Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PageProduct Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceProduct Description
© 2009 Schneider ElectricAll Rights Reserved
206/2009
Product Description
Surge protective device (SPD) units protect electronic equipment from transients. The I-Line® Plug-On Unit with Surgelogic® Surge Protective Device (SPD) is a modular parallel surge protective device designed for service entrance, distribution, or branch panel applications. The device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused.
The I-Line plug-on unit with a Surgelogic surge protective device is a high performance surge suppressor package incorporating individual modules for each phase. Modes of protection include:
• Line-to-Neutral (L–N)• Line-to-Ground (L–G)• Neutral-to-Ground (N–G)• Line-to-Line (L–L)
A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL® Recognized thermosetting epoxy material—another performance element that provides additional protection.
Each surge suppression module is individually fused and uses circuitry with thermal cutouts to isolate the SPD and ensure shutdown in the event of MOV damage during severe overvoltages—even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package.
Design Features
• Same easy installation as I-Line circuit breakers• Requires 13.50 in. (343 mm) of mounting space• FC units mount in the same mounting slots as FA circuit breakers. FI units
mount in the same mounting slots as KA circuit breakers• Can be applied in a six-disconnect panel or switchboard (SPD counts as
one disconnect)• High-energy parallel design for ANSI/IEEE C62.41 and C62.45
category B and C3 applications.
I-Line Plug-On Unit with Surgelogic SPD
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceApplication Information
306/2009© 2009 Schneider Electric
All Rights Reserved
Application Information
The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients. Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction.
A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors. Protection should also be provided for critical areas with equipment essential to the company.
Square D® brand SPD products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include:
• Banking• Education• Government• Petrochemical• Military• Publishing
• Transportation• Wastewater/Sanitation• Medical• Financial• Telecommunications• Automated Manufacturing
• Retail• Utility• Insurance• Data Processing
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceSelection and Specifications
© 2009 Schneider ElectricAll Rights Reserved
406/2009
Selection and Specifications
Model Number Format
The model number format consists of: Device Type, Voltage Code, SPD Model, Surge Current Rating Code, and Option Code. The possible device types and codes are shown in the tables below.
In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac 3-phase 4-wire 160 kA surge capacity with surge counter.
Specifications
Device Types, Interrupting Ratings, and Continuous Current Ratings
Device Type
Interrupting Rating Continuous Current Ratingat 240 Vac at 480 Vac at 600Y/347 Vac
FC 100 kA 65 kA — 60 A
FI 200 kA 200 kA 100 kA 60 A
Voltage Codes and Systems
Voltage Code Voltage System
1 120/240 Vac 1-phase, 3-wire
2 208Y/120 Vac 3-phase, 3- or 4-wire
3 240/120 Vac 3-phase, 4-wire (high leg Delta)
4 480Y/277 Vac, 3-phase, 3- or 4-wire
7 380Y/220 or 415Y/240 Vac, 3-phase, 3- or 4-wire
8 600Y/347 Vac, 3-phase, 3- or 4-wire
Surge Current Rating Codes and Surge Capacities
Surge Current Rating Code Per PhasePer Mode
L–N L–G N–G
12 120 kA 60 kA 60 kA 120 kA
16 160 kA 80 kA 80 kA 120 kA
24 240 kA 120 kA 120 kA 120 kA
Descriptions and Option Codes
Option Description Option Code
Surge counterDisplays the combined total number of transient voltage surges detected from L–N, L–G, N–G, and L–L since the counter was last reset.
C
Remote monitorDisplays the alarm status of the surge protective device up to 1000 ft (305 m) away from the unit. This option uses the dry contacts.
Order catalog number
TVS12RMU
Dry contacts Provides available Form C type contacts. Standard
Audible alarm with enable/disable switch
Provides audible indication that there is a loss of protection. Standard
FC 4 CIMA 16
Voltage CodeDevice Type
SPD Model (IMA only)Surge Current Rating CodeOption Code
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceSelection and Specifications
506/2009© 2009 Schneider Electric
All Rights Reserved
UL Suppression Voltage Ratings
IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR)
Partial Catalog Number
Voltage Service L–N L–G N–G L–L MCOV▲
FC1IMAFI1IMA
120/240 Vac, 1-phase, 3-wire 400 400 400 800 150
FC2IMAFI2IMA
208Y/120 Vac,3-phase, 3- or 4-wire 400 400 400 800 150
FC3IMAFI3IMA
240/120 Vac,3-phase, 4-wire(high leg Delta)
800/400 800/400 400 1500/800 275/150
FC4IMAFI4IMA
480Y/277 Vac,3-phase, 3- or 4-wire 800 800 800 1600 320
FC7IMAFI7IMA
380Y/220 Vac3-phase, 3- or 4-wire 800 800 800 1600 320
FI8IMA ■ 600Y/347 Vac,3-phase, 3- or 4-wire 1200 1200 1200 2000 420
▲ MCOV = Maximum Continuous Operating Voltage.■ Not available as FC device.
Standard Features and Descriptions
Feature Description
Environmental
Relative humidity: 0 to 95% non condensing
Operating frequency: 47–63 Hz
Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪
Storage temperature: -40–+65 °C (-40–+149 °F)
Compliancestandards(SPD unit only)
UL 1449, Second Edition, UL 1283
cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5
Meets 2002 NEC® Article 285.6
Fused suppression paths
Fused with individual surge-rated fuses (200 kAIR)
Thermal protection Thermal cutout for low current faults
Diagnostics
On-line test functions
Indication per phase
Service indicator shown on the front panel of each SPD unit
Replaceable modules
Separate, replaceable modules for each phase
Self-contained suppression circuits and filtering for each module
LED indicators Indication of loss of protection
Suppression modules Individually-fused
Solid state Bi-directional
Front panel alarm Includes an enable/disable switch
High-energy parallel design Category A, B, and C3 applications
EMI/RFI Filtering Up to -50 dB (100 kHz to 100 MHz)
Short-circuit current rating 200 kA (SPD modules only)
Duty cycle testedANSI C62.41 C3,10 kA 20 kV
Minimum 5000 impulses
Warranty Ten years
✪ Surge counter liquid crystal display may not indicate at temperatures less than -20 °C (-4 °F).
Surgelogic® I-Line® Plug-on SPD Unit
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceReplacement Parts
© 2009 Schneider ElectricAll Rights Reserved
606/2009
Replacement Parts
MA Module Replacements
Voltage System ● Peak SurgeCurrent Rating
Catalog Number
Phase A Phase B Phase C
120/240 Vac, 1-phase, 3-wire
120 kA MA1IMA12 Empty MA1IMA12
160 kA MA1IMA16 Empty MA1IMA16
240 kA MA1IMA24 Empty MA1IMA24
208Y/120 Vac, 3-phase, 3- or 4-wire
120 kA MA1IMA12 MA1IMA12 MA1IMA12
160 kA MA1IMA16 MA1IMA16 MA1IMA16
240 kA MA1IMA24 MA1IMA24 MA1IMA24
240/120 Vac, 3-phase, 4-wire (high leg Delta) ▼
120 kA MA1IMA12 MA3IMA12 MA1IMA12
160 kA MA1IMA16 MA3IMA16 MA1IMA16
240 kA MA1IMA24 MA3IMA24 MA1IMA24
480Y/277 Vac, 3-phase, 3- or 4-wire
120 kA MA4IMA12 MA4IMA12 MA4IMA12
160 kA MA4IMA16 MA4IMA16 MA4IMA16
240 kA MA4IMA24 MA4IMA24 MA4IMA24
380Y/ 220 or 415Y/240 Vac,3-phase, 3- or 4-wire
120 kA MA7IMA12 MA7IMA12 MA7IMA12
160 kA MA7IMA16 MA7IMA16 MA7IMA16
240 kA MA7IMA24 MA7IMA24 MA7IMA24
600Y/347 Vac, 3-phase, 3- or 4-wire
120 kA MA8IMA12 MA8IMA12 MA8IMA12
160 kA MA8IMA16 MA8IMA16 MA8IMA16
240 kA MA8IMA24 MA8IMA24 MA8IMA24
● With all system voltages, SPD devices must be grounded in accordance with all applicable standards.
▼ Phase B modules are different than Phase A and Phase C modules.
Surgelogic® Device Mounted in Panel with 4-Piece Trim Installed
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective DeviceDimensions and Weights
706/2009© 2009 Schneider Electric
All Rights Reserved
Dimensions and Weights
FC I-Line® Plug-On Unit (Front View)
FI I-Line Plug-On Unit (Front View)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
1310CT0201R05/09 © 2009 Schneider Electric All Rights Reserved Replaces 1310CT0201R5/07 dated May 2007.
Schneider Electric USA1601 Mercer RoadLexington, KY 40511 USA1-888-SquareD (1-888-778-2733)www.schneider-electric.us
Schneider Electric Canada19 Waterman Avenue,M4B 1 Y2Toronto, Ontario1-800-565-6699www.schneider-electric.ca
06/2009
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com