+ All Categories
Home > Documents > Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200...

Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200...

Date post: 07-Feb-2018
Category:
Upload: duongliem
View: 223 times
Download: 0 times
Share this document with a friend
16
The Kidde ADS FM-200 System is an innovative system developed by Kidde engineers to provide economic protection for larger enclosures requiring longer agent flow distances, and as a “drop-in” replacement for Halon. With the patented-technology of “piston flow”, the Kidde ADS FM-200 System is capable of delivering greater mass flow rates (2.5 to 3 times faster) than those achievable with a standard FM-200 system. This innovation allows networking of longer pipe runs in complex configurations with smaller pipe sizes for protection of larger hazard areas. These characteristics allow the ADS System to be a virtual “drop-in” replacement for existing Halon systems. Most installations will require only new nozzles and agent storage cylinders and can use most of the existing pipework—which provides substantial savings when retrofitting existing systems. Superior by Design The Kidde ADS TM FM-200 System Engineered to Provide Exceptional Performance Kidde Fire Systems—We Are the Right Protection... Every Time, Everywhere, Every Application. Kidde ADS System Features: Virtual “drop-in” replacement for existing Halon installations. Uses existing piping, changes limited to replacement of agent storage cylinders and nozzles Increased agent flow rates and distances provide better coverage for larger hazard areas Smaller piping diameter results in installation cost savings Ultimate design flexibility provides the most economical protection for many applications UL Listed, EPA Listed FM Approved and USCG Approved A UTC Fire & Security Company
Transcript
Page 1: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

The Kidde ADS FM-200 System is an innovative system developed by Kidde engineers to provide economic protection for larger enclosures requiring longer agent flow distances, and as a “drop-in” replacement for Halon.

With the patented-technology of “piston flow”, the Kidde ADS FM-200 System is capable of delivering greater mass flow rates (2.5 to 3 times faster) than those achievable with a standard FM-200 system. This innovation allows networking of longer pipe runs in complex configurations with smaller pipe sizes for protection of larger hazard areas.

These characteristics allow the ADS System to be a virtual “drop-in” replacement for existing Halon systems. Most installations will require only new nozzles and agent storage cylinders and can use most of the existing pipework—which provides substantial savings when retrofitting existing systems.

Superior by DesignThe Kidde ADSTM FM-200 SystemEngineered to Provide Exceptional Performance

Kidde Fire Systems—We Are the Right Protection...Every Time, Everywhere, Every Application.

Kidde ADS System Features:

• Virtual “drop-in” replacement for existing Halon installations. Uses existing piping, changes limited to replacement of agent storage cylinders and nozzles

• Increased agent flow rates and distances provide better coverage for larger hazard areas

• Smaller piping diameter results in installation cost savings

• Ultimate design flexibility provides the most economical protection for many applications

UL Listed, EPA Listed FM Approved

and USCG Approved

A UTC Fire & Security Company

Page 2: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Why Choose a Kidde ADS Series FM-200 System?

Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant into the hazard area providing the fastest fire protection available. This results in less damage, fewer repair costs and reduced downtime.

Damage-Free. Removed from the hazard area by ventilation, FM-200 allows virtually immediate return to “business as usual” without the interruption of a costly clean-up and the expense of damage to assets from suppressant residue.

People-Safe. The most comprehensive toxicology data of any clean agent available affirms FM-200 is non-toxic when used in compliance with NFPA Standard 2001. FM-200 does not impair breathing or obscure vision in an emergency situation—providing an added measure of safety for personnel.

Evironmentally-Conscientious. With a zero Ozone Depletion Potential, a low atmospheric lifetime, and its speedy suppression performance—FM-200 not only offers low environmental impact but reduces the potentially devastating atmospheric pollutants of an uncontrolled fire.

Laboratory-Tested. FM-200 has been tested and found to be effective on the widest possible range of Class A (wood, paper and cloth), Class B (flammable liquids) and Class C (electrical) fuels.

Globally-Accepted. Used in more than 70 countries around the world, FM-200 meets the standards of Underwriters Laboratories, Factory Mutual, the National Fire Protection Association (2001 Standard), the U.S. EPA SNAP program and most global approval authorities.

Kidde-Approved. That means Kidde, a world leader in clean agent protection, stands behind FM-200 fire suppression performance and reliability.

Typical Applications

The Kidde ADS Series FM-200 System is an advanced system innovation developed by Kidde engineers to provide economic protection for larger enclosures requiring longer agent flow distances.

• Replacement of Existing Halon 1301 Systems

• Telecommunications Facilities

• Internet Hosting Sites

• Health Care Facilities

• Recording Studios

• Multi-Level Sites

• Larger Manufacturing Complexes

ADS Series FM-200 System

Kidde and ADS are registered trademarks of Kidde-Fenwal, Inc.FM-200 is a registered trademark of Great Lakes Chemical Corp.

SS K-007 January 2007 ©Kidde-Fenwal, Inc.All Rights Reserved.

A UTC Fire & Security Company400 Main StreetAshland, MA 01721Tel.: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

FernandoCarrera
Rectángulo
Page 3: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Protecting Your Assets Today;Protecting Our Environment TomorrowKidde Engineered Fire Suppression SystemDesigned for use with 3M™ Novec™ 1230 Fire Protection Fluid

Novec 1230 Fire Protection Fluid Features:

• Zero Ozone Depleting Potential

• Global Warming Potential (GWP) of just one—99.9% lower than any other halocarbon agent acceptable for use in occupied spaces

• Atmospheric Lifetime of just five days—the closest alternative is 33 years

• Safety Margin of 100%—higher than any other type of clean agent fire suppressant

• Easy to handle and charge—stored as a liquid (at room temperature) so cylinders are not pressurized

Kidde Fire Systems—Setting the Standard in Fire Protection

UL Listed,FM Approved andUSCG Approved

At Kidde, we are committed to providing more than fire protection—we strive to deliver value. This guiding principle was paramount in the development of the Kidde Engineered Fire Suppression System Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid. Kidde engineers set out to manufacture a suppression system flexible enough to satisfy the requirements of a wide range of special hazard applications while meeting the environmental standards of today, as well as those of the foreseeable future. Novec 1230 fluid is the ideal suppressant for the system as it provides the greatest margin of safety of any clean agent replacement. In addition, it is the first clean agent to offer a viable, long-term solution to the environmental challenges presented in today’s environmentally aware society.

Page 4: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Kidde is a registered trademark of Kidde-Fenwal, Inc.3M and Novec are trademarks of 3M.

SS K-001 March 2007 ©Kidde-Fenwal, Inc.All Rights Reserved.

Why Choose a Kidde Engineered System using Novec 1230 Fluid?

Environment Friendly. Novec 1230 fluid has a zero Ozone Depletion Potential, a Global Warming Potential of just one, and an atmospheric lifetime of only five days.

Safe. Independent scientific studies have proven that Novec 1230 fluid poses no safety risk to people in occupied spaces at the normal design concentration. It also offers a safety margin of up to 100%—that’s higher than any other type of clean fire suppression agent.

Efficient. Novec 1230 fluid puts fires out quickly, before they can do any serious damage. It does this by reaching extinguishing concentrations in ten seconds or less. Because Novec 1230 fluid extinguishes fires with a combination of heat absorption and chemical interface with the flame, it is effective on a wide range of Class A, B and electrical fires.

Clean. Novec 1230 fluid, stored as a liquid, discharges as a colorless, electrically non-conductive, and non-corrosive gas. It does not leave any residue behind, and there is no need for costly clean-up operations.

Cost-Effective. Kidde has produced a cost-effective Novec 1230 fluid Fire Suppression System with independent third party approvals recognized worldwide.

Novec 1230 Fluid System

1

32

4

65

Typical Applications:

• Petrochemical Installations

• Steam Turbine Generators

• Telecommunications

• Marine Applications

• Pharmaceutical/Healthcare

• Food Processing Facilities

• Railway Traffic Controls

• Electrical Equipment

• Power Generation

• Packaging Plants

• Universities/Collegiate

• Printing Facilities

• Science Labs

System Components:1. Novec 1230 Fluid Cylinders

2. ARIES Control Panel

3. Notification Device

4. Horn

5. Nozzles

6. Detection - Intelligent

FernandoCarrera
Rectángulo
Page 5: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Kidde WHDR™ Wet Chemical Systems:24 Hour Protection for Commercial Kitchens

The heart and soul of every eating establishment is the kitchen. Equipped with ranges, broilers, fryers and a myriad of other high-temperature cooking appliances—no other environment demands proper fire protection more than today’s commercial kitchen.

The Kidde WHDR System is designed specifically for commercial kitchen applications. By offering the most flexible system configurations in the industry, Kidde provides the most efficient protection for all cooking applications and facilities. You can specify the type of detection, control and cylinder size to fit your application.

Investing in a Kidde WHDR System guarantees more than compliance with UL Standard 300, NFPA 96, NFPA 17A and insurance codes—it provides protection from the devastating consequences of a fire.

UL Listed and ULC Listed

Kidde WHDR System

The Kidde WHDR System:

• Economical—cost-effective, code-compliant fire suppression

• Fast and easy maintenance—semi-annual system inspections and routine maintenance per NFPA regulations are performed quickly and efficiently

• Reliable, proven protection—the WHDR System is the choice of commercial kitchens, with thousands of installations worldwide

• Global network—designed, manufactured and installed by factory-trained Kidde Distributors found around the world

A UTC Fire & Security Company

Page 6: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

1. Fire is detected activating the XV TM Control System (or the manual pull station is actuated)... causing the cylinder valve to open.

2. Pressure stored in the cylinder propels the wet chemical agent through the system piping and out of strategically located nozzles. The Kidde WHDR System automatically shuts down the power source to appliances removing the heat.

3. The wet chemical agent knocks down flames quickly and forms a protective layer that suppresses fire and prevents fire re-ignition.

The Kidde WHDR system uses Kidde APC wet chemical agent, which extinguishes fire by:

• Saponifying the surface grease (converting it into combustion-resistant soap)

• The cooling effects of water vaporization

• Interrupting the chemical chain reaction of combustion

Kidde APC wet chemical agent is proven to be the best suppressant for quick knock-down and prevention of re-ignition of flame.

3

33

1 1

2

2

1

2 2 2

How the Agent Works

How the System Works

Kidde is a registered trademark of Kidde-Fenwal, Inc.WHDR and XV are trademarks of Kidde-Fenwal, Inc.

SS K-008 September 2006 ©Kidde-Fenwal, Inc.All Rights Reserved.

Typical Appliances Protected:• Ventilation • Fryers• Char-Broilers • Ranges • Woks• Griddles

Class K ExtinguishersPortable fire extinguishers play an important role in early defense against fire.

Class K-type suppressant is used to combat the especially difficult fuel hazard presented by extremely hot grease in cooking environments.

Secondary Defense

A UTC Fire & Security Company400 Main StreetAshland, MA 01721Tel.: 508.881.2000Fax: 508.881.8920www.kiddefiresystems.com

FernandoCarrera
Rectángulo
Page 7: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Clean, Dependable Suppression:The Kidde Carbon Dioxide SystemFast Fire Protection for Challenging Hazards

Kidde Fire Systems—Setting the Standard in Fire Protection.

Kidde Carbon Dioxide System Features:

• Damage-Free Fire Suppression Reduces Loss

• Design Versatility with Three System Configurations: - Total Flooding - Local Application - Local Hose Line

• Rapid Response—Discharges in Seconds

• No Residue Clean-Up Minimizes Downtime

• Surface or Deep-Seated Fires

Flammable materials and vapors present a significant risk of fire for many industrial processes and environments. The Kidde Carbon Dioxide Suppression System was designed to provide complete fire protection for a wide range of challenging applications from printing presses and generator enclosures to dip tanks and commercial fryers. Carbon Dioxide delivers clean, dependable suppression in seconds, greatly reducing the loss of assets, productivity and revenue associated with a fire-related business interruptions.

The Kidde Carbon Dioxide System utilizes highly sophisticated electric and/or pneumatic detection units which sense fire at its inception—immediately alerting the control system. The Control Panel initiates the release of Carbon Dioxide from the system cylinders. The suppressant is delivered through a fixed piping network with specially designed nozzles— providing rapid, automatic fire protection around the clock.

UL Listed, FM Approvedand USCG Approved

Page 8: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Kidde is a registered trademark of Kidde-Fenwal, Inc.SS K-011 September 2007 ©Kidde-Fenwal, Inc.All Rights Reserved.

Why Choose a Kidde Carbon Dioxide System?

Superior Suppression. Carbon Dioxide (CO2) is a colorless, odorless, electrically-nonconductive gas whose density is approximately 50% greater than air. A Kidde Carbon Dioxide System suppresses fire by providing a blanket of heavy gas that absorbs heat from the fire and reduces the oxygen content of the atmosphere to a point where combustion becomes impossible.

Damage-Free. A naturally-occurring atmospheric element, Carbon Dioxide dissipates into the air allowing an almost immediate return to “business as usual” without the interruption of a costly clean-up and the expense of damage to assets from suppressant residue. This results in fewer repair costs and reduced downtime.

Design Versatility. Because Carbon Dioxide is an ideal suppressant for a wide variety of industrial applications, Kidde offers three system configurations to efficiently protect different hazard types: Total Flooding—ideal for enclosed hazard areas, Local Application—used to protect a specified hazard area in an open floor plan, or a Local Hose Line— cost effective protection for fighting smaller fires throughout a hazard.

Kidde Quality. At Kidde, we know a fire-related business interruption can keep your company from being competitive in a global market. We are committed to researching, developing and providing the most advanced fire protection technology and best customer service in the industry. We understand the marketplace demands an “up and running” business world around the clock. We are dedicated to keeping industry “in business” by keeping fires out.

The Kidde Carbon Dioxide System is ideal for industrial processes where flammable materials and vapors present a potential hazard. For this reason, it is essential to have sufficient fire protection on site:

• Flammable Liquid Storage Areas

• Marine Applications

• Quench and Dip Tanks

• Large Commercial Fryers

• Engine and Electrical Rooms

• Spray Booths and Paint Lockers

A Kidde Carbon Dioxide System designed specifically for the hazard and operated automatically, assures immediate detection and rapid suppression.

• Turbine Generators

• Printing Presses

• Rolling Mills

• Dust Collectors

• Industrial Ovens

• Mixing Operations

Typical Applications

Local Application CO2 System

Total Flooding CO2 System

FernandoCarrera
Rectángulo
Page 9: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

KIDDE-FENWAL, INC.400 Main Street, Ashland, MA 01721(508) 881-2000 FAX: (508) 881-8920

FORM No. KF-0042 ©2001 Kidde-Fenwal, Inc. Printed in U.S.A.

This literature is provided for infor-mational purposes only. KIDDEassumes no responsibility for theproduct’s suitability for a particu-lar application. The product mustbe properly applied to work cor-rectly. If you need more informa-tion on this product, or if you havea particular problem or question,contact KIDDE, Ashland, MA01721: Tel: (508) 881-2000.

Kidde IND™ Systems are Available From…

Our Quality isCertifiedKidde IND Dry Chemical Fire

Suppression Systems are made in

America in accordance with ISO

9001 certified quality standards

and installed and serviced by

Kidde Distributors worldwide.

When you’ve specified “Kidde,”

you’ve chosen the world’s most

respected name in fire protection.

The Engineering Specification

Rugged Kidde IND™ Systems AreRecommended For All Types of Industrial Fire Protection...

Fire SystemsThe fire suppression system for

(INSERT HAZARD AREA DESCRIP-

TION) shall be a Kidde Model IND

Industrial Dry Chemical fire sup-

pression system. The hardware

shall be manufactured by Kidde,

400 Main Street, Ashland, MA USA.

The dry chemical agent shall be

[CHOOSE ONE (ABC, monoammo-

nium phosphate or BC, sodium

bicarbonate)]. The dry chemical

agent shall be stored in steel cylin-

ders meeting DOT requirements

and shall be painted red. The cylin-

ders shall be of the stored pressure

type with a maximum pressure of

360 psig @ 70°F. Cylinder valves

must be equipped with a pressure

gauge. The design concept shall be

of the pre-engineered type with

piping parameters and discharge

nozzle types pre-determined by

the fire suppression manufacturer.

No hydraulic calculations shall be

used to accomplish the piping

design. The design application for

this hazard shall be [CHOOSE ONE

(Total Flooding or Local

Application)]. The fire suppression

equipment shall be capable of a

minimum storage temperature of

-40°F (-40°C). The design, piping

and installation shall be in accor-

dance with NFPA 17 and the Kidde

Industrial Dry Chemical Instruction

Manual. Acceptance of the fin-

ished system shall be in accordance

with NFPA 17 and the Kidde

Instruction Manual.

Processes Involving Flammable Liquids

Quench Tanks

• Industrial/Automotive

Paint Spray Booths

• Coating Operations

• Dip Tanks

Electrical/Mechanical Rooms

Boiler Rooms

• Switchgear Rooms

• Generator Rooms

• Furnace Rooms

Flammable Liquid Storage Areas

Flammable Liquid Storage

• Paint Mixing Areas

• Spill Containment Dikes

• Bulk Storage

Specialty Hazards

Modular HazMat Storage Facilities

• Exhaust Ducts

• Environmental Storage Facilities

• Machinery Spaces

Kidde IND™ Dry ChemicalFire Suppression SystemsMaximum Fire-Killing Power for Industrial Applications

FernandoCarrera
Rectángulo
FernandoCarrera
Rectángulo
Page 10: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

The Kidde Pre-Engineered Approach to Fire Protection. Precise. Effective. Affordable.Could you afford to have your pro-

duction line shut down due to a fire?Is there room in your operating bud-get to replace machinery and facilitiesdamaged by fire? If your company istypical of today’s high-productivity,cost-conscious facilities, the answer is‘no, we can’t have our operationinterrupted by any type of fire.’That’s why a Kidde IND Dry ChemicalSystem is your best choice for protec-tion of any industrial process ormachinery where flammable liquidsor hazardous materials are involved.

Costs Less To Install andMaintainBacked by more than 20 years of

industrial experience, Kidde engineers

have perfected a system to meet the

needs of today’s facility, plant and

maintenance managers. We’ve

designed the Kidde IND System to be

like your facility’s environment,

rugged and reliable, yet compact. Our

pre-engineered concept saves you

money in both hardware and installa-

tion costs, while offering precise pro-

tection for a wide variety of industrial

fire hazards. Finally, the recharging

of a Kidde IND System is fast and eco-

nomical, a real bonus for anyone with

an eye on their maintenance budget.

KIDDE IND™ Dry Chemical Fire SuppressionSystems... Automatic, 24-Hour Protection for Industrial Applications.

Versatile Fire Suppression Kidde IND Systems use either ClassABC or Class BC dry chemical to sup-press fire. Pound for pound, drychemical suppresses more fire thanany other agent, providing both rapidsuppression and protection againstfire re-ignition. Our sodium bicarbon-ate-based dry chemical is more effec-tive than water on Class B (flammableliquid) and Class C (electrical) fires.ABC dry chemical also suppresses ClassA (wood, paper, cloth) fires. Both areenvironmentally safe, non-toxic andeconomical to use in both initialinstallations and recharge situations.No wonder dry chemical is preferredfor more applications throughoutindustry than any other agent.

Quick ResponseMinimizes Fire DamageKidde IND Systems are designed tosense fires quickly, sound alarms towarn personnel in the area and dis-charge dry chemical on the source ofthe fire. All these actions occur inseconds, before the fire has theopportunity to grow in intensity orspread to other areas of the facility.For your peace of mind, Kidde INDSystems offer the surety of automaticfire protection – whether or not per-sonnel are present – 24 hours a day.

Proven KiddePerformanceKidde IND Systems protect more

industrial hazards in more types of

plants worldwide than any other

brand. So it stands to reason that we

have a better understanding of how

to specify the right system for your

application, install it with a minimum

amount of disruption to operations

and keep your Kidde IND System in

perfect working condition through

our global network of Kidde

Distributors. It’s exactly the perfor-

mance you’d expect from the leader

in fire protection.

Kidde IND Systems are available in

two basic configurations. In a localapplication system, the nozzles are

positioned either overhead or tank-

side to deliver the dry chemical agent

directly onto the hazard being pro-

tected. A total flooding system, rec-

ommended for protection of enclosed

Local Application or Total Flooding Designs

TOTAL FLOODING

LOCAL APPLICATION

Superior CoverageDue to our advanced nozzle design,

Kidde IND Systems cover more volume

of hazard area with less dry chemical

agent than any other brand of total

flooding system. Dry chemical is dis-

charged both radially and downward

to maximize coverage. What this

means is that we can protect your

application using a minimum number

of agent storage cylinders. Less hard-

ware means a lower installed cost.

Listed and ApprovedKidde IND Systems, with ABC or BC

dry chemical agents, are listed by

Underwriters Laboratories, Inc.,

Underwriters Laboratories Canada and

approved by Factory Mutual for oper-

ating in temperature ranges from

-40°F to 120°F.

Three Choices of FireDetectionDepending upon your hazard, one of

three Kidde detection methods will

best suit your needs. Mechanicaldetection uses fusible link detectors

to provide reliable performance at

low cost. Electric detection offers

enhanced sensitivity and the design

versatility of thermal, smoke or optical

detectors for compatibility with just

about any type of hazard environ-

ment. Pneumatic detection com-

bines high sensitivity with no-spark

operation necessary for explosion-sen-

sitive applications or where electrical

power for system operation is not

available.

Single or Multiple SystemControlIf you have one hazard area to pro-

tect, the Kidde SCORPIO™ ControlPanel gives you microprocessor-based

reliability in a fully supervised sup-

pression release and alarm output sys-

tem. If you’re controlling multiple

Kidde fire alarm or suppression sys-

tems, the smart choice is the KiddePEGAsys™ Control System, our lat-

est detection technology that uses a

“distributed intelligence” concept to

of more detection and alarm capabili-

ty, faster response time, more immuni-

ty to nuisance alarms and lower main-

tenance costs.

The Right Cylinder SizesYour Kidde Distributor can choose

from three sizes of agent storage

cylinders using ABC or BC dry chemical

– Kidde IND 21 (ABC)/25 (BC), Kidde

IND 45 (ABC)/50 (BC) or Kidde 70

(ABC)/75 (BC) – to design the precise

system that best meets your fire pro-

tection requirements while conserving

hardware and dry chemical agent

cost.

Hazard Longest Area Volume Area Volume Area VolumeHeight (Ft.) Side (Ft.) (Ft.2) (Ft.3) (Ft.2) (Ft.3) (Ft.2) (Ft.3)

12 or Less 15 112.5 1350 225 2700 450 5400

13 15 104.0 1350 208 2700 416 5400

14 15 96.5 1350 193 2700 386 5400

15 15 90.0 1350 180 2700 360 5400

16 15 84.5 1350 169 2700 338 5400

17 15 79.5 1350 159 2700 318 5400

18 15 75.0 1350 150 2700 300 5400

19 15 71.0 1350 142 2700 284 5400

20 15 67.5 1350 135 2700 270 5400

TOTAL CYLINDER COVERAGE

Max. Coverage per Nozzle 2 Nozzles – IND 21/25 4 Nozzles – IND 45/50

room and processes, rapidly “floods”

the protected area with dry chemical

agent to create an atmosphere that

will not support combustion but is

non-toxic to personnel. Your Kidde

Distributor can help you select the

proper design approach for each of

your applications.

Page 11: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant
Page 12: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant
Page 13: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant
Page 14: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant
Page 15: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant
Page 16: Superior by Design The Kidde ADSTM FM-200 · PDF fileWhy Choose a Kidde ADS Series FM-200 System? Rapid-Response. In seconds—not minutes, the ADS System discharges FM-200 suppressant

Recommended