8/12/2019 Submittal for Substation Lighting - 1 http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 1/14  TECHNICAL SUBMITTAL FOR SUBSTATION LIGHTING
Transcript
Page 1: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 1/14

 

TECHNICAL SUBMITTAL

FORSUBSTATION LIGHTING

Page 2: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 2/14

Page 3: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 3/14

 

B122/2 SUBSTATION

LIGHTING AND SMALL

POWER LAYOUT

Page 4: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 4/14

Page 5: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 5/14

Page 6: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 6/14

 

B122/2 SUBSTATION

LIGHTING CALCULATION

Page 7: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 7/14

Page 8: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 8/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: 3.3KV Switchgear Room

Design level of illumination: 23 fc (initial)

15 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Room Length….……………………………………………… 11.96 m (39 ft)

Room Width……………………………………………….… 6.60 m (22 ft)

Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)

Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)

Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)

Room Surface Reflectances Luminaire

Ceiling………………………………………………………… 80% Manufacturer……….… Thorn

Walls above luminaire plane…………………………………50% Catalog No. ……………PP236

Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp

Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650

Floor…………………………………………………………… 20% Maint. Factor...….... : 70%

SELECTION OF COEFFICIENT OF UTILIZATION

1. Determine cavity ratios by formula:

5 x hcc x (L + W)

(L x W)

  5 x 1.64 x (39 + 22)

(39 x 22)

5 x hrc x (L + W)

(L x W)

  5 x 4.92 x (39 + 22)

(39 x 22)

2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 71%

3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 19%

4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.66

  using RCR, pcc and wall reflectance.

Foot Candle x Area of Room (Sq. ft)

Lamps/Fixture x lumens/lamp x c.u. x m.f.

 

LIGHTING CALCULATION FOR NEW PACKAGED

(ZONAL CAVITY METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 2 of 8

  = 1.75 or 1.8

  = 8 LUMINAIRES

  =23 x (22 x 39)

2 x 2650 x .66 x .7

No.of fixture required =

Ceiling Cavity Ratio (CCR): =

  = .58 or .60

Room Cavity Ratio (RCR): =

 

hrc

hfc

hcc

work plane

floor 

ceiling

luminaire

B

Page 9: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 9/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: Low Voltage Room

Design level of illumination: 23 fc (initial)

15 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Room Length….……………………………………………… 16.538 m (54 ft)

Room Width……………………………………………….… 6.60 m (22 ft)

Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)

Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)

Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)

Room Surface Reflectances Luminaire

Ceiling………………………………………………………… 80% Manufacturer……….… Thorn

Walls above luminaire plane…………………………………50% Catalog No. ……………PP236

Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp

Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650

Floor…………………………………………………………… 20% Maint. Factor...….... : 70%

SELECTION OF COEFFICIENT OF UTILIZATION

1. Determine cavity ratios by formula:

5 x hcc x (L + W)

(L x W)

  5 x 1.64 x (54 + 22)

(54 x 22)

5 x hrc x (L + W)

(L x W)

  5 x 4.92 x (54 + 22)

(54 x 22)

2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 73%

3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 19%

4. Find coefficient of utilization from published data (for pfc=20%) C.U. = 0.66  using RCR, pcc and wall reflectance.

Foot Candle x Area of Room (Sq. ft)

Lamps/Fixture x lumens/lamp x c.u. x m.f.

  = 1.57

 

LIGHTING CALCULATION FOR NEW PACKAGED

(ZONAL CAVITY METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 3 of 8

2 x 2650 x .66 x .7

No.of fixture required =

Ceiling Cavity Ratio (CCR): =

  = .52 or .5

Room Cavity Ratio (RCR): =

 

= 11.15 or 12 LUMINAIRES

  =23 x (54 x 18)

hrc

hfc

hcc

work plane

floor 

ceiling

luminaire

B

Page 10: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 10/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: Fire Fighting Gas Cylinder Room

Design level of illumination: 23 fc (initial)

15 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Room Length….……………………………………………… 2.50 m (8 ft)

Room Width……………………………………………….… 1.50 m (5 ft)

Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)

Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)

Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)

Room Surface Reflectances Luminaire

Ceiling………………………………………………………… 80% Manufacturer……….… Thorn

Walls above luminaire plane…………………………………50% Catalog No. ……………PP236

Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp

Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650

Floor…………………………………………………………… 20% Maint. Factor...….... : 70%

SELECTION OF COEFFICIENT OF UTILIZATION

1. Determine cavity ratios by formula:

5 x hcc x (L + W)

(L x W)

  5 x 1.64 x (8 + 5)

(8 x 5)

5 x hrc x (L + W)

(L x W)

  5 x 4.92 x (8 + 5)

(8 x 5)

2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 49%

3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 16%

4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.58  using RCR, pcc and wall reflectance.

Foot Candle x Area of Room (Sq. ft)

Lamps/Fixture x lumens/lamp x c.u. x m.f.

  = .4 or 1 LUMINAIRE

  =23 x (8 x 5)

2 x 2650 x .58 x .7

No.of fixture required =

Ceiling Cavity Ratio (CCR): =

  = .2.67

Room Cavity Ratio (RCR): =

  = 8.0

 

LIGHTING CALCULATION FOR NEW PACKAGED

(ZONAL CAVITY METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 4 of 8

hrc

hfc

hcc

work plane

floor 

ceiling

luminaire

B

Page 11: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 11/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: Battery Room

Design level of illumination: 23 fc (initial)

15 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Room Length….……………………………………………… 2.40 m (7.87 ft)

Room Width……………………………………………….… 2.05 m (6.7 ft)

Height of Room between luminaire and work plane (hrc). : 1.5 m (4.92 ft)

Distance from luminaire plane to ceiling (hcc)…………….. .5 m (1.64 ft)

Height of work plane above floor (hfc)………………………1 m ( 3.28 ft)

Room Surface Reflectances Luminaire

Ceiling………………………………………………………… 80% Manufacturer……….… Thorn

Walls above luminaire plane…………………………………50% Catalog No. ……………Petrelux 7, P7236 /HF

Walls between luminarie and workplane……………………50% No. & Type lamps……..2 x 36W Flourescent lamp

Walls below work plane……………………………………… 50% Lumens/Lamp……… : 2650

Floor…………………………………………………………… 20% Maint. Factor...….... : 70%

SELECTION OF COEFFICIENT OF UTILIZATION

1. Determine cavity ratios by formula:

5 x hcc x (L + W)

(L x W)

  5 x 1.64 x (7.87 + 6.7)

(7.87 x 6.6)

5 x hrc x (L + W)

(L x W)

  5 x 4.92 x (7.87 + 6.7)

(7.87 x 6.7)

2. Obtain ef fective cei ling cavi ty ref lectances (pcc) from Table A; pcc = 53%

3. Obtain effective floor cavity reflectances (pfc) from Table A; pfc = 16%

4. Find coefficient of util ization from published data (for pfc=20%) C.U. = 0.58  using RCR, pcc and wall reflectance.

Foot Candle x Area of Room (Sq. ft)

Lamps/Fixture x lumens/lamp x c.u. x m.f.

  = 6.8

 

LIGHTING CALCULATION FOR NEW PACKAGED

(ZONAL CAVITY METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 5 of 8

2 x 2650 x .58 x .7

No.of fixture required =

Ceiling Cavity Ratio (CCR): =

  2.26

Room Cavity Ratio (RCR): =

 

= .56 or 1 LUMINAIRE

  =23 x (7.87 x 6.7)

hrc

hfc

hcc

work plane

floor 

ceiling

luminaire

B

B

Page 12: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 12/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: Walkways and stairs area

Design level of illumination: 3.3 fc (initial)

2 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Length (L) ….…………………………………………… : 2.3 m (6.89 ft)

Height (H) ………………………………………………. : 3 m (9.84 ft)

Distance (D) ………………………………………..….. : 3.66 m (12 ft)

Luminaire

Manufacturer……….……. : Thorn

Catalog No. …………….... : DBV1040

No. & Type lamps……... : 1 x 70W Son-E High Pressure Sodium lamp

Lumens/Lamp……… : 5800

Maint. Factor...….... : 70%

Candle Power……….: 870

Foot candle computation:fc = CP x H x LLF

  D³

where:

fc - Foot Candles

CP - Candle Power of Luminaire

H - Mounting Height

D - Distance

LLF - Light Loss Factor or Maintenance Factor 

fc = 870 x 9.84 x .7

  (12)³

= 3.47 fc

* Since the foot candle computed is larger than the design level of illumination (3.47 > 3.3)

  then the lamp proposed is adequate.

 

LIGHTING CALCULATION FOR NEW PACKAGED

SUBSTATION B122/2

(POINT BY POINT METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 6 of 8

floor 

wall

H

luminaire

L

D

B

Page 13: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 13/14

Rev. B

GENERAL INFORMATION

Location: B122/2 Substation

 Area to be lighted: Transformer Area

Design level of illumination: 3.3 fc (initial)

2 fc (service)

DESCRIPTION OF AREA AND LUMINAIRE

Dimensions

Length (L) ….…………………………………………… : 5.9 m (19.35 ft)

Height (H) ………………………………………………. : 4.5 m (14.76 ft)

Distance (D) ………………………………………..….. : 7.42 m (24.34 ft)

Luminaire

Manufacturer……….……. : Thorn

Catalog No. …………….... : Sonpak 7/15 OT100T.4

No. & Type lamps……... : 1 x 100W HPS-T High Pressure Sodium Lamp

Lumens/Lamp……… : 9,200

Maint. Factor...….... : 70%

Candle Power……….: 5,520

Foot candle computation:fc = CP x H x LLF

  D³

where:

fc - Foot Candles

CP - Candle Power of Luminaire

H - Mounting Height

D - Distance

LLF - Light Loss Factor or Maintenance Factor 

fc = 5,520 x14.76 x .7

  (20.87)³

= 3.96 fc

* Since the foot candle computed is larger than the design level of illumination (3.96 > 3.3)

  then the lamp proposed is adequate.

 

LIGHTING CALCULATION FOR NEW PACKAGED

SUBSTATION B122/2

(POINT BY POINT METHOD)

Contract No. CB / PD / 1105

Project: KNPC VACUUM RE-RUN REVAMP

PROJECT

DOC. NO. 9063B-004-A4111-001

Page 7 of 8

floor 

wall

H

luminaire

L

D

B

Page 14: Submittal for Substation Lighting - 1

8/12/2019 Submittal for Substation Lighting - 1

http://slidepdf.com/reader/full/submittal-for-substation-lighting-1 14/14

90 70 50 30 80 70 50 30 70 50 30 70 50 30 65 50 30 10 50 30 10 50 30 10

0 90 90 90 90 80 80 80 80 70 70 70 50 50 50 30 30 30 30 20 20 20 10 10 10

0.1 90 89 88 87 79 79 78 78 69 69 68 59 49 48 30 30 29 29 20 20 20 10 10 10

0.2 89 88 86 85 79 78 77 76 68 67 66 49 48 47 30 29 29 28 20 20 19 10 10 9

0.3 89 87 85 83 78 77 75 74 68 66 64 49 47 46 30 29 28 27 20 19 18 10 10 9

0.4 88 86 83 81 78 76 74 72 67 65 63 48 46 45 30 29 27 26 20 19 18 11 10 9

0.5 88 85 81 78 77 75 73 70 66 64 61 48 46 44 29 28 27 25 20 19 17 11 10 9

0.6 88 84 80 76 77 75 71 68 65 62 59 47 45 43 29 28 26 25 20 18 17 11 10 9

0.7 88 83 78 74 76 74 70 66 65 61 58 47 44 42 29 28 26 24 20 18 16 11 10 8

0.8 87 82 77 73 75 73 69 65 64 60 56 47 43 41 29 27 25 23 19 18 16 11 10 8

0.9 87 81 76 71 75 72 68 63 63 59 55 46 43 40 29 27 25 22 19 17 15 11 9 8

1 86 80 74 69 74 71 66 61 63 58 53 46 42 39 29 27 24 22 19 17 15 11 9 8

1.1 86 79 73 67 74 71 65 60 62 57 52 46 41 38 29 26 24 21 19 17 15 11 9 8

1.2 86 78 72 65 73 70 64 58 61 56 50 45 41 37 29 26 23 20 19 16 14 12 9 7

1.3 85 78 70 64 73 69 63 57 61 55 49 45 40 36 29 26 23 20 19 16 14 12 9 7

1.4 85 77 69 62 72 68 62 55 60 54 48 45 40 35 28 26 22 19 19 16 13 12 9 7

1.5 85 76 68 61 72 68 61 54 59 53 47 44 39 34 28 28 22 18 20 16 13 12 9 7

1.6 85 75 66 59 71 67 60 53 59 52 45 44 39 33 28 25 21 18 19 15 13 12 9 7

1.7 84 74 65 58 71 66 59 52 58 51 44 44 38 32 28 25 21 17 19 15 12 12 9 7

1.8 84 73 64 56 70 65 58 50 57 50 43 43 37 32 28 25 21 17 19 15 12 12 9 6

1.9 84 73 63 55 70 65 57 49 57 49 42 43 37 31 28 25 20 16 19 15 11 12 9 6

2 83 72 62 53 69 64 56 48 56 48 41 43 37 30 28 24 20 16 18 15 11 12 9 6

2.1 83 71 61 52 69 63 55 47 56 47 40 43 36 29 28 24 20 16 19 15 11 13 9 6

2.2 83 70 60 51 68 63 54 45 55 46 39 42 36 29 28 24 19 15 19 14 11 13 9 6

2.3 83 69 59 50 68 62 53 44 54 46 38 42 35 28 28 24 19 15 19 14 11 13 9 6

2.4 82 68 58 48 67 61 52 43 54 45 37 42 35 27 28 24 19 14 19 14 10 13 9 6

2.5 82 68 57 47 67 61 51 42 53 44 36 41 34 27 27 23 18 14 18 14 10 13 9 6

2.6 82 67 56 46 66 60 50 41 53 43 35 41 34 26 27 23 18 13 18 14 9 13 9 5

2.7 82 66 55 45 66 60 49 40 52 43 34 41 33 26 27 23 18 13 18 14 9 13 9 5

2.8 81 66 54 44 66 59 48 39 52 42 33 41 33 28 27 23 18 13 18 14 9 13 9 5

2.9 81 65 53 43 65 58 48 38 51 41 33 40 33 25 27 23 17 12 18 13 9 13 9 5

3 81 64 52 42 65 58 47 38 51 40 32 40 32 24 27 22 17 12 18 13 9 13 8 5

3.1 80 64 51 41 64 57 46 37 50 40 31 40 32 24 27 22 17 12 18 13 9 13 8 5

3.2 80 63 50 40 64 57 45 36 50 39 30 40 31 23 27 22 16 11 18 12 8 13 8 5

3.3 80 62 49 39 64 56 44 35 49 39 30 39 31 23 27 22 16 11 18 12 8 13 8 5

3.4 80 62 48 38 63 56 44 34 49 38 29 39 31 22 27 22 16 11 18 12 8 13 8 53.5 79 61 48 37 63 55 43 33 48 38 29 39 30 22 26 22 16 11 18 12 8 13 8 5

3.6 79 60 47 36 62 54 42 33 48 37 28 39 30 21 26 21 15 10 17 12 8 13 8 5

3.7 79 60 46 35 62 54 42 32 48 37 27 38 30 21 26 21 15 10 17 12 7 13 8 4

3.8 79 59 45 35 62 53 41 31 47 36 27 38 29 21 26 21 15 10 17 12 7 13 8 4

3.9 78 59 45 34 61 53 40 30 47 36 26 38 29 20 26 21 15 10 17 12 7 13 8 4

4 78 58 44 33 61 52 40 30 46 35 26 38 29 20 26 21 15 9 17 12 7 13 8 4

4.1 78 57 43 32 60 52 39 29 46 35 25 37 28 20 26 21 14 9 17 11 7 13 8 4

4.2 78 57 43 32 60 51 39 29 46 34 25 37 28 19 26 20 14 9 17 11 7 13 8 4

4.3 78 56 42 31 60 51 38 28 45 34 25 37 28 19 26 20 14 9 17 11 7 13 8 4

4.4 77 56 41 30 59 51 38 28 45 34 24 37 27 19 26 20 14 8 17 11 6 13 8 4

4.5 77 55 41 30 59 50 37 27 45 33 24 37 27 19 25 20 14 8 17 11 6 14 8 4

4.6 77 55 40 29 59 50 37 26 44 33 24 36 27 18 25 20 14 8 17 11 6 14 8 4

4.7 77 54 40 29 58 49 36 26 44 33 23 36 26 18 25 20 13 8 17 11 6 14 8 4

4.8 76 54 39 28 58 49 36 25 44 32 23 36 26 18 25 19 13 8 17 11 6 14 8 4

4.9 76 53 38 28 58 49 35 25 44 32 23 36 26 18 25 19 13 7 17 11 6 14 8 4

5 76 53 38 27 57 48 35 25 43 32 22 36 26 17 25 19 13 7 17 11 6 14 8 4

 

TABLE A - EFFECTIVE CAVITY REFLECTANCES

% Ceiling or Floor

Reflectance 90 80 70 50

LIGHTING CALCULATION FOR NEW PACKAGED

SUBSTATION B122/2

Contract No.CB/PD/1105

   C  e   i   i  n  g  o  r   F   l  o  o  r   C  a  v   i   t  y   R  a   t   i  o

30 20 10

% Wall Reflectance

Project: KNPC VACUUM RE-

RUN REVAMP PROJECT

Doc. No.9063B-004-A4111-001

Rev. B Page 8 of 8