DESIGN TEAM SYMBOLS
NORTH
ABBREVIATIONS
VICINITY MAP
INDEX TO DRAWINGSA TENANT IMPROVEMENT FOR:
TAYLORSVILLE, UTAH
ARCHITECT PASKER GOULD AMES & WEAVER INC.5263 SOUTH COMMERCE DRIVEMURRAY, UTAH 84107PHONE # (801) 266 - 4669 FAX # (801) 262 - 6122CONTACT: CRAIG AMES
CODE ANALYSIS - IBC 2012
ALLOWABLE OCCUPANT AREA
EXIT ACCESS TRAVEL DISTANCE NUMBER OF REQUIRED PLUMBING FIXTURES : 2012 I.P.C.
1855 WEST 5400 SOUTH
PLUMBING & MECHANICALROYAL ENGINEERING2335 SOUTH STATE STREETPROVO, UTAH 84606PHONE # (801) 375 - 2228 FAX # (801) 375 - 2676CONTACT: MIKE PRESSON
ARCHITECTS / PLANNERS
ARCHITECTURAL DRAWINGS
T 1.0TITLE
TITLE SHEET AND DRAWING INDEX
REFLECTED CEILING PLAN AND DETAILSA 2.0
DEMOLITION PLAND 1.0FLOOR PLAN AND INTERIOR ELEVATIONSA 1.0
DEFERRED SUBMITTALS· BUILDING SIGNAGE -
WILL BE SUBMITTEDFOR SEPARATE PERMIT
PENNY ANN'S CAFE
OCCUPANCY A-2 RESTAURANTTYPE II A CONSTRUCTION
OCCUPANT LOAD
T 2.0 DRAWING STANDARDS
PLUMBING DRAWINGS
PLUMBING SCHEDULES AND SCHEMATICSP 201
CULINARY WATER PLANP 101GAS AND WASTE PLANP 102
PLUMBING DETAILSP 202
MECHANICAL DRAWINGS
MECHANICAL DETAILSM 102
DEMOLITION PLANMP 100MECHANICAL PLANM 101
SPECIFICATIONSMP 101
ELECTRICAL DRAWINGS
SCHEDULESE 2.1
DEMOLITIONE 1.0POWERE 1.1
SCHEDULESE 2.2DETAILSE 2.3
LIGHTINGE 1.2
72 MALE72 FEMALE
FULLY SPRINKLERED
ELECTRICALROYAL ENGINEERING2335 SOUTH STATE STREETPROVO, UTAH 84606PHONE # (801) 375 - 2228 FAX # (801) 375 - 2676CONTACT: KYLE BREINHOLT
PROJECT LOCATION
5400 SOUTH
RED
WO
OD
RO
AD
1900
WES
T
DETAILSE 2.4SPECIFICATIONSE 2.5
PASK
ER G
OU
LD A
MES
& W
EAV
ER
A TE
NAN
T IM
PRO
VEM
ENT
FOR:
PEN
NY
ANN
'S C
AFE
ARCHITECTS / PLANNERS
T1.0
TITL
E SH
EET
AN
D D
RA
WIN
G IN
DEX
HANDICAPPED - TYPICAL MOUNTING STANDARDS 3
FIRE EXTINGUISHER CABINET 4
HANDICAPPED TOILET ROOM - TYPICAL MOUNTING STANDARDS 2
RESISTIVE CONSTRUCTION AND GENERAL NOTES 6HANDICAP ACCESS SIGN5
1
TYP. CABINET STANDARDS 7 8SIGN MOUNTING DIAGRAM
MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS
9MOP SINK
PASK
ER G
OU
LD A
MES
& W
EAV
ER
A TE
NAN
T IM
PRO
VEM
ENT
FOR:
PEN
NY
ANN
'S C
AFE
ARCHITECTS / PLANNERS
T.o2.0
AC
CES
SIB
ILIT
Y S
TAN
DA
RD
S
DEMOLITION PLAN2 NORTH
KITCHEN
EXISTING TOILET
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
A TE
NAN
T IM
PRO
VEM
ENT
FOR:
PEN
NY
ANN
'S C
AFE
ARCHITECTS / PLANNERS
D1.0
DEM
OLO
TIO
N P
LAN
FLOOR PLAN1NORTH
CB
S-2
T-3
UC
-1
T-2
T-2
CB
S-1
FM
D-1
CG
-1
DD
-1
DD
-1
SS
P-1
SS
P-1
ST
T-1
SS
P-2
BR
-1
G-3
G-2
G-1
F-1
F-1
F-1
R-2
T-1
TILT
EX
IS
T.
R-1
DESCRIPTIONITEM
2
1
QTY
3
EACH
EACH
EACH
UNIT
EACH
EACH
2
1
21
11
11
1
EACH
EACH
EACHEACH
EACH
EACH
EACH
EACH
1 EACH
12 CUP AUTOMATIC COFFEE BREWER (3GTR)
UC-1
T-3
CBS-2CBS-1
1
SSP-1
T-2
EACH
ICE-1
H-1
TILT-1
CO-1
G-2
DD-1
G-3
F-1
R-2
G-1SK3STT-112 CUP AUTOMATIC COFFEE BREWER W/ 4 WARMERS (6GTN)1 EACH
2 EACH
SCHEDULE: FOOD SERVICE EQUIPMENT
EACH
UNDER-COUNTER: SOLID DOOR REFRIGERATOR
12 CU. FT. MEGA-TOP SOLID DOOR SANDWICH / SALAD UNIT
HEAVY DUTY GAS GRIDDLE: 48"
ELECTRIC HOT FOOD TABLE: OPEN BASE, STATIONARY (EXISTING)
WALL MOUNT HAND SINK (EXISTING)STAINLESS STEEL TABLE: 30"x72"
ICE MAKER: MOUNTED TO SODA DISPENSER
STAINLESS STEEL TABLE: 30"x48" 1 EACHHS-1
SODA DISPENSER: PROVIDED BY VENDER
STAINLESS STEEL THREE COMPARTMENT SINK (EXISTING)
31
HEAVY DUTY GAS GRIDDLE: 72"
HEAVY DUTY GAS GRIDDLE: 36"
STAINLESS STEEL EXHAUST HOOD (EXISTING)
TILTING KETTLE (EXISTING)
DOUBLE DECK ELECTRIC CONVENTION OVEN
FREE STANDING GAS FRYER
DISHWASHER1 EACHDW-136" HEAVY DUTY ELECTRIC BROILER
DESCRIPTIONITEM QTY UNIT
1 EACHSSP-2 18 CU. FT. MEGA-TOP SOLID DOOR SANDWICH / SALAD UNIT1 EACHT-1 STAINLESS STEEL TABLE: 30"x36"
COFFEE GRINDER / MODEL 250CG-1 1 EACHFRESH MIX DISPENSERFMD-1 1 EACH
ENDURANCE GAS RESTAURANT RANGE: 6 BURNERS
1 EACHBR-1
1 EACHSL-1 THE EDGE12 SLICER (EXISTING)
SL-1
HS
-1
HS
-1
HS
-1
HS
-1
SK
3
H-1
H-1
DW
-1
IC
E-1
IC
E-1
CO
-1
FZ
-1
48 CU.FT. REACH-IN FREEZER1 EACHFZ-1
1 EACHUC-2 UNDER-COUNTER: SOLID DOOR REFRIGERATOR (EXISTING)
UC-1
REF-1
23 CU.FT. REACH-IN REFRIGERATOR (EXISTING)1 EACHREF-1
IC
E-2
1 EACHICE-2 ICE MAKER (EXISTING)
MEN INTERIOR ELEVATIONS2
ELEVATION "A" ELEVATION "B" ELEVATION "C" ELEVATION "D"
WOMEN INTERIOR ELEVATIONS3
ELEVATION "A" ELEVATION "B" ELEVATION "C" ELEVATION "D"
H-1
H-1
DOOR FRAME DETAILS REMARKSLOCATION
DOOR SCHEDULE
HARDWARE
DINING103
VESTIBULE101
WAITING102
WOMEN104
MEN105
KITCHEN107
EXISTING COOLER108
EXISTING TOILET106
T-1
COUNTER SECTION4 FLOOR FINISH TRANSITION DETAIL5
T-2
T-3
T-1
PASK
ER G
OU
LD A
MES
& W
EAV
ER
A TE
NAN
T IM
PRO
VEM
ENT
FOR:
PEN
NY
ANN
'S C
AFE
ARCHITECTS / PLANNERS
A1.0
FLO
OR
PLA
N A
ND
INTE
RIO
R E
LEV
ATI
ON
S
FLOOR PLAN1NORTH
CEILING LEGEND
NEW GYP. BD. CEILING - PAINTED
EXISTING 2'X4' LAY-IN CEILING SYSTEM
NEW GYP. BD. CEILING - EPOXY PAINTED
CEILING GRID SEISMIC BRACING DETAIL TYPICAL FIXTURE SUPPORT DETAIL
UNATTACHED MOLDING DETAIL - PERIMETER
SUSPENDED TILE CEILING - SEISMIC PLAN
ATTACHED MOLDING DETAIL - PERIMETER
DINING103
VESTIBULE101
WAITING102
WOMEN104
MEN105
KITCHEN107
EXISTING COOLER108
EXISTING TOILET106
EXISTING GYP. BD. CEILING
PASK
ER G
OU
LD A
MES
& W
EAV
ER
A TE
NAN
T IM
PRO
VEM
ENT
FOR:
PEN
NY
ANN
'S C
AFE
ARCHITECTS / PLANNERS
A2.0
REF
LEC
TED
CEI
LIN
G P
LAN
AN
D D
ETA
ILS
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
MP100THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
MP
DEM
OLI
TIO
N P
LAN
MECHANICAL KEYED NOTES:
KITCHEN
EXISTING TOILET
EXIST. COOLER
DEMO PLANN
PERFORMANCE NOTES: GENERAL NOTES:
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
M101THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
M
MEC
HA
NIC
AL
PLA
N
MECHANICAL KEYED NOTES:
MECHANICAL PLANN
SEISMIC SUPPORT NOTES:
COMMISSIONING NOTES:
WAITING
DINING
KITCHEN
WOMEN
MEN
EXISTING TOILET
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
M102THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
M
MEC
HA
NIC
AL
DET
AIL
S
ROUND TAKE-OFF DIFFUSER CONNECTION DETAIL
TYPICAL DUCT STRAP HANGER DETAIL
FLEXIBLE DUCT STRAP HANGER DETAIL
DUCT LINER DETAILDUCT CONSTRUCTION DETAIL
ROOF MOUNTED EXHAUST FAN SCHEDULE
ROOF MOUNTED EXHAUST FAN DETAIL
DIFFUSER SCHEDULE
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
MP101THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
MP
SPEC
IFIC
ATI
ON
S
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
P101THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
P
CU
LIN
ARY
WA
TER
PLA
N
SEISMIC SUPPORT NOTES:
PLUMBING SYMBOLS
PLUMBING KEYED NOTES:
CULINARY WATER PLANN
WAITING
DINING
KITCHEN
WOMEN
MEN
EXISTING TOILET
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
P102THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
P
GA
S A
ND
WA
STE
PLA
N
PLUMBING KEYED NOTES:
GAS AND WASTE PLANN
WAITING
DINING
KITCHEN
WOMEN
MEN
EXISTING TOILET
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
P201THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
P
PLU
MBI
NG
SC
HED
ULE
S A
ND
SC
HEM
ATI
CS
PLUMBING FIXTURE SCHEDULE
NOTES:1. VERIFY ALL MANUFACTURERS, FINISHES, AND OPTIONS WITH OWNER BEFORE ORDERING ANY PLUMBING FIXTURES.
2. MINIMUM UNDERGROUND PIPING SIZE SHALL BE 2 INCHES.
CULINARY WATER PIPING SCHEMATICS
WASTE AND VENT PIPING SCHEMATICS
TYPICAL URINALTYPICAL LAVATORY TYPICAL WATER CLOSET
LAVATORYWATER CLOSETWATER CLOSET
TYPICAL FLOOR SINK TYPICAL FLOOR DRAIN
SODA MACHINE
GAS PIPING SCHEMATIC
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
P202THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/01/2016J16041.00
P
PLU
MBI
NG
DET
AIL
S
TYPICAL FLOOR SINK DETAIL
TYPICAL WALL CLEANOUT DETAIL
TYPICAL FLOOR CLEANOUT DETAIL
PIPE HANGERS DETAIL
BURIED PIPE DETAIL
FLOOR DRAIN WITH TRAP GUARD TYPICAL 2LB GAS CONNECTION DETAIL
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
1.0THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
DEM
OLI
TIO
N
ELECTRICAL KEYED NOTES:
ELECTRICAL GENERAL NOTES:
NCAFE DEMOLITION PLAN
KITCHEN
EXISTING TOILET
EXIST. COOLER
DINING
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
1.1THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
POW
ER
ELECTRICAL KEYED NOTES:
ELECTRICAL GENERAL NOTES:
NCAFE POWER PLAN
WAITING
DINING
KITCHEN
WOMEN
MEN
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
1.2THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
LIG
HTI
NG
NCAFE LIGHTING PLAN
ELECTRICAL GENERAL NOTES:
ELECTRICAL KEYED NOTES:
WAITING
DINING
KITCHEN
WOMEN
MEN
EXIST. COOLER
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
2.1THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
SCH
EDU
LES
PANEL SCHEDULE "DP"VOLTAGE: 208 Y/ 120 VOLTS BUS RATING (AMPS): 600 REMARKS: EXISTING GE PANEL. EXST= EXISTING, NEW= NEW, REU= RE-USE,
RED= RED COLORED.MOUNTING: RECESSED PHASE: 3 MAIN LUGS ONLYENCLOSURE: NEMA 1 WIRE: 4 MINIMUM EQUIPMENT RATING: 22,000 AMPS (RMS-SYM)
CIRCUIT BREAKERCIRCUIT NAME
FEEDER CKT. LOAD LOAD/PHASE (VA) CKT. LOAD FEEDERCIRCUIT NAME
CIRCUIT BREAKER
No. AMPS POLE MOD. C WIRE GRD DEMANDFACTOR WATTS ØA ØB ØC WATTS DEMAND
FACTOR GRD WIRE C MOD. POLE AMPS No.
1 100 3 EXST RTU MAIN CENTER 1.00 0 1.00 RTU WEST EXST 3 50 23 - - EXST - - - 1.00 0 1.00 - - - EXST - - 45 - - EXST - - - 1.00 0 1.00 - - - EXST - - 67 50 3 EXST RTU EAST 1.00 0 1.00 RTU EAST CENTER EXST 3 50 89 - - EXST - - - 1.00 0 1.00 - - - EXST - - 1011 - - EXST - - - 1.00 0 1.00 - - - EXST - - 1213 50 3 EXST RTU WEST CENTER 1.00 0 1.00 SHUNT CONTROL EXST 1415 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 1617 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 1819 20 1 EXST RTU GFCI 1.00 0 1.00 EXISTING EXST 1 20 2021 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2223 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2425 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2627 40 3 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2829 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 3031 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 3233 - SPACE 1.00 0 1.00 SPACE - 3435 - SPACE 1.00 0 1.00 SPACE - 36
225A 3P SUB-FEEDCIRCUIT BREAKER
PANEL K-1 SEE ONE-LINE 1.00 3,648 7,970 4,323 1.00 SEE ONE-LINE PANEL K-2225A 3P SUB-FEEDCIRCUIT BREAKER- - DIAGRAM FOR 1.00 7,260 9,243 1,983 1.00 DIAGRAM FOR -
- REQUIREMENTS 1.00 7,531 9,334 1,803 1.00 REQUIREMENTS -NOTES :
1. ALL INSULATION ON CONDUCTORS TO BE THHN UNLESS NOTED OTHERWISE. ØA ØB ØC TOTALSINSULATION ON ALL UNDERGROUND EXTERIOR CONDUCTORS SHALL BE THHW. 7,970 9,243 9,334 26,547 CONNECTED LOAD (VA)
2. LOAD DEMANDS CALCULATED AS PER SECTIONS 210 & 220 OF THE NATIONAL 74 CONNECTED LOAD (A)ELECTRICAL CODE. 0 0 0 0 DEMAND FACTOR ADJUSTMENTS (VA)
3. PANEL COVER SHALL BE FIELD MARKED FOR FLASH PROTECTION WITH A PERMANENT LABEL 7,970 9,243 9,334 26,547 TOTAL LOAD (VA)AS REQUIRED BY THE NATIONAL ELECTRICAL CODE SECTION 110. LABEL SHALL READ: 66 77 78 TOTAL LOAD (A)"DANGER: POTENTIAL ARC FLASH HAZARD" 78 MAXIMUM LOAD (A)
4. ABBREVIATIONS: CO-CONVENIENCE OUTLET, RR-RESTROOM, (N)ORTH, (S)OUTH, 30% 35% 35% PHASE BALANCE(E)AST, (W)EST.
PANEL SCHEDULE "K1 SEC A"VOLTAGE: 208 Y/ 120 VOLTS BUS RATING (AMPS): 225 REMARKS: EXISTING GE PANEL. EXST= EXISTING, NEW= NEW, REU= RE-USE,
RED= RED COLORED.MOUNTING: RECESSED PHASE: 3 MAIN LUGS ONLYENCLOSURE: NEMA 1 WIRE: 4 MINIMUM EQUIPMENT RATING: 22,000 AMPS (RMS-SYM)
CIRCUIT BREAKERCIRCUIT NAME
FEEDER CKT. LOAD LOAD/PHASE (VA) CKT. LOAD FEEDERCIRCUIT NAME
CIRCUIT BREAKER
No. AMPS POLE MOD. C WIRE GRD DEMANDFACTOR WATTS ØA ØB ØC WATTS DEMAND
FACTOR GRD WIRE C MOD. POLE AMPS No.
1 20 3 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 23 - - EXST - - - 1.00 1,300 1,300 1.25 #12 #12 ¾" DINING LIGHTING EXST 1 20 45 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 67 20 3 EXST EXISTING 1.00 950 950 1.25 #12 #12 ¾" DINING, RR LIGHTING EXST 1 20 89 - - EXST - - - 1.00 0 1.00 EXISTING EXST 1 20 1011 - - EXST - - - 1.00 708 708 1.00 #12 #12 ¾" UC-1 EXST 1 20 1213 20 1 EXST EXISTING 1.00 900 900 1.00 #12 #12 ¾" WAITING CO EXST 1 20 1415 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 1617 20 1 EXST EXISTING 1.00 888 888 1.00 #12 #12 ¾" REF-1 EXST 1 20 1819 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2021 20 1 EXST EXISTING 1.00 1,200 1,200 1.00 #12 #12 ¾" DD-1 EXST 1 20 2223 20 1 EXST EXISTING 1.00 1,440 1,440 1.00 #12 #12 ¾" ICE-1 EXST 1 20 2425 20 1 EXST EXISTING 1.00 1,200 1,200 1.00 #12 #12 ¾" DD-1 EXST 1 20 2627 20 1 EXST EXISTING 1.00 1,440 1,440 1.00 #12 #12 ¾" ICE-1 EXST 1 20 2829 20 1 EXST EXISTING 1.00 1,500 1,500 1.00 #12 #12 ¾" DISHWASHER EXST 1 20 3031 20 1 EXST NEW TERMINAL BOARD ¾" #12 #12 1.00 360 360 1.00 EXISTING EXST 1 20 3233 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 3435 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 3637 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 3839 20 1 EXST EXISTING 1.00 2,995 2,995 1.00 #10 #8 ¾" BR-1 - 1 40 4041 20 1 EXST EXISTING 1.00 2,995 2,995 1.00 #10 #8 ¾" - - 1 40 42
FEED-THROUGHLUGS
SEE ONE-LINE 1.00 0- - DIAGRAM FOR 1.00 0
- REQUIREMENTS 1.00 0NOTES :
1. ALL INSULATION ON CONDUCTORS TO BE THHN UNLESS NOTED OTHERWISE. ØA ØB ØC TOTALSINSULATION ON ALL UNDERGROUND EXTERIOR CONDUCTORS SHALL BE THHW. 3,410 6,935 7,531 17,876 CONNECTED LOAD (VA)
2. LOAD DEMANDS CALCULATED AS PER SECTIONS 210 & 220 OF THE NATIONAL 50 CONNECTED LOAD (A)ELECTRICAL CODE. 238 325 0 563 DEMAND FACTOR ADJUSTMENTS (VA)
3. PANEL COVER SHALL BE FIELD MARKED FOR FLASH PROTECTION WITH A PERMANENT LABEL 3,648 7,260 7,531 18,439 TOTAL LOAD (VA)AS REQUIRED BY THE NATIONAL ELECTRICAL CODE SECTION 110. LABEL SHALL READ: 30 60 63 TOTAL LOAD (A)"DANGER: POTENTIAL ARC FLASH HAZARD" 63 MAXIMUM LOAD (A)
4. ABBREVIATIONS: CO-CONVENIENCE OUTLET, RR-RESTROOM, (N)ORTH, (S)OUTH, 20% 39% 41% PHASE BALANCE(E)AST, (W)EST.
PANEL SCHEDULE "K1 SEC B"VOLTAGE: 208 Y/ 120 VOLTS BUS RATING (AMPS): 225 REMARKS: EXISTING GE PANEL. EXST= EXISTING, NEW= NEW, REU= RE-USE,
RED= RED COLORED.MOUNTING: RECESSED PHASE: 3 MAIN LUGS ONLYENCLOSURE: NEMA 1 WIRE: 4 MINIMUM EQUIPMENT RATING: 22,000 AMPS (RMS-SYM)
CIRCUIT BREAKERCIRCUIT NAME
FEEDER CKT. LOAD LOAD/PHASE (VA) CKT. LOAD FEEDERCIRCUIT NAME
CIRCUIT BREAKER
No. AMPS POLE MOD. C WIRE GRD DEMANDFACTOR WATTS ØA ØB ØC WATTS DEMAND
FACTOR GRD WIRE C MOD. POLE AMPS No.
1 40 2 EXST EXISTING 1.00 0 1.00 EXISTING EXST 2 20 23 - - EXST - - - 1.00 0 1.00 - - - EXST - - 45 40 2 EXST EXISTING 1.00 0 1.00 EXISTING EXST 2 30 67 - - EXST - - - 1.00 0 1.00 - - - EXST - - 89 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 1011 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 1213 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 1415 20 1 EXST DINING LIGHTING ¾" #12 #12 1.25 1,850 1,850 1.00 EXISTING EXST 1 20 1617 20 1 EXST DINING LIGHTING ¾" #12 #12 1.25 1,500 2,220 720 1.00 #12 #12 ¾" RESTROOM CO EXST 1 20 1819 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2021 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 2223 20 1 EXST EXISTING 1.00 1,872 1,872 1.00 #12 #12 ¾" SSP-1 NEW 1 20 2425 20 1 EXST EXISTING 1.00 1,440 1,440 1.00 #12 #12 ¾" POS TERMINALS NEW 1 20 2627 20 1 EXST FRONT POS TERMINAL ¾" #12 #12 1.00 360 2,160 1,800 1.00 #12 #12 ¾" CBS-2 NEW 1 20 2829 20 1 EXST EXISTING 1.00 3,600 3,600 1.00 #10 #8 ¾" CBS-1 NEW 1 40 3031 20 1 EXST EXISTING 1.00 1,080 1,080 1.00 #12 #12 ¾" CG-1 NEW 1 20 3233 30 3 EXST EXISTING 1.00 1,800 1,800 1.00 #12 #12 ¾" FMD-1 NEW 1 20 3435 - - EXST - - - 1.00 1,056 1,056 1.00 #12 #12 ¾" SSP-2 NEW 1 20 3637 - - EXST - - - 1.00 2,160 2,160 1.00 #10 #10 ¾" R2 & CO NEW 1 30 3839 20 1 - EF-1 ¾" #12 #12 1.00 240 240 1.00 SPACE NEW 4041 - SPACE 1.00 0 1.00 SPACE NEW 42
NOTES :1. ALL INSULATION ON CONDUCTORS TO BE THHN UNLESS NOTED OTHERWISE. ØA ØB ØC TOTALS
INSULATION ON ALL UNDERGROUND EXTERIOR CONDUCTORS SHALL BE THHW. 4,680 6,050 8,748 19,478 CONNECTED LOAD (VA)2. LOAD DEMANDS CALCULATED AS PER SECTIONS 210 & 220 OF THE NATIONAL 54 CONNECTED LOAD (A)
ELECTRICAL CODE. 0 463 375 838 DEMAND FACTOR ADJUSTMENTS (VA)3. PANEL COVER SHALL BE FIELD MARKED FOR FLASH PROTECTION WITH A PERMANENT LABEL 4,680 6,513 9,123 20,316 TOTAL LOAD (VA)
AS REQUIRED BY THE NATIONAL ELECTRICAL CODE SECTION 110. LABEL SHALL READ: 39 54 76 TOTAL LOAD (A)"DANGER: POTENTIAL ARC FLASH HAZARD" 76 MAXIMUM LOAD (A)
4. ABBREVIATIONS: CO-CONVENIENCE OUTLET, RR-RESTROOM, (N)ORTH, (S)OUTH, 23% 32% 45% PHASE BALANCE(E)AST, (W)EST.
PANEL SCHEDULE "K2"VOLTAGE: 208 Y/ 120 VOLTS BUS RATING (AMPS): 225 REMARKS: EXISTING GE PANEL. EXST= EXISTING, NEW= NEW, REU= RE-USE,
RED= RED COLORED.MOUNTING: RECESSED PHASE: 3 MAIN LUGS ONLYENCLOSURE: NEMA 1 WIRE: 4 MINIMUM EQUIPMENT RATING: 22,000 AMPS (RMS-SYM)
CIRCUIT BREAKERCIRCUIT NAME
FEEDER CKT. LOAD LOAD/PHASE (VA) CKT. LOAD FEEDERCIRCUIT NAME
CIRCUIT BREAKER
No. AMPS POLE MOD. C WIRE GRD DEMANDFACTOR WATTS ØA ØB ØC WATTS DEMAND
FACTOR GRD WIRE C MOD. POLE AMPS No.
1 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 1 20 23 20 1 EXST GAS GRIDDLE CO ¾" #12 #12 1.00 180 180 1.00 EXISTING EXST 3 30 45 20 1 EXST EXISTING 1.00 0 1.00 - - - EXST - - 67 20 1 EXST EXISTING 1.00 0 1.00 - - - EXST - - 89 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 3 70 1011 20 1 EXST EXISTING 1.00 0 1.00 - - - EXST - 1213 20 1 EXST FRZ-1 ¾" #12 #12 1.00 1,260 1,260 1.00 - - - EXST - - 1415 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 3 50 1617 20 1 EXST EXISTING 1.00 0 1.00 - - - EXST - - 1819 20 1 EXST EXISTING 1.00 0 1.00 - - - EXST - - 2021 20 1 EXST EXISTING 1.00 1,803 1,803 1.00 #10 #8 ¾" DISHWASHER BOOSTER EXST 3 40 2223 20 1 EXST EXISTING 1.00 1,803 1,803 1.00 - #8 - - EXST - - 2425 20 1 EXST EXISTING 1.00 1,803 1,803 1.00 - #8 - - EXST - - 2627 20 1 EXST EXISTING 1.00 0 1.00 EXISTING EXST 2 40 2829 30 2 EXST EXISTING 1.00 0 1.00 - - - EXST - - 3031 - - EXST - 1.00 0 1.00 EXISTING EXST 2 40 3233 30 2 EXST EXISTING 1.00 0 1.00 - - - EXST - - 3435 - - EXST - 1.00 0 1.00 EXISTING EXST 3 40 3637 20 1 - CO-1 ¾" #12 #12 1.00 1,260 1,260 1.00 - - - EXST - - 3839 - SPACE 1.00 0 1.00 - - - EXST - - 4041 - SPACE 1.00 0 1.00 EXISTING EXST 1 20 42
NOTES :1. ALL INSULATION ON CONDUCTORS TO BE THHN UNLESS NOTED OTHERWISE. ØA ØB ØC TOTALS
INSULATION ON ALL UNDERGROUND EXTERIOR CONDUCTORS SHALL BE THHW. 4,323 1,983 1,803 8,108 CONNECTED LOAD (VA)2. LOAD DEMANDS CALCULATED AS PER SECTIONS 210 & 220 OF THE NATIONAL 23 CONNECTED LOAD (A)
ELECTRICAL CODE. 0 0 0 0 DEMAND FACTOR ADJUSTMENTS (VA)3. PANEL COVER SHALL BE FIELD MARKED FOR FLASH PROTECTION WITH A PERMANENT LABEL 4,323 1,983 1,803 8,108 TOTAL LOAD (VA)
AS REQUIRED BY THE NATIONAL ELECTRICAL CODE SECTION 110. LABEL SHALL READ: 36 17 15 TOTAL LOAD (A)"DANGER: POTENTIAL ARC FLASH HAZARD" 36 MAXIMUM LOAD (A)
4. ABBREVIATIONS: CO-CONVENIENCE OUTLET, RR-RESTROOM, (N)ORTH, (S)OUTH, 53% 24% 22% PHASE BALANCE(E)AST, (W)EST.
KITCHEN EQUIPMENT SCHEDULESYMBOL DESCRIPTION
SERVICE DISCONNECT LOADREMARKS
VOLTS PHASE SIZE NEMA VA AMPSCBS
1CURTIS COFFEE
BREWER 120 V 1Ø PLUG/CORD - 3,600 30.0 A
CBS2
CURTIS COFFEEBREWER 120 V 1Ø PLUG/
CORD 5-15P 1,800 15.0 A
CG1
COFFEEGRINDER 120 V 1Ø PLUG/
CORD - 1,080 9.0 A
UC1
KELVINATORREFRIGERATOR 120 V 1Ø PLUG/
CORD 5-15P 708 5.9 A UNDER COUNTER REFRIGERATOR
SL1
EDGESLICER 120 V 1Ø PLUG/
CORD - 1,800 15.0 A EXISTING SLICER. FIELD VERIFY ALL REQUIREMENTS AND CONDITIONS.
SSP1
SALAD SANDWICHPREP 120 V 1Ø PLUG/
CORD 5-15P 936 7.8 A 12 CU' SALAD SANDWICH PREP TABLE
SSP2
SALAD SANDWICHPREP 120 V 1Ø PLUG/
CORD 5-15P 1,056 8.8 A 18 CU' SALAD SANDWICH PREP TABLE
CO1
CONVECTIONOVEN 120 V 1Ø PLUG/
CORD 5-15P 948 7.9 A SOUTHBEND CONVECTION OVEN
FMD1
BUNN DRINKDISPENSER 120 V 1Ø PLUG/
CORD - 1,800 15.0 A
BR1 ELECTRIC BROILER 208 V 1Ø CIRCUIT
BREAKER - 5,990 28.8 A 36" ELECTRIC BROILER
R2 RANGE 120 V 1Ø PLUG/
CORD - 708 5.9 A 60" SOUTHBEND RANGE
REF1 REFRIGERATOR 120 V 1Ø PLUG/
CORD 5-15P 888 7.4 A KELVINATOR REACH IN FRIDGE
FRZ1 FREEZER 120 V 1Ø PLUG/
CORD 5-20P 1,260 10.5 A KELVINATOR REACH IN FREEZER
DD1 DRINK DISPENSER 120 V 1Ø PLUG/
CORD - 1,200 10.0 A PROVIDED BY VENDOR. FIELD VERIFY ALL REQUIREMENTS.
ICE1
DRINK DISPENSERMOUNTED ICE MAKER 120 V 1Ø PLUG/
CORD - 1,440 12.0 A PROVIDED BY VENDOR. FIELD VERIFY ALL REQUIREMENTS.
ICE2
DRINK DISPENSERMOUNTED ICE MAKER 120 V 1Ø PLUG/
CORD - 1,800 15.0 A EXISTING ICE DISPENSER. FIELD VERIFY ALL REQUIREMENTS AND CONDITIONS.
NOTES:1. VERIFY ALL EQUIPMENT LOCATIONS AND CONNECTION REQUIREMENTS (i.e. VOLTAGE, PHASE, FLA, ETC.) WITH KITCHEN DRAWINGS/SUBMITTALS BEFORE FOR ACTUAL EQUIPMENT INSTALLED.2. ALL FUSES SHALL BE DUAL ELEMENT TIME DELAY. FINAL BREAKER/FUSE & DISCONNECT SIZE SHALL BE DETERMINED BY MANUFACTURER'S RECOMMENDATION FOR ACTUAL EQUIPMENT INSTALLED.3. MAXIMUM VALUES INDICATED.4. DISCONNECTING MEANS NOT REQUIRED FOR EQUIPMENT WITHIN SIGHT (AS DEFINED IN NEC) OF BRANCH PANEL SERVING EQUIPMENT. SEE NEC 422.31 (B).5. DISCONNECTING MEANS NOT REQUIRED FOR APPLIANCES NOT OVER 300 VA. SEE NEC 422.31 (A).
ELECTRICAL GENERAL NOTES:
EQUIPMENT SCHEDULESYMBOL DESCRIPTION
SERVICE DISCONNECTSTARTER
LOADREMARKS
VOLTS PHASE SIZE FUSE HP/TON VA AMPSEF1 EXHAUST FAN 120 V 1Ø INTEGRAL
PLUG - - FRAC 240 2.0 A EF CONTROLLED BY 24-HR TIMER
NOTES:1. VERIFY ALL EQUIPMENT LOCATIONS AND CONNECTION REQUIREMENTS (i.e. VOLTAGE, PHASE, FLA, ETC.) WITH MECHANICAL DRAWINGS/SUBMITTALS BEFORE FOR ACTUAL EQUIPMENT INSTALLED.2. ALL FUSES SHALL BE DUAL ELEMENT TIME DELAY. FINAL BREAKER/FUSE & DISCONNECT SIZE SHALL BE DETERMINED BY MANUFACTURER'S RECOMMENDATION FOR ACTUAL EQUIPMENT INSTALLED.3. MAXIMUM VALUES INDICATED.4. DISCONNECTING MEANS NOT REQUIRED FOR EQUIPMENT WITHIN SIGHT (AS DEFINED IN NEC) OF BRANCH PANEL SERVING EQUIPMENT. SEE NEC 422.31 (B).5. DISCONNECTING MEANS NOT REQUIRED FOR APPLIANCES NOT OVER 300 VA. SEE NEC 422.31 (A).
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
2.2THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
SCH
EDU
LES
LIGHT FIXTURE SCHEDULEFIXTURE FIXTURE FIXTURE LAMPS FIXTURE DESCRIPTION REMARKSNUMBER MANUFACTURER CATALOG # TYPE QTY. VOLTS WATTS MOUNTING
F1
LSIMETALUXCOLUMBIADAYBRITEORACLE
LITHONIAHE WILLIAMS
WNA10-LED-SS-WW-UEWNLED-LD1-41-UNV-L835-CD1-U
LWC4-35LW-ED-UOWL-4-40L-835-UNIV-DIM
4-OIW-LED-3400L-DIM10-MVOLT-35K-80LBL4-30L-EZ1-LP835
17-4-L27-/835-A-DIM-UNV
LED - 120 48 SURFACECEILING
1X4 SURFACE LED (~2F32)
F2-EM
LSIMETALUX
VISIONEERINGDAYBRITEORACLE
LITHONIADECO
W444-LED-SS-WW-UE-EM4BCLED-LD4-36SL-UNV-EL14W-L835-CD1-U
LCAD48-LED-8-35K-020L-UNV-B39CSW-48-28-35-UNV-DZT-ZO-EMLED
4-OW1B-LED-3000L-DIM10-MVOLT-35K-80-O-EMG-LEDWL4-30L-EZ1-L835-EL7L
DSBL-LED-SD-4-35-UNV-PA-EM
LED - 120 37 SURFACEWALL
48" WALL MTD. LED (~1F32)
T1 - EXISTING TRACK LIGHTING - - 120 600 CEILING EXISTING 8' TRACK SECTIONS AND ACCOMPANYINGTRACK HEADS
TRACK LIGHTING FIGURED AT 75W PER FT AS PERNEC 220.43 (B)
T2 - EXISTING TRACK LIGHTING - - 120 300 CEILING EXISTING 4' TRACK SECTIONS AND ACCOMPANYINGTRACK HEADS
TRACK LIGHTING FIGURED AT 75W PER FT AS PERNEC 220.43 (B)
F3 - OWNER SPECIFIED PENDANT - - 120 50 PENDANT PENDANT FIXTURE CHOSEN BY OWNER NOT TO EXCEED50W EACH
CHOSEN BY OWNER PROVIDED AND INSTALLED BYE.C. $300.00 CONTRACTOR ALLOWANCE.
F4
METALUXCOLUMBIA
LSIDAYBRITEORACLE
HE WILLIAMSLITHONIA
24GR-LD4-38-A125-UNV-L835-CD1-ULJT24-35LWG-FSA12125-ED-U
GA24-LED-SS-WW-UE-P122-T-G-48L-835-4-FS-02F-UNV-DIM
24-OT-LED-4000L-DIM10-MVOLT-35K-85-A12LPT24-L42/835-SA12125-DIM-UNV
2GTL-4-40L-EZ1-LP835
LED - 120 45 LAY-INGRID
2X4 LED LAYIN PRISMATIC FIXTURE (~2F32)
EM
LITHONIASURE-LITESMcPHILBENEXITRONIXDUAL-LITE
LIGHTOLIERLSI
MAXILUME
ELM2CC-6-WH
CT6LL-90EZ-2
E611WLTEM-WH
ELM-LED-861
INCLUDED 2 120 5.4 CEILING 2-HEAD EM WALL PACK (CEILING)
EX1
LITHONIASURE-LITESMcPHILBENLIGHTOLIEREXITRONIX
DECOLSI
MAXILUME
LHQM-S-1-G-EL-NLPX-70-DGWHDH
CCAXL-1-GWLC18NH71GW
GVEX-U-BP-WH-EL90DCLX-C-1-G
LPRX-G-U-WHELX-703-G-W
INCLUDED 2 120 5.4 SURFACEWALL
2-HEAD EM WALL PACK (SURFACE) WITH EXIT LIGHT
LIGHTING CONTROL PANEL "LCP" AUTOMATION SCHEDULE
MOUNTING: SURFACE LOCATION: NW CORNER NEAR FACP
Auto
ON
/ Aut
o OF
F
Man
ual O
N / A
uto
OFF
Dusk
- Da
wn
Dusk
- Au
to O
FF
Dayli
ght S
enso
r
BRANCH CIRCUIT FOR CONTROL POWER: K1A-8
SPACE RELAYSUPPLY VA LV SWITCH*
NUMBER AMP POLEAREA SERVED
1 20 1 K1A-8 950 WAITING AND DINING LIGHTING X
2 20 1 K1A-2 1,300 N DINING ROOM LIGHTING X
3 20 1 K1B-17 1,500 E DINING ROOM LIGHTING X
4 20 1 K1B-15 1,850 S DINING ROOM LIGHTING X
* SEE PLAN FOR LOCATION OF LOW VOLTAGE SWITCH
NOTE: ELECTRICAL CONTRACTOR TO PROVIDE SPACE IN THIS PANEL FOR FUTURE EXPANSION
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
2.3THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
DET
AIL
S
ELECTRICAL SYMBOLSCOPPER FEEDER SCHEDULE
EQUIPMENT GROUNDING CONDUCTORSSCHEDULE
EXISTING PARTIAL POWER ONE-LINE
KEYED NOTE:
COMMUNICATIONS RISER DIAGRAM
EST FIRE
FIRE ALARM RISER DIAGRAM
NOTE:
EXISTING
SHIELDFACP
KEYED NOTE: PARTIAL INTERLOCK DIAGRAM
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
2.4THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
DET
AIL
S
MOTION SENSOR WITH LV SWITCH
WALL PENETRATION FLOOR PENETRATION
FIRE RATED PENETRATION DETAILTYPICAL RECESSED FIXTURE MOUNTING DETAIL
ELECTRICAL DEVICE MOUNTING HEIGHTS INSTALLATION DETAILTYPICAL ROUGH-IN REQUIREMENTS DETAIL FOR MC CABLE
ELECTRICAL KEYED NOTES:
ELECTRICAL GENERAL NOTES:
KEYED NOTES:
ELECTRICAL EQUIPMENT WORK SPACE CLEARANCES
GENERAL NOTE:
ELECTRICAL GENERAL NOTES:
DATA/VOICE JACK INSTALLATION DETAIL
PASK
ER G
OU
LD A
MES
& W
EAV
ER
ARCHITECTS / PLANNERS
A NE
W T
ENAN
T IM
PRO
VEM
ENT
FOR:
PENN
Y AN
N'S
R
DE
S
T
IG
RE
SET
AF UET
OA T
L
H
AE
PR FO ISS NO
NE
REENG
I
2.5THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THEINFORMATION CONTAINED HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITHROYAL ENGINEERING'S INTERPRETATIONS, DECISIONS, OBSERVATIONS ANDADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN WHOLE OR INPART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR.511 (1991). WHICH PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT17 U.S.C. PAR. 301 (1991).
COPYRIGHT© JOB# DATE PLOTTED: 03/02/2016J16041.00
E
SPEC
IFIC
ATI
ON
S
ELECTRICAL SPECIFICATIONS
GENERAL PROVISIONA. REFERENCE
1. THE GENERAL CONDITIONS AND OTHER CONTRACT DRAWINGS AS SET FORTH IN THE FOREGOING PAGES ARE HEREBY INCORPORATED INTO ANDBECOME A PART OF THE SPECIFICATIONS FOR WORK UNDER THIS TITLE, INSOFAR AS THEY APPLY HERETO.
2. ALL SPECIFICATIONS UNDER THIS DIVISION TITLE ARE DIRECTED TO AND ARE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, UNLESS OTHERTRADES OR PERSONS ARE SPECIFICALLY MENTIONED, “ELECTRICAL CONTRACTOR” IS INFERRED AND INTENDED.
B. CONTRACT DRAWINGS1. THE DRAWINGS ACCOMPANYING THESE SPECIFICATIONS ARE COMPLEMENTARY EACH TO THE OTHER AND WHAT IS CALLED FOR BY ONE SHALL BE AS
IF CALLED FOR BY BOTH.2. CONSULT ALL CONTRACT DRAWINGS WHICH MAY AFFECT THE LOCATION OF EQUIPMENT, CONDUIT AND WIRING AND MAKE MINOR ADJUSTMENTS IN
LOCATION TO SECURE COORDINATION.3. WIRING LAYOUT IS SCHEMATIC AND EXACT LOCATIONS SHALL BE DETERMINED BY FIELD CONDITIONS.4. OTHER THAN MINOR ADJUSTMENTS SHALL BE SUBMITTED TO THE OWNER'S REPRESENTATIVE FOR APPROVAL BEFORE PROCEEDING WITH THE WORK.
C. JOB-SITE COPY OF DOCUMENTS1. MAINTAIN AT THE SITE, ONE COPY OF ALL DRAWINGS, SPECIFICATIONS, ADDENDA APPROVED SHOP DRAWINGS, CHANGE ORDERS AND OTHER
MODIFICATIONS, IN GOOD ORDER AND MARKED TO RECORD ALL CHANGES MADE DURING CONSTRUCTION. THESE SHALL BE AVAILABLE TO THEOWNER'S REPRESENTATIVE. THE DRAWINGS MARKED TO RECORD ALL CHANGES MADE DURING CONSTRUCTION SHALL BE DELIVERED TO THEOWNER'S REPRESENTATIVE FOR THE OWNER UPON COMPLETION OF THE WORK. AN ADDITIONAL SET OF DRAWINGS WILL BE FURNISHED BY THEOWNER'S REPRESENTATIVE FOR THIS PURPOSE UPON REQUEST.
D. MANUFACTURER'S DRAWINGS1. THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT FOR REVIEW. (6) COPIES OF MANUFACTURER'S DRAWINGS AND WIRING DIAGRAMS. THE
ENGINEER WILL REVIEW CONTRACTOR'S SHOP DRAWINGS AND RELATED SUBMITTALS (AS INDICATED BELOW) WITH RESPECT TO THE ABILITY OF THEDETAILED WORK, WHEN COMPLETE, TO BE A PROPERLY FUNCTIONING INTEGRAL ELEMENT OF THE OVERALL SYSTEM DESIGNED BY THE ENGINEER.BEFORE SUBMITTING A SHOP DRAWING OR ANY RELATED MATERIAL TO THE ENGINEER, CONTRACTOR SHALL: REVIEW EACH SUCH SUBMISSION FORCONFORMANCE WITH THE MEANS, METHODS, TECHNIQUES, SEQUENCES, AND OPERATIONS OF CONSTRUCTION, AND SAFETY PRECAUTIONS ANDPROGRAMS INCIDENTAL THERETO, ALL OF WHICH ARE THE SOLE RESPONSIBILITY OF CONTRACTOR: APPROVE EACH SUCH SUBMISSION BEFORESUBMITTING IT; AND SO STAMP EACH SUCH SUBMISSION BEFORE SUBMITTING IT. THE ENGINEER SHALL ASSUME THAT NO SHOP DRAWING OR RELATEDSUBMITTAL COMPRISES A VARIATION UNLESS CONTRACTOR ADVISES ENGINEER OTHERWISE VIA A WRITTEN INSTRUMENT WHICH IS ACKNOWLEDGEDBY ENGINEER IN WRITING. THE ITEMS, TYPES OF SUBMITTALS AND RELATED MATERIAL (IF ANY) CALLED FOR ARE INDICATED BELOW:
ITEMS TYPE SUBMITTALS REQUESTEDLIGHTING FIXTURES CATALOG CUTS
E. GUARANTEES1. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEFECTS, REPAIRS AND REPLACEMENTS IN MATERIALS AND WORKMANSHIP FOR A
PERIOD OF ONE (1) YEAR AFTER DATE OF SUBSTANTIAL COMPLETION AS DETERMINED BY THE OWNER'S REPRESENTATIVE. PRODUCT GUARANTEESGREATER THAN ONE (1) YEAR SHALL BE PASSED ALONG TO THE OWNER FOR FULL BENEFIT OF THE MANUFACTURER'S WARRANTY.
DEMOLITIONA. DESCRIPTION OF WORK
1. ALL RELOCATIONS, RECONNECTIONS AND REMOVALS ARE NOT NECESSARILY INDICATED ON DRAWINGS. ALL SUCH REQUIRED WORK SHALL BEINCLUDED WITHOUT ADDITIONAL COST TO OWNER. OTHER DEMOLITION WORK SHALL BE PERFORMED AS REQUIRED TO MAINTAIN SYSTEM OPERATION.
2. THE INTENT OF THE DRAWINGS IS NOT TO SHOW EVERY DEVICE, OUTLET, FIXTURE, CONDUIT, ETC. AFFECTED BY DEMOLITION WORK.3. THE DRAWINGS DO NOT NECESSARILY REFLECT AS-BUILT CONDITIONS. THE CONTRACTOR SHALL VISIT THE JOBSITE PRIOR TO BIDDING TO
DETERMINE THE OVERALL SCOPE OF DEMOLITION WORK.4. REFER TO SECTIONS OF OTHER DIVISIONS FOR APPLICABLE REQUIREMENTS AFFECTING DEMOLITION WORK.
B. GENERAL1. DEMOLITION WORK SHALL BE LAID OUT IN ADVANCE TO ELIMINATE UNNECESSARY CUTTING, DRILLING, CHANNELING, ETC. WHERE SUCH CUTTING,
DRILLING, OR CHANNELING BECOMES NECESSARY, PERFORM WITH CARE, USE SKILLED MECHANICS OF THE TRADES INVOLVED. REPAIR DAMAGE TOBUILDING AND EQUIPMENT. CUTTING WORK OF OTHER CONTRACTORS SHALL BE DONE ONLY WITH THE CONSENT OF THAT CONTRACTOR. CUTTING OFSTRUCTURAL MEMBERS SHALL NOT BE PERMITTED.
C. PATCHING AND REPAIR1. THE CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION, PATCHING AND REPAIR OF ALL FINISHED INTERIOR SURFACES PERTAINING TO THE
INSTALLATION OF THIS PARTICULAR PHASE OF WORK. ALL SURFACES SHALL BE FINISHED (PAINTED, ETC.) TO MATCH THE ADJACENT MATERIALS,FINISHES AND COLORS.
2. HARD SURFACES: WHENEVER DEMOLITION OR EXCAVATION IS REQUIRED FOR THE INSTALLATION OF THEELECTRICAL SYSTEM, IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO MAKE REPAIRS AND/ORREPLACEMENTS OF HARD FINISH SURFACES SUCH AS CONCRETE, ASPHALT, ETC.
3. THE METHOD OF PATCHING AND REPAIR SHALL FOLLOW GOOD CONSTRUCTION PRACTICES AND ALL FINISHED SURFACES SHALL MATCH MATERIALSAND FINISH WHEREIN THE DEMOLITION OCCURRED.
D. EXISTING EQUIPMENT:1. THE NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE EXISTING SYSTEM AS REQUIRED. AUXILIARY
SYSTEMS SHALL COMPLY, UNLESS OTHERWISE SPECIFIED.2. THE EXISTING ELECTRICAL DEVICES, CONDUIT AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED.
PROVIDE CONDUIT, WIRING, JUNCTION BOXES, ETC. AS REQUIRED TO EXTEND EXISTING CIRCUITS AND SYSTEMS TO RELOCATED DEVICES OREQUIPMENT.
3. THE NEW FIXTURES INDICATED FOR EXISTING OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH THE FIXTURE SPECIFICATIONS.4. WHEN INSTALLING EQUIPMENT IN THE EXISTING BUILDING, IT SHALL BE CONCEALED.5. EXISTING RACEWAYS SHALL BE USED WHERE POSSIBLE, EXCEPT AS NOTED. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT USED IN THE
REMODELED AREA SHALL BE CAREFULLY REMOVED, AND TURNED OVER TO THE OWNER. THOSE FIXTURES INDICATED FOR RE-USE SHALL BETHOROUGHLY CLEANED, REPAIRED AS REQUIRED, RELAMPED AND INSTALLED AS INDICATED.
6. OBTAIN PERMISSION FROM THE ARCHITECT AND OWNER'S REPRESENTATIVE BEFORE PENETRATING ANY CEILING, FLOOR, AND WALL SURFACES.
WORK INCLUDEDA. INSTALLATION, MATERIALS, AND WORKMANSHIP
1. FURNISH AND INSTALL ALL NECESSARY ANCHORS, SUPPORTS, STRAPS, BOXES, FITTINGS AND OTHER SIMILAR APPURTENANCES NOT INDICATED ONTHE DRAWINGS BUT WHICH ARE REQUIRED FOR A COMPLETE AND PROPERLY INSTALLED SYSTEM CONSISTENT WITH THE ARCHITECTURALTREATMENT OF THE BUILDING.
2. THE ELECTRICAL CONTRACTOR, INSOFAR AS THE WORK IS CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT AND ORDERLYCONDITION. AND AT THE COMPLETION OF THE WORK, SHALL PROPERLY CLEAN UP AND CART AWAY DEBRIS AND EXCESS MATERIALS. ELECTRICALCONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF DUMPSTER & REFUSED DISPOSAL AS REQUIRED FOR ELECTRICAL WORK.
3. ALL MATERIALS SHALL BE NEW AND UNDETERIORATED AND OF A QUALITY NOT LESS THAN THE MINIMUM SPECIFIED.B. COORDINATION OF PLANS AND SPECIFICATIONS
1. CONTACT THE OWNER'S REPRESENTATIVE IMMEDIATELY IF THERE IS ANY QUESTIONS REGARDING THE MEANING OR INTENT OF EITHER PLANS ORSPECIFICATIONS, OR UPON NOTICING ANY DISCREPANCIES OR OMISSIONS IN EITHER PLANS OR SPECIFICATIONS.
C. CUTTING AND PATCHING1. ALL ELECTRICAL EQUIPMENT SHALL BE KEPT DRY AND CLEAN DURING THE CONSTRUCTION PERIOD. INTERIOR OF ALL ENCLOSURES SHALL BE
CLEANED OF DIRT AND DEBRIS BEFORE INSTALLING TRIM OR COVERS.2. ALL FINISHED SURFACES OF EQUIPMENT FURNISHED UNDER THIS CONTRACT SHALL BE THOROUGHLY CLEANED OF DIRT AND ALL SCRATCHED OR
DAMAGED SURFACES SHALL BE TOUCHED UP WITH MATCHING MATERIALS BEFORE FINAL ACCEPTANCE OF THE WORK.3. WHEN ALL WORK IS COMPLETED AND ALL WORK HAS BEEN SATISFACTORILY TESTED AND ACCEPTED BY THE OWNER'S REPRESENTATIVE, ALL
CONDUIT AND OTHER EXPOSED SURFACES SHALL BE THOROUGHLY CLEANED.
CODES AND FEESA. CODES:
1. ALL WORK PERFORMED UNDER THIS SPECIFICATION SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODEAS PREPARED AND PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION AND ANY APPLICABLE STATE OR LOCAL CODES.
B. FEES:1. OBTAIN AND PAY FOR ANY AND ALL PERMITS REQUIRED BY ALL LAWS AND REGULATIONS AND PUBLIC AUTHORITY HAVING SUCH JURISDICTION.
TESTS AND INSPECTIONSA. OBTAIN ALL INSPECTIONS REQUIRED BY ALL LAWS, ORDINANCES, RULES, REGULATIONS OR PUBLIC AUTHORITY HAVING JURISDICTION AND OBTAIN
CERTIFICATES OF SUCH INSPECTIONS AND SUBMIT SAME TO THE OWNER'S REPRESENTATIVE. PAY ALL FEES, CHARGES AND OTHER EXPENSES INCONNECTION THEREIN. OBTAIN OCCUPANCY PERMIT AS REQUIRED BY OWNER. FINAL PAYMENT SHALL NOT BE MADE UNTIL OCCUPANCY PERMIT ISOBTAINED.
B. WORK SHALL BE UNACCEPTABLE WHEN FOUND TO BE DEFECTIVE OR CONTRARY TO THE PLANS SPECIFICATIONS, CODES SPECIFIED OR ACCEPTEDSTANDARDS OF GOOD WORKMANSHIP.
C. THE CONTRACTOR SHALL PROMPTLY CORRECT ALL WORK FOUND UNACCEPTABLE BY THE OWNER'S REPRESENTATIVE WHETHER OBSERVED BEFORE ORAFTER SUBSTANTIAL COMPLETION AND WHETHER OR NOT FABRICATED, INSTALLED OR COMPLETED. THE CONTRACTOR SHALL BEAR ALL COSTS OFCORRECTING SUCH UNACCEPTABLE WORK, INCLUDING COMPENSATION FOR THE OWNERS REPRESENTATIVE ADDITIONAL SERVICES MADE NECESSARYTHEREBY.
CONDUITA. FURNISH AND INSTALL ALL CONDUITS, BOXES, FITTINGS, ETC., FOR A COMPLETE RACEWAY SYSTEM.B. ALL WIRING SHALL BE RUN IN EMT CONDUIT OR MC CABLE WITH GROUND CONDUCTOR UNLESS OTHERWISE NOTED.C. ALL CONDUIT SIZES STATED HEREIN OR MARKED ON THE DRAWINGS ARE MINIMUM SIZE AND SHALL BE NO LESS THAN 12" UNLESS OTHERWISE NOTED.D. ALL CONDUIT SHALL BE SUBSTANTIALLY SUPPORTED BY PIPE STRAPS OR SUITABLE CLAMPS OR HANGERS ATTACHED TO THE ELEMENTS OF THE BUILDING
STRUCTURE TO PROVIDE RIGID INSTALLATION; IN NO CASE SHALL CONDUIT BE ATTACHED OR SUPPORTED FROM ADJOINING PIPE OR INSTALLED IN SUCH AMANNER AS TO PREVENT THE READY REMOVAL OF OTHER PIPE FOR REPAIRS.
WIRE AND CABLEA. ALL CONDUCTORS SHALL BE COPPER AND OF THE AWG SIZE AND TYPE SHOWN ON THE DRAWINGS. WHERE NO SIZE OR TYPE IS SHOWN. CONDUCTORS
SHALL NOT BE LESS THAN #12 TYPE XHHW, THHN, OR THWN. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED COPPER AND HAVE 600 VOLTINSULATION; BE UL LABELED AND OF AMERICAN MANUFACTURER.
B. ALL CONNECTIONS ARE TO BE MADE USING PRESSURE TYPE TERMINALS.C. THE FOLLOWING COLOR CODE SHALL BE USED:
120/240 VOLT 120/208 VOLT 277/480 VOLTPHASE A BLACK BLACK BROWNPHASE B RED RED ORANGEPHASE C BLUE YELLOWNEUTRAL WHITE WHITE WHITEGROUND GREEN GREEN GREEN
D. CONDUCTORS NO. 10 AWG OR SMALLER SHALL HAVE INSULATION COLORED AS NOTED ABOVE.E. CONDUCTORS NO. 8 AWG OR LARGER SHALL HAVE INSULATION COLORED AS NOTED ABOVE OR COLORED TAPE, MINIMUM SIZE 12'', WRAPPED TWICE
AROUND AT THE FOLLOWING POINTS:1. AT EACH TERMINAL2. AT EACH CONDUIT ENTRANCE3. AT INTERVALS NOT MORE THAN 12 INCHES APART IN ALL BOXES, PANEL TUBS, SWITCHBOARDS, ETC
F. ALL BRANCH CIRCUITS SHALL BE MARKED IN THE PANEL BOARD GUTTERS. MARKERS SHALL INDICATE CORRESPONDING BRANCH--CIRCUIT NUMBERS.G. EACH BRANCH CIRCUIT REQUIRING A NEUTRAL SHALL BE FURNISHED WITH A SEPARATE INDIVIDUAL NEUTRAL CONDUCTOR.
BOXES AND PLATESA. FURNISH AND INSTALL ALL OUTLET, JUNCTION, AND PULL BOXES AS INDICATED ON THE DRAWINGS AND AS NECESSARY TO INSTALL THE REQUIRED
CONDUIT AND WIRING IN A NEAT AND WORKMANLIKE MANNER.B. PULL BOXES AND JUNCTION BOXES SHALL BE GALVANIZED AND OF THE CORRECT SIZE AND GAUGE, SIZED IN ACCORDANCE WITH CODE REQUIREMENTS
AND SHALL BE U.L. LABELED.C. BOXES AT EXTERIOR AREAS TO BE WATERTIGHT AND DUST-TIGHT WITH GASKETED COVERS.
D. ALL BOXES FOR EXPOSED WORK IN FINISHED SPACES SHALL BE ''FS'' TYPE WITH THREADED HUBS WITH RIGID CONDUIT RISER (DEEP WIRE MOLD BOXES)E. ALL BOXES SHALL BE RIGIDLY SUPPORTED INDEPENDENT OF THE CONDUIT SYSTEM. BOXES CAST INTO MASONRY OR CONCRETE ARE CONSIDERED TO BE
RIGIDLY SUPPORTED.
WIRING DEVICESA. WIRING DEVICES SHALL BE SIMILAR TO THOSE LISTED BELOW AND OF SPECIFIED AMPERAGE. OTHER SPECIAL PURPOSE DEVICES SHALL BE AS SPECIFIED
ON THE DRAWINGS.B. DUPLEX GROUNDING TYPE RECEPTACLE--20 AMP, 125 VOLT--
1. HUBBELL--53522. ARROW HART--5352
C. SINGLE POLE SWITCHES - 20 AMP, 120 VOLTD. WEATHERPROOF RECEPTACLES - 20 AMP, 125 VOLT--NEMA 5--20R
1. HUBBELL--5352 WITH 5205 COVER INTERMATIC GUARDIAN2. I SERIES, NEMA 3R COVER3. ARROW HART--5352 WITH 4500 COVER
E. G.F.C.I. RECEPTACLE- 20 AMP, 125 VOLT--NEMA 5-20 R1. HUBBELL- GF 5262 WITH MATCHING NYLON COVER PLATE OR WO-26 W.P. COVER
F. GROUND ALL RECEPTACLES IN ACCORDANCE WITH ARTICLE 250-146 OF NEC AND AS INDICATED IN THE GROUNDING SECTION OF THIS SPECIFICATION.
IDENTIFICATIONA. EACH PIECE OF SERVICE EQUIPMENT AND INDIVIDUAL SWITCHES, ALL DISCONNECTS, STARTERS, ALL EXHAUST FAN MANUAL STARTING SWITCHES.B. IDENTIFICATION SHALL BE IN THE FORM OF LAMINATED PLASTIC NAMEPLATES, BLACK RACE, WITH THE LETTERS ENGRAVED INTO THE WHITE
BACKGROUND, MINIMUM ¼'' HIGH. PLATES SHALL BE DRILLED ON EACH END FOR SHEET METAL SCREW ATTACHMENT. NO “DYMO” OR SIMILAR TYPE LABELSWILL BE ALLOWED.
C. PANEL BOARD DIRECTORY: A TYPED CIRCUIT DIRECTORY SHALL BE PROVIDED INDICATING LOCAL AREA SERVED AND LOCATION FOR EACH BRANCHCIRCUIT.
GROUNDINGA. ALL FEEDERS AND BRANCH CIRCUITS OVER 100 VOLTS SHALL INCLUDE A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC TABLE 250-122,
EXCEPT NOT BE SMALLER THAN #12 FOR POWER AND LIGHTING CIRCUITS AND #14 FOR CONTROL CIRCUITS. ALL GROUND CONDUCTORS SHALL BE GREEN,OR AS SPECIFIED UNDER “WIRE AND CABLE”.
B. ALL GROUND CLAMPS SHALL BE PENN-UNION “GPL” TYPE OR SIMILAR BY O.Z. OR BURNDY.C. CONDUIT FOR SOLITARY GROUND CONDUCTORS SHALL BE RIGID SCHEDULE 40 PVC NON- METALLIC ELECTRICAL CONDUIT WITH U.L. LABEL SOLITARY
GROUND CONDUCTORS SHALL NOT BE PLACED THROUGH METALLIC SLEEVES OR CONDUITS AND SHALL NOT BE COMPLETELY ENCIRCLED BY METALLICHANGERS OR SUPPORTS.
D. THE GROUND CONDUCTOR SHALL BE CONNECTED TO THE NEUTRAL IN ONLY TWO LOCATIONS -ON THE SUPPLY SIDE OF THE SERVICE DISCONNECT MEANSPER NEC--250--24 AND ON SEPARATELY DERIVED SYSTEMS PER NEC 250-30.
E. AT EACH RECEPTACLE BOX, THE GROUND CONDUCTOR SHALL ENTER AND CONNECT, WITH NORMAL WIRING CONNECTOR, TO: 1) THE GROUND PIGTAIL TORECEPTACLE: 2) THE GROUND PIGTAIL TO THE BOX GROUND SCREW; AND 3) THE OUTGOING GROUND CONDUCTOR TO NEXT DEVICE, IF NOT AT END OFRUN. METAL TO METAL CONTACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE AS A BOND FOR EITHER SURFACE. MOUNTEDBOXES OR FLUSH TYPE BOXES.
F. CONDUIT SYSTEM SHALL BE ELECTRICALLY CONTINUOUS. ALL LOCK NUTS SHALL CUT THROUGH ENAMELED OR PAINTED SURFACES ON ENCLOSURES.WHERE ENCLOSURES AND NON-CURRENT CARRYING METALS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVEDCLAMPS. WHERE REDUCING WASHERS ARE USED AND WHERE CONCENTRIC OR ECCENTRIC KNOCKOUTS ARE NOT COMPLETELY REMOVED BONDINGBUSHINGS SHALL BE REQUIRED.
INTERRUPTION OF SERVICE AND OWNER'S OPERATIONA. THE ELECTRICAL CONTRACTOR SHALL ORGANIZE HIS WORK SO THAT THESE ALTERATIONS AND ADDITIONS SHALL CAUSE A MINIMUM OF INTERFERENCE
AND DISTURBANCE TO THE OWNER. ARRANGEMENTS SHALL BE MADE WITH THE OWNER AND ENGINEER BEFORE INTERRUPTING SERVICE IN ANY AREA. AWRITTEN DETAILED METHOD OF INTERRUPTION PROCEDURE INDICATING ELAPSED TIME REQUIRED AND TIME OF INTERRUPTION SHALL BE PREPARED BYTHE ELECTRICAL CONTRACTOR AND SUBMITTED TO THE OWNER FOR APPROVAL.
B. ALL INTERRUPTIONS OF SERVICE SHALL BE MADE WHEN THE LOAD IS AT A MINIMUM AND SHALL BE SCHEDULED AT THE OWNER'S CONVENIENCE. (SERVICEINTERRUPTIONS WILL BE SCHEDULED FOR OTHER THAN NORMAL DAYTIME WORKING HOURS. THE ELECTRICAL CONTRACTOR SHALL INCLUDE NECESSARYCOST FOR OVERTIME LABOR IN ALL BIDS.)
C. AT NO TIME SHALL THE ELECTRICAL CONTRACTOR OR HIS EMPLOYEES NORMALLY WORKING ON THE PROJECT LEAVE THE FACILITY DURING A TIME WHENANY NORMALLY LIVE CIRCUITS OR FEEDERS ARE DISCONNECTED, WITHOUT PERMISSION OF THE ENGINEER.
D. ALL MATERIALS, CONNECTIONS AND EQUIPMENT FOR TEMPORARY CONTROL OR POWER WIRING TO MAINTAIN CONTINUITY OF SERVICE DURINGCONSTRUCTION SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
POWER AND LIGHTING PANELSA. FURNISH AND INSTALL, AS SCHEDULED AND SHOWN ON THE DRAWINGS, POWER PANELS FOR OPERATION ON VOLTAGES INDICATED.B. ALL TERMINATIONS SHALL BE MARKED “75°C ONLY”, “60/75° C” OR LISTED FOR USE OF 75° C INSULATED CONDUCTORS AT FULL 75° C AMPACITY.C. ALL BUS BARS SHALL BE SILVER OR TIN PLATED COPPER.D. CABINETS SHALL BE OF COMMERCIAL GALVANIZED SHEET STEEL, CODE GAUGE AND SIZE, SURFACE OR RECESSED MOUNTED AS CALLED FOR IN THE
DRAWINGS.E. NEUTRAL ASSEMBLY SHALL HAVE INDIVIDUAL ANTI-TURN SOLDERLESS TERMINALS, SIMILAR TO SQUARE D TYPE PK, FOR CONNECTION OF ULTIMATE
NUMBER OF NEUTRAL WIRES. SHEET METAL TERMINAL STRIPS AND CONNECTIONS WILL BE REJECTED.F. PANEL SHALL HAVE A COPPER GROUND BAR SIMILAR TO NEUTRAL BAR IN NUMBER, SIZE, AND TYPE OF ANTI-TURN SOLDERLESS LUGS. THIS GROUND BAR
SHALL BE FACTORY BONDED TO THE PANEL TUB IN THE GUTTER SPACE OPPOSITE THE MAINS AND THE NEUTRAL ASSEMBLY AND SHALL HAVE THESCREWDRIVER SLOTS FACING THE FRONT OF THE PANEL.
G. QUALITY STANDARD: SQUARE D TYPE NQOD
LIGHTING FIXTURESA. CONTRACTOR SHALL FURNISH AND INSTALL LIGHTING FIXTURES AS INDICATED IN FIXTURE SCHEDULE SHOWN ON DRAWINGS, AND SPECIFIED HEREIN.B. NEUTRAL ASSEMBLY SHALL HAVE INDIVIDUAL ANTI-TURN SOLDERLESS TERMINALS, SIMILAR TO SQUARE D TYPE PK, FOR CONNECTION OF ULTIMATE
NUMBER OF NEUTRAL WIRES. SHEET METAL TERMINAL STRIPS AND CONNECTIONS WILL BE REJECTED.C. ALL LAMP HOLDERS INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE FURNISHED COMPLETE WITH NEW LAMPS OF THE SIZE INDICATING ON THE
FIXTURE SCHEDULE.D. ANY FIXTURES SCRATCHED, BENT, CRACKED OR IN ANY WAY DAMAGED BEFORE ACCEPTANCE BY OWNER SHALL BE REPLACED AT THIS CONTRACTOR'S
EXPENSE.E. ALL FIXTURES SHALL BE IN WORKING ORDER AT THE TIME OF FINAL ACCEPTANCE OF THE WORK BY THE OWNER.F. ALL LIGHTING FIXTURES ARE TO BE GROUNDED ON THE INTERIOR OF THE FIXTURE HOUSING, ON CLEAN BARE METAL (FREE OF PAINT). BY USE OF PIGTAIL
AND FASTENED BY A SCREW USED FOR NO OTHER PURPOSE.G. PACKAGED BATTERY SYSTEMS
1. LIGHTING PACKSa. PROVIDE APPROPRIATE BALLAST FOR SIZE AND TYPE OF FIXTURE.b. BATTERY SHALL BE LONG LIFE NICKEL CADMIUM TYPE. CHARGER SHALL BE CAPABLE FULL RECHARGE IN 24 HOURS.e. UNIT SHALL BE COMPLETE WITH CHARGING INDICATOR LIGHT AND TEST SWITCH.
2. INSTALLATIONa. EMERGENCY LIGHTING PACK MAY REQUIRE REMOTE LOCATION. INSTALL WITH CHARGING INDICATOR LIGHT AND TEST SWITCH MOUNTED IN
JUNCTION BOX WITH COVERPLATE NEXT TO FIXTURE.b. WIRE SO UNIT CAN BE TESTED WITH LIGHTS ON.c. WIRE SO FIXTURES IN NORMAL MODE ARE SWITCHED OFF WITH OTHER LIGHTING IN AREA. CONNECT EMERGENCY LIGHTING UNIT TO UNSWITCHED
CONDUCTOR OF NORMAL LIGHTING CIRCUIT.
TELEPHONE/DATA SYSTEMSA. SUMMARY
1. INCLUDES BUT NOT LIMITED TOa. MODIFICATIONS TO BUILDING TELEPHONE AND COMPUTER NETWORK RACEWAY AND CABLE SYSTEM AS DESCRIBED IN CONTRACT DOCUMENTS
INCLUDING, BUT NOT LIMITED TO, RACEWAY, OUTLETS, MODULAR JACKS, DEVICE PLATES, CABLES, PUNCH DOWN BLOCKS, BACKBOARDS,CABINETS, PATCH PANELS, GROUNDING AND OTHER MISCELLANEOUS ITEMS REQUIRED FOR A COMPLETE SYSTEM.
b. FURNISH AND INSTALL MAIN SERVICE RACEWAY AS DESCRIBED IN CONTRACT DOCUMENTS AND TO COMPLY WITH TELEPHONE COMPANYREQUIREMENTS.
B. COMPONENTS1. TELEPHONE OUTLET BOX SHALL BE SINGLE DEVICE BOX.2. BUILDING TELEPHONE AND COMPUTER NETWORK SYSTEM CABLE
a. 23 GAUGE, SOLID TINNED COPPER, FOUR TWISTED PAIRS. CATEGORY 6b. USE PLENUM-RATED CABLE IN CEILINGS AND AREAS USED FOR PLENUM AIR RETURN
3. TELEPHONE TERMINATION BLOCKSa. UL VERIFIED CATEGORY 3.b. 66 TERMINATION WITH TIN LEAD PLATED IDC
4. NETWORK PATCH PANELSa. UL VERIFIED CATEGORY 6b. 110 TERMINATION WITH TIN LEAD PLATED IDCc. 19" RACK MOUNT WITH BACKBOARD MOUNTING FRAME.d. 48 PORTS
5. TELEPHONE/NETWORK JACKSa. WALL JACKS
1) CAT6 - HUBBELL HXJ6GYG OR ALTERNATE MANUFACTURER WITH EQUIVALENT PERFORMANCE STANDARD.2) CAT3 - HUBBELL HXJ3W OR ALTERNATE MANUFACTURER WITH EQUIVALENT PERFORMANCE STANDARD.
b. PLATES1) HUBBELL - IFP SERIES (PORT QUANTITY AS REQUIRED, COLOR BY ARCHITECT)
6. BACKBOARDS: INTERIOR GRADE PLYWOOD WITHOUT VOIDS, 3 4 INCH THICK; UL-LABELED FIRE RETARDANT.a. SIZE: 48 INCHES WIDE 96 INCHES HIGH.b. DO NOT PAINT OVER UL LABEL.c. PROVIDE ONE 48" MULTI-OUTLET POWER STRIP WITH INTEGRAL SURGE PROTECTION AND OUTLETS AT 6" O.C. (MINIMUM 7 OUTLETS) MOUNTED AT
CENTER OF TERMINAL BOARD.C. INSTALLATION
1. RUN 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE FROM EACH OUTLET. INSTALL CABLE FROM TERMINAL BOARD TO EACH TELEPHONE/NETWORKOUTLET.
2. TERMINATE CABLES AT EACH OUTLET WITH SPECIFIED MODULAR JACK ASSEMBLY.3. TERMINATE CABLES ON PUNCH DOWN BLOCKS OR PATCH PANELS AT TERMINAL BOARD.4. PROVIDE TYPED LABELS AT ALL JACKS CORRESPONDING TO TYPED NUMBERING SYSTEM AT PATCH PANEL OR TERMINAL STRIP.
D. QUALITY ASSURANCE1. COMPLY WITH APPLICABLE PORTIONS OF NEC ANSI/EIA/TIA 568 AS TO TYPE PRODUCTS USED AND INSTALLATION OF COMPONENTS. PROVIDE
PRODUCTS AND MATERIALS WHICH HAVE BEEN UL-LISTED AND LABELED.ALARM & DETECTION SYSTEMSA. SUMMARY
1. INCLUDES BUT NOT LIMITED TO: MODIFICATIONS TO AN EXISTING MICROPROCESSOR-CONTROLLED, INTELLIGENT REPORTING FIRE ALARMEQUIPMENT REQUIRED TO FORM A COMPLETE COORDINATED SYSTEM THAT IS READY FOR OPERATION.
B. SYSTEM DESCRIPTION1. THE FIRE ALARM SYSTEM SHALL COMPLY WITH REQUIREMENTS OF NFPA STANDARD NO. 72 FOR PROTECTED PREMISES SIGNALING SYSTEMS
EXCEPT AS MODIFIED AND SUPPLEMENTED BY THIS SPECIFICATION. THE SYSTEM SHALL BE ELECTRICALLY SUPERVISED AND MONITOR THEINTEGRITY OF ALL CONDUCTORS.
2. THE SYSTEM SHALL BE AN ACTIVE/INTERROGATIVE TYPE SYSTEM WHERE EACH DEVICE IS REPETITIVELY SCANNED, CAUSING A SIGNAL TO BETRANSMITTED TO THE MAIN FIRE ALARM CONTROL PANEL (FACP) INDICATING THAT THE ASSOCIATED INITIATING DEVICE AND NOTIFICATIONAPPLIANCE CIRCUIT WIRING IS FUNCTIONAL. LOSS OF SUCH A SIGNAL AT THE MAIN FACP SHALL RESULT IN A TROUBLE INDICATION ASSPECIFIED HEREINAFTER FOR THE PARTICULAR INPUT.
3. SYSTEM OPERATION: OPERATION OF MANUAL STATION OR AUTOMATIC ACTIVATION OF ANY SMOKE DETECTOR OR HEAT DETECTOR SHALL -a. CAUSE SYSTEM EVACUATION HORNS TO SOUND AND LAMPS TO FLASH.b. THE 80 CHARACTER LCD DISPLAY SHALL INDICATE ALL INFORMATION ASSOCIATED WITH THE FIRE ALARM CONDITION, INCLUDING THE
TYPE OF ALARM POINT AND ITS LOCATION WITHIN THE PROTECTED PREMISES.c. INITIATE OFF-SITE ALARM NOTIFICATION.d. RELEASE MAGNETIC DOOR HOLDERS.e. INITIATE SHUT DOWN OF MECHANICAL UNITS WITH AIR FLOW IN EXCESS OF 2000CFM.f. INITIATE CLOSURE OF ALL FIRE/SMOKE DAMPERS.
4. WIRING: THE MULTIPLEX BUSS AND DATA COMMUNICATION BUS (OPTIONS BUS) SHALL BE WIRED WITH STANDARD NEC 760 COMPLIANTWIRING. ALL FACP SCREW TERMINALS SHALL BE CAPABLE OF ACCEPTING 14 AWG (1.8 MM) TO 18 AWG (1.2 MM) WIRE. ALL SYSTEM WIRINGSHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 70, THE NATIONAL ELECTRICAL CODE (NEC) AND ALSO COMPLY WITH ARTICLE760 OF THE NEC.
C. QUALITY ASSURANCE1. REGULATORY REQUIREMENTS -
a. SYSTEM SHALL MEET APPROVAL OF AUTHORITY HAVING JURISDICTION (AHJ). CHANGES OR ADDITIONS SHALL BE MADE TO THE SYSTEMAS REQUIRED WITHOUT ADDITIONAL COST TO OWNER.
b. EQUIPMENT, DEVICES, AND CABLE SHALL BE UL OR FACTORY MUTUAL LISTED FOR USE IN FIRE ALARM SYSTEMS.c. DESIGNER QUALIFICATIONS: NICET LEVEL III OR IV (3 OR 4) CERTIFIED FIRE ALARM TECHNICIAN OR REGISTERED FIRE PROTECTION
ENGINEER, EMPLOYED BY FIRE ALARM CONTROL PANEL MANUFACTURER, CONTRACTOR, OR INSTALLER.d. INSTALLER QUALIFICATIONS: FIRM WITH MINIMUM 3 YEARS DOCUMENTED EXPERIENCE INSTALLING FIRE ALARM SYSTEMS OF THE
SPECIFIED TYPE AND PROVIDING CONTRACT MAINTENANCE SERVICE AS A REGULAR PART OF THEIR BUSINESS.1) AUTHORIZED REPRESENTATIVE OF CONTROL UNIT MANUFACTURER; SUBMIT MANUFACTURER'S CERTIFICATION THAT INSTALLER IS
AUTHORIZED; INCLUDE NAME AND TITLE OF MANUFACTURER'S REPRESENTATIVE MAKING CERTIFICATION.2) INSTALLER PERSONNEL: FACTORY TRAINED AND CERTIFIED WITH AT LEAST 2 YEARS OF EXPERIENCE INSTALLING FIRE ALARM
SYSTEMS.3) SUPERVISOR: NICET LEVEL III OR IV (3 OR 4) CERTIFIED FIRE ALARM TECHNICIAN; FURNISH NAME AND ADDRESS.
D. FIELD MOUNTED SYSTEM COMPONENTS1. FIRE ALARM INITIATING DEVICES
a. ADDRESSABLE SMOKE DETECTORS1) CEILING MOUNTED, ADDRESSABLE PHOTOELECTRIC2) UL LISTED COMPATIBLE WITH THE FIRE ALARM CONTROL PANEL.3) SHALL HAVE A FLASHING STATUS LED FOR VISUAL SUPERVISION. WHEN THE DETECTOR IS ACTUATED, THE FLASHING LED WILL
LATCH ON SOLID. THE LED SHALL FLASH AT A 1/SEC RATE IF THE CHAMBER IS OUT OF CALIBRATION RANGE. THE DETECTOR MAY BERESET BY ACTUATING THE CONTROL PANEL'S RESET SWITCH.
b. SMOKE DETECTOR GUARDS1) UNDERWRITERS LABORATORIES TESTED AND LISTED BY FOR USE WITH THE SMOKE DETECTORS THEY PROTECT.2) GUARD DESIGN SHALL NOT AFFECT THE DETECTOR OPERATING SENSITIVITY AND SHALL NOT REDUCE THE LISTED DETECTOR
SPACING.3) CONSTRUCTED OF 16-GAUGE STEEL WITH A BAKED WHITE FINISH TO MATCH THE DETECTORS.4) TAMPERPROOF MOUNTING HARDWARE SHALL BE PROVIDED.
c. ADDRESSABLE FIXED TEMPERATURE-ROR HEAT DETECTOR1) ADDRESSABLE COMBINATION FIXED TEMPERATURE / RATE-OF-RISE2) NOMINAL FIXED TEMPERATURE ALARM POINT RATING OF 135°F (57°C) AND A RATE OF RISE ALARM POINT OF 15°F(9°C) PER MINUTE.3) RATED FOR CEILING INSTALLATION AT A MINIMUM OF 70 FT (21.3M) CENTERS AND BE SUITABLE FOR WALL MOUNT APPLICATIONS.
d. DETECTOR BASES: STANDARD DETECTOR MOUNTING BASES SUITABLE FOR MOUNTING ON EITHER NORTH AMERICAN 1-GANG, 3½ OR 4INCH OCTAGON BOX AND 4 INCH SQUARE BOX, OR EUROPEAN BESA OR 1-GANG BOX. THE BASE SHALL, CONTAIN NO ELECTRONICS ANDSUPPORT ALL SERIES DETECTOR TYPES.
e. ADDRESSABLE MANUAL STATION1) ADDRESSABLE DOUBLE ACTION, SINGLE STAGE2) POLYCARBONATE CONSTRUCTION WITH INTERNAL TOGGLE SWITCH.3) FINISHED IN RED WITH SILVER "PULL IN CASE OF FIRE" LETTERING4) SUITABLE FOR MOUNTING ON NORTH AMERICAN 2 ½ (64MM) DEEP 1-GANG BOXES AND 1 ½ (38MM) DEEP 4 SQUARE BOXES WITH
1-GANG COVERS.2. FIRE ALARM ACTUATING DEVICES.
a. NOTIFICATION APPLIANCES1) LOW PROFILE HORN-STROBES
a) AUDIBLE OUTPUT OF 92 DBA AT 10 FT. WHEN MEASURED IN REVERBERATION ROOM PER UL-464.b) INTEGRALLY MOUNTED FLASHING LIGHT UNIT WITH BLOCK LETTERS 'FIRE'. MULTI-CANDELA WITH FIELD-SELECTABLE
SETTINGS OF 15CD, 30CD, 60CD, 75CD & 110CD, AND FLASH RATE BETWEEN ONE AND THREE HERTZ. ALL UNITS SHALL FLASHIN SYNCHRONIZATION WITH EACH OTHER.
c) THE HORN SHALL HAVE A SELECTABLE STEADY OR SYNCHRONIZED TEMPORAL OUTPUT.d) IN AND OUT SCREW TERMINALS SHALL BE PROVIDED FOR WIRING.e) LOW PROFILE HORN/STROBES SHALL MOUNT IN A NORTH AMERICAN 1-GANG BOX.
2) LOW PROFILE STROBESa) PROVIDE LOW PROFILE WALL MOUNTED STROBES AT THE LOCATIONS SHOWN ON THE DRAWINGS. IN AND OUT SCREW
TERMINALS SHALL BE PROVIDED FOR WIRING. STROBES SHALL PROVIDE SYNCHRONIZED FLASH OUTPUTS. STROBE OUTPUTSHALL BE DETERMINED AS REQUIRED BY ITS SPECIFIC LOCATION AND APPLICATION FROM A FAMILY OF 15CD, 30CD, 60CD,75CD, OR 110CD DEVICES. LOW PROFILE STROBES SHALL MOUNT IN A NORTH AMERICAN 1-GANG BOX.
3. INITIATION & CONTROL MODULESa. RELAY MODULE
1) PROVIDE ADDRESSABLE CONTROL RELAY CIRCUIT MODULES AS REQUIRED. THE MODULE SHALL PROVIDE ONE (1) FORM C DRYRELAY CONTACTS RATED AT 24VDC @ 2 AMPS (PILOT DUTY) TO CONTROL EXTERNAL APPLIANCES OR EQUIPMENT. THE POSITIONOF THE RELAY CONTACT SHALL BE CONFIRMED BY THE SYSTEM FIRMWARE.
E. INSTALLATION1. INSTALL FIRE ALARM AND DETECTION SYSTEMS AS INDICATED, IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S WRITTEN INSTRUCTIONS,
AND COMPLYING WITH APPLICABLE PORTIONS OF NEC, NFPA AND NECA'S "STANDARD OF INSTALLATION".2. INSTALL WIRING, RACEWAYS, CONDUCTORS, ELECTRICAL BOXES AND FITTINGS IN ACCORDANCE WITH CONDUIT, WIRE AND CABLE, AND BOXES
AND PLATES SECTION OF THIS SPEC.3. LABEL PULL AND JUNCTION BOXES "FIRE ALARM" WITH RED INDELIBLE INK.4. LOOP WIRES THROUGH EACH DEVICE ON ZONE FOR PROPER SUPERVISION. TEE-TAPS NOT PERMITTED.5. PROVIDE DUST PROTECTION FOR INSTALLED SMOKE DETECTORS UNTIL FINISH WORK IS COMPLETED AND BUILDING IS READY FOR
OCCUPANCY.6. PROTECT CONDUCTORS FROM CUTS, ABRASION AND OTHER DAMAGE DURING CONSTRUCTION.7. MINIMUM CONDUCTOR SIZE SHALL BE 14 AWG UNLESS OTHERWISE SPECIFIED.8. DO NOT INSTALL CEILING MOUNTED DETECTORS WITHIN 3 FEET OF AIR DISCHARGE GRILLS. COORDINATE WITH OTHER TRADES AS REQUIRED.9. POST COPY OF WIRE IDENTIFICATION LIST INSIDE FIRE ALARM PANEL DOOR OR OTHER AREA ACCESSIBLE TO FIRE ALARM SERVICE
PERSONNEL.10. PROVIDE DUCT SMOKE DETECTORS FOR ALL MECHANICAL UNITS WITH AIR FLOW IN EXCESS OF 2000 CFM AND TIE INTO FIRE ALARM CONTROL
PANEL. PROVIDE FAN SHUT DOWN CIRCUIT AND ASSOCIATED CONTROL EQUIPMENT FOR ALL REQUIRED MECHANICAL UNITS.11. INSTALL CONDUCTORS AND MAKE CONNECTIONS TO ALL, WATER FLOW SWITCHES, VALVE TAMPER SWITCHES, LOW AIR PRESSURE SWITCHES,
AND DOOR HOLDING DEVICES.12. INSTALL CONDUCTORS AND MAKE CONNECTIONS TO ALL FIRE/SMOKE DAMPERS. REFER TO MECHANICAL DRAWINGS FOR EXACT NUMBER AND
LOCATIONS.H. FIELD QUALITY CONTROL
1. TEST & INSPECTIONa. ALL INTELLIGENT ADDRESSABLE DEVICES SHALL BE TESTED FOR CURRENT ADDRESS AND USER DEFINED MESSAGE.b. ALL WIRING SHALL BE TESTED FOR CONTINUITY, SHORTS, AND GROUNDS BEFORE THE SYSTEM IS ACTIVATED.c. ALL TEST EQUIPMENT, INSTRUMENTS, TOOLS AND LABOR REQUIRED TO CONDUCT THE TESTS SHALL BE MADE AVAILABLE BY THE
INSTALLING CONTRACTOR.d. THE SYSTEM INCLUDING ALL ITS SEQUENCE OF OPERATIONS SHALL BE DEMONSTRATED TO THE OWNER, HIS REPRESENTATIVE, AND THE
LOCAL FIRE INSPECTOR. IN THE EVENT THE SYSTEM DOES NOT OPERATE PROPERLY, THE TEST SHALL BE TERMINATED. CORRECTIONSSHALL BE MADE AND THE TESTING PROCEDURE SHALL BE REPEATED UNTIL IT IS ACCEPTABLE TO THE OWNER, HIS REPRESENTATIVESAND THE FIRE INSPECTOR.
e. ALL FIRE ALARM TESTING SHALL BE IN ACCORDANCE WITH NATIONAL FIRE ALARM CODE, NFPA 72.I. MANUFACTURER'S FIELD SERVICE -
1. INSTRUCT OWNER'S REPRESENTATIVE IN PROPER OPERATION AND MAINTENANCE PROCEDURES.2. PROVIDE A MINIMUM OF 4 HOURS TRAINING.