Packaged water cooled liquid chillers for indoor installation equipped withoil-free centrifugal compressors and flooded single-shell evaporator.
280 ÷ 1840 kW
technicalcatalogueT_FRGTRBFL_1012_GB
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 2/28
2 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
INDEX
EUROVENT CERTIFICATION ........................................................................................................................... 3
GENERAL CHARACTERISTICS ....................................................................................................................... 3
SERIES IDENTIFICATION ................................................................................................................................. 3
MODEL IDENTIFICATION.................................................................................................................................. 3
WORKING LIMITS............................................................................................................................................... 4
COMPONENTS ................................................................................................................................................... 6
OPTIONAL ACCESSORIES .............................................................................................................................. 8
TECHNICAL DATA .............................................................................................................................................. 9
ACOUSTIC DATA............................................................................................................................................ 13
ELECTRIC DATA ............................................................................................................................................. 13
MICROPROCESSOR CONTROL SYSTEM ................................................................................................. 14
MACHINE DRAWINGS .................................................................................................................................... 15
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 3/28
3RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
EUROVENT CERTIFICATION
This product has been certified by Eurovent.
RC GROUP SpA participates in the EUROVENT program for: LCP and HP (Liquid ChillingPackages and Heat Pumps).Check ongoing validity of certification on -line: www.eurovent-certification.com
GENERAL CHARACTERISTICSFRIGO TURBO FL: Water cooled liquid chillers equipped with oil-free centrifugal compressorsand flooded evaporator
The machines are made for indoor installation.
Framework with sections of thick steel for high resistance to the greatest stress during handling andtransport.
Machines supply fully assembled with refrigerant charge and control systems. The installationrequires only electrical and hydraulic connections allowing costs and time savings.
Final assembly on all machines before shipment including running test, reading and monitoring ofoperating parameters, alarms simulation and visual check.
Design, assembly and test as per the Company Quality Assurance program in full compliance withISO 9001. RC Group has been the first Italian company in its segment to get the ISO 9001 inOctober 13
th, 1991 with certificate ICIM 0018.
The machines are in full compliance with European Norms 2006/42CE, 2006/95CE, 2004/108CE,97/23CE and subsequent amendments.
SERIES IDENTIFICATION
FRIGO TURBO FL – Water cooled liquid chillers equipped with oil-free centrifugal compressors,flooded evaporator and shall and tube condenser.
Cooling capacity 280 ÷ 1840 kW
MODEL IDENTIFICATION
FRIGO TURBO FL 280 T 1 P4
280 Cooling capacity (kW) at nominal conditions
T TURBO centrifugal compressor
1 Compressor number
P4 Machine with shell and tube 4-passes condenser
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 4/28
4 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
WORKING LIMITS
EVAPORATOR:8 ÷ 22°C Range of chilled fluid inlet temperature.4 ÷ 18°C Range of chilled fluid outlet temperature.4 ÷ 6°C Δt operation between the inlet and outlet chilled fluid.90 ÷ 105% “Ideal” water flow range compared to the nominal value reported in the
technical data table.65 ÷ 120% “Extended” water flow range compared to the nominal value reported in the
technical data table.
WARNINGThe deviation of the water flow from “ideal” range towards “extended” range can cause aremarkable performance worsening. Please contact the RC GROUP CommercialDepartment to verify operation conditions.
CONDENSER:20 ÷ 52°C Range of water outlet temperature (in relation to the machine model).5 ÷ 15°C Δt operation temperature between the inlet and outlet water.70 ÷ 125% 2-passes type: range of water flow allowed from the nominal value reported in
"Technical data table".45 ÷ 100% 4-passes type: range of water flow allowed from the nominal value reported in
"Technical data table"..40% Maximum concentration of antifreeze solution (Ethylene or Propylene Glycol)
WARNINGPlease contact the RC GROUP Commercial Department in case of use of other antifreezedifferent from the ones listed.
WORKING AREA
WARNINGThe values are indicative.
For further information and limit operation conditions, please contact the RC GROUPCommercial Department.
Limit curves (identified by a letter on the graphic above): A) Minimum compression ratio;B) Maximum evaporation pressure;C) Maximum condensing temperature;
Chilled fluid outlet temperature (°C)
C o n d e n s e r o u t l e t w a t e r t e m
e r a t u r e ° C
D) Maximum electric absorption (maximumcompression ratio);
E) Minimum evaporating pressure;F) Minimum rotation speed.
Legend:
Models: 280 T1, 560 T2,840 T3
Models: 380 T1, 760 T2,1140 T3, 1520 T4
Models: 460 T1, 920 T2,1380 T3, 1840 T4
Compression ratio between
the values of absolute andsuction pressure.
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 5/28
5RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
ANTIFREEZE MIXTURES
EVAPORATOR HYDRAULIC CIRCUITMachines can work with antifreeze mixtures although not necessary, because the machines donot accept outlet temperature of the liquid cooled below 4°C, the use of glycol mixture is ageneric antifreeze protection, for machines not in operation during the winter season.
CONDENSER HYDRAULIC CIRCUIT
In case of heat exhaustion through a close hydraulic circuit on a dry cooler, is mandatory to loadthe circuit with antifreeze mixture.The choice of glycol percentage may be based on the following table:
Freezing point [°C] % Ethylene glycol volume % Propylene glycol volume
-10 24 27
-20 36 39
-30 46 49
_______________________________________________
STORING TEMPERATURE
If the machine is not installed on receipt and is stored for a long time, store it in a protectedplace, at temperatures ranging between -30°C and 50°C in absence of superficial condensationand direct sun light.
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 6/28
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 7/28
7RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
ELECTRICALPANELIn accordance with EN60204-1 norms, suitable for indoor installation, complete with:
Main switch with door lock safety.
Fuses for compressors.
Contactors for compressors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with “Touch Screen” graphic display for control and monitor ofoperating and alarms status. The system includes:- Voltage free contact for remote general alarm.- Main components hour-meter.- Integrated “Data logger” function for the recording of events and alarms. - Non-volatile “Flash” memory for data storage. - Menu with protection password.
HYDRAULIC CONNECTIONS OF HEAT EXCHANGERS
The hydraulic connections with flange (FL) are supplied as standard with counter flange.
The hydraulic connections with grooved end (Victaulic) are supplied as standard with
Victaulic joint and adapter pipe.
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 8/28
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 9/28
9RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
TECHNICAL DATA
MODEL 280 T1 280 T1 380 T1 380 T1 460 T1 460 T1
TYPE (1) P4 P4 P4
COOLING CAPACITY (2) kW 280 273 380 371 460 431
Compressors power input kW 55,4 58,5 75,2 78,8 90,7 89,2
Compressors operating current A 88,8 93,9 121,0 126,0 145,0 143,0EVAPORATOR
Water flow rate m³/h 48,2 47,0 65,4 63,8 79,1 74,2
Pressure drops kPa 25 24 29 28 27 24
CONDENSER
Water flow rate m³/h 57,7 40,8 78,3 55,3 94,7 64,0
Pressure drops kPa 13 44 22 76 21 63
COMPRESSORS centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
Quantity n. 1 1 1 1 1 1
Maximum current A 139 139 210 210 172 172
Starting current A 5 5 5 5 5 5
Stepless capacity control % 44…100% 46…100% 42…100% 43…100% 34…100% 36…100%
EVAPORATOR n. 1 1 1 1 1 1
Water volume l 47 47 60 60 74 74Max water flow rate m³/h 115,3 115,3 115,3 115,3 135,4 135,4
CONDENSER n. 1 1 1 1 1 1
Water volume l 101 101 101 101 125 125
Max water flow rate m³/h 132,6 66,3 132,6 66,3 170,3 85,2
REFRIGERANT R134a R134a R134a R134a R134a R134a
Refrigerant charge kg 120 120 170 170 120 120
Gas circuits n. 1 1 1 1 1 1
POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Ratio kW/kW 5,05 4,67 5,05 4,71 5,07 4,83
ESEER - Eurovent Standard 8,65 8,69 8,81 8,90 9,12 9,17
IPLV- ARI Standard 550/590 9,27 9,31 9,77 9,87 9,90 9,95
SOUND LEVELSound pressure level [Lp] (3) dB(A) 73,9 73,9 74,3 74,3 76,1 76,1
Sound power level [Lw] (4) dB(A) 92,5 92,5 92,9 92,9 94,7 94,7
DIMENSIONS
Length mm 3050 3050 3050 3050 3050 3050
Width mm 1320 1320 1320 1320 1320 1320
Height mm 1870 1870 1870 1870 1870 1870
NET WEIGHT kg 1948 1948 2029 2029 2264 2264
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet/outlet – Victaulic - OD Ø mm 114,3 114,3 168,3 114,3 168,3 168,3
CONDENSER
Inlet/outlet - FL DN 125 100 125 100 125 100
1. Standard machine: 2-passes condenserType P4 machine = 4-passes condenser
2. Referred to chilled water temperature 12/7°C; water to the condenser 30/35°C.Type P4: water to the condenser 30/37°C.
3. Sound pressure level 1m far according to ISO EN 37444. Sound power level according to ISO EN 9614 – 2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 10/28
10 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
TECHNICAL DATA
MODEL 560 T2 560 T2 760 T2 760 T2 840 T3 840 T3
TYPE (1) P4 P4 P4
COOLING CAPACITY (2) kW 560 547 760 742 840 820
Compressors power input kW 111,0 118,0 149,0 156,0 166,0 177,0
Compressors operating current A 178,0 189,0 239,0 251,0 267,0 283,0
EVAPORATOR
Water flow rate m³/h 96,3 94,0 131,0 128,0 144,0 141,0
Pressure drops kPa 31 30 27 26 32 30
CONDENSER
Water flow rate m³/h 115,0 81,6 156,0 110,0 173,0 122,0
Pressure drops kPa 19 63 22 70 26 91
COMPRESSORS centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
Quantity n. 2 2 2 2 3 3
Maximum current A 279 279 420 420 418 418
Starting current A 5 5 5 5 5 5
Stepless capacity control % 22…100% 23…100% 23…100% 23…100% 20…100% 21…100%
EVAPORATOR n. 1 1 1 1 1 1
Water volume l 84 84 125 125 197 197
Max water flow rate m³/h 135,7 135,7 173,9 173,9 346,1 346,1
CONDENSER n. 1 1 1 1 1 1
Water volume l 176 176 239 239 341 341
Max water flow rate m³/h 207,6 103,8 280,7 140,4 311,3 155,7
REFRIGERANT R134a R134a R134a R134a R134a R134a
Refrigerant charge kg 160 160 275 275 352 352
Gas circuits n. 1 1 1 1 1 1
POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Ratio kW/kW 5,05 4,64 5,10 4,76 5,06 4,63
ESEER - Eurovent Standard 8,70 8,64 9,09 9,19 8,64 8,64
IPLV- ARI Standard 550/590 9,29 9,26 9,84 9,95 9,26 9,26
SOUND LEVEL
Sound pressure level [Lp] (3) dB(A) 76,1 76,1 76,3 76,3 77,1 77,1
Sound power level [Lw] (4) dB(A) 94,7 94,7 94,9 94,9 95,7 95,7
DIMENSIONS
Length mm 3130 3130 3662 3662 4500 4500
Width mm 1320 1320 1355 1355 1406 1406
Height mm 2040 2040 2040 2040 2090 2090
NET WEIGHT kg 2781 2781 3215 3215 4572 4572
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet/outlet – Victaulic - OD Ø mm 168,3 168,3 168,3 168,3 168,3 168,3
CONDENSER
Inlet/outlet – Victaulic - OD Ø mm 168,3 141,3 168,3 141,3 168,3 141,3
1. Standard machine: 2-passes condenserType P4 machine = 4-passes condenser
2. Referred to chilled water temperature 12/7°C; water to the condenser 30/35°C.Type P4: water to the condenser 30/37°C.
3. Sound pressure level 1m far according to ISO EN 37444. Sound power level according to ISO EN 9614 – 2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 11/28
11RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
TECHNICAL DATA
MODEL 920 T2 920 T2 1140 T3 1140 T3 1380 T3 1380 T3
TYPE (1) P4 P4 P4
COOLING CAPACITY (2) kW 920 863 1140 1113 1380 1295
Compressors power input kW 179,0 178,0 218,0 233,0 270,0 264,0
Compressors operating current A 287,0 285,0 350,0 373,0 433,0 423,0
EVAPORATOR
Water flow rate m³/h 158,0 148,0 196,0 191,0 237,0 223,0
Pressure drops kPa 57 50 35 33 38 34
CONDENSER
Water flow rate m³/h 189,0 128,0 234,0 165,0 284,0 191,0
Pressure drops kPa 22 70 29 97 30 91
COMPRESSORS centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
Quantity n. 2 2 3 3 3 3
Maximum current A 344 344 630 630 517 517
Starting current A 5 5 5 5 5 5
Stepless capacity control % 18…100% 19…100% 13…100% 14…100% 11…100% 12…100%
EVAPORATOR n. 1 1 1 1 1 1
Water volume l 141 141 253 253 299 299
Max water flow rate m³/h 270,7 270,7 313,1 313,1 334,4 334,4
CONDENSER n. 1 1 1 1 1 1
Water volume l 329 329 428 428 572 572
Max water flow rate m³/h 335,3 167,7 391,9 196 475,8 237,9
REFRIGERANT R134a R134a R134a R134a R134a R134a
Refrigerant charge kg 301 301 420 420 450 450
Gas circuits n. 1 1 1 1 1 1
POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Ratio kW/kW 5,14 4,85 5,23 4,78 5,11 4,91
ESEER - Eurovent Standard 9,16 9,19 9,23 9,26 9,08 9,26
IPLV- ARI Standard 550/590 9,98 10,01 9,73 9,76 9,89 10,09
SOUND LEVEL
Sound pressure level [Lp] (3) dB(A) 77,8 77,8 77,1 77,1 77,7 77,7
Sound power level [Lw] (4) dB(A) 96,8 96,8 96,6 96,6 97,2 97,2
DIMENSIONS
Length mm 3820 3820 4500 4500 4500 4500
Width mm 1406 1406 1406 1406 1406 1406
Height mm 2040 2040 2090 2090 2090 2090
NET WEIGHT kg 3685 3685 5168 5168 5920 5920
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet/outlet – Victaulic - OD Ø mm 168,3 168,3 219,1 219,1 219,1 219,1
CONDENSER
Inlet/outlet – Victaulic - OD Ø mm 168,3 141,3 168,3 141,3 168,3 141,3
1. Standard machine: 2-passes condenserType P4 machine = 4-passes condenser
2. Referred to chilled water temperature 12/7°C; water to the condenser 30/35°C.Type P4: water to the condenser 30/37°C.
3. Sound pressure level 1m far according to ISO EN 37444. Sound power level according to ISO EN 9614 – 2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 12/28
12 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
TECHNICAL DATA
MODEL 1520 T4 1520 T4 1840 T4 1840 T4
TYPE (1) P4 P4
COOLING CAPACITY (2) kW 1520 1484 1840 1727
Compressors power input kW 290,0 310,0 358,0 352,0
Compressors operating current A 464,0 497,0 574,0 564,0
EVAPORATOR
Water flow rate m³/h 261,0 255,0 316,0 297,0
Pressure drops kPa 28 27 36 32
CONDENSER
Water flow rate m³/h 311,0 220,0 378,0 255,0
Pressure drops kPa 25 86 36 111
COMPRESSORS centrifugo centrifugo centrifugo centrifugo
Quantity n. 4 4 4 4
Maximum current A 840 840 689 689
Starting current A 5 5 5 5
Stepless capacity control % 11…100% 11…100% 9…100% 9…100%
EVAPORATOR n. 1 1 1 1
Water volume l 371 371 391 391
Max water flow rate m³/h 417,4 417,4 445,9 445,9
CONDENSER n. 1 1 1 1
Water volume l 606 606 606 606
Max water flow rate m³/h 560,7 280,4 560,7 280,4
REFRIGERANT R134a R134a R134a R134a
Refrigerant charge kg 430 430 430 430
Gas circuits n. 1 1 1 1
POWER SUPPLY V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50
ENERGY EFFICIENCY INDEXES
EER – Energy Efficiency Ratio kW/kW 5,24 4,79 5,14 4,91
ESEER - Eurovent Standard 9,04 9,06 9,17 9,26
IPLV- ARI Standard 550/590 9,69 9,71 9,97 10,07
SOUND LEVEL
Sound pressure level [Lp] (3) dB(A) 78,0 78,0 79,5 79,5
Sound power level [Lw] (4) dB(A) 97,5 97,5 99,0 99,0
DIMENSIONS
Length mm 4990 4990 4990 4990
Width mm 1406 1406 1406 1406
Height mm 2090 2090 2090 2090
NET WEIGHT kg 7034 7034 7240 7240
HYDRAULIC CONNECTIONS
EVAPORATOR
Inlet/outlet – Victaulic - OD Ø mm 219,1 219,1 219,1 219,1
CONDENSER
Inlet/outlet – Victaulic - OD Ø mm 219,1 168,3 219,1 168,3
1. Standard machine: 2-passes condenserType P4 machine = 4-passes condenser
2. Referred to chilled water temperature 12/7°C; water to the condenser 30/35°C.Type P4: water to the condenser 30/37°C.
3. Sound pressure level 1m far according to ISO EN 37444. Sound power level according to ISO EN 9614 – 2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 13/28
13RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
ACOUSTIC DATA
MODELLO 280 T1 380 T1 460 T1 560 T1 760 T2 840 T3
280 T1 P4 380 T1 P4 460 T1 P4 560 T1 P4 760 T2 P4 840 T3 P4
Sound power level [Lw] (1) dB(A) 92,5 92,9 94,7 94,7 94,9 95,7
Sound pressure level at [Lp] 1m (2) dB(A) 73,9 74,3 76,1 76,1 76,3 77,1
Sound pressure level at [Lp] 5m (3) dB(A) 65,5 65,9 67,7 67,7 67,9 68,7
Sound pressure level at [Lp] 10m (3) dB(A) 60,5 60,9 62,7 62,7 62,9 63,7
MODELLO 920 T2 1140 T3 1380 T3 1520 T4 1840 T4
920 T2 P4 1140 T3 P4 1380 T3 P4 1520 T4 P4 1840 T4 P4
Sound power level [Lw] (1) dB(A) 96,8 96,6 97,2 97,5 99,0
Sound pressure level at [Lp] 1m (2) dB(A) 77,8 77,1 77,7 78,0 79,5
Sound pressure level at [Lp] 5m (3) dB(A) 69,6 69,2 69,8 70,1 71,6
Sound pressure level at [Lp] 10m (3) dB(A) 64,7 64,4 65,0 65,3 66,8
1. Sound power level [Lw] according to ISO EN 9614 – 2.2. Sound pressure level [Lp]1m far according to ISO EN 3744.3. Sound pressure level [Lp] in free field condition.
IMPORTANT
For further information about units acoustic data, please refer to “The Noise” bulletin ofRC GROUP technical literature.
ELECTRIC DATA
MAXIMUM ELECTRIC ABSORPTION CALCULATION
This chapter is showing the maximum electrical absorption calculation of unit (A), correspondingto extreme working conditions.
The involved components are the following:
Compressors electric motorThe electrical data of the various components are indicated in the relative technical data sheets.
EXAMPLE n.1:Calculation for FRIGO TURBO FL 560 T2:
MAXIMUM ELECTRIC ABSORPTION● Compressors A 279,0
Maximum electric absorption A 279,0
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 14/28
14 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MICROPROCESSOR CONTROL SYSTEM
The microprocessor controls the machine guaranteeing on the one hand a precise and punctualtemperature regulation, on the other hand integrating the safety functions relative to all fluid-dynamiccircuits.The microprocessor controls the outlet temperatures of the chilled water through two set
parameters, xK1 e xK2, as outlet temperatures from the evaporators, with possible remotecommutation through voltage free contact.In any case, the microprocessor will modulate the electric input to the compressors motors toguarantee the maximum temperature precision in respect of the working range allowed by thecentrifugal compressors.For any working condition, the control will cleverly manage the number of compressors to beactivated in a combined optics of safety and energy saving.
The system includes:Compact controller for DIN rail mounting 24Vac 50/60Hz32-bit microprocessor2 +2 MB flash memory (retains data without power) and memory RAM 512kBIntegrated “Data logger” function for the recording of events and alarms. Graphic touch screen colour display 7”
TOUCH-SCREEN DISPLAY1 Alarms signalling LED.2 Interlock signalling LED.3 On/off LED for terminal feeding.
REMOTE CONTROLS/ALARMSINLETS1 External enabling • 2 Cooling set-point changeover (xK1 - xK2) • OUTLETS1 General alarm 1 - (programmable) ••
• remote controls/alarms•• voltage free controls/alarms
1
2
3
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 15/28
15RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 280 T1
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 16/28
16 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 380 T1
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 17/28
17RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 460 T1
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 18/28
18 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 560 T2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 19/28
19RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 760 T2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 20/28
20 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 840 T3
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 21/28
21RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 920 T2
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 22/28
22 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 1140 T3
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 23/28
23RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 1380 T3
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 24/28
24 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
MACHINE DRAWINGSDimensions in mm
MODEL 1520 T4
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 25/28
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 26/28
26 RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 27/28
27RC GROUP S.p.A. ● T_FRGTRBFL_1012_GB ● R134a
8/10/2019 t Frgtrbfl 1012 Gb
http://slidepdf.com/reader/full/t-frgtrbfl-1012-gb 28/28
The continuous improvement of products may imply changes in the data shown in this catalogue.
RC GROUP S.p.A. • Via Roma, 5 • 27010 Valle Salimbene (PV), Italy www.rcgroup.it • Tel. +39 (0) 382 433 811 • Fax +39 (0) 382 587 148
T_FRGTRBFL_1012_GB