NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Inspection Type Last EditedTime InInspectionId
SUCCESS ACADEMY WASHINGTON HEIGHTS - MANHATTAN, 701 FORT WASHINGTON AVE, MANHATTAN, NY, 10040School:
1317 2019-01-10 04:34AM 2019-06-27 04:04PMARCHITECTURAL - SENIOR
1330 2019-01-10 07:12AM 2019-01-10 01:19PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Kelsey Depalo
Principal Organization Success Academy Charter School - Washington Heights - New
York 1
Meeting with Principal? No
Principal Feedback Principal questionnaire was returned with following comments
1 - The Gymnasium water leakage from above has damaged the
floor.
2- There are issues with Heating and Cooling in the building.
Custodian Was not present
Fireman Gerardo Rodriguez
Building Square Footage 65,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 3+B+SB+PH
Comments on the Year Built 1890
Comments on the Student Population 480
Comments on the Staff Population 70
Comments on the Number of Classrooms 24
Weather Fair
Facade Photo
Fort Washington Avenue - East view
Page 1 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural InspectionMain Entrance Photo
Fort Washington
Roof Photo
Roof 1 - Southeast view
No System UpgradedHave any Systems/Major Building Components been upgraded?
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? Yes
Year Leased 2014
Inspection Type Partial Inspection
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
NoExterior Entrances & Exits
SADDLE HEIGHT > 1/2"
NoNoExterior H/C Lifts
Page 2 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
NoInterior Corridors & Lobbies
CHANGE IN ELEVATION
NoYesInterior Elevators
CAB SIZE < 51 IN. DEEP
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes NoRoom B3
NOT ON ACCESSIBLE ROUTE
NoAuditorium
Cafeteria
Yes NoBasement
NOT ON ACCESSIBLE ROUTE
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
NoComputer Rooms
Gymnasium
Yes NoSub- Basement ( Church )
NOT ON ACCESSIBLE ROUTE
Library
Yes YesRoom 103B
Main Office
Yes Yes1st Floor
Multi-purpose Room
Yes Yes1st Floor
Nurse's Office
Yes NoRoom F
NOT ON ACCESSIBLE ROUTE
NoPool
Science Lab
Yes YesRoom D and E
Toilet Rooms (boys)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (girls)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Page 3 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on Facade V Inspected
3- FairInstance Condition
Instance Quantity 1
Instance Quantity Uom EACH
AREAWAY GRATINGS:MINOR RUSTINGDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Playground near Gymnasium
Violations No violations recorded
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 4 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
InspectedCHIMNEY
MetalMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCOPING
Condition 4- Between Fair and Poor
METAL:OPEN TRANSVERSE JOINTS WITH DAMAGED
CAULKING
Deficiency
Deficiency Location/Instance
400Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
All Roofs
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL CLAD:DETERIORATED DOOR AND FRAME -
MINOR DETERIORATION
Deficiency
Deficiency Location/Instance
4Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 5 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo 1
Exit Door at Gymnasium
Deficiency Photo 2
Exit Door at Detailed view
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 4- Between Fair and Poor
CONCRETE:MINOR CRACKS/SPALLINGDeficiency
Roof Plan Reference
Elevation
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
EXTERIOR SOFFITS
Deficiency Photo 1
Main entrance
Violations No violations recorded
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
50,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 50,000
Instance Quantity Uom S.F.
No deficiencies recordedDeficiency
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
MasonryMaterial Type(s)
6,000Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 22,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
3- FairCondition
RAILINGS/PANELS:DETERIORATED, MINOR RUSTINGDeficiency
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
Page 7 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOF BARRIER
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 8
Violations No violations recorded
Does not existROOF CAGE
Does not existROOF FENCE
Does not existROOF HATCH/SMOKE HATCH
InspectedROOFING
Instance on Modified Bitumen:Roofs 1 to 5 Inspected
1- GoodInstance Condition
Instance Quantity 13,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2012
Source of Installation Year Custodial Staff
No deficiencies recordedDeficiency
Instance on Modified Bitumen:Roof 6 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2012
Source of Installation Year Custodial Staff
No deficiencies recordedDeficiency
Instance on Modified Bitumen:Roofs 7and 8 Inspected
3- FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 1995
Source of Installation Year Inspector Estimate
MODIFIED BITUMEN:FLASHING:CAP FLASHING MISSINGDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Page 8 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Quantity Uom L.F.
Potential Action INSTALL NEW
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 7
Violations No violations recorded
MODIFIED BITUMEN:ROOFING:BEYOND USEFUL LIFEDeficiency
Modified Bitumen:Roofs 7and 8Deficiency Location/Instance
6,000Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 1Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
3- FairCondition
BULKHEAD/PENTHOUSE
WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
Deficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1- Bulkhead
Violations No violations recorded
Page 9 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
ROOF
SPECIALTIES
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 4- Between Fair and Poor
MASONRY UNIT:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - South side Exit by the Cafeteria
Deficiency Photo 2
Facade A - South side Exit by the Cafeteria
Violations No violations recorded
InspectedRAILINGS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS
Condition 3- Fair
STONE:OPEN JOINTSDeficiency
Deficiency Location/Instance
Page 10 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
10Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Side stair
Violations No violations recorded
InspectedWINDOWS
15,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:Original Buildings Facades Inspected
1- GoodInstance Condition
Instance Quantity 8,000
Instance Quantity Uom S.F.
Installation Year 2012
Source of Installation Year Inspector Estimate
No deficiencies recordedDeficiency
Instance on Aluminum - Other:Annex, Gymnasium and Custodian
Office
Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
Installation Year 1958
Source of Installation Year Inspector Estimate
ALUMINUM - OTHER:AIR/WATER INFILTRATIONDeficiency
Roof Plan Reference
Page 11 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Elevation Reference Facade G, H, k, L
350Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Nurses room F
Violations No violations recorded
Instance on Steel:Staircases - Original Building Inspected
3- FairInstance Condition
Instance Quantity 1,000
Instance Quantity Uom S.F.
Installation Year 2012
Source of Installation Year Inspector Estimate
STEEL:BROKEN PANEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade G, L, M
20Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Page 12 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency Photo 1
Stair C - 2nd Floor Landings
Violations No violations recorded
INTERIOR Inspected
Does not existAUDITORIUM
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Room B2Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 13 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
South of Room
Violations No violations recorded
GYPSUM BOARD:DAMAGED/DETERIORATEDDeficiency
Room B2Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of Room
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
TERRAZZO:CRACKSDeficiency
Corridor near Room 110, 113, 119 , 210Deficiency Location/Instance
35Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 210
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
Page 14 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
No deficiencies recordedDeficiency
GYMNASIUM
Instance on Sub-Basement Inspected
Ceiling
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
ACOUSTIC TILES ON PLASTER:DAMAGED/MISSINGDeficiency
North of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North of Room
Violations No violations recorded
PLASTER:CRACKS/SPALLINGDeficiency
North of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North of Room
Violations No violations recorded
Door(s)
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
WOOD:DAMAGED/DETERIORATEDDeficiency
Page 15 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Floor Finish
West of RoomDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West of Room
Violations No violations recorded
Seating
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Sub-Basement Does not exist
Stage
Instance on Sub-Basement Inspected
Stage
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Sub-Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Sub-Basement Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Page 16 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
KITCHEN
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Northwest of RoomDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Northwest of Room
Deficiency Photo 2
North West of Room
Violations No violations recorded
LIBRARY
Instance on Room 103B Inspected
Built-in Furnishing
Instance on Room 103B Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Ceiling
Instance on Room 103B Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 103B Inspected
Page 17 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
LIBRARY
Door(s)
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 103B Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 103B Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLOCKER ROOM
MULTI-PURPOSE ROOM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Does not exist
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
TERRAZZO:CRACKSDeficiency
Northwest of RoomDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Northwest of Room
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Inspected
Stage
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Page 18 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Stage
Stage Curtain Rigging
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
SCIENCE LAB
Instance on Room E Inspected
YesAlternative Use
Instance on Room D Inspected
YesAlternative Use
Fixed Equipment
Instance on Room E Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room D Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Room E1 Inspected
YesAlternative Use
Instance on Room D1 Inspected
YesAlternative Use
Fixed Equipment
Instance on Room E1 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room D1 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? Partially
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
Page 19 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
METAL:DAMAGEDDeficiency
North of Gymnasium at BalconyDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North of Gymnasium at Balcony
Violations No violations recorded
InspectedStairs and Landings
Condition 2- Between Good and Fair
TERRAZZO:CRACKSDeficiency
Stair A2Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A2, B2
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 3- Fair
CONCRETE
COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMEN
T EXPOSED
Deficiency
Attic storageDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Page 20 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Slab structure at storage
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE:CRACKS/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
BasementDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Mechanical room
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 4- Between Fair and Poor
CONCRETE:WATER INFILTRATION IN NON-
INSTRUCTIONAL SPACE
Deficiency
BasementDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Basement-Mechanical room 2
Page 21 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Violations No violations recorded
CONCRETE:WATER INFILTRATION IN INSTRUCTIONAL
SPACE
Deficiency
BasementDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Gymnasium- South side wall
Violations No violations recorded
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
Page 22 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Boys Toilet Room at BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of Boys Toilet Room at Basement
Violations No violations recorded
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
InspectedSTEEL STAIRS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
InspectedDRAINAGE SYSTEM FOR SOIL
InspectedCatch Basins/Manhole - Surrounded by Soil
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Soil Covering
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
Page 23 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
4- Between Fair and PoorCondition
HEAVINGDeficiency
Along Cabrini Blvd and Fort Washington AvenueDeficiency Location/Instance
400Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Cabrini Blvd,
Violations No violations recorded
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Cabrini Blvd and Fort Washington AvenueDeficiency Location/Instance
1,675Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Cabrini Blvd,
Violations No violations recorded
DAMAGED CURBSDeficiency
Along Cabrini Blvd and Fort Washington AvenueDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Cabrini Blvd,
Violations No violations recorded
Page 24 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
4- Between Fair and PoorCondition
CRACKS - MINORDeficiency
Near Stair C, Parking Area , Along Cabrini Blvd, near Main
Entrance
Deficiency Location/Instance
1,025Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Stair C, at Ground Hog Court
Deficiency Photo 2
Near Main Entrance
Violations No violations recorded
DAMAGED CURBSDeficiency
East Drive wayDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East Drive Way
Violations No violations recorded
HEAVINGDeficiency
Near Main EntranceDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Page 25 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of Main Entrance
Violations No violations recorded
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedStudent Non-Use
Gravel Exists? No
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existStudent Use
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 2- Between Good and Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? Yes
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Ground Hog CourtDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South of Ground Hog Court
Violations No violations recorded
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
West of Ground Hog CourtDeficiency Location/Instance
20Deficiency Quantity
Page 26 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
M387Architectural Inspection
Question Response
SITE
RETAINING WALLS
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West of Ground Hog Court
Violations No violations recorded
InspectedSEATING
InspectedBenches
Does not existConcrete
InspectedMetal/Wood/Plastic
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existBleachers
InspectedSITE WALLS (NOT RETAINING WALLS)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs/ramps
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 27 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)