8
SR LV UE EX UHVE OHE OHT *** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT CIRCUIT BREAKER PANEL MOMENTARY CONTACT SWITCH PUSH BUTTON SINGLE RECEPT. FAN SPEED CONTROL TIME DELAY SWITCH SWITCHED DUPLEX RECEPT. FOURPLEX RECEPT. DUPLEX RECEPT. ABOVE COUNTER RECEPT. DEDICATED DUPLEX RECEPT. 240 VOLT RECEPT. EQUIPMENT PLUG RECEPT ON DROP CORD (DUPLEX SHOWN) RECEPT ON CORD REEL (DUPLEX SHOWN) FLUSH FLOOR RECEPT. (DUPLEX SHOWN) ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48". * DISTANCE ABOVE TOP OF DOOR FRAME J TIMER SWITCH WALL HEATER (TYPE DENOTED) ** DISTANCE TO TOP OF EQUIPMENT OR DEVICE D1 H2 HATCHED SYMBOL INDICATES REMOVED HAND OR HAIR DRYER (TYPE DENOTED) DASHED SYMBOL INDICATES EXISTING H T TC IR OS R SF-1 T BUS DUCT WITH PLUG UN DISCONNECT (FUSED) LIGHT LEVEL SENSOR - TYPE DENOTED TIME CONTROL SWITCH (TIME SWITCH) HUMIDISTAT THERMOSTAT PHOTOCELL ENCLOSED CIRCUIT BREAKER RELAY COMB. MOTOR STARTER (NON-FUSED) MAG. MOTOR STARTER OR CONTACTOR SAFETY DISC. SW. (FUSED) SAFETY DISC. SW. (NON-FUSED) COMB. MOTOR STARTER (FUSED) POWER OR DISTRIBUTION PANEL MOTOR (SEE SCHEDULE) TRANSFORMER (TYPE DENOTED) MOTOR HP. RATED SWITCH SPECIAL CABINET (TYPE DENOTED) J J J A P A GROUND CONNECTION - EXOTHERMIC WELD GROUND CONNECTION TO STEEL OR STRUCTURE SPECIAL CONNECTION (SEE SCHEDULE) SPECIAL RECEPT. OR CONN. (SEE SCHEDULE) JUNCTION BOX PULL BOX GROUND ROD (PLAN VIEW) SURGERY SERVICE COLUMN CLOCK (TYPE DENOTED) POWER POLE (OPEN OFFICE STYLE) MULTIOUTLET ASSEMBLY (TYPE DENOTED) MULTIOUTLET ASSEMBLY (TYPE DENOTED) POWER SYMBOLS FLEXIBLE CONDUIT OR FIXTURE WHIP PROJECTOR CONTROL OUTLET CCTV CAMERA WITH PAN/TILT DRIVE **** DISTANCE BELOW CEILING CCTV CAMERA ***** DISTANCE TO BOTTOM OF DEVICE SPEAKER (WALL OR CEILING MT.) S MICROPHONE OUTLET HORN TYPE SPEAKER VOLUME CONTROL V UNDERFLOOR RACEWAY SYSTEM CABLE TRAY INFORMATION OUTLET WALL TELEPHONE OUTLET INTERCOM OUTLET LOCATION TELEPHONE OUTLET TELEVISION OUTLET W DOOR CONTACTS CARD READER ELECTRIC STRIKE MOTION DETECTOR (TYPE DENOTED) MD ES KEYPAD F.A. PULLSTATION (TYPE DENOTED) F.A. DOOR CLOSER F.A. DOOR HOLDER F.A. INDIVIDUAL ADDRESSABLE MODULE FIRE ALARM SHUT DOWN RELAY F.A. ZONE ADDRESSABLE MODULE FR F P HEAT DETECTOR (TYPE & TEMP DENOTED) CONDUIT TRANSITION DOWN CONDUIT TRANSITION UP BRANCH CIRCUIT HOME RUN UNDERGROUND HIGH VOLTAGE ELECTRICAL UNDERGROUND ELECTRICAL LOW VOLTAGE POWER WIRING EXISTING CONDUIT OVERHEAD TELEPHONE OVERHEAD ELECTRIC CONDUIT EXPOSED SURFACE RACEWAY CONDUIT STUBBED OUT CONDUIT CONCEALED BELOW FLOOR CONDUIT CONCEALED IN WALL OR OVERHEAD FIRE ALARM CHIME FIRE ALARM BELL FIRE ALARM BELL W/STROBE (CANDELAS) SMOKE DETECTOR (TYPE DENOTED) FIRE ALARM STROBE (CANDELAS) FIRE ALARM SPEAKER W/STROBE (CANDELAS) FIRE ALARM CHIME W/STROBE (CANDELAS) P FIRE ALARM HORN FIRE ALARM HORN W/STROBE (CANDELAS) F 110cd UTILITY SERVICE POWER POLE (SITE) UNDERGROUND TELEPHONE UT UCOM UNDERGROUND COMMUNICATIONS UTV UNDERGROUND CABLE TELEVISION UFIBR UNDERGROUND FIBER OPTIC DEDICATED FOURPLEX RECEPT. M C T TD SP M B P P B VARIABLE FREQUENCY DRIVE A LS C P OCCUPANCY SENSOR - TYPE DENOTED IC S S S M P 110cd 110cd 110cd F F F F F F 110cd P FIRE ALARM REMOTE ANNUNCIATOR FA ANNUN Z I DC CR MAGNETIC LOCK ML IR FS CONDUIT SLEEVE 1 KEYED NOTE (SEE SCHEDULE) WIRELESS ACCESS POINT WAP GFI RECEPT. ABOVE COUNTER GFI RECEPT. TV FLUSH CEILING MOUNT RECEPT. SYMBOLS & ABBREVIATIONS CIRCUITRY SYMBOLS SIGNALS & COMMUNICATION SYMBOLS MISCELLANEOUS SYMBOLS FLAG NOTE CENTERLINE LIGHT FIXTURE ON (EM) LIFE SAFETY BRANCH LIGHT FIXTURE WITH EMERGENCY BALLAST LIGHT FIXTURE ON EMERGENCY CIRCUIT LIGHT FIXTURE ON (EM) CRITICAL BRANCH 2 POLE SINGLE THROW SW. SINGLE POLE SW. DIMMER SWITCH OCCUPANCY SENSOR SWITCH 2 3 KEYED SW. 3-WAY SW. 4-WAY SW. LIGHTING SYMBOLS WALL MOUNTED FLOODLIGHT POLE MOUNTED LIGHT RECESSED LIGHT SURFACE LIGHT EXIT SIGN SUSPENDED OR PENDANT LIGHT TRACK AND TRACK LIGHT SURFACE LINEAR LIGHT STRIP LIGHT EMERGENCY BATTERY LIGHT RECESSED LINEAR LIGHT POLE MOUNTED FLOODLIGHT P2 P1 TR1 T1 T1 EM H ST1 BB G AA R C D F 4 K D O S MULTIPLE SERVICE OUTLET OUTLET IN FLOOR (MICROPHONE SHOWN) M MULTIPLE SERVICE FLR OUTLET ELEVATION MARKER x x.xx X - INDICATES DETAIL NUMBER X.XX - INDICATES SHEET WHERE DETAIL IS FOUND - DIRECTION OF ARROW INDICATES PLAN ORIENTATION IN RELATION TO DETAIL XX-X EQUIPMENT IDENTIFIER KEYNOTE KEY NOTES: 1 NOTE:"CONTRACTOR" MEANS "ELECTRICAL CONTRACTOR" WHEN REFERENCED ANYWHERE IN THE ELECTRICAL CONSTRUCTION DOCUMENTS UNLESS WORK AND EQUIPMENT HAS BEEN COORDINATED BETWEEN THE ELECTRICAL AND GENERAL CONTRACTORS TO BE PROVIDED BY THE GENERAL CONTRACTOR. "NEEDED", "PROVIIDE", AND "INSTALL" MEANS ALL ITEMS CALLED OUT IN THE CONTRACT DOCUMENTS AND ANY ADDITIONAL ITEMS NOT CALLED OUT BUT REQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM. SCOPE: THE INTENT OF THE DRAWINGS IS TO PROVIDE A COMPLETE AND FULLY OPERATIONAL ELECTRICAL SYSTEM. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL LABOR, MATERIAL AND EQUIPMENT NECESSARY TO COMPLETE THE ELECTRICAL WORK. PERMITS AND FEES: THE ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, FEES AND INSPECTIONS NECESSARY TO COMPLETE THE ELECTRICAL SCOPE OF WORK PRIOR TO STARTING THE WORK. WARRANTY: THE ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY WARRANTY ALL WORK TO BE FREE OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER OR OWNER'S REPRESENTATIVE AND WILL REPAIR OR REPLACE ANY DEFECTIVE WORK PROMPTLY AND WITHOUT CHARGE AND RESTORE ANY OTHER EXISTING WORK DAMAGED IN THE COURSE OF REPAIRING DEFECTIVE MATERIALS AND WORKMANSHIP. CODES: PERFORM ALL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE, STATES, CITY ELECTRICAL CODES, AND ALL OTHER APPLICABLE CODES INCLUDING ANY STATE OR LOCAL ENERGY CODES. ALL WORK SHALL ALSO BE IN COMPLIANCE WITH BUILDING OWNER'S CRITERIA. IN CASE OF CONFLICT BETWEEN THE DRAWINGS, SPECIFICATIONS, CODES, ORDINANCES, AND AUTHORITIES HAVING JURISDICTION, THE MOST STRINGENT STANDARD (IN THE OPINION OF THE ENGINEER) SHALL APPLY. STANDARDS: EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE PROVISIONS OF NEC, WAC, ASTM, UL, ETL, NEMA, ANSI, AND OTHER APPLICABLE AGENCY AS THEY APPLY TO EACH INDIVIDUAL UNIT OR ASSEMBLY. COPYRIGHT 2016 GENERAL NOTES: THESE DRAWINGS ARE PROVIDED FOR YOUR USE RELATING EXCLUSIVELY TO THE PROJECT CONTAINED HEREIN. SEA-TAC ELECTRIC, INC. PROVIDES THESE DRAWINGS WITH THE FOLLOWING STIPULATIONS: 1. THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF SEA-TAC ELECTRIC, INC. AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN CONSENT OF SEA-TAC ELECTRIC, INC. THE DESIGNS CONTAINED HEREIN ARE PROTECTED BY THE RULES AND REGULATIONS OF U.S. COPYRIGHT LAWS. 2. THESE DRAWINGS AND DOCUMENTS WERE COPIED FROM COMPUTER DATA CREATED AS A STEP IN THE PRODUCTION OF PHYSICAL DATA FOR THIS PROJECT. THERE MAY BE DISCREPANCIES BETWEEN THESE DOCUMENTS AND THE COMPUTER DATA. WHERE SUCH DISCREPANCIES EXIST, ONLY THE PHYSIAL DOCUMENTS AND DRAWINGS CAN BE RELIED ON TO REFLECT THE WORK OF SEA-TAC ELECTRIC, INC., WHO MAKES NO GUARANTEES OR WARRANTIES REGARDING THESE DOCUMENTS OR THE DATA THEREIN. 3. IN ACCEPTING THESE DOCUMENTS, YOU ASSUME ALL LIABILITY FOR THE ACCUARCY, UTILITY, OR SUITABILITY FOR ANY PRUPOSE FOR ANY DATA THESE DRAWINGS CONTAIN. COPYRIGHT 2016 NOTES REGARDING DRAWINGS: GENERAL DESCRIPTION SCOPE OF WORK ELECTRICAL CONSTRUCTION FOR CORE & SHELL OF NEW ONE STORY METAL STUD BUILDING TO INCLUDE THE FOLLOWING: (1) 2000A 480V ELECTRICAL SERVICE, FEEDERS & PANELBOARD (1) POWER CHASE TO EACH PROPOSED TENANT SPACE (1) 2” LV CHASE TO EACH PROPOSED TENANT SPACE (1) 4X8 TELE/DATA BACKBOARD (1) 1” CHASE TO EACH PROPOSED TENANT SPACE FOR FIRE ALARM (8) EMERGENCY EGRESS LIGHTS (1) DEDICATED RECEPTACLE IN ELECTRICAL ROOM (1) DEDICATED RECEPTACLE ON PHONE BOARD (10) WP GCFI RECEPTACLES ON ROOF FOR HOLIDAY LIGHTING (1) PROGRAMMABLE LIGHTING CONTROL PANEL (3) WP GFCI RECEPTACLES AT BUILDING EXTERIOR PROVIDE AND INSTALL (11) 4’ F-1 FIXTURES PROVIDE AND INSTALL (8) F-2 FIXTURES PROVIDE AND INSTALL (25) F-3 FIXTURES PROVIDE AND INSTALL (6) F-4 FIXTURES P H O N E ( 2 5 3 ) 8 7 2 - 5 5 5 3 F A X ( 2 5 3 ) 8 7 2 - 4 1 1 2 K E N T , W A 9 8 0 3 2 7 0 5 6 S O U T H 2 2 0 T H S T R E E T E L E C T R I C I N C . S E A T A C SCALE DATE DRAWN BY CHECKED BY PROJECT NUMBER w w w . s e a t a c e l e c t r i c . c o m 11/7/2016 3:06:43 PM 12" = 1'-0" C:\Users\iane\Documents\VATL_A_EL_IanEdmunds.rvt E0.01 SYMBOLS AND ABBREVIATIONS T H E V I L L A G E A T T O T E M L A K E - B L D G A K I R K L A N D , W A 9 8 0 3 4 CM CM, IE, NP 11/07/2016 15115 9 0 % C D S E T CENTERCAL PROPERTIES, LLC 1600 EAST FRANKLIN EL SEGUNDO, CA 90245 ABBREVIATIONS A, AMP AMPERE AC INDICATES ABOVE COUNTER MOUNTING AT +4" ABOVE BACKSPLASH OR +6" ABOVE COUNTERS WITHOUT BACKSPLASH. AFF ABOVE FINISHED FLOOR ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAGE BTS BASE TRANSFER STATION CB CIRCUIT BREAKER CKT CIRCUIT DED DEDICATED DW DISHWASHER E EXISTING EPO EMERGENCY POWER OFF EWC ELECTRIC WATER COOLER FA FIRE ALARM FBIOC FURNISHED BY OTHERS INSTALLED BY CONTRACTOR FI FILM ILLUMINATOR G, GND GROUND GD GARBAGE DISPOSAL GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER HT HEIGHT HWT HOT WATER TANK IGN IGNITION J-BOX JUNCTION BOX MW MICROWAVE - COORDINATE MOUNTING HEIGHT N NEUTRAL NC NURSE CALL P POLE PH PHASE PNL PANEL PROVIDE FURNISH AND INSTALL R RELOCATED (INDICATES EXISTING EQUIPMENT TO BE RE-INSTALLED AS SHOWN) REC RECEPTACLE REFER REFRIGERATOR RO RACEWAY ONLY S SAFETY TYPE TELCO TELEPHONE COMPANY TELE TELEPHONE TR TELEPHONE RISER TYP TYPICAL UC UNDERCABINET V VOLT W WIRE OR WATT W/O WITHOUT WP WEATHERPROOF DRAWING INDEX E0.01 SYMBOLS AND ABBREVIATIONS E0.02 ELECTRICAL SCHEDULES E1.01 ELECTRICAL SITE PLAN E2.01 LEVEL 1 POWER PLAN E2.02 MEZZANINE, ENLARGED ELECTRICAL ROOM, AND ENLARGED LOADING DOCK POWER PLAN E2.03 MAIN ROOF POWER PLAN E5.01 ONE-LINE RISER DIAGRAM No. Description Date 1 CITY OF KIRKLAND REVIEW COMMENTS 11/02/2016 1 11-8-2016 ENR16-08749 Page 1 of 7 City of Kirkland Reviewed by J Tumelson 11/22/2016 MUST REMAIN ON JOBSITE
Transcript
  • SR

    LV

    UE

    EX

    UHVE

    OHE

    OHT

    *** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT

    CIRCUIT BREAKER PANEL

    MOMENTARY CONTACT SWITCH

    PUSH BUTTON

    SINGLE RECEPT.

    FAN SPEED CONTROLTIME DELAY SWITCH

    SWITCHED DUPLEX RECEPT.

    FOURPLEX RECEPT.

    DUPLEX RECEPT.

    ABOVE COUNTER RECEPT.

    DEDICATED DUPLEX RECEPT.

    240 VOLT RECEPT.

    EQUIPMENT PLUG

    RECEPT ON DROP CORD (DUPLEX SHOWN)RECEPT ON CORD REEL (DUPLEX SHOWN)

    FLUSH FLOOR RECEPT. (DUPLEX SHOWN)

    ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED.DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48".DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48".

    * DISTANCE ABOVE TOP OF DOOR FRAME

    J

    TIMER SWITCH

    WALL HEATER (TYPE DENOTED)

    ** DISTANCE TO TOP OF EQUIPMENT OR DEVICE

    D1

    H2

    HATCHED SYMBOL INDICATES REMOVED

    HAND OR HAIR DRYER (TYPE DENOTED)

    DASHED SYMBOL INDICATES EXISTING

    H

    T

    TC

    IROS

    R

    SF-1

    T

    BUS DUCT WITH PLUG UN DISCONNECT (FUSED)

    LIGHT LEVEL SENSOR - TYPE DENOTED

    TIME CONTROL SWITCH (TIME SWITCH)

    HUMIDISTAT

    THERMOSTAT

    PHOTOCELL

    ENCLOSED CIRCUIT BREAKER

    RELAY

    COMB. MOTOR STARTER (NON-FUSED)

    MAG. MOTOR STARTER OR CONTACTOR

    SAFETY DISC. SW. (FUSED)

    SAFETY DISC. SW. (NON-FUSED)

    COMB. MOTOR STARTER (FUSED)

    POWER OR DISTRIBUTION PANEL

    MOTOR (SEE SCHEDULE)

    TRANSFORMER (TYPE DENOTED)

    MOTOR HP. RATED SWITCH

    SPECIAL CABINET (TYPE DENOTED)

    J

    J J

    A

    P

    A

    GROUND CONNECTION - EXOTHERMIC WELD

    GROUND CONNECTION TO STEEL OR STRUCTURE

    SPECIAL CONNECTION (SEE SCHEDULE)

    SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)

    JUNCTION BOXPULL BOX

    GROUND ROD (PLAN VIEW)

    SURGERY SERVICE COLUMN

    CLOCK (TYPE DENOTED)

    POWER POLE (OPEN OFFICE STYLE)

    MULTIOUTLET ASSEMBLY (TYPE DENOTED)

    MULTIOUTLET ASSEMBLY (TYPE DENOTED)

    POWER SYMBOLS

    FLEXIBLE CONDUIT OR FIXTURE WHIP

    PROJECTOR CONTROL OUTLET

    CCTV CAMERA WITH PAN/TILT DRIVE

    **** DISTANCE BELOW CEILING

    CCTV CAMERA

    ***** DISTANCE TO BOTTOM OF DEVICE

    SPEAKER (WALL OR CEILING MT.)S

    MICROPHONE OUTLET

    HORN TYPE SPEAKER

    VOLUME CONTROLV

    UNDERFLOOR RACEWAY SYSTEM

    CABLE TRAY

    INFORMATION OUTLET

    WALL TELEPHONE OUTLET

    INTERCOM OUTLET LOCATION

    TELEPHONE OUTLET

    TELEVISION OUTLET

    W

    DOOR CONTACTS

    CARD READER

    ELECTRIC STRIKE

    MOTION DETECTOR (TYPE DENOTED)MD

    ES

    KEYPAD

    F.A. PULLSTATION (TYPE DENOTED)

    F.A. DOOR CLOSER

    F.A. DOOR HOLDER

    F.A. INDIVIDUAL ADDRESSABLE MODULE

    FIRE ALARM SHUT DOWN RELAY

    F.A. ZONE ADDRESSABLE MODULE

    FR

    FP

    HEAT DETECTOR (TYPE & TEMP DENOTED)

    CONDUIT TRANSITION DOWN

    CONDUIT TRANSITION UP

    BRANCH CIRCUIT HOME RUN

    UNDERGROUND HIGH VOLTAGE ELECTRICAL

    UNDERGROUND ELECTRICAL

    LOW VOLTAGE POWER WIRING

    EXISTING CONDUIT

    OVERHEAD TELEPHONE

    OVERHEAD ELECTRIC

    CONDUIT EXPOSED

    SURFACE RACEWAY

    CONDUIT STUBBED OUT

    CONDUIT CONCEALED BELOW FLOOR

    CONDUIT CONCEALED IN WALL OR OVERHEAD

    FIRE ALARM CHIME

    FIRE ALARM BELL

    FIRE ALARM BELL W/STROBE (CANDELAS)

    SMOKE DETECTOR (TYPE DENOTED)

    FIRE ALARM STROBE (CANDELAS)

    FIRE ALARM SPEAKER W/STROBE (CANDELAS)

    FIRE ALARM CHIME W/STROBE (CANDELAS)

    P

    FIRE ALARM HORN

    FIRE ALARM HORN W/STROBE (CANDELAS)

    F

    110cd

    UTILITY SERVICE POWER POLE (SITE)

    UNDERGROUND TELEPHONEUT

    UCOM UNDERGROUND COMMUNICATIONSUTV UNDERGROUND CABLE TELEVISION

    UFIBR UNDERGROUND FIBER OPTIC

    DEDICATED FOURPLEX RECEPT.

    MC

    T

    TD

    SP

    M

    B

    P

    PB

    VARIABLE FREQUENCY DRIVE

    ALS

    CP

    OCCUPANCY SENSOR - TYPE DENOTED

    IC

    S

    S S

    M

    P

    110cd

    110cd

    110cd

    F

    F

    F

    F

    F

    F

    110cd

    P

    FIRE ALARM REMOTE ANNUNCIATORFA ANNUN

    Z

    I

    DC

    CR

    MAGNETIC LOCKML

    IR

    F S

    CONDUIT SLEEVE

    1 KEYED NOTE (SEE SCHEDULE)

    WIRELESS ACCESS POINTWAPGFI RECEPT.

    ABOVE COUNTER GFI RECEPT.

    TV

    FLUSH CEILING MOUNT RECEPT.

    SYMBOLS & ABBREVIATIONS

    CIRCUITRY SYMBOLS

    SIGNALS & COMMUNICATION SYMBOLS

    MISCELLANEOUS SYMBOLS

    FLAG NOTE

    CENTERLINE

    LIGHT FIXTURE ON (EM) LIFE SAFETY BRANCH

    LIGHT FIXTURE WITH EMERGENCY BALLAST

    LIGHT FIXTURE ON EMERGENCY CIRCUITLIGHT FIXTURE ON (EM) CRITICAL BRANCH

    2 POLE SINGLE THROW SW.

    SINGLE POLE SW.

    DIMMER SWITCH

    OCCUPANCY SENSOR SWITCH

    2

    3

    KEYED SW.

    3-WAY SW.

    4-WAY SW.

    LIGHTING SYMBOLS

    WALL MOUNTED FLOODLIGHT

    POLE MOUNTED LIGHT

    RECESSED LIGHT

    SURFACE LIGHT

    EXIT SIGN

    SUSPENDED OR PENDANT LIGHT

    TRACK AND TRACK LIGHT

    SURFACE LINEAR LIGHT

    STRIP LIGHT

    EMERGENCY BATTERY LIGHT

    RECESSED LINEAR LIGHT

    POLE MOUNTED FLOODLIGHT

    P2P1

    TR1T1T1

    EM

    H

    ST1

    BB

    G

    AA

    R

    C D

    F

    4

    K

    D

    OS

    MULTIPLE SERVICE OUTLETOUTLET IN FLOOR (MICROPHONE SHOWN)M

    MULTIPLE SERVICE FLR OUTLET

    ELEVATION MARKER

    xx.xx

    X - INDICATES DETAIL NUMBERX.XX - INDICATES SHEET WHERE DETAIL IS FOUND- DIRECTION OF ARROW INDICATES PLAN ORIENTATION IN RELATION TO DETAIL

    XX-X EQUIPMENT IDENTIFIER

    KEYNOTE

    KEY NOTES:1

    NOTE:"CONTRACTOR" MEANS "ELECTRICAL CONTRACTOR" WHEN REFERENCED ANYWHERE INTHE ELECTRICAL CONSTRUCTION DOCUMENTS UNLESS WORK AND EQUIPMENT HAS BEENCOORDINATED BETWEEN THE ELECTRICAL AND GENERAL CONTRACTORS TO BE PROVIDED BYTHE GENERAL CONTRACTOR. "NEEDED", "PROVIIDE", AND "INSTALL" MEANS ALL ITEMS CALLEDOUT IN THE CONTRACT DOCUMENTS AND ANY ADDITIONAL ITEMS NOT CALLED OUT BUTREQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM.

    SCOPE:THE INTENT OF THE DRAWINGS IS TO PROVIDE A COMPLETE AND FULLY OPERATIONALELECTRICAL SYSTEM. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL LABOR,MATERIAL AND EQUIPMENT NECESSARY TO COMPLETE THE ELECTRICAL WORK.

    PERMITS AND FEES:THE ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, FEES ANDINSPECTIONS NECESSARY TO COMPLETE THE ELECTRICAL SCOPE OF WORK PRIOR TOSTARTING THE WORK.

    WARRANTY:THE ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY WARRANTY ALL WORK TO BE FREEOF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATEOF FINAL ACCEPTANCE BY THE OWNER OR OWNER'S REPRESENTATIVE AND WILL REPAIR ORREPLACE ANY DEFECTIVE WORK PROMPTLY AND WITHOUT CHARGE AND RESTORE ANY OTHEREXISTING WORK DAMAGED IN THE COURSE OF REPAIRING DEFECTIVE MATERIALS ANDWORKMANSHIP.

    CODES:PERFORM ALL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE,STATES, CITY ELECTRICAL CODES, AND ALL OTHER APPLICABLE CODES INCLUDING ANY STATEOR LOCAL ENERGY CODES. ALL WORK SHALL ALSO BE IN COMPLIANCE WITH BUILDINGOWNER'S CRITERIA. IN CASE OF CONFLICT BETWEEN THE DRAWINGS, SPECIFICATIONS,CODES, ORDINANCES, AND AUTHORITIES HAVING JURISDICTION, THE MOST STRINGENTSTANDARD (IN THE OPINION OF THE ENGINEER) SHALL APPLY.

    STANDARDS:EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE PROVISIONS OF NEC, WAC,ASTM, UL, ETL, NEMA, ANSI, AND OTHER APPLICABLE AGENCY AS THEY APPLY TO EACHINDIVIDUAL UNIT OR ASSEMBLY.

    COPYRIGHT 2016

    GENERAL NOTES:

    THESE DRAWINGS ARE PROVIDED FOR YOUR USE RELATING EXCLUSIVELY TO THE PROJECTCONTAINED HEREIN. SEA-TAC ELECTRIC, INC. PROVIDES THESE DRAWINGS WITH THEFOLLOWING STIPULATIONS:

    1. THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS ANINSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF SEA-TAC ELECTRIC, INC.AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THEWRITTEN CONSENT OF SEA-TAC ELECTRIC, INC. THE DESIGNS CONTAINED HEREIN AREPROTECTED BY THE RULES AND REGULATIONS OF U.S. COPYRIGHT LAWS.

    2. THESE DRAWINGS AND DOCUMENTS WERE COPIED FROM COMPUTER DATA CREATED AS ASTEP IN THE PRODUCTION OF PHYSICAL DATA FOR THIS PROJECT. THERE MAY BEDISCREPANCIES BETWEEN THESE DOCUMENTS AND THE COMPUTER DATA. WHERE SUCHDISCREPANCIES EXIST, ONLY THE PHYSIAL DOCUMENTS AND DRAWINGS CAN BE RELIED ONTO REFLECT THE WORK OF SEA-TAC ELECTRIC, INC., WHO MAKES NO GUARANTEES ORWARRANTIES REGARDING THESE DOCUMENTS OR THE DATA THEREIN.

    3. IN ACCEPTING THESE DOCUMENTS, YOU ASSUME ALL LIABILITY FOR THE ACCUARCY,UTILITY, OR SUITABILITY FOR ANY PRUPOSE FOR ANY DATA THESE DRAWINGS CONTAIN.

    COPYRIGHT 2016

    NOTES REGARDING DRAWINGS:GENERAL DESCRIPTION SCOPE OF WORKELECTRICAL CONSTRUCTION FOR CORE & SHELL OF NEW ONE STORY METAL STUD BUILDING TO INCLUDE THE FOLLOWING:• (1) 2000A 480V ELECTRICAL SERVICE, FEEDERS & PANELBOARD• (1) POWER CHASE TO EACH PROPOSED TENANT SPACE• (1) 2” LV CHASE TO EACH PROPOSED TENANT SPACE• (1) 4X8 TELE/DATA BACKBOARD• (1) 1” CHASE TO EACH PROPOSED TENANT SPACE FOR FIRE ALARM• (8) EMERGENCY EGRESS LIGHTS• (1) DEDICATED RECEPTACLE IN ELECTRICAL ROOM• (1) DEDICATED RECEPTACLE ON PHONE BOARD• (10) WP GCFI RECEPTACLES ON ROOF FOR HOLIDAY LIGHTING• (1) PROGRAMMABLE LIGHTING CONTROL PANEL• (3) WP GFCI RECEPTACLES AT BUILDING EXTERIOR• PROVIDE AND INSTALL (11) 4’ F-1 FIXTURES• PROVIDE AND INSTALL (8) F-2 FIXTURES• PROVIDE AND INSTALL (25) F-3 FIXTURES• PROVIDE AND INSTALL (6) F-4 FIXTURES

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    3 P

    M

    12" = 1'-0"

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E0.01

    SYMBOLS AND ABBREVIATIONS

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    ABBREVIATIONS

    A, AMP AMPERE

    AC INDICATES ABOVE COUNTER MOUNTING AT +4" ABOVE BACKSPLASH OR+6" ABOVE COUNTERS WITHOUT BACKSPLASH.

    AFF ABOVE FINISHED FLOOR

    ATS AUTOMATIC TRANSFER SWITCH

    AWG AMERICAN WIRE GAGE

    BTS BASE TRANSFER STATION

    CB CIRCUIT BREAKER

    CKT CIRCUIT

    DED DEDICATED

    DW DISHWASHER

    E EXISTING

    EPO EMERGENCY POWER OFF

    EWC ELECTRIC WATER COOLER

    FA FIRE ALARM

    FBIOC FURNISHED BY OTHERS INSTALLED BY CONTRACTOR

    FI FILM ILLUMINATOR

    G, GND GROUND

    GD GARBAGE DISPOSAL

    GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER

    HT HEIGHT

    HWT HOT WATER TANK

    IGN IGNITION

    J-BOX JUNCTION BOX

    MW MICROWAVE - COORDINATE MOUNTING HEIGHT

    N NEUTRAL

    NC NURSE CALL

    P POLE

    PH PHASE

    PNL PANEL

    PROVIDE FURNISH AND INSTALL

    R RELOCATED (INDICATES EXISTING EQUIPMENT TO BE RE-INSTALLED ASSHOWN)

    REC RECEPTACLE

    REFER REFRIGERATOR

    RO RACEWAY ONLY

    S SAFETY TYPE

    TELCO TELEPHONE COMPANY

    TELE TELEPHONE

    TR TELEPHONE RISER

    TYP TYPICAL

    UC UNDERCABINET

    V VOLT

    W WIRE OR WATT

    W/O WITHOUT

    WP WEATHERPROOF

    DRAWING INDEX

    E0.01 SYMBOLS AND ABBREVIATIONS

    E0.02 ELECTRICAL SCHEDULES

    E1.01 ELECTRICAL SITE PLAN

    E2.01 LEVEL 1 POWER PLAN

    E2.02 MEZZANINE, ENLARGED ELECTRICALROOM, AND ENLARGED LOADING DOCKPOWER PLAN

    E2.03 MAIN ROOF POWER PLAN

    E5.01 ONE-LINE RISER DIAGRAM

    No. Description Date

    1 CITY OF KIRKLANDREVIEW COMMENTS

    11/02/2016

    1

    11-8-2016

    ENR16-08749Page 1 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

    MUST REMAIN ON JOBSITE

  • PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    3 P

    M

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E0.02

    ELECTRICAL SCHEDULES

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    Checker

    Author

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    5 WHERE FIXTURES ARE SHOWN SHADED PROVIDE BATTERY BALLAST WITH REMOTE TEST BUTTON.

    4. CONTRACTOR TO VERIFY CEILING CONDITIONS FOR PROPER MOUNTING HARDWARE

    3. ALL FLUORESCENT AND HID LIGHTING FIXTURES SHALL BE PROVIDED WITH IN-LINE GLR FUSE.

    2. PROVIDE COLD WEATHER BALLASTS FOR ALL OUTDOOR FIXTURES.

    CLOSING FOR ENGINEERING ANALYSIS

    TO BE DETERMINED BY ENGINEER. ALL SUBSTITUTIONS SHALL INCLUDE PHOTOMETRICS AND BE RECEIVED (5) BUSINESS DAYS PRIOR TO

    PHOTOMETRICS, CONSTRUCTION/COMPONENT QUALITY AND DESIGN INTEGRITY ARE SHOWN TO BE EQUAL TO THE DESIGN INTENT. FINAL DISCRETION

    ALL SUCH ITEMS DISCLOSED IN FIXTURE DESCRIPTION AND/OR SPECIFICATIONS. SUBSTITUTION OF FIXTURE TYPES WILL ONLY BE ACCEPTED IF

    ALL OPTIONS, ACCESSORIES AND/OR FIXTURE COMPONENTS MAY NOT BE REFLECTED IN THIS NUMBER AND CONTRACTOR RESPONSIBLE FOR PROVIDING

    1. ALL INDICATED CATALOG NUMBERS REPRESENT A DESIGN BASIS ONLY AND CORRESPOND TO THE LISTED MANUFACTURERS SERIES NUMBER.

    GENERAL NOTES

    OR APPROVED EQUAL OR APPROVED EQUAL LED LED

    S-2 TO BE DETERMINED TO BE DETERMINED 277 1 42W 42W MAN-DOOR EGRESS LIGHT FIXTURE.

    OR APPROVED EQUAL OR APPROVED EQUAL LED LED

    S-1 TO BE DETERMINED TO BE DETERMINED 277 1 42W 42W EGRESS LIGHT FIXTURE.

    OR APPROVED EQUAL OR APPROVED EQUAL UL LISTED FOR WET LOCATIONS.

    DF-2 TO BE DETERMINED TO BE DETERMINED DECORATIVE EXTERIOR SCONCE. MAXIMUM ALLOWANCE OF $2500 FOR FIXTURES.

    OR APPROVED EQUAL OR APPROVED EQUAL $2500 FOR FIXTURES. UL LISTED FOR WET LOCATIONS.

    DF-1 TO BE DETERMINED TO BE DETERMINED 3'-0" DECORATIVE EXTERIOR PENDANT AT BUILDING "A" - WHOLE FOODS. MAXIMUM ALLOWANCE OF

    OR APPROVED EQUAL OR APPROVED EQUAL DRIVER

    F-4 SPECTRUM LIGHTING SGE6LEDGV-26W-30K-E2-(COORDINATE)-AR6222GV-SO-277 277 1 26 LED 28.6 RECESSED LED DOWNLIGHT AT EXTERIOR CANOPY LOCATIONS. UL LISTED FOR WET LOCATION.

    OR APPROVED EQUAL OR APPROVED EQUAL LED DRIVER 12V TRANSFORMER REQUIRED FOR OPERATION. UL LISTED FOR WET LOCATION.

    F-3 LIMIERE 203-CRS-50MR16-12-(VERIFY)-LVR (HEX CELL LOUVER) 12 1 10W LED 50 ELECTRICAL CONTRACTOR TO PROVIDE 10W SORAA OUTDOOR LED MR16 41 DEGREE, 2700K.

    CAMBRIA SERIES BUILDING MOUNTED ADJUSTABLE DOWLIGHT CONCEALED BEHIND CANOPY.

    OR APPROVED EQUAL OR APPROVED EQUAL LED DRIVER TO COORDINATE ALL PARTS AND ACCESSORIES FOR A FULLY OPERABLE LIGHTING SYSTEM.

    F-1 LUMINII KENDO M WET-2900K-MO-S-F-F-SA 277 1 3.2W/LF LED 3.2W/LF LED UPLIGHT AT BUILDING CANOPY. UL LISTED FOR WET LOCATION. ELECTRICAL CONTRACTOR

    SITE LIGHTING

    OR APPROVED EQUAL OR APPROVED EQUAL DRIVER LIFE. INTEGRAL 2-CIRCUIT TRANSFER RELAY & NICAD BATTERY FOR EMERGENCY OPERATION.

    X-01 LITHONIA EXGLEDELMD 277 1 5W LED LED 5 SHOWN ON PLANS. WHITE POLYCARBONATE HOUSING WITH STENCIL FACE. 20-YEAR LED

    UNIVERSAL MOUNT LED EXIT SIGN WITH GREEN LETTERS, FACES AND ARROW INDICATORS AS

    OR APPROVED EQUAL OR APPROVED EQUAL

  • DN

    J

    J

    J

    J

    -

    -

    --

    15'-0"

    2000KVA PSEUTILITY XFMRBLDG A & B

    (6) 4" PVC-40(4) 750 KCMIL AL (EA)

    DF-1 DF-1 DF-1 DF-1 DF-1 DF-1 DF-1 F-4 F-4 F-4 F-4 F-4 F-4 F-4 F-4 F-4 F-4 F-4

    F-4

    F-4

    DF-2

    DF-2

    DF-2

    DF-2

    DF-2

    DF-2

    F-1-180'-0"

    MDS-A

    F-3

    F-3

    F-3

    F-3

    F-3

    F-3

    F-3

    F-3

    F-3

    F-3

    1

    1

    B

    C

    D

    E

    F

    G

    A.4

    A.5

    E.8

    E.2

    D.7

    C.8

    B.9

    B.1

    A.8

    1234567

    2.73.4

    4.85.4

    5.8

    5.9

    1.21.73.54.56.8 6.6 5.7 5.3 2.5

    A.2

    A.1

    A.3

    A1.9

    F.1

    F.7

    8.1

    8.2

    Y

    S-1

    S-1

    S-1

    S-2

    S-2

    S-2

    S-2

    S-2

    EM

    EMEM

    EM

    EM

    11

    -

    ---

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    4 P

    M

    3/32" = 1'-0"

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E1.01

    ELECTRICAL SITE PLAN

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    GENERAL NOTES

    1. MULTI-WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4REQUIREMENTS.

    2. COLOR OF ALL WIRING DEVICES AND COVER PLATES SHALLBE AS SELECTED BY THE ARCHITECT, U.N.O.. VERIFY WITHARCHITECT PRIOR TO ORDERING

    3. EQUIPMENT SHOWN IN BOLD IS NEW.

    4. EQUIPMENT SHOWN IN DASHED IS EXISTING.

    3/32" = 1'-0"

    SITE ENLARGED ELECTRICAL PLAN

    KEY NOTES

    1 ELECTRICAL CONTRACTOR TO TERMINATE LIGHTING WIRINGAT JUNCTION BOX. EXTERIOR LIGHTING TO BE CIRCUITEDUNDER TENANT IMPROVEMENT PHASE.

    No. Description Date

    11-8-2016

    ENR16-08749Page 3 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

  • --

    PANEL MDS-A

    B

    C

    D

    E

    F

    G

    A.4

    A.5

    E.8

    E.2

    D.7

    C.8

    B.9

    B.1

    A.8

    1234567

    2.73.4

    4.85.4

    5.8

    5.9

    1.21.73.54.56.8 6.6 5.7 5.3 2.5

    A.2

    A.1

    A.3

    A1.9

    F.1

    F.7

    8.1

    8.2

    Y

    E2.02

    2

    WP

    WP

    WP

    WP

    E2.02

    3

    1

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    4 P

    M

    3/32" = 1'-0"

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E2.01

    LEVEL 1 POWER PLAN

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    GENERAL NOTES

    1. MULTI-WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.

    2. COLOR OF ALL WIRING DEVICES AND COVER PLATES SHALL BE ASSELECTED BY THE ARCHITECT, U.N.O.. VERIFY WITH ARCHITECT PRIORTO ORDERING.

    3. EQUIPMENT SHOWN BOLD IS NEW.

    4. EQUIPMENT SHOWN DASHED IS EXISTING.

    5. ITEMS NOTED AS "TYPICAL" ON ANY DRAWING REFERS TO ALLDRAWINGS.

    6. PROVIDE NYLON PULL STRING IN ALL EMPTY RACEWAYS.

    7. NO STRUCTURAL MEMBERS SHALL BE CUT OR ALTERED WITHOUTPRIOR APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER.

    8. LOCATIONS OF ALL MOUNTED DEVICES ARE SHOWN SCHEMATICALLY.COORDINATE WITH THE ARCHITECTURAL DRAWINGS, ELEVATIONS ANDCASEWORK SUPPLIERS SHOP DRAWINGS FOR EXACT LOCATION OFDEVICES PRIOR TO ROUGH IN.

    9. EQUIPMENT, LUMINAIRES, RACEWAYS, DEVICES, ETC. SHALL BE ULLISTED.

    3/32" = 1'-0"

    LEVEL 1 POWER PLAN

    No. Description Date

    1 CITY OF KIRKLANDREVIEW COMMENTS

    11/02/2016

    11-8-2016

    ENR16-08749Page 4 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

  • ELEVATOR

    104

    BC3456

    2.7

    3.4

    4.85.4

    5.8

    5.9

    A.2

    A.1

    A.3

    A1.9

    8.1 8.2

    6

    A.2

    A.1

    A1.9

    8.1

    1

    4 3.4

    A.2A1.9

    MDS-A

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    5 P

    M

    As indicated

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E2.02

    MEZZANINE, ENLARGEDELECTRICAL ROOM, AND

    ENLARGED LOADING DOCK POWERPLAN

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    GENERAL NOTES

    1. MULTI-WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.

    2. COLOR OF ALL WIRING DEVICES AND COVER PLATES SHALL BE ASSELECTED BY THE ARCHITECT, U.N.O.. VERIFY WITH ARCHITECT PRIORTO ORDERING.

    3. EQUIPMENT SHOWN BOLD IS NEW.

    4. EQUIPMENT SHOWN DASHED IS EXISTING.

    5. ITEMS NOTED AS "TYPICAL" ON ANY DRAWING REFERS TO ALLDRAWINGS.

    6. PROVIDE NYLON PULL STRING IN ALL EMPTY RACEWAYS.

    7. NO STRUCTURAL MEMBERS SHALL BE CUT OR ALTERED WITHOUTPRIOR APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER.

    8. LOCATIONS OF ALL MOUNTED DEVICES ARE SHOWN SCHEMATICALLY.COORDINATE WITH THE ARCHITECTURAL DRAWINGS, ELEVATIONS ANDCASEWORK SUPPLIERS SHOP DRAWINGS FOR EXACT LOCATION OFDEVICES PRIOR TO ROUGH IN.

    9. EQUIPMENT, LUMINAIRES, RACEWAYS, DEVICES, ETC. SHALL BE ULLISTED.

    3/16" = 1'-0"

    MEZZANINE POWER PLAN

    1/4" = 1'-0"2

    LEVEL 1 ENLARGED LOADING

    DOCK POWER PLAN

    KEY NOTES

    1 ELECTRICAL CONTRACTOR TO PROVIDE RACEWAY FOR FUTURELOADING DOCK MOTOR, ROLL-UP DOORS, AND CONTROL BOX.ELECTRICAL CONNECTIONS TO BE PROVIDED BY TENANT.

    No. Description Date

    1 CITY OF KIRKLANDREVIEW COMMENTS

    11/02/2016

    1/4" = 1'-0"3

    LEVEL 1 ENLARGED

    ELECTRICAL ROOM1

    11-8-2016

    ENR16-08749Page 5 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

  • J

    --

    B

    C

    D

    E

    F

    G

    A.4

    A.5

    E.8

    E.2

    D.7

    C.8

    B.9

    B.1

    A.8

    1234567

    2.73.4

    4.85.4

    5.8

    5.9

    1.21.73.54.56.8 6.6 5.7 5.3 2.5

    A.2

    A.1

    A.3

    A1.9

    F.1

    F.7

    8.1

    8.2

    Y

    1

    WP

    WP

    WPWP WP

    WP

    WP

    WP

    WP

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    5 P

    M

    3/32" = 1'-0"

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E2.03

    MAIN ROOF POWER PLAN

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    GENERAL NOTES

    1. MULTI-WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.

    2. COLOR OF ALL WIRING DEVICES AND COVER PLATES SHALL BE ASSELECTED BY THE ARCHITECT, U.N.O.. VERIFY WITH ARCHITECT PRIORTO ORDERING.

    3. EQUIPMENT SHOWN BOLD IS NEW.

    4. EQUIPMENT SHOWN DASHED IS EXISTING.

    5. ITEMS NOTED AS "TYPICAL" ON ANY DRAWING REFERS TO ALLDRAWINGS.

    6. PROVIDE NYLON PULL STRING IN ALL EMPTY RACEWAYS.

    7. NO STRUCTURAL MEMBERS SHALL BE CUT OR ALTERED WITHOUTPRIOR APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER.

    8. LOCATIONS OF ALL MOUNTED DEVICES ARE SHOWN SCHEMATICALLY.COORDINATE WITH THE ARCHITECTURAL DRAWINGS, ELEVATIONS ANDCASEWORK SUPPLIERS SHOP DRAWINGS FOR EXACT LOCATION OFDEVICES PRIOR TO ROUGH IN.

    9. EQUIPMENT, LUMINAIRES, RACEWAYS, DEVICES, ETC. SHALL BE ULLISTED.

    3/32" = 1'-0"

    MAIN ROOF POWER PLAN

    KEY NOTES

    1 ELECTRICAL CONTRACTOR TO TERMINATE RECEPTACLE WIRING ATJUNCTION BOX. EXTERIOR ROOFTOP POWER TO BE CIRCUITED UNDERTENANT IMPROVEMENT PHASE.

    No. Description Date

    11-8-2016

    ENR16-08749Page 6 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

  • 250kCMIL CU

    G

    N

    PROVIDE UFER GROUND: 20' BARECOPPER CABLE IN CONCRETEFOOTING SIZED AND INSTALLEDPER NEC 250-81(c) BOND TO MAINWATER PIPE.EXOTHERMIC WELD OR

    OTHER APPROVED METHOD

    MAIN WATER PIPE

    M

    2000

    A/3

    P

    MAIN DISTRIBUTION SWITCHBOARD2000A, 480Y/277V 3PH, 4WW/KIRK KEY SYSTEM42,000 AIC

    XFMR VAULT

    NEW SERVICE FEEDERS:

    (6) 4" PVC-40

    (4) 750 KCMIL AL (EA)

    *PROVIDE AND INSTALL NEW, 2000A SERVICE

    FEEDERS (UP TO 75'-0" WITHIN 5'-0" OF

    BUILDING) FOR NEW 2000A, 480Y/277V,3P,4W

    MAIN DISTRIBUTION SWITCHBOARD

    GRADE

    GFP

    1

    NEW (OR EXISTING)PSE

    4-WAY LOAD BREAKJUNCTION HUB

    2

    2

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    SP

    AC

    E

    5

    INTERIORNEMA 1

    EXTERIORNEMA 3R

    NEW 2000KVAPSE LOOPED UTILITY

    TRANSFORMER

    45,2

    00

    NEW / EXISTING SITE MEDIUM VOLTAGE FEEDER:

    SIZED, PROVIDED AND PRICED BY PSEELBOW TERMINATION:

    PROVIDED AND PRICED BY PSE

    39,6

    31

    6

    SP

    AC

    E

    SP

    AC

    E

    7

    PH

    ON

    E (

    253)

    872-5

    553

    FA

    X (

    25

    3)

    87

    2-4

    112

    KE

    NT

    , W

    A 9

    8032

    7056 S

    OU

    TH

    220T

    H S

    TR

    EE

    T

    ELE

    CT

    RIC

    IN

    C.

    SE

    A T

    AC

    SCALE

    DATE

    DRAWN BY

    CHECKED BY

    PROJECT NUMBER

    ww

    w.s

    eata

    cele

    ctric

    .com

    11/7

    /2016 3

    :06:4

    6 P

    M

    12" = 1'-0"

    C:\U

    sers

    \iane\D

    ocum

    ents

    \VA

    TL_A

    _E

    L_Ia

    nE

    dm

    unds.r

    vt

    E5.01

    ONE-LINE RISER DIAGRAM

    T HE

    VIL

    LAG

    E A

    T TO

    TEM

    LA

    KE

    - B

    LDG

    A

    KI R

    KLA

    ND

    , WA

    980

    34

    CM

    CM, IE, NP

    11/07/2016

    15115

    90%

    CD

    SE

    T

    CENTERCAL PROPERTIES,LLC 1600 EAST FRANKLINEL SEGUNDO, CA 90245

    GENERAL NOTES

    1. ALL CONDUCTORS ARE #12 AWG CU UNLESS NOTED OTHERWISE. MCFEEDER CAN BE USED WHERE APPROPRIATE AND AT CONTRACTOR'SDISCRETION. MC FEEDER SHALL BE SIZED PER NEC REQUIREMENTS.

    2. RISER DIAGRAM IS NOT REPRESENTATIVE OF ACTUAL SWITCHBOARDLAYOUT. SEE ELECTRICAL ROOMS OR PANEL LOCATIONS (SHEETE2.01-E2.08) AND PANEL SCHEDULES (SHEET E5.02-E5.03) FORPHYSICAL LAYOUT WITH RESPECT TO ACTUAL MANUFACTURED ANDPOTENTIAL INSTALLED CONDITIONS.

    3. EQUIPMENT SHOWN BOLD IS NEW.

    4. EQUIPMENT SHOWN DASHED IS EXISTING.

    5. FIELD VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION.

    6. ALL SWITCHBOARDS AND PANELBOARDS SUPPLIED BY A FEEDERSHALL BE MARKED TO INDICATE THE DEVICE OR EQUIPMENT WHERETHE POWER SUPPLY ORIGINATES PER NEC 408.4(B).

    7. FEEDERS ARE ALUMINUM WITH THHN/THWN INSULATION.

    8. PROVIDE PULL BOXES AS REQUIRED BY THE NEC.

    9. SHORT CIRCUIT CURRENTS LESS THAN 10,000 AIC FOR 208V PANELSAND 14,000 AIC FOR 480V PANELS ARE NOT SHOWN.

    10. THE ONE-LINE DIAGRAM IS DIAGRAMMATIC AND DOES NOT SHOW THEACTUAL ROUTING OF RACEWAYS.

    11. FOR TWO SECTION PANELS PROVIDE FULL SIZE FEEDER CONNECTIONSFROM SECTION 1 TO SECTION 2.

    12. NOT ALL CIRCUIT BREAKERS ARE SHOWN, REFER TO PANEL ANDSWITCHBOARD SCHEDULES FOR OTHER LOADS SERVED, AND SPARECIRCUIT BREAKERS.

    FLAG NOTES

    CONCRETE HOUSEKEEPING PAD UNDER TRANFORMER(S)/SWITCHBOARD(S)/ GENERATOR(S) TO BE PROVIDED BY OTHERS.REFER TO STRUCTURAL PLANS FOR INSTALLATION DETAILS.

    CT ENCLOSURE/TERMINAL CABINET PER POWER COMPANYREQUIREMENTS.

    NOT USED

    NOT USED

    (1) 1-1/2" EMT CONDUIT TO BE PROVIDED FROM ELECTRICAL ROOMAND TO BE CAPPED AT ROOF.

    PER NEC 240.87, PROVIDE DOCUMENTATION OR METHOD TO REDUCECLEARING TIME FOR ARC ENERGY REDUCTION.

    MAIN BONDING JUMPER TO BE PROVIDED BY GEAR MANUFACTURERAND SHALL COMPLY WITH NEC 250.102(C)(1) NOTE #1. IF THEUNGROUNDED SUPPLY CONDUCTORS ARE LARGER THAN 1100KCMILCOPPER OR 1750 KCMIL ALUMINUM, THE GROUNDED CONDUCTOR ORBONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OFTHE AREA OF THE LARGEST UNGROUNDED SUPPLY CONDUCTOR OREQUIVALENT AREA FOR PARALLEL SUPPLY CONDUCTORS. THEGROUNDED CONDUCTOR OR BONDING JUMPER SHALL NOT BEREQUIRED TO BE LARGER THAN THE LARGEST UNGROUNDEDCONDUCTOR OR SET OF UNGROUNDED CONDUCTORS.

    12" = 1'-0"

    ONE-LINE RISER DIAGRAM

    1

    2

    3

    4

    5

    Line to Line RMS Fault at MAIN DISTRIBUTION... 39,631.45 Amps

    Multiplier "M" = 1/(1+f) 0.876802

    f-Factor 0.140508

    Phase (1ph = 2, 3ph = 1.73) 1.73

    Voltage (L-L) 480

    Distance (Feet) 115

    No. of Parellel Runs 6

    Z /1000' @.85pf (NEC Table 9) 0.045

    Conduit type (S=Steel, P=PVC) P

    Conductor type (AL=Alum, CU=Copper) AL

    Wire Size 750 kcmil

    Starting Fault Value at UTILITY ===> 45200.00 Amps

    Conductor

    Calculation for Fault Value at MAIN DISTRIBUTION SWITCHBOARD

    FAULT CURRENT @ UTILITY XFMR SECONDARY =========> 45200.00 Amps

    VILLAGE AT TOTEM LAKE - BUILDING "A" FAULT CURRENT CALCULATION SUMMARY

    12

    11

    10 -- -- -- -- ... SPACE --

    9 -- -- -- -- ... SPACE --

    8 -- -- -- -- ... SPACE --

    7 -- -- -- -- ... SPACE --

    6 -- -- -- -- ... SPACE --

    5 -- -- -- -- ... SPACE --

    4 -- -- -- -- ... SPACE --

    3 -- -- -- -- ... SPACE --

    2 -- -- -- -- ... SPACE --

    1 -- -- -- -- ... SPACE --

    CKT FRAME POLES FUSE A B C DESCRIPTION/NAMEPLATE NOTES

    DISTRIBUTION SECTION No. 1

    NOTES:

    EST. DEMAND... 0 A

    CONN. CURRENT: 0 A

    EST. DEMAND LOAD: 0 VA

    CONN. LOAD: 0 VA

    LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

    BLDG A - "MDS" 38"x28" MAIN... 0 VA

    SWBD LOAD CONN. LOAD

    LOAD SUMMARY

    BLDG A - "MDS" 38"x28" DIST... 0 VA

    DISTRIBUTION SUMMARY CONN. LOAD

    2000 3

    FRAME POLES FUSE SPECIAL DESCRIPTION/NAMEPLATE

    MAIN DEVICE

    CUSTOMER POWER QUALITY METER

    C.T. COMPARTMENT: CURRENT TRANSFORMER, POTENTIAL TRANSFORMER

    MAIN SECTION

    BUS AMPS: 2000 SPECIAL:

    MAIN DEVICE: MAIN CB AIC RATING: 42,000 AMPS SYMMETRICAL

    LOCATION: MERCANTILE 4 VOLTAGE: 480Y/277V.3Ø4W.

    SWITCHBOARD: MDS-A

    Suitable as equipment feeder only. Not to be used for panel feeder

    not be used for sizing parallel feeders. Load cannot exceed feeder ampacity

    * - Indicates acceptable overcurrent device rating for single feeder. This rating shall

    Chapter 9 - Table 4 and Table - 5.

    NOTE: Based on NEC 2014, THHN insulation, EMT conduit and Annex C - Table C.10, or

    200 (6) 3" 3-600kcmil, 1 #400 G. 2040/2000 75-deg rating

    200N (6) 2 1/2" 4-600kcmil, 1 #400 G. 2040/2000 75-deg rating

    160 (6) 2 1/2" 3-400kcmil, 1 #350 G. 1620/1600 75-deg rating

    160N (6) 3" 4-400kcmil, 1 #350 G. 1620/1600 75-deg rating

    150 (5) 3" 3-500kcmil, 1 #350 G. 1550/1500 75-deg rating

    150N (5) 3" 4-500kcmil, 1 #350 G. 1550/1500 75-deg rating

    120 (4) 3" 3-500kcmil, 1 #250 G. 1240 / 1200 75-deg rating

    120N (4) 3" 4-500kcmil, 1 #250 G. 1240 / 1200 75-deg rating

    100 (3) 3" 3-600kcmil, 1 #4/0 G. 1020 / 1000 75-deg rating

    100N (3) 3 1/2" 4-600kcmil, 1 #4/0 G. 1020 / 1000 75-deg rating

    90 (3) 3" 3-500kcmil, 1 #4/0 G. 930 / 900 75-deg rating

    90N (3) 3" 4-500kcmil, 1 #4/0 G. 930 / 900 75-deg rating

    80 (3) 2 1/2" 3-400kcmil, 1 #3/0 G. 810 / 800 75-deg rating

    80N (3) 3" 4-400kcmil, 1 #3/0 G. 810 / 800 75-deg rating

    75 (3) 2 1/2" 3-350kcmil, 1 #3/0 G. 750 / 750 75-deg rating

    75N (3) 3" 4-350kcmil, 1 #3/0 G. 750 / 750 75-deg rating

    60 (2) 3" 3-500kcmil, 1 #2/0 G. 620 / 600 75-deg rating

    60N (2) 3" 4-500kcmil, 1 #2/0 G. 620 / 600 75-deg rating

    50 (2) 2 1/2" 3-350kcmil, 1 #1/0 G. 500 / 500 75-deg rating

    50N (2) 3" 4-350kcmil, 1 #1/0 G. 500 / 500 75-deg rating

    45 (2) 2 1/2" 3 -300kcmil, 1 #1/0 G. 460 / 450 75-deg rating

    45N (2) 2 1/2" 4 -300kcmil, 1 #1/0 G. 460 / 450 75-deg rating

    40 (2) 2 1/2" 3 -250kcmil, 1 #1 G. 410 / 400 75-deg rating

    40N (2) 2 1/2" 4 -250kcmil, 1 #1 G. 410 / 400 75-deg rating

    34 3" 3-600kcmil, 1 #1 G. 340 / 300 75-deg rating

    34N 3 1/2" 4-600kcmil, 1 #1 G. 340 / 300 75-deg rating

    30 3" 3-500kcmil, 1 #2 G. 310 / 300 75-deg rating

    30N 3" 4-500kcmil, 1 #2 G. 310 / 300 75-deg rating

    27 2 1/2" 3-400kcmil, 1 #2 G. 270 / 250 75-deg rating

    27N 3" 4-400kcmil, 1 #2 G. 270 / 250 75-deg rating

    25 2 1/2" 3-350kcmil, 1 #2 G. 250 / 250 75-deg rating

    25N 3" 4-350kcmil, 1 #2 G. 250 / 250 75-deg rating

    22 2 1/2" 3 -300kcmil, 1 #2 G. 230 / 225 75-deg rating

    22N 2 1/2" 4 -300kcmil, 1 #2 G. 230 / 225 75-deg rating

    20 2 1/2" 3 -250kcmil, 1 #4 G. 205 / 200 75-deg rating

    20N 2 1/2" 4 -250kcmil, 1 #4 G. 205 / 200 75-deg rating

    18 2" 3 - #4/0, 1 #4 G. 180 / 175 75-deg rating

    18N 2 1/2" 4 - #4/0, 1 #4 G. 180 / 175 75-deg rating

    15 2" 3 - #3/0, 1 #4 G. 155 / 150 75-deg rating

    15N 2" 4 - #3/0, 1 #4 G. 155 / 150 75-deg rating

    13 2" 3 - #2/0, 1 #4 G. 135 / 125 75-deg rating

    13N 2" 4 - #2/0, 1 #4 G. 135 / 125 75-deg rating

    12 1 1/2" 3 - #1/0, 1#4 G. 120 / 110 75-deg rating

    12N 2" 4 - #1/0, 1#4 G. 120 / 110 75-deg rating

    10 1 1/2" 3 - #1/0, 1#6 G. 120 / 100 75-deg rating

    10N 2" 4 - #1/0, 1#6 G. 120 / 100 75-deg rating

    8 1 1/4" 3 - #1, 1#6 G. 85 / 80 60-deg rating

    08N 1 1/4" 4 - #1, 1#6 G. 85 / 80 60-deg rating

    7 1 1/4" 3 - #2, 1#6 G. 75 / 70 60-deg rating

    07N 1 1/4" 4 - #2, 1#6 G. 75 / 70 60-deg rating

    06 1 1/4" 3 - #3, 1#8 G. 65 / 60 60-deg rating

    06N 1 1/4" 4 - #3, 1#8 G. 65 / 60 60-deg rating

    05 1" 3 - #4, 1#8 G. 55 / 50 60-deg rating

    05N 1 1/4" 4 - #4, 1#8 G. 55 / 50 60-deg rating

    04 1" 3 - #6, 1#8 G. 40 / 40 60-deg rating

    04N 1" 4 - #6, 1#8 G. 40 / 40 60-deg rating

    03 3/4" 3 - #8 1#8 G. 30 / 30 60-deg rating

    03N 3/4" 4 - #8, 1#8 G. 30 / 30 60-deg rating

    ID NO RACEWAY WIRE COUNT & SIZE OCP SIZE NOTES

    EMT AMPACITY/

    FEEDER SCHEDULE ALUMINUM

    6

    No. Description Date

    1 CITY OF KIRKLANDREVIEW COMMENTS

    11/02/2016

    71

    1

    11-8-2016

    ENR16-08749Page 7 of 7

    City of KirklandReviewed by J Tumelson11/22/2016

    Supersededwith revision

    dated 4/27/2017

  • ENR16-08749Revised Approved Plans

    Page 1 of 1

    City of KirklandReviewed by J Tumelson04/27/2017

    SheetsE0.01 - SYMBOLS AND ABBREVIATIONSE0.02 - ELECTRICAL SCHEDULESE1.01 - ELECTRICAL SITE PLANE2.01 - LEVEL 1 POWER PLANE2.02 - MEZZANINE, ENLARGED ELECTRICAL ROOM, AND ENLARGED LOADING DOCK POWER PLANE2.03 - MAIN ROOF POWER PLANE5.01 - ONE-LINE RISER DIAGRAM