFC Rotations per minute 677Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 11,780 Liners SolidExternal static @ Actual (in w.g.) 1.00

Page 81: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 20

Untitled • P.BAJA ADMIN.

Tuesday, January 21, 2003 Page 81 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W Q 5 C - 36T x 76 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1517.7319.5

11,7800

3890.49

78.7 / 67.453.5 / 52.9

Actual

Water102.2

2.544.054.12.6

5 / 3657.476.030.3

5 / 1245

Air handler1@2 1/21@2 1/2

MPT

Page 82: Submit Tal Mater No in f David

FAN CURVE • UMA # 20

Untitled • P.BAJA ADMIN.

Tuesday, January 21, 2003 Page 82 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 H M Air flow (ft³/min) 11,780Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.84Style Draw-thru Rotations per minute 677Inlet vanes No Brake power @ Altitude (HP) 8.61Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

7,500 9,000 10,500 12,000 13,500 15,000 16,500 18,000

2.25

15.0

0

2.00

13.5

0

1.75

12.0

0

1.50

10.5

0

1.25

9.00

1.00

7.50

0.75

6.00

0.50

4.50

Page 83: Submit Tal Mater No in f David

DRAWING • UMA # 20

Untitled • P.BAJA ADMIN.

Tuesday, January 21, 2003 Page 83 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0 in26.5 in

2.0

in26

.5 in

101.

0 in

/2,3

42 lb

12.8 in27.4 in

56.0

in/2

,130

lb

72.0 in

72.0 in

88.0

in3.

0 in

3.0

in

94.0

in

39.0

in20

.4 in

94.0

in

Page 84: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 19

Untitled • P.BAJA FARMACIA

Tuesday, January 21, 2003 Page 84 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.76Maximum bypass air flow (ft³/min) 2,191

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.88Internal isolation Spring Brake power @ Actual (HP) 1.62Arrangement #3 Rotations per minute 1,124Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 2.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,824 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.88

Page 85: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 19

Untitled • P.BAJA FARMACIA

Tuesday, January 21, 2003 Page 85 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 C - 14T x 44 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1188.390.9

2,8240

4140.53

83.1 / 73.352.9 / 52.8

Actual

Water36.45.6

44.054.418.6

5 / 1422.344.06.8

5 / 127

Air handler1@1 1/21@1 1/2

MPT

Page 86: Submit Tal Mater No in f David

FAN CURVE • UMA # 19

Untitled • P.BAJA FARMACIA

Tuesday, January 21, 2003 Page 86 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,824Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 1.88Style Draw-thru Rotations per minute 1,124Inlet vanes No Brake power @ Altitude (HP) 1.62Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000

2.10

4.50

1.95

4.00

1.80

3.50

1.65

3.00

1.50

2.50

1.35

2.00

1.20

1.50

1.05

1.00

Page 87: Submit Tal Mater No in f David

DRAWING • UMA # 19

Untitled • P.BAJA FARMACIA

Tuesday, January 21, 2003 Page 87 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.20.0 in

15.0 in

1.0

in15

.0 in

65.0

in/7

40 lb

12.4

in13

.6 in

37.5

in/1

,057

lb

38.5 in

78.0 in

54.0

in3.

0 in

3.0

in

60.0

in

25.6

in15

.8 in

60.0

in

Page 88: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 18

Untitled • P.BAJA CONSULTA

Tuesday, January 21, 2003 Page 88 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 240 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 16C Combination filter/mixing box section

Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.12

B. Shipping split

C. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.68Maximum bypass air flow (ft³/min) 14,078

Refer to attached pages for coil performance.

D. Shipping split

E. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.80Internal isolation Spring (standard) Brake power @ Actual (HP) 8.80Arrangement #3 Rotations per minute 537Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 15,507 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.80

Page 89: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 18

Untitled • P.BAJA CONSULTA

Tuesday, January 21, 2003 Page 89 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W Q 5 C - 34T x 106 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1749.2455.1

15,5070

3890.49

79.6 / 68.152.3 / 52.2

Actual

Water140.6

3.644.054.76.6

5 / 3454.2

106.039.9

5 / 1242

Air handler1@2 1/21@2 1/2

MPT

Page 90: Submit Tal Mater No in f David

FAN CURVE • UMA # 18

Untitled • P.BAJA CONSULTA

Tuesday, January 21, 2003 Page 90 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 240 V M Air flow (ft³/min) 15,507Fan type Forward curved (standard/25-25) Static pressure @ Altitude (in w.g.) 1.80Style Draw-thru Rotations per minute 537Inlet vanes No Brake power @ Altitude (HP) 8.80Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000

2.00

22.5

0

1.80

20.0

0

1.60

17.5

0

1.40

15.0

0

1.20

12.5

0

1.00

10.0

0

0.80

7.50

0.60

5.00

Page 91: Submit Tal Mater No in f David

DRAWING • UMA # 18

Untitled • P.BAJA CONSULTA

Tuesday, January 21, 2003 Page 91 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 2

40 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

40.0 in

38.0 in

2.0

in38

.0 in

49.0

in/1

,103

lb34

.0 in

/1,7

97 lb

82.5 in18.4

in31

.3 in

70.0

in/4

,785

lb

82.5 in

162.5 in

116.

0 in

3.0

in3.

0 in

122.

0 in

45.4

in31

.3 in

122.

0 in

Page 92: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 17

Untitled • E.P.3-ESTE

Tuesday, January 21, 2003 Page 92 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.90Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.53Internal isolation Spring (standard) Brake power @ Actual (HP) 3.80Arrangement #3 Rotations per minute 636Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,860 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.03

Page 93: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 17

Untitled • E.P.3-ESTE

Tuesday, January 21, 2003 Page 93 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W F 6 C - 22T x 76 LH Q 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

B. Fin material - 0.008 Polycoat

A,B

#1394.8238.0

7,8600

4250.67

79.4 / 67.951.2 / 51.2

Actual

Water71.33.5

44.055.17.2

5 / 2235.176.018.5

6 / 1222

Air handler1@2 1@2 MPT

Page 94: Submit Tal Mater No in f David

FAN CURVE • UMA # 17

Untitled • E.P.3-ESTE

Tuesday, January 21, 2003 Page 94 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 7,860Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.53Style Draw-thru Rotations per minute 636Inlet vanes No Brake power @ Altitude (HP) 3.80Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.65

9.00

1.50

8.00

1.35

7.00

1.20

6.00

1.05

5.00

0.90

4.00

0.75

3.00

Page 95: Submit Tal Mater No in f David

DRAWING • UMA # 17

Untitled • E.P.3-ESTE

Tuesday, January 21, 2003 Page 95 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,458

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,789

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 96: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 16

Untitled • E.P.3-OESTE

Tuesday, January 21, 2003 Page 96 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 100 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidPre-filter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.18Access panels One

B. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.23

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.42

Refer to attached pages for coil performance.

D. Section 1 Horizontal draw-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 0.83Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.83Arrangement #3 Brake power @ Actual (HP) 5.65Motor type High Eff. TEFC Rotations per minute 825Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 8,070 Liners SolidExternal static @ Actual (in w.g.) 1.00

Page 97: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 16

Untitled • E.P.3-OESTE

Tuesday, January 21, 2003 Page 97 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 4 C - 28T x 62 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1354.2215.0

8,0700

4200.42

78.6 / 67.653.8 / 53.4

Actual

Water70.85.5

44.054.017.9

5 / 2844.662.019.2

4 / 1214

Air handler1@1 1/21@1 1/2

MPT

Page 98: Submit Tal Mater No in f David

FAN CURVE • UMA # 16

Untitled • E.P.3-OESTE

Tuesday, January 21, 2003 Page 98 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 100 H M Air flow (ft³/min) 8,070Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.83Style Draw-thru Rotations per minute 825Inlet vanes No Brake power @ Altitude (HP) 5.65Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,800 6,000 7,200 8,400 9,600 10,800 12,000 13,200

2.40

13.5

0

2.20

12.0

0

2.00

10.5

0

1.80

9.00

1.60

7.50

1.40

6.00

1.20

4.50

1.00

3.00

Page 99: Submit Tal Mater No in f David

DRAWING • UMA # 16

Untitled • E.P.3-OESTE

Tuesday, January 21, 2003 Page 99 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

00 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

8.6 in19.0 in

133.

0 in

/2,9

31 lb

58.0 in

58.0 in

78.0

in

36.0

in22

.0 in

78.0

in

Page 100: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 15

Untitled • E.P.2-AUDIT.

Tuesday, January 21, 2003 Page 100 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 100 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.18

B. Shipping split

C. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.28Internal isolation Spring (standard) Brake power @ Actual (HP) 4.66Arrangement #3 Rotations per minute 719Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive Fixed Access panels OneAir flow (ft³/min) 8,175 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.78 Pressure drop (in w.g.) 0.60

Refer to attached pages for coil performance.

Page 101: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 15

Untitled • E.P.2-AUDIT.

Tuesday, January 21, 2003 Page 101 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 28T x 62 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1389.9234.4

8,1750

4250.60

78.6 / 67.652.0 / 51.8

Actual

Water76.03.9

44.054.39.9

5 / 2844.662.019.2

6 / 1021

Air handler1@1 1/21@1 1/2

MPT

Page 102: Submit Tal Mater No in f David

FAN CURVE • UMA # 15

Untitled • E.P.2-AUDIT.

Tuesday, January 21, 2003 Page 102 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 100 V M Air flow (ft³/min) 8,175Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.28Style Draw-thru Rotations per minute 719Inlet vanes No Brake power @ Altitude (HP) 4.66Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

3,600 4,800 6,000 7,200 8,400 9,600 10,800 12,000

1.56

9.00

1.44

8.00

1.32

7.00

1.20

6.00

1.08

5.00

0.96

4.00

0.84

3.00

0.72

2.00

Page 103: Submit Tal Mater No in f David

DRAWING • UMA # 15

Untitled • E.P.2-AUDIT.

Tuesday, January 21, 2003 Page 103 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

00 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

10.0

in/4

41 lb

58.0 in16.4

in19

.0 in

51.0

in/2

,915

lb

58.0 in

114.5 in

78.0

in

36.0

in22

.0 in

78.0

in

Page 104: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 14

Untitled • E.P.2-ESTE

Tuesday, January 21, 2003 Page 104 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.48Internal isolation Spring (standard) Brake power @ Actual (HP) 3.79Arrangement #3 Rotations per minute 626Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,975 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.98

Page 105: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 14

Untitled • E.P.2-ESTE

Tuesday, January 21, 2003 Page 105 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1381.4232.6

7,9750

4310.61

79.2 / 67.752.1 / 51.9

Actual

Water70.44.8

44.054.816.1

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 106: Submit Tal Mater No in f David

FAN CURVE • UMA # 14

Untitled • E.P.2-ESTE

Tuesday, January 21, 2003 Page 106 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 7,975Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.48Style Draw-thru Rotations per minute 626Inlet vanes No Brake power @ Altitude (HP) 3.79Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.56

9.00

1.44

8.00

1.32

7.00

1.20

6.00

1.08

5.00

0.96

4.00

0.84

3.00

0.72

2.00

Page 107: Submit Tal Mater No in f David

DRAWING • UMA # 14

Untitled • E.P.2-ESTE

Tuesday, January 21, 2003 Page 107 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,425

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,789

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 108: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 13

Untitled • E.P.2-OESTE

Tuesday, January 21, 2003 Page 108 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.16

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.05Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.72Internal isolation Spring (standard) Brake power @ Actual (HP) 5.20Arrangement #3 Rotations per minute 681Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,100 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.22

Page 109: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 13

Untitled • E.P.2-OESTE

Tuesday, January 21, 2003 Page 109 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1333.2232.5

9,1000

4920.74

76.3 / 64.752.7 / 52.4

Actual

Water59.34.0

44.055.311.9

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 110: Submit Tal Mater No in f David

FAN CURVE • UMA # 13

Untitled • E.P.2-OESTE

Tuesday, January 21, 2003 Page 110 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,100Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.72Style Draw-thru Rotations per minute 681Inlet vanes No Brake power @ Altitude (HP) 5.20Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,500 9,000 10,500 12,000 13,500 15,000 16,500

1.80

12.0

0

1.65

10.8

0

1.50

9.60

1.35

8.40

1.20

7.20

1.05

6.00

0.90

4.80

0.75

3.60

Page 111: Submit Tal Mater No in f David

DRAWING • UMA # 13

Untitled • E.P.2-OESTE

Tuesday, January 21, 2003 Page 111 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,425

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,856

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 112: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 12

Untitled • PISO 6-ESTE(FUTURO)

Tuesday, January 21, 2003 Page 112 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.47Internal isolation Spring (standard) Brake power @ Actual (HP) 5.09Arrangement #3 Rotations per minute 586Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,560 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.97

Page 113: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 12

Untitled • PISO 6-ESTE(FUTURO)

Tuesday, January 21, 2003 Page 113 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1377.2262.1

9,5600

4060.63

76.2 / 64.550.8 / 50.8

Actual

Water61.33.2

44.056.37.8

5 / 2844.676.023.6

6 / 1221

Air handler1@1 1/21@1 1/2

MPT

Page 114: Submit Tal Mater No in f David

FAN CURVE • UMA # 12

Untitled • PISO 6-ESTE(FUTURO)

Tuesday, January 21, 2003 Page 114 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,560Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.47Style Draw-thru Rotations per minute 586Inlet vanes No Brake power @ Altitude (HP) 5.09Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.60

9.00

1.40

8.00

1.20

7.00

1.00

6.00

0.80

5.00

0.60

4.00

0.40

3.00

Page 115: Submit Tal Mater No in f David

DRAWING • UMA # 12

Untitled • PISO 6-ESTE(FUTURO)

Tuesday, January 21, 2003 Page 115 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,849

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,141

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in

Page 116: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 11

Untitled • PISO 6-OESTE ( FUTURO )

Tuesday, January 21, 2003 Page 116 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.81Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.45Internal isolation Spring (standard) Brake power @ Actual (HP) 5.68Arrangement #3 Rotations per minute 594Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 10,160 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.95

Page 117: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 11

Untitled • PISO 6-OESTE ( FUTURO )

Tuesday, January 21, 2003 Page 117 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1347.8256.2

10,1600

4310.58

75.9 / 64.152.6 / 52.5

Actual

Water61.42.9

44.055.35.1

5 / 2844.676.023.6

5 / 1223

Air handler1@1 1/21@1 1/2

MPT

Page 118: Submit Tal Mater No in f David

FAN CURVE • UMA # 11

Untitled • PISO 6-OESTE ( FUTURO )

Tuesday, January 21, 2003 Page 118 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 10,160Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.45Style Draw-thru Rotations per minute 594Inlet vanes No Brake power @ Altitude (HP) 5.68Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.60

9.00

1.40

8.00

1.20

7.00

1.00

6.00

0.80

5.00

0.60

4.00

0.40

3.00

Page 119: Submit Tal Mater No in f David

DRAWING • UMA # 11

Untitled • PISO 6-OESTE ( FUTURO )

Tuesday, January 21, 2003 Page 119 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,746

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,141

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in

Page 120: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 10

Untitled • PISO 5-ESTE

Tuesday, January 21, 2003 Page 120 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.17

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.08Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.75Internal isolation Spring (standard) Brake power @ Actual (HP) 5.41Arrangement #3 Rotations per minute 688Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,250 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.25

Page 121: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 10

Untitled • PISO 5-ESTE

Tuesday, January 21, 2003 Page 121 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1342.1239.1

9,2500

5000.76

76.7 / 64.852.8 / 52.5

Actual

Water61.74.2

44.055.112.8

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 122: Submit Tal Mater No in f David

FAN CURVE • UMA # 10

Untitled • PISO 5-ESTE

Tuesday, January 21, 2003 Page 122 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,250Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.75Style Draw-thru Rotations per minute 688Inlet vanes No Brake power @ Altitude (HP) 5.42Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600

1.95

12.0

0

1.80

10.8

0

1.65

9.60

1.50

8.40

1.35

7.20

1.20

6.00

1.05

4.80

0.90

3.60

Page 123: Submit Tal Mater No in f David

DRAWING • UMA # 10

Untitled • PISO 5-ESTE

Tuesday, January 21, 2003 Page 123 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,425

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,856

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 124: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 9

Untitled • PISO 5-OESTE

Tuesday, January 21, 2003 Page 124 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.16

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.16Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.82Internal isolation Spring (standard) Brake power @ Actual (HP) 5.45Arrangement #3 Rotations per minute 699Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,130 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.32

Page 125: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 9

Untitled • PISO 5-OESTE

Tuesday, January 21, 2003 Page 125 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 C - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1347.9243.8

9,1300

4930.85

76.3 / 64.651.6 / 51.6

Actual

Water58.64.0

44.055.911.6

5 / 2235.176.018.5

6 / 1216

Air handler1@1 1/21@1 1/2

MPT

Page 126: Submit Tal Mater No in f David

FAN CURVE • UMA # 9

Untitled • PISO 5-OESTE

Tuesday, January 21, 2003 Page 126 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,130Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.82Style Draw-thru Rotations per minute 699Inlet vanes No Brake power @ Altitude (HP) 5.45Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600

1.95

13.5

0

1.80

12.0

0

1.65

10.5

0

1.50

9.00

1.35

7.50

1.20

6.00

1.05

4.50

0.90

3.00

Page 127: Submit Tal Mater No in f David

DRAWING • UMA # 9

Untitled • PISO 5-OESTE

Tuesday, January 21, 2003 Page 127 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,458

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,856

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 128: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 8

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 128 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.15

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.94Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.59Internal isolation Spring (standard) Brake power @ Actual (HP) 7.07Arrangement #3 Rotations per minute 632Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 11,080 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.09

Page 129: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 8

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 129 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1406.6287.7

11,0800

4700.65

76.9 / 65.052.8 / 52.7

Actual

Water75.23.5

44.054.87.3

5 / 2844.676.023.6

5 / 1223

Air handler1@1 1/21@1 1/2

MPT

Page 130: Submit Tal Mater No in f David

FAN CURVE • UMA # 8

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 130 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 11,080Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.59Style Draw-thru Rotations per minute 632Inlet vanes No Brake power @ Altitude (HP) 7.07Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600

2.00

12.0

0

1.80

10.8

0

1.60

9.60

1.40

8.40

1.20

7.20

1.00

6.00

0.80

4.80

0.60

3.60

Page 131: Submit Tal Mater No in f David

DRAWING • UMA # 8

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 131 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,746

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,141

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in

Page 132: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 7

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 132 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 080 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 13 Cartridge/bag

Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidPre-filter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.24Access panels One

B. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.30

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.96

Refer to attached pages for coil performance.

D. Section 1 Horizontal draw-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.50Internal isolation Spring (standard) Total static @ Actual (in w.g.) 2.50Arrangement #3 Brake power @ Actual (HP) 7.47Motor type High Eff. TEFC Rotations per minute 1,134Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 7,680 Liners SolidExternal static @ Actual (in w.g.) 1.00

Page 133: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 7

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 133 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W F 8 B - 23T x 62 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1616.7281.6

7,6800

4870.96

85.8 / 75.751.3 / 51.3

Actual

Water112.9

5.344.054.917.0

5 / 2336.762.015.8

8 / 1023

Air handler1@2 1@2 MPT

Page 134: Submit Tal Mater No in f David

FAN CURVE • UMA # 7

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 134 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 080 H M Air flow (ft³/min) 7,680Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.50Style Draw-thru Rotations per minute 1,134Inlet vanes No Brake power @ Altitude (HP) 7.47Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000

3.00

13.5

0

2.70

12.0

0

2.40

10.5

0

2.10

9.00

1.80

7.50

1.50

6.00

1.20

4.50

0.90

3.00

Page 135: Submit Tal Mater No in f David

DRAWING • UMA # 7

Untitled • PISO 4-OESTE

Tuesday, January 21, 2003 Page 135 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 0

80 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

5.2 in16.0 in

123.

5 in

/2,7

05 lb

51.0 in

51.0 in

78.0

in

37.0

in18

.8 in

78.0

in

Page 136: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 6

Untitled • PISO 3-ESTE

Tuesday, January 21, 2003 Page 136 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.87Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.49Internal isolation Spring (standard) Brake power @ Actual (HP) 5.31Arrangement #3 Rotations per minute 592Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,730 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.99

Page 137: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 6

Untitled • PISO 3-ESTE

Tuesday, January 21, 2003 Page 137 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W F 6 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1463.5288.3

9,7300

4130.65

78.8 / 67.251.3 / 51.3

Actual

Water82.93.2

44.055.26.1

5 / 2844.676.023.6

6 / 1228

Air handler1@2 1@2 MPT

Page 138: Submit Tal Mater No in f David

FAN CURVE • UMA # 6

Untitled • PISO 3-ESTE

Tuesday, January 21, 2003 Page 138 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,730Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.49Style Draw-thru Rotations per minute 592Inlet vanes No Brake power @ Altitude (HP) 5.31Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.60

9.00

1.40

8.00

1.20

7.00

1.00

6.00

0.80

5.00

0.60

4.00

0.40

3.00

Page 139: Submit Tal Mater No in f David

DRAWING • UMA # 6

Untitled • PISO 3-ESTE

Tuesday, January 21, 2003 Page 139 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,849

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,141

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in

Page 140: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 5

Untitled • PISO 3-OESTE

Tuesday, January 21, 2003 Page 140 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.15

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.97Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.62Internal isolation Spring (standard) Brake power @ Actual (HP) 4.64Arrangement #3 Rotations per minute 660Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,680 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.12

Page 141: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 5

Untitled • PISO 3-OESTE

Tuesday, January 21, 2003 Page 141 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1336.1228.2

8,6800

4690.69

76.8 / 65.252.5 / 52.3

Actual

Water60.24.1

44.055.212.2

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 142: Submit Tal Mater No in f David

FAN CURVE • UMA # 5

Untitled • PISO 3-OESTE

Tuesday, January 21, 2003 Page 142 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 8,680Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.62Style Draw-thru Rotations per minute 660Inlet vanes No Brake power @ Altitude (HP) 4.64Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,500 9,000 10,500 12,000 13,500 15,000 16,500

1.80

10.8

0

1.65

9.60

1.50

8.40

1.35

7.20

1.20

6.00

1.05

4.80

0.90

3.60

0.75

2.40

Page 143: Submit Tal Mater No in f David

DRAWING • UMA # 5

Untitled • PISO 3-OESTE

Tuesday, January 21, 2003 Page 143 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,425

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,789

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 144: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 4

Untitled • PISO 2-ESTE

Tuesday, January 21, 2003 Page 144 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 100 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.22

B. Section 20 External face & bypass section

Liners Solid Pressure drop (in w.g.) 0.28

C. Section 7 Short cooling coil section

Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.59

Refer to attached pages for coil performance.

D. Section 1 Horizontal draw-thru fan section

Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.09Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.59Arrangement #3 Brake power @ Actual (HP) 6.42Motor type High Eff. TEFC Rotations per minute 812Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 70.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 9,155 Liners SolidExternal static @ Actual (in w.g.) 0.50

Page 145: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 4

Untitled • PISO 2-ESTE

Tuesday, January 21, 2003 Page 145 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W H 5 B - 28T x 62 LH 1 Section C - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1325.2232.1

9,1550

4760.59

76.8 / 64.853.3 / 52.8

Actual

Water61.34.7

44.054.617.1

5 / 2844.662.019.2

5 / 1014

Air handler1@1 1/21@1 1/2

MPT

Page 146: Submit Tal Mater No in f David

FAN CURVE • UMA # 4

Untitled • PISO 2-ESTE

Tuesday, January 21, 2003 Page 146 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 100 H M Air flow (ft³/min) 9,155Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.59Style Draw-thru Rotations per minute 812Inlet vanes No Brake power @ Altitude (HP) 6.42Altitude (ft) 0 Coldest dry bulb (°F) 70.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

4,800 6,000 7,200 8,400 9,600 10,800 12,000 13,200

1.95

10.8

0

1.80

9.60

1.65

8.40

1.50

7.20

1.35

6.00

1.20

4.80

1.05

3.60

0.90

2.40

Page 147: Submit Tal Mater No in f David

DRAWING • UMA # 4

Untitled • PISO 2-ESTE

Tuesday, January 21, 2003 Page 147 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

00 H

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

8.6 in19.0 in

113.

0 in

/2,9

93 lb

58.0 in

58.0 in

78.0

in

36.0

in22

.0 in

78.0

in

Page 148: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 3

Untitled • PISO 2-OESTE

Tuesday, January 21, 2003 Page 148 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.14

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.93Maximum bypass air flow (ft³/min) 7,570

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.57Internal isolation Spring (standard) Brake power @ Actual (HP) 4.32Arrangement #3 Rotations per minute 648Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,430 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.07

Page 149: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 3

Untitled • PISO 2-OESTE

Tuesday, January 21, 2003 Page 149 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1360.1231.3

8,4300

4560.66

77.7 / 66.452.2 / 52.1

Actual

Water65.04.4

44.055.114.0

5 / 2235.176.018.5

6 / 1016

Air handler1@1 1/21@1 1/2

MPT

Page 150: Submit Tal Mater No in f David

FAN CURVE • UMA # 3

Untitled • PISO 2-OESTE

Tuesday, January 21, 2003 Page 150 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 120 V M Air flow (ft³/min) 8,430Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.57Style Draw-thru Rotations per minute 648Inlet vanes No Brake power @ Altitude (HP) 4.32Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.65

9.00

1.50

8.00

1.35

7.00

1.20

6.00

1.05

5.00

0.90

4.00

0.75

3.00

Page 151: Submit Tal Mater No in f David

DRAWING • UMA # 3

Untitled • PISO 2-OESTE

Tuesday, January 21, 2003 Page 151 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

20 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,425

lb

58.0 in17.5

in24

.9 in

51.0

in/2

,789

lb

58.0 in

114.5 in

94.0

in

39.6

in22

.9 in

94.0

in

Page 152: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 2

Untitled • PISO 1- ESTE

Tuesday, January 21, 2003 Page 152 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.82Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.44Internal isolation Spring (standard) Brake power @ Actual (HP) 4.91Arrangement #3 Rotations per minute 580Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,420 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.94

Page 153: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 2

Untitled • PISO 1- ESTE

Tuesday, January 21, 2003 Page 153 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 6 C - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1390.3263.9

9,4200

4000.62

76.9 / 65.050.9 / 50.9

Actual

Water64.23.3

44.056.28.5

5 / 2844.676.023.6

6 / 1221

Air handler1@1 1/21@1 1/2

MPT

Page 154: Submit Tal Mater No in f David

FAN CURVE • UMA # 2

Untitled • PISO 1- ESTE

Tuesday, January 21, 2003 Page 154 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,420Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.44Style Draw-thru Rotations per minute 580Inlet vanes No Brake power @ Altitude (HP) 4.91Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.80

10.0

0

1.60

9.00

1.40

8.00

1.20

7.00

1.00

6.00

0.80

5.00

0.60

4.00

0.40

3.00

Page 155: Submit Tal Mater No in f David

DRAWING • UMA # 2

Untitled • PISO 1- ESTE

Tuesday, January 21, 2003 Page 155 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,849

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,074

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in

Page 156: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 1

Untitled • PISO 1-OESTE

Tuesday, January 21, 2003 Page 156 of 159 Version 3.70 - Released 5/13/2002 - VA01

CS² Air Handler

Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only

Notes

- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.

A. Section 10F2 Flat filter section

Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12

B. Section 18 Internal face & bypass short coil section

Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.66Maximum bypass air flow (ft³/min) 10,094

Refer to attached pages for coil performance.

C. Shipping split

D. Section 3 Vertical draw-thru fan section

Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.28Internal isolation Spring (standard) Brake power @ Actual (HP) 4.60Arrangement #3 Rotations per minute 557Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,430 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.78

Page 157: Submit Tal Mater No in f David

PERFORMANCE SUMMARY • UMA # 1

Untitled • PISO 1-OESTE

Tuesday, January 21, 2003 Page 157 of 159 Version 3.70 - Released 5/13/2002 - VA01

Air Handler Coils

Coil Tag Model # Qty Location Footnotes

CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type

#1 5 W P 5 B - 28T x 76 LH 1 Section B - Coil A

A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.

A

#1319.8233.4

9,4300

4000.45

76.1 / 64.353.2 / 52.7

Actual

Water60.02.8

44.054.74.9

5 / 2844.676.023.6

5 / 1023

Air handler1@1 1/21@1 1/2

MPT

Page 158: Submit Tal Mater No in f David

FAN CURVE • UMA # 1

Untitled • PISO 1-OESTE

Tuesday, January 21, 2003 Page 158 of 159 Version 3.70 - Released 5/13/2002 - VA01

Supply Fan Specification

Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,430Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.28Style Draw-thru Rotations per minute 557Inlet vanes No Brake power @ Altitude (HP) 4.60Altitude (ft) 0 Coldest dry bulb (°F) 54.0

Fan Curve

Air flow (ft³/min)

Stat

ic p

ress

ure

@ A

ltitu

de (i

n w

.g.)

Brak

e po

wer

@ A

ltitu

de (H

P)

6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400

1.50

8.00

1.35

7.20

1.20

6.40

1.05

5.60

0.90

4.80

0.75

4.00

0.60

3.20

0.45

2.40

Page 159: Submit Tal Mater No in f David

DRAWING • UMA # 1

Untitled • PISO 1-OESTE

Tuesday, January 21, 2003 Page 159 of 159 Version 3.70 - Released 5/13/2002 - VA01

Side

vie

w -

AH

D2

FS 1

50 V

M

Ente

ring

air v

iew

Leav

ing

air v

iew

This

dra

win

g is

not

to s

cale

; it i

s to

be

used

for d

imen

sion

al p

urpo

ses

only

.

42.0

in/1

,713

lb

72.0 in16.5

in27

.4 in

56.0

in/3

,074

lb

72.0 in

142.5 in

94.0

in

39.0

in20

.4 in

94.0

in


Recommended