Page 1 of 1 2429 Members Way Lexington KY 40504 859.253.0892 www.cmta.com MEP Engineering | Performance Contracting | Zero Energy Engineering | Technology | Commissioning Submittal Review Summary Project: Transy Strickland Auditorium Renovation Submittal: RTU CMTA Project Code: XTSA20 Reviewed by: RSJ Date Received: 2021-05-26 Date Returned: 2021-06-14 Corrections or comments made on the shop drawings during this review do not relieve the contractor from compliance with requirements of the drawings and specifications. This check is only for review of general compliance with the information given in the contract documents. The contractor is responsible for confirming and correlating all quantities and dimensions; selecting fabrication processes and techniques of construction; coordinating his work with that of all other trades; and performing his work in a safe and satisfactory manner. Reviewed Furnish as Corrected Rejected Revise and Resubmit COMMENTS: 1. Revise feeder to be 4-#8, #10 G in ¾” conduit with 50/3 breaker. Coordinate 120V field power to service receptacle.
Transcript

Page 1 of 1

2429 Members Way Lexington KY 40504 859.253.0892 www.cmta.com

MEP Engineering | Performance Contracting | Zero Energy Engineering | Technology | Commissioning

Submittal Review Summary

Project: Transy Strickland Auditorium Renovation

Submittal: RTU

CMTA Project Code: XTSA20 Reviewed by: RSJ

Date Received: 2021-05-26 Date Returned: 2021-06-14

Corrections or comments made on the shop drawings during this review do not relieve the contractor

from compliance with requirements of the drawings and specifications. This check is only for

review of general compliance with the information given in the contract documents. The contractor is

responsible for confirming and correlating all quantities and dimensions; selecting fabrication processes

and techniques of construction; coordinating his work with that of all other trades; and performing his

work in a safe and satisfactory manner.

Reviewed Furnish as Corrected

Rejected Revise and Resubmit

COMMENTS:

1. Revise feeder to be 4-#8, #10 G in ¾” conduit with 50/3 breaker. Coordinate 120V field

power to service receptacle.

Submittal Data

Project: Strickland Auditorium

Bid Category: HVAC

Project Number:

Construction Manager: Churchill Mcgee

Spec Section: HVAC

Submittal For: RTU

Manufacturer: Diakin

Supplier: Thermal Equipment

Contact Name & Phone #: Jay Mckinney

The attached submittal data has been reviewed by C&C Industrial for compliance with the specifications

and plan schedule for this project.

In order to maintain the project schedule, we request that this submittal be returned to C&C Industrial

within 7 days.

_____x__ Reviewed

_______ Drawing

_______ Rejected

5/25/21 Date

By James Randall

C&C Industrial

Len Figler
Approved

LEXINGTON 680 Bizzell Drive, Lexington KY 40510 859.255.9665 LOUISVILLE 13151 Middletown Industrial Boulevard, Louisville KY 40223 502.473.0829 PADUCAH 115 Eaglet Cove, Paducah KY 42003 270.898.6976

JOB NAME: STRICKLAND AUDITORIUM RENOVATION Transylvania University 300 North Broadway Lexington, KY 40508 ARCHITECT: ROSSTARRANT ARCHITECTS 101 Old Lafayette Avenue Lexington, KY 40502 ENGINEER: CMTA, INC. 2429 Members Way Lexington, KY 40504 CONTRACTOR: C&C INDUSTRIAL 280 Midland Trail Mount Sterling, KY 40353 SPECIFICATION SECTION: 23 02 00 HVAC EQUIPMENT AND

HYDRONIC SPECIALTIES – Section 2A Rooftop Equipment SALESMAN: Jay McKinney Rodney Sproul TES FILE #: 17068

S

U

B

M

I

T

T

A

L

17068 Strickland Auditorium Renovation Page 1 of 20 5/25/2021

ONE (1) DAIKIN APPLIED – Packaged Applied Heat Pump with Electric Aux Heat Unit (TAGGED: RTU-1) Current Lead Time ~ 12 to 14 weeks Unit weight is approximately 1,411 lbs (67.0” l x 40.8” h x 87.0” w)

• Exterior: Painted Galvanized Steel • Insulation and Liners: 1" injected foam, R-7, Galvanized Steel Liner • Heat Pump with Electric Aux Heat • Vertical Return and Supply connections • Approval Listing: cETLus • Unit Voltage: 460v / 60hz / 3ph

o 65kA SCCR non-fused disconnect per specification o Phase failure monitor o 115v GFCI receptacle – field powered

• Economizer with Comparative enthalpy control and barometric relief • Control System: Microtech III, BACnet protocol card – BACnet MSTP

o Variable Volume control o Supply – Direct Drive - ECM Motor - Premium efficiency

• Filter Section o Combo filter rack 2”/4” configuration o 2” MERV 8 Filters

• Indoor Coil Section o Copper tube / aluminum fin o BTU/hr Total Capacity o Stainless steel drain pan with condensate overflow switch

• Hot Gas Reheat Coil Section o Modulating hot gas reheat with duct humidity sensor o Aluminum tube micro-channel

• Electric Heat Section o 18kW capacity o 4 step control

• Air Cooled Condensing Section o (1) Inverter scroll compressor o Capacity Control: Modulating control with inverter compressor o Refrigerant Type: R-410a o Condenser Coil: Aluminum Microchannel 23 fpi o 1 Condenser Fan ECM Motor

Ship loose items included in the quotation (field installed by others)

• Combination digital temperature and humidity sensor with adjustable setpoint and tenant override • 18” insulated roofcurb for flat roofs

Start-up and warranty:

• Check, Test and Startup and Owner Training by Thermal Equipment Sales • 1st year parts only warranty by Daikin Applied • 5-Year compressor parts warranty by Daikin Applied

Specific Exclusions

• Labor warranty • Unit powered GFI is not available with 65kA fused disconnect – requires field power

17068 Strickland Auditorium Renovation Page 2 of 20 5/25/2021

SUBMITTAL NOTES:

UNIT CONFIGURATION: This unit is configured as single zone VAV, mixed air or 100% outside air unit, heat pump unit with hot gas reheat and electric heating. Unit is shipped as a bottom supply / bottom return unit that is to be mounted on the shipped loose knock-down roof curb for flat roofs for field install by others. Please ensure curb is level and square side to side, front to back.

SINGLE POINT POWER and DISCONNECT: Power required for these units is 460v / 3ph / 60hz. We are providing factory mounted 65kA SCCR non-fused disconnect and phase failure monitor. A FIELD powered 115v GFCI outlet is provided.

FIELD PIPING: Contractor, please note, units DO NOT have condensate traps, a properly sized external trap with a depth of at least 2 times the unit ESP as a rule of thumb is required for proper drainage. External piping is not provided and assumed to be by others.

FILTERS AND FILTER RACKS: A combo 2/4” filter rack with access door with 2” MERV-8 filters being provided; the unit is provided with (1) set of filters. All others are assumed to be by others.

TCC/BMS CONTRACTOR: The unit is being provided with a factory Microtech III controller with BACnet MSTP communication card. A shipped loose combination humidity and temperature sensor is provided with the unit for field installation by others. Any additional control requirements are assumed to be by others including smoke detectors.

CHECK, TEST and START-UP: Thermal Equipment Sales, Inc. is providing factory authorized startup for quality control purposes.

WARRANTY and LABOR WARRANTY: The unit has a ONE YEAR (entire unit parts), and a FIVE YEAR (compressor) parts only warranty, this is provided by Daikin. This warranty begins at substantial completion. Thermal Equipment Sales is not providing labor warranty for the equipment.

17068 Strickland Auditorium Renovation Page 3 of 20 5/25/2021

SUBMITTAL DATA for

17068 Transy Strickland Auditorium

Prepared for

CMTA, INC.

Job Number: MZL2HP

Prepared by

Jay McKinney

Rodney Sproul

Thermal Equipment Sales

5/25/2021

17068 Strickland Auditorium Renovation Page 4 of 20 5/25/2021

Table of Contents

Item Summary for RTU-1 ........................................................................................................................................................... 4

Technical Data Sheet for RTU-1 .................................................................................................................................................. 6

Fan Curve - Supply for RTU-1 ................................................................................................................................................... 10

3-6 DoorSwing No ERW_Drawing for RTU-1 ............................................................................................................................. 11

Drawings(1) for RTU-1 ............................................................................................................................................................. 12

Drawings(2) for RTU-1 ............................................................................................................................................................. 13

Drawings(3) for RTU-1 ............................................................................................................................................................. 14

Small and Medium Cabinet Rebel Base Rail_Drawing for RTU-1 .............................................................................................. 15

Cabinet AB Sensor Locations_Drawing for RTU-1 ..................................................................................................................... 16

Rebel 910191961_Drawing for RTU-1 ...................................................................................................................................... 17

17068 Strickland Auditorium Renovation Page 5 of 20 5/25/2021

Item Summary for RTU-1 Item Summary for RTU-1

Job Information Item Summary

Job Name 17068 Transy Strickland Auditorium Date 5/25/2021 Model DPS006A Software Version 09.00 Unit Tag RTU-1

Unit Options Code Item

Code Value

Description

1 DPS UNIT TYPE; Daikin Rebel Rooftop 2 006 UNIT SIZE; 6 ton 3 A VINTAGE; Vintage 1 4 H COOLING EFFICIENCY; High 5 H UNIT STYLE; Heat Pump 6 E HEAT; Electric heat 7 4F VOLTAGE/POWER CONNECTION; 460/60/3 power with fused disconnect [65 KAIC] 8 W APPLICATION; Variable Volume Space Control 9 V AIRFLOW PATTERN; Vertical Discharge and Return

10 A CONTROLS; Microtech III Controls 11 T COMMUNICATION CARDS; BACnet/MSTP card, Factory installed 12 1CY OUTSIDE AIR; Economizer, Comparative Enthalpy 13 R EXHAUST TYPE; Barometric Relief 14 A FILTERS; 2 inch, MERV 8 15 4 DX COIL; 4 row 16 T DRAIN PAN; Stainless Steel with Overflow Switch 17 G LINERS; Galvanized Steel 18 M HOT GAS REHEAT; Modulating Hot Gas Reheat 19 Y COIL OPTIONS; None 20 Y INTELLIGENT EQUIPMENT; None 21 HM SUPPLY FAN MOTOR; 4.0 HP ECM Fan Motor 22 16DY SUPPLY FAN; 16 inch, Direct Drive 23 1692 SUPPLY FAN RPM; Fan RPM 24 018Y4 HEAT; 18 KW Heat, 4 stage control 25 1 LOW AMBIENT CONTROL; Low Ambient Control 26 J ELECTRICAL OPTIONS; Field powered GFI Receptacle Phase Volt Monitor 27 Y SMOKE DETECTORS; None 28 Y OA MONITORING; None 29 Y UV LIGHT; None 30 F ECON DIAGNOSTICS; Economizer with Fault Detection Diagnostics 31 Y COMPRESSOR ISOLATION VALVES; None 32 YYY HEAT WHEEL OPTIONS; None 33 YY ENERGY WHEEL CONTROL; None 34 Y ENERGY WHEEL FILTRATION; None 35 YY EXHAUST FAN MOTOR; None 36 YYYY EXHAUST FAN; None 37 AYD UNIT APPROVALS; ETL Unit, AHRI Certified, ASHRAE 90.1-2016 38 Y OUTDOOR COIL OPTIONS; None 39 S EXPANSION VALVE; Electronic Expansion Valve 40 A PARTS WARRANTY; Standard one year 41 Q COMPRESSOR WARRANTY; Additional Four year, Five year total 42 Y GAS HEAT EXCHANGER WARRANTY; None 43 02000 SAF CFM; SAF CFM 44 009 SAF BHP; SAF BHP 45 548 DISCHARGE AIR TEMP; SAF DAT

17068 Strickland Auditorium Renovation Page 6 of 20 5/25/2021

Item Summary for RTU-1 Code Item

Code Value

Description

46 00000 EAF RPM; EAF RPM 47 000 EAF BHP; EAF BHP 48 Y SPECIAL; None 49 Y IBC SEISMIC; None 50 YYYYY CHILLED WATER COIL; None 51 Y WATER ISOLATION VALVE; None 52 YY UNIT LABOR WARRANTY; None 53 YY COMPRESSOR LABOR WARRANTY; None 54 E SUPPLY FAN MOTOR RPM; ECM Fan 55 YY FUTURE USE; None 56 YY FUTURE USE; None

Accessories Part Number Description Qty Ext Qty

910191961 Combo Digital Temp and Humidity Sensor w/Adj setpoint and tenent override

1 1

17068 Strickland Auditorium Renovation Page 7 of 20 5/25/2021

Technical Data Sheet for RTU-1 Technical Data Sheet for RTU-1

Job Information Technical Data Sheet Job Name 17068 Transy Strickland Auditorium Date 5/25/2021 Submitted By Tom Erpenbeck Software Version 09.00

Unit Tag RTU-1

Unit Overview

Model Number Voltage V/Hz/Phase

Design Cooling Capacity

UOM_OSelected_CoilTotal

AHRI360 Standard Efficiency ASHRAE 90.1 EER IEER

DPS006A 460/60/3 76260 11 18.8 ASHRAE 90.1-2016

compliant

Unit

Model Number: DPS006A Model Type: Heat Pump

Heat Type: Electric Hot Gas Reheat: MHGRH with Combination Space Temperature and Humidity Sensor

Energy Recovery: None Application: Variable Air Volume, Single Zone (Mixed Air or 100% OA)

Controls: Microtech III Outside Air: 0-100% Economizer with Comparative Enthalpy Control

Altitude: 0 ft Approval cETLus

Physical Dimensions and Weight

Length Height Width Weight

67.0 in 40.8 in 87.0 in 1411 lb Corner Weights

L1 L2 L3 L4

266 lb 261 lb 438 lb 447 lb Construction

Exterior Insulation and Liners Air Opening Location Return Supply

Painted Galvanized Steel 1" Injected Foam, R-7, Galvanized Steel Liner

Bottom Bottom

Electrical Unit FLA MCA MROPD SCCR

33.4 A 40.5 A 45 A 65 kAIC

Note: Use only copper supply wires with ampacity based on 75° C conductor rating. Connections to terminals must be made with copper lugs and copper wire.

Return/Outside/Exhaust Air Outside Air Option

Type Damper Pressure Drop Exhaust Air Type

90.1 and California Title 24 Compliant Economizer

0.05 inH₂O Barometric Relief

17068 Strickland Auditorium Renovation Page 8 of 20 5/25/2021

Technical Data Sheet for RTU-1

Filter Section Physical

Type Quantity / Size Face Area Face Velocity Air Pressure Drop

Combo 2"/4" rack with 2" MERV 8

4 / 16 in x 16 in x 2 in 7.1 ft² 281.7 ft/min 0.12

DX Cooling Coil Physical

Coil Type Refrigerant Type Fins per Inch Rows Face Area Face Velocity Air Pressure drop

Drain Pan Material

Cu Tube/ Al Fin

R410A 16 4 6.0 ft² 331.1 ft/min 0.34 inH₂O Stainless

Steel Cooling Performance

Capacity Indoor Air Temperature Ambient air Temperature

°F Total

Btu/hr Sensible Btu/hr

Moisture Removal

lb/h

Entering Leaving Dry Bulb

°F Wet Bulb

°F Dry Bulb

°F Wet Bulb

°F Dewpoint

°F

76260 55104 18.2 80.0 67.0 54.8 54.7 54.6 95.0

Condensate Connection Size: 3/4 in. Male NPT Heating Performance

Total Capacity Btu/hr

Refrigerant Type

Indoor Air Temperature Dry Bulb Ambient Air Temperature

°F Entering

°F Leaving

°F

67994 R410A 57.0 88.1 47.0

Hot Gas Reheat Coil Section Type Face Area Air Pressure Drop Total Capacity Leaving Air Temperature

Dry Bulb Wet Bulb

Aluminum Tube Micro-Channel

5.5 ft² 0.07 inH₂O 32976 Btu/hr 70.0 °F 60.3 °F

Fan Section Fan

Type Fan Wheel Diameter Fan Isolation

SWSI AF 16 in None Performance

Airflow Total Static Pressure Fan Speed Brake Horsepower Altitude

2000 CFM 1.7 inH₂O 1692 rpm 0.92 HP 0 ft Motor Drive

Type Horsepower Efficiency FLA Type

ECM Motor 4.0 Premium 4.0 A Direct Drive

17068 Strickland Auditorium Renovation Page 9 of 20 5/25/2021

Technical Data Sheet for RTU-1 Electric Heat Section

Physical Electrical

Airflow Size Control FLA A

2000 CFM 18 kW 4 Stages 21.7 Performance

Capacity Btu/hr

Air Temperature Air Pressure Drop Entering

°F Leaving

°F inH₂O

61434 57.0 85.3 0.36

Unit Discharge Conditions AirTemperature

Motor Heat Btu/hr

Moisture Removal lb/h

Unit Leaving Dry Bulb °F

Unit Leaving Wet Bulb °F

Unit Leaving Dewpoint °F

3351 18.2 56.4 55.2 54.6

Condensing Section Compressor

Type Quantity Refrigerant Charge lb

Total Power Capacity Control Compressor Isolation

Inverter Scroll 1 19.7 4.82 kW Mod Control with

Inverter Compressors Rubber in Shear

Compressor Amps: Compressor 1 6.8 A

Condenser Coil

Type Fins per Inch Fin Material

Copper Tube 23 Aluminum

Condenser Fan Motors

Number of Motors Full Load Current (Total)

1 0.9 A

AHRI 360 Certified Data at AHRI 360 Standard Conditions

Net Capacity EER IEER Heat Net Capacity at 47°F

COP at 47°F Heat Net Capacity at 17°F

COP at 17°F

67000 Btu/hr 11 18.8 66000 Btu/hr 3.69 39000 Btu/hr 2.54

Internal Pressure Drop Calculation External Static Pressure: 0.75 inH₂O

Filter: 0.12 inH₂O Outside Air: 0.05 inH₂O

DX Coil: 0.34 inH₂O Hot Gas Reheat: 0.07 inH₂O

Electric Heat: 0.36 inH₂O Total Static Pressure: 1.70 inH₂O

Sound Sound Power (db)

Frequency 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 73 71 79 74 76 70 65 59

Discharge 73 74 82 79 82 76 73 67

Radiated 82 82 78 75 73 68 61 54

17068 Strickland Auditorium Renovation Page 10 of 20 5/25/2021

Technical Data Sheet for RTU-1 Options

Electrical

Field Connection: Fused Disc: 65 kAIC - 208/230/460V: 22 kAIC 575V Powered Receptacle: Field powered 115V GFI outlet

Power Options: Phase Failure Monitor Controls

Communication Card: BACnet/MSTP card, Factory installed

Factory Installed Sensors

Leaving Coil/Entering Fan Temperature Sensor Duct High Limit Switch BACnet/MSTP Card Return Air Temperature Sensor Discharge Air Temperature sensor – Wired in unit, mounted in supply duct Outside Air Temperature Sensor Return Air Enthalpy Sensor Outside Air Enthalpy Sensor Dirty Filter On/Off Switch Supply Fan Air Proving Via Modbus Condensate Overflow Switch

Warranty

Parts: Standard One Year

Compressor: Additional Four Year, Five Year Total

AHRI Certification

All equipment is rated and certified in accordance with AHRI 360.

Notes

Accessories Mandatory

Part Number Description

910191961 Combo Digital Temp and Humidity Sensor w/Adj setpoint and tenent override

17068 Strickland Auditorium Renovation Page 11 of 20 5/25/2021

Fan Curve - Supply for RTU-1 Fan Curve - Supply for RTU-1

17068 Strickland Auditorium Renovation Page 12 of 20 5/25/2021

3-6 DoorSw

ing No ERW

_Draw

ing for RTU-1

3-6 D oorSwi ng No ERW_Drawi ng for RTU-1

Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 13 of 20 5/25/2021

Draw

ings(1) for RTU-1

Drawings(1) for RTU-1

Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 14 of 20 5/25/2021

Drawings(2) for RTU-1 Drawings(2) for RTU-1

Product Drawing Unit Tag: RTU-1

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 15 of 20 5/25/2021

Draw

ings(3) for RTU-1

Drawings(3) for RTU-1

Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 16 of 20 5/25/2021

Small and Medium Cabinet Rebel Base Rail_Drawing for RTU-1 Small and Me dium Ca binet Rebel Base Rail_Dra wing for RTU-1

Product Drawing Unit Tag: RTU-1

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 17 of 20 5/25/2021

Cabinet AB Sensor Locations_Drawing for RTU-1 Cabi net AB Sensor Locations_ Drawing for RTU-1

Product Drawing Unit Tag: RTU-1

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Model: DPS006A Sales Office: Thermal Equipment Sales Engineer: May 25, 2021 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 18 of 20 5/25/2021

Rebel 910191961_Draw

ing for RTU-1

Rebel 9101 9196 1_Drawi ng for RTU-1

Product Drawing Unit Tag: RTU-1 Sales Office: Thermal Equipment

13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 09.00

Product: Project Name: 17068 Transy Strickland Sales Engineer: Model: DPS006A May 25, 2021 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in [mm]

No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.

17068 Strickland Auditorium Renovation Page 19 of 20 5/25/2021