Next MTR 

6 ÷ 15 kW

Air conditioners for Metrology Labs with upflow air delivery

technicalcatalogueT_NXTMTR_0511_GB

Page 2: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 2/32

neXt mtr 

2 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

INDEX

GENERAL CHARACTERISTICS ................................................................... .............................. 3 

SERIES IDENTIFICATION............................................................. .............................................. 3 

MODEL IDENTIFICATION ...................................................... ..................................................... 3 

WORKING RANGE ................................................... ........................................................... ........ 4 

WORKING LIMITS .............................................................. ......................................................... 5 

MAIN COMPONENTS ................................................................................................................. 6 

OPTIONAL ACCESSORIES ........................................................................................ ................ 8 

TECHNICAL DATA - NEXT MTR DX .................................................................. ........................ 9 

TECHNICAL DATA - NEXT MTR DW ................................................................. ...................... 10 

ELECTRICAL DATA .................................................................................................................. 17 

MP.COM: MICROPROCESSOR CONTROL SYSTEM ......................... .................................... 18 

OPTIONAL ACCESSORIES – REMOTE AIR COOLED CONDENSER .................................... 19 

OPTIONAL ACCESSORIES - CONDENSATE DISCHARGE PUMP ......................................... 21 

OPTIONAL ACCESSORIES - FLOOR STAND ........................................................ .................. 22 

OPTIONAL ACCESSORIES - BOTTOM PANEL .................................................................. ..... 23 

OPTIONAL ACCESSORIES - SANDWICH PANEL ........................................................... ........ 23 

OPTIONAL ACCESSORIES - NON RETURN MOTORIZED DAMPER .................................... 24 

OPTIONAL ACCESSORIES - AIR DELIVERY PLENUM .......................................................... 25 

OPTIONAL ACCESSORIES – MP.COM REMOTE TERMINAL ................................................ 26 

MACHINE DRAWINGS ......................................................... ..................................................... 27 

TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITHREMOTE AIR COOLED CONDENSER .......................................................... ........................... 29 

EXAMPLE FOR MACHINES NOISE EMISSION CALCULATION ............................................. 31 

Page 3: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 3/32

neXt mtr

3RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

GENERAL CHARACTERISTICSNEXT MTR: Air conditioners for metrology labs with upflow air delivery.The series is suitable for all applications where high precision is required in maintaining thecharacteristics of temperature-humidity of the air conditioned room as laboratories, clean rooms,rooms for precision measurements etc..

The machines are made for indoor installation.

The constructive solutions and the internal lay-out allow high application flexibility and the frontalaccess to the main components for the inspection and routine maintenance.

Machines supply fully assembled with refrigerant charge and control systems. The installationrequires electrical and hydraulic /refrigerant connections only allowing high costs and timereduction.

Final assembly on all machines before shipment including running test, reading and monitoringof operating parameters, alarms simulation and visual check.

Design, assembly and test as per the Company Quality Assurance program in full compliancewith ISO 9001. RC Group has been the first Italian company in its segment to get the ISO 9001in October 13

th, 1991 with certificate ICIM 0018.

The machines are in full compliance with European Norms 2006/42CE, 2006/95CE,2004/108CE, 97/23CE and subsequent amendments.

SERIES IDENTIFICATION

Frontal air suction and upflow air delivery.

NEXT MTR DX: Direct expansion air conditioners for metrology labs, for matching with remoteair cooled condenser, and equipped with scroll compressors and Plug-fans.Cooling capacity 6,6 ÷ 14,4 kW

NEXT MTR DW: Direct expansion close control air conditioners for metrology labs, with built-inwater cooled condenser and equipped with scroll compressors and Plug-fans.Cooling capacity 7,0 ÷ 15,3 kW

MODEL IDENTIFICATION

NEXT MTR DX O 013 Z 1 H3

DX Machine typeDX direct expansion – air cooledDW direct expansion – water cooled

O Air deliveryO upflow

013 Cooling capacity (kW) at nominal conditionsZ Compressor type

Z Scroll hermetic compressor for R407C1 Number of compressors

H3 Cabinet size

Page 4: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 4/32

Page 5: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 5/32

neXt mtr

5RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

WORKING LIMITS

Room air temperature:14°C minimum temperature with wet bulb.24°C maximum temperature with wet bulb.35°C maximum temperature with dry bulb.

Room air humidity:

20%RH minimum relative humidity.75%RH maximum relative humidity.

STORING TEMPERATUREIf the machine is not installed on receipt and is stored for a long time, store it in a protectedplace, at temperatures ranging between -30°C and 50°C in absence of superficialcondensation and direct sun light.

Page 6: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 6/32

neXt mtr 

6 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

MAIN COMPONENTS

FRAMEWORK

•  Base in aluminium extrusion, painted with epoxy powders.

•  Inner frame and upper frame in aluminium profile, painted with epoxy powders. Theinner frame is provided with seals to ensure air tight with the panels.

•  Galvanized steel sheet panels externally coated with PVC film and internallyinsulated with noise absorption material.The panels are fixed to the frame with non visible mounting system.

•  Electric board in separate technical compartment on the machine front.•  Colour: RAL 9005 for base and frame

Similar to RAL7015 for panels, with hammered finish

•  Air intake from the front through honeycomb type grille and air delivery from the top.•  Washable air pre-filters with G2 efficiency, with cells in synthetic fibre .

COMPRESSORS•  Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized for

R407C refrigerant.•  Continuous control of the cooling capacity by hot gas by-pass.

•  2-pole 3-phase electric motor with direct on line starting.•  Crankcase heater.

•  Electric motor thermal protection via internal winding temperature sensors.•  Terminal box with IP54 enclosure class.

•  Rubber supports.

FILTER SECTION

•  Washable air filters with G4 efficiency, with cells in synthetic fibre and metallic frame(EN 779-2002).

EVAPORATING SECTION

•  Heat exchanger coil with internally corrugated copper tubes and high efficiencyaluminium fins, specifically developed to provide high heat transfer and lowerpressure drops.

•  Cooling capacity control.

•  Frame in galvanized steel.

•  Condensate tray in peraluman with PVC flexible discharge pipe.

HEATING SECTION

•  3 working steps electric heater consisting of aluminium armoured elements withintegral fins and safety thermostat (binary control logic).

•  Modulating type hot gas reheating system.

HUMIDIFICATION SECTION•  Proportional controlled steam humidifier with immersed electrodes fitted with safety

and running accessories.

DE- HUMIDIFICATION SECTION

•  Dehumidification system with automatic air flow reduction.

FANS SECTION•  Centrifugal fans with backward curved blades, single suction and without scrollhousings (Plug-fans), directly coupled to external rotor electric motor.Brushless type synchronous EC motor with integrated electronic commutated systemand continuous variation of the rotation speed. The motor rotation control is obtainedwith the EC system (Electronic Commutation) that manage the motor according tothe 0÷10V proportional signal coming from the microprocessor control.

•  Temperature/humidity sensors on air intake.

REFRIGERANT CIRCUIT

•  Thermostatic expansion valve. •  Sight glass. 

•  Filter dryer on liquid line.•  Pressure transducers with indication, control and protection functions, on low and

high refrigerant pressure.•  High pressure safety switch with manual reset.•  Safety valve.•  Liquid receiver with accessories.•  3-way modulating valve for hot gas re-heating system.

•  Check valve for hot gas re-heating system.

Page 7: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 7/32

neXt mtr

7RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

•  Hot gas injection valve for capacity control.

•  Balancing valve for hot gas capacity control.•  Refrigerant circuit with copper tubing with anticondensate insulation of the suction

line.

•  Plastic capillary hoses for pressure sensors connection.•  R407C refrigerant charge.

•  NEXT MTR DX:

- Valves on gas delivery and liquid return for coupling to remote air cooledcondenser.

- 0÷10V proportional signal to manage the condensing control system of theremote air cooled condenser.

•  NEXT MTR DW:- Copper brazed plate type with cover plates, plates and connections in AISI 316

stainless steel.- 0÷10V proportional signal to manage the condensing control system of the 2-

way motorized valve.

ELECTRICAL PANELIn accordance with EN60204-1 norms complete with:

•  Main switch with door lock safety.

•  Magnetothermic switch for supply fan, compressor, electric heaters and humidifier.

•  Contactors for each load.The supply fans equipped with EC electric motor are not supplied with contactors.

•  Transformer for auxiliary circuit and microprocessor supply.

•  Panel with machine controls.•  Power supply: 400/3/50.

CONTROL SYSTEM

•  MP.COM microprocessor system with graphic display for control and monitor ofoperating and alarms status. The system includes:- Voltage free contact for remote general alarm.- Main components hour-meter.- Non-volatile “Flash” memory for data storage.- Menu with protection password.- LAN connection.

WARNINGFor DX units it is necessary to provide the refrigerant and the lubricant oil charge forthe connection pipes and for the remote air cooled condenser.

Page 8: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 8/32

neXt mtr 

8 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

OPTIONAL ACCESSORIES

•  Remote air cooled condensers with axial fans series TEAM MATE MR (version DX).•  2-way motorized valve with proportional control (0÷10V) for condensing control and

emergency manual control (version DW).•  Electronic expansion valve.•  Solenoid valve on the liquid line (DX version - for remote condenser connection with

refrigerant line longer than 10m).

•  Compressor capacitor for power factor - cosϕ 0,9.

•  Phase sequence control relay for compressor.•  Compressor soundproof cap for a noise reduction of about 3 dB(A).•  Washable air filter with F5 efficiency.

•  Unit floor stand with height adjusting rubber holders. It is not possible to match theunit floor stand with plenum installed under the machine.

•  Condensate drain kit including pump with activation float and 10 linear meters longdischarge pipe. The optional is supplied in mounting kit.

•  Sandwich panels with interposed mattress in soundproof material.•  Blind frontal panel. The accessory allows the intake air from the bottom of the

machine.

•  Unit base noise insulation with special bottom panel.•  Differential pressure switch on the air side for clogged filters alarm signal.

•  Loss of air flow alarm.•  Underfloor water alarm through sensor to be placed on the floor.

•  Additional underfloor water sensor kit.•  Temperature sensor on air delivery.•  Non-return air damper driven by electric servomotor for installation on the machine

air delivery.

•  Air distribution plenum with double row adjustable grilles on three sides.•  Air distribution plenum with double row adjustable grilles on front side and noise

absorption partitions.

•  Plenum with F6/F7/F9 efficiency filters on air delivery.•  Plenum with noise absorption partitions on air delivery .•  MP.COM microprocessor control accessories:

- MP3000 Touch Screen graphic display.- Remote terminal

- Clock card for alarms date and time displaying and storing.- Line current indication.- Line voltage indication.- Serial port RCcom, MBUS/JBUS- Serial port LON- Serial port BACnet for Ethernet – SNMP – TCP/IP- Serial port BACnet for MS/TP- Serial port for GSM modem- Data logger for the memorization of the intervened alarms.- Additional module with the following inlets / outlets:

INLETSo  External alarmo  Smoke / Fire alarmo  Cooling enablingo

  Heating enablingOUTLETSo  External alarm 2o  General alarm 3

- Driver for the additional module.

WARNINGRC GROUP reserves the right to accept the matching of the optional installed on themachine.

Page 9: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 9/32

neXt mtr

9RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

TECHNICAL DATA - NEXT MTR DX

MODEL 007 Z1 009 Z1 011 Z1 013 Z1 015 Z1S S S S S

SIZE H2 H2 H2 H3 H3COOLING CAPACITY (1)Total kW 6,6 8,7 9,8 11,3 14,4Sensible kW 6,6 8,7 9,8 11,3 14,4Compressors power input kW 1,5 1,8 2,2 2,7 3,3Compressors operating current A 2,8 3,4 4,2 5,0 6,1

SUPPLY FANS n. 1 1 1 1 1Air flow m /h 2300 3000 3300 4000 5500Nominal external static pressure Pa 50 50 50 50 50Max external static pressure Pa 625 530 480 600 640Power input (2) kW 0,12 0,22 0,27 0,29 0,64Max power input kW 1,0 1,0 1,0 2,7 2,7Operating current (2) A 0,26 0,48 0,60 0,45 1,00Max operating current (FLA) A 2,2 2,2 2,2 4,30 4,30

COMPRESSORS scroll scroll scroll scroll scrollQuantity n. 1 1 1 1 1Max current A 4,2 5,1 6,3 7,0 10,0Starting current A 24 32 40 46 50Capacity steps n. Modulating Modulating

 Modulating

 Modulating

 Modulating

 AIR FILTERS n. 1 1 1 1 1Efficiency G4 G4 G4 G4 G4

REFRIGERANT R407C R407C R407C R407C R407CRefrigerant charge (3) kg 5,4 5,4 5,4 6,8 6,8Gas circuits n. 1 1 1 1 1

POWER SUPPLY V/Ph/Hz 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+NENERGY EFFICIENCY INDEXESEER – Energy Efficiency Ratio (4) kW/kW 3,75 3,70 3,45 3,38 3,31

SOUND LEVEL – ISO 3744 (5)On air delivery dB(A) 54,5 59,3 61,1 59,0 65,3On air intake dB(A) 54,4 54,8 55,1 55,9 57,1

DIMENSIONSLength mm 785 785 785 1085 1085Width mm 650 650 650 750 750Height mm 1925 1925 1925 1925 1925

NET WEIGHT k 235 238 244 295 305REMOTE CONDENSER (6)Quantity n. 1 1 1 1 1TEAM MATE STD series Mod. M.10 M.18 M.18 M.18 M.22

HOT GAS REHEATING SYSTEM Modulatin Modulatin   Modulatin   Modulatin   Modulatin  Heating capacity kW 7,7 8,4 9,0 10,6 11,9

ELECTRIC HEATERCapacity kW 5,1 5,1 5,1 6,0 6,0Operating current (OA) A 7,4 7,4 7,4 8,6 8,6Capacity steps n. 3 3 3 3 3

HUMIDIFIERSteam capacity kg/h 3 3 3 3 3Power input kW 2,3 2,3 2,3 2,3 2,3Operating current (OA) A 3,2 3,2 3,2 3,2 3,2Max operating current (FLA) A 4,5 4,5 4,5 4,5 4,5

REFRIGERANT CONNECTIONSGas delivery ODS Ø 16 16 16 18 18Liquid return ODS Ø 12 12 12 16 16

CONNECTIONS ISO 228/1-GHumidifier filling F Ø 3/4" 3/4" 3/4" 3/4" 3/4"Condensate discharge – rubber pipe F Ø 1/2" 1/2" 1/2" 1/2" 1/2"

THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD1. Characteristics referred to entering air at 24°C-50%RH; 35°C ambient temperature.2. Corresponding to the nominal external static pressure3. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.4. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the

table.5. Noise level at 1 meter in free field (external static pressure 50 Pa)

6. For matching to other remote air cooled condensers please refer to RC WORLD selectionprogram

Page 10: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 10/32

neXt mtr 

10 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

TECHNICAL DATA - NEXT MTR DW

MODEL 007 Z1 009 Z1 011 Z1 013 Z1 015 Z1S S S S S

SIZE H2 H2 H2 H3 H3COOLING CAPACITY (1)

Total kW 7,0 8,9 10,3 12,3 15,3Sensible kW 7,0 8,9 10,1 12,3 15,3Compressors power input kW 1,2 1,6 1,9 2,2 2,6Compressors operating current A 2,5 3,2 3,9 4,4 5,4Condenser water flow rate m /h 1,2 1,5 1,8 2,1 2,6Condenser pressure drop kPa 19 24 23 21 15

SUPPLY FANS n. 1 1 1 1 1Air flow m /h 2300 3000 3300 4000 5500Nominal external static pressure Pa 50 50 50 50 50Max external static pressure Pa 625 530 480 600 640Power input (2) kW 0,12 0,22 0,27 0,29 0,64Max power input kW 1,0 1,0 1,0 2,7 2,7Operating current (2) A 0,26 0,48 0,60 0,45 1,00Max operating current (FLA) A 2,2 2,2 2,2 4,30 4,30

COMPRESSORS Scroll Scroll Scroll Scroll ScrollQuantity n. 1 1 1 1 1Max current A 4,2 5,1 6,3 7,0 10,0Starting current A 24 32 40 46 50Capacity steps n. Modulating Modulating  Modulating  Modulating  Modulating 

WATER COOLED CONDENSER n. 1 1 1 1 1Water volume l 0,8 0,9 1,0 1,3 1,4Max water flow rate m /h 0,6 0,8 1,0 1,1 1,4

AIR FILTERS n. 1 1 1 1 1Efficiency G4 G4 G4 G4 G4

REFRIGERANT R407C R407C R407C R407C R407CRefrigerant charge (3) kg 5,8 5,8 5,8 7,5 7,5Gas circuits n. 1 1 1 1 1

POWER SUPPLY V/Ph/Hz 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+NENERGY EFFICIENCY INDEXES

EER – Energy Efficiency Ratio kW/kW 5,22 4,94 4,68 4,88 4,59SOUND LEVEL – ISO 3744 (4)

On air delivery dB(A) 55,0 59,8 61,6 59,3 65,6On air intake dB(A) 54,4 54,8 55,1 55,9 57,1

DIMENSIONSLength mm 785 785 785 1085 1085Width mm 650 650 650 750 750Height mm 1925 1925 1925 1925 1925

NET WEIGHT k 239 242 249 300 312HOT GAS REHEATING SYSTEM Modulatin Modulatin   Modulatin   Modulatin   Modulatin  

Heating capacity kW 7,7 8,4 9,0 10,6 11,9ELECTRIC HEATER

Capacity kW 5,1 5,1 5,1 6,0 6,0Operating current (OA) A 7,4 7,4 7,4 8,6 8,6Capacity steps n. 3 3 3 3 3

HUMIDIFIERSteam capacity kg/h 3 3 3 3 3Power input kW 2,3 2,3 2,3 2,3 2,3Operating current (OA) A 3,2 3,2 3,2 3,2 3,2Max operating current (FLA) A 4,5 4,5 4,5 4,5 4,5

CONNECTIONS ISO 228/1-GCondenser water inlet/outlet M Ø 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4"Humidifier filling F Ø 3/4" 3/4" 3/4" 3/4" 3/4"Condensate discharge – rubber pipe F Ø 1/2" 1/2" 1/2" 1/2" 1/2"

THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMALLOAD

1. Characteristics referred to entering air at 24°C-50%RH; water to the condenser 30-36°C

2. Corresponding to the nominal external static pressure3. Unit refrigerant charge optional excluded.4. Noise level at 1 meter in free field (external static pressure 50 Pa)

Page 11: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 11/32

neXt mtr

11RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

WORKING LOGIC

The control of temperature and humidity conditions, with very small tolerances, are obtainedwith a proportional working logic of the system which provides continuous anduninterrupted operation of the compressor (H) (MAN ON set on microprocessor) for thesimultaneous production of cooling and heating.

Temperature control:During cooling phase the system produce only sensible cooling, without dehumidification

This is done by raising the expansion temperature by increasing the fan speed automatically(by 0-10V proportional signal from microprocessor) and by hot gas injection in the evaporatingcoil (B) though the valve (M) until you cancel the latent component of the cooling produced bythe evaporating coil.

Any excess of cooling is canceled by the proportional hot gas reheating system (C+I) thatuses the hot gas from the compressor to reheating the air flow.

The accuracy of the hot gas reheating system is obtained through a proportional valve withcontinuous control (I) directly driven by 0-10V proportional signal from microprocessor.

The excess of condensation heat, not used by the hot gas reheating system, is exhausted bythe condenser (U).

•  DX version: remote air cooled condenser equipped with axial fans and modulatingcondensing control system. Condensers are also available with centrifugal fans.

•  DW version: built-in water cooled condenser equipped with 2-way modulating valvefor the water flow control.

In case of heating request, primarily using the hot gas reheating system and, if it is notsufficient, the 3 steps electric heaters (D) are activated (in combination with the hot gasreheating system).The steps of the electric heaters are very close and allow a precise temperature control.

Humidity control :In case of dehumidification request, the system automatically controls the latent coolingcapacity by producing cool with forced dehumidification through a reduction of the supply fanrotation speed (by 0-10V proportional signal from microprocessor) and closing the hot gasinjection valve (M). In this way the expansion temperature decrease and consequently thelatent cooling component increase.

Also in this case any excess of sensible cooling is compensated by the hot gas reheating colias previously described.

The humidification is obtained by the proportional steam humidifier with immersed electrodes(G). The humidifier is oversized compared to the standards used in traditional air conditioners.

NOTE : To avoid any potential conflict of the regulation control, the system always has priorityon the control of temperature.Only after reaching the temperature set-point the system begins to control the humidity.

Page 12: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 12/32

neXt mtr 

12 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

A

B

C

D

E

F

H

G

LI

MN

O

P

Q

RR

RR

S

U

R

T

A Air filtersB Evaporating coilC Hot gas re-heating coilD Electric heatersE Steam distributorF Supply fanG Steam humidifierH CompressorI Hot gas re-heating 3-way valveL Check valve

M Hot gas injection valveN Balancing valveO Expansion valveP Liquid indicatorQ Refrigerant filterR Manual valveS Safety valveT Liquid receiverU Remote air cooled condenser

NEXT MTR DX – WORKING DIAGRAM

Page 13: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 13/32

neXt mtr

13RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

A

B

C

D

E

F

H

G

LI

MN

O

P

Q

RS

U

V

T

NEXT MTR DW – WORKING DIAGRAM

A Air filters

B Evaporating coilC Hot gas re-heating coilD Electric heatersE Steam distributorF Supply fanG Steam humidifierH CompressorI Hot gas re-heating 3-way valveL Check valve

M Hot gas injection valve

N Balancing valveO Expansion valveP Liquid indicatorQ Refrigerant filterR Manual valveS Safety valveT Liquid receiverU Built-in water cooled condenserV 2-way motorized valve for condensing control

water flow

Page 14: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 14/32

neXt mtr 

14 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

BASIC PARAMETERS FOR THE NEXT MTR

The compressor must be set MANUAL ON.

Here's an example of the restrictive temperature / humidity parameters setting :

Page 15: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 15/32

neXt mtr

15RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

Page 16: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 16/32

Page 17: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 17/32

Page 18: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 18/32

neXt mtr 

18 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

1 4 54 632 7 8

M P . C O M   g r a p h i c i n t e r f a c e

13:35 - S -  nn - 21/01/07

°C 22.4 %53rH

%

1 2

MP.COM: MICROPROCESSOR CONTROL SYSTEM 

The MP.COM microprocessor control system is equipped with 8 keys terminal and backlighted graphic display on which all information in different languages or easily identifiablesymbols are displayed.The system disposes of a “flash” memory that preserves the information even in absence ofpower supply.

KEYBOARD FUNCTIONS

KEY 1 Switches on/off the unit.

KEY 2 Stops the alarm acoustical signal and displays the intervened alarm.

KEY 3 Accedes to the parameters of possible units connected in LAN network.LAN connection with 3 wires without additional accessories. It is possible to connectin network different capacity units and with different number of compressors.

KEY 4 Home key – displays the main screen.

KEY 5 Accedes to control and visualization menus as:- Unit working status- Set-points- Alarms reset (protected by password)- Service parameters setting (protected by password)- Intervened alarms history- Setting for main components manual operation (protected by password)- Date and time setting- Setting of communication system for SMS messages dispatch

KEY 6 Scrolls the pages inside each menu and decreases the displayed value

KEY 7 Scrolls the pages inside each menu and increases the displayed value

KEY 8 Shifts the cursor inside each menu and confirms a parameter insertion

REMOTE CONTROLS/ALARMS

INLETS1 External enabling •2 Cooling enabling •3 Smoke/Fire alarm •4 Temperature set-point compensation (optional) •

OUTLETS1 General alarm 1 – deviating contact ••2 General alarm 2 – programmable deviating contact (optional) ••3 General alarm 3 - programmable deviating contact (optional) ••

4 Clogged filters alarm (optional) ••

• controls/alarms for remotization•• voltage free controls/alarms for remotization

Page 19: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 19/32

neXt mtr

19RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

OPTIONAL ACCESSORIES – REMOTE AIR COOLED CONDENSER

Remote air cooled condenser series TEAM MATE with horizontal air flow, from coil to fan.

The machines are made with weather resistant materials and suitable for outdoor installation.

Design, assembly and test as per the Company Quality Assurance program in full compliance

with ISO 9001. RC Group has been the first Italian company in its segment to get the ISO9001 in October 13

th, 1991 with certificate ICIM 0018.

The machines are in full compliance with European Norms 2006/42CE, 2006/95CE,2004/108CE, 97/23CE and subsequent amendments.

AVAILABLE VERSIONSThe TEAM MATE series is available in 3 versions:

•  TEAM MATE STD - No air flow and sound level reduction

•  TEAM MATE LNO – Air flow reduction at 85% with consequent sound levelreduction.

•  TEAM MATE ELN – Air flow reduction at 70% with further sound level reduction.

MAIN COMPONENTS

FRAMEWORK

•  Base, self supporting frame and panelling in steel plate with protective surfacestreatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and paintedwith epoxy powders.

•  Colour: RAL 9002

FANS SECTION•  Axial fans with sickle-shaped blades, fan guard and optimized for low noise levels.•  External rotor electric motor with stepless variable speed for condensing pressure

control.

•  IP54 enclosure class.

CONDENSING COIL

•  Heat exchanger coil with internally corrugated copper tubes and high efficiencyaluminium fins, specifically developed to provide high heat transfer and lowerpressure drops. The combination of two factors, special tubes and fins, allow tooptimally combine the following aspects:- Maximum capacity relative to the size of the exchanger.- Minimum charge of refrigerant.- Reduction of the air flow required for the heat exchange.

•  Frame in galvanized steel.

REFRIGERANT CIRCUIT•  Valves on gas and liquid line for coupling to refrigerant pipe. The condenser is

supplied with nitrogen seal.

ELECTRICAL PANELIn accordance with EN60204-1 norms, suitable for outdoor installation, IP54 enclosure class,

complete with:•  Terminals for 230/1/50 power supply (from network).

•  Terminals for 0÷10V signal for condensing control system (connect to indoormachine).

•  Terminals for alarm signal (connect to indoor machine).•  Fans speed regulator for condensing control.

OPTIONAL ACCESSORY

•  Support legs for vertical air flow.

Page 20: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 20/32

neXt mtr 

20 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

TECHNICAL DATA

TEAM MATE DXA STD

MODEL M 10 M 18 M 22AXIAL FANS n. 1 1 1Air flow m³/h 3400 4400 5600Max power input kW 0,19 0,35 0,40Max operating current (FLA) A 0,86 2,00 2,20SOUND PRESSURE LEVEL (1) dB(A) 57,0 59,0 58,0

TEAM MATE DXA LNO

MODEL M.10 M.18 M.22AXIAL FANS n. 1 1 1Air flow m³/h 2890 3740 4760Max power input kW 0,16 0,3 0,34Max operating current (FLA) A 0,73 1,7 1,87SOUND PRESSURE LEVEL (1) dB(A) 54,2 55,7 55,7

TEAM MATE DXA ELN

MODEL M.10 M.18 M.22AXIAL FANS n. 1 1 1

Air flow m³/h 2380 3080 3920Max power input kW 0,13 0,25 0,28Max operating current (FLA) A 0,6 1,4 1,54SOUND PRESSURE LEVEL (1) dB(A) 50,8 52,3 52,3

COMMON DATA

POWER SUPPLY V/ph/Hz 230/1/50 230/1/50 230/1/50REFRIGERANT CHARGE (2) kg 9,9 9,9 10,6DIMENSIONS

Version with horizontal air flow

Length mm 855 855 1155Width mm 482 482 482Height mm 726 726 726

Version with vertical air flow

Length mm 855 855 1155Width mm 786 786 786Height mm 750 750 750

NET WEIGHT kg 31 31 47

1. Sound pressure level [Lp] 1m far according to ISO EN 3744.2. The condenser is supplied with nitrogen seal. For the refrigerant charge consider, in

addition to the these value, even the refrigerant pipes for the connection to the indoormachine and lubricant oil in 10% ratio of charged refrigerant.

Page 21: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 21/32

neXt mtr

21RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

OPTIONAL ACCESSORIES - CONDENSATE DISCHARGE PUMP

A plastic case contains the vertical type pump, the water tank with float plus safety switch andhydraulic and electric connection.Together the pump 10 linear meters anti-crushing plastic discharge spiral tube is suppliedThe optional has to be installed as shown in the documentation delivered together with theunit.Wiring includes power supply and an alarm, displayed on microprocessor, that includes motor

pump thermal protection and tank overflow.The condensate discharge pump operation is fully automatic.

WARNINGThe optional is supplied in mounting kit.

TECHNICAL DATAPower supply 230/1/50Power input W 75Absorbed current A 0,5Capacity tank l 2Discharge pipe Ø mm 10/16Maximum water flow l/h 300Minimum water flow l/h 3

Discharge head- with min. water flow mH2O 4,5- with max. water flow mH2O 0,3

CONDENSATE DISCHARGE PUMP

Condensate discharge ∅ 3/8”

Condensate inlet

∅ 28

Page 22: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 22/32

neXt mtr 

22 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

   8   2

   H

63 63 A

OPTIONAL ACCESSORIES - FLOOR STAND

It is not possible to match the unit floor stand with plenum installed under the machine.For a correct installation of the air conditioner we suggest you to utilize a gasket between thefloor stand and the unit base.The floor stand is available in 3 different heights. 

SIZE H2 H3

A mm 691 791

MODEL 230 330 390

H minimum height mm 255 355 400

H maximum height mm 350 450 510

FLOOR STAND

Page 23: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 23/32

neXt mtr

23RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

1

2

4

3

OPTIONAL ACCESSORIES - BOTTOM PANEL

With this accessory it is possible a noise insulation of the machine base, when the machine isinstalled directly on particular floor as raised floor, wood floor etc.The accessory includes:• Panel in galvanized steel sheet.• Noise insulation with special soundproof material.

The bottom panel is supplied assembled inside the unit base and does not modify the unitdimensions. 

OPTIONAL ACCESSORIES - SANDWICH PANEL

The accessory includes:• External part as standard panel.

• Internal part in galvanized steel sheet.• Noise insulation with special soundproof material.

The accessory increase the unit weight:

1. Add this value to the total unit weight

Size H2 H3

Weight increasing kg 43 54

BOTTOM PANEL

1) Air conditioner2) Air conditioner base3) Bottom panel4) Insulation with special sound soundproof material 

Page 24: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 24/32

neXt mtr 

24 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

OPTIONAL ACCESSORIES - NON RETURN MOTORIZED DAMPER

Accessory to install on units air delivery and it can be matched to air conditioner, plenums andfloor stand.The damper is provided with connecting flange for the air delivery duct.For a correct installation we suggest you to utilize a gasket between the damper and the unitor the plenum.

1. Add this value to the total unit weight

Size H2 H3

A mm 785 1085

B mm 650 750C mm 450 750

D mm 510 610

E mm 214 214

F mm 73 73

G mm 48 48

Weight (1) kg 23 30

NON RETURN MOTORIZED DAMPER

1) Non return damper

2) Gasket3) Air conditioner 

Page 25: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 25/32

neXt mtr

25RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

OPTIONAL ACCESSORIES - AIR DELIVERY PLENUM

The plenums have same technical characteristics and base dimensions of the machinecabinet.

1. Add this value to the total unit weight

FOR ALL PLENUMS

Size H2 H3

Plenum (1) kg 21 20Plenum with filters (1) kg 27 27Plenum with partitions (1) kg 27 30

Size H2 H3

Plenum with grilles (1) kg 26 28Plenum with grilles and partitions (1) kg 30 37

Size H2 H3

Plenum with grilles (1) kg 23 30

Size H2 H3A mm 490 490

NEXT MTR PLENUM

•  Plenum for ducting

•  Plenum for ducting with F6/F7/F9efficiency filters

•  Plenum for ducting with noise absorptionpartitions

• Plenum with grille for frontal airdistribution into the room andnoise absorption partitions

• Plenum with grilles on 3 sides, fordirect air distribution into the room.

Page 26: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 26/32

neXt mtr 

26 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

OPTIONAL ACCESSORIES – MP.COM REMOTE TERMINAL

The remote terminal is supplied in kit and includes a painted steel sheet box contained theTerminal and the “T” card for the connection to the unit.The box has a wall mounting predisposition.With the remote terminal it is possible the remote management of all the units connected inLAN network (max 10 units).

MP.COM REMOTE TERMINAL

1) LCD display with keyboard2) Rubber fairlead 16MV3) “T” card for connection4) Wall mounting box 

Page 27: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 27/32

neXt mtr

27RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

MACHINE DRAWINGSDimensions in mm

NEXT MTR H2

Page 28: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 28/32

neXt mtr 

28 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

MACHINE DRAWINGSDimensions in mm

NEXT MTR H3

Page 29: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 29/32

neXt mtr

29RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES

WITH REMOTE AIR COOLED CONDENSER 

WARNINGIt is necessary to provide the refrigerant charge for the connection pipes and for theremote air cooled condenser.

Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of chargedrefrigerant.Lubricant oil must be the same type as the charged one as shown on the compressorplate.

1) Air conditioner2) Remote air cooled condenser3) Gas discharge line4) Liquid line

5) Trap. Foresee a trap every 5m of the rising pipe.6) Additional liquid receiver external to the conditioner with valves and safety valve.Suggested part in the following cases:a) refrigerant line longer than 25-30mb) plant operation with ambient temperature lower than 0°C with refrigerant line any lengthInstall the liquid receiver close to the air conditioner.

7) Solenoid valve of the liquid l ine. It is an optional accessory of the air conditioner for refrigeration plants withrefrigerant pipe longer than 10m

THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT. 

Page 30: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 30/32

neXt mtr 

30 RC GROUP S.p.A. ● T_NXTMTR_0511_GB ● R407C

 

TYPICAL INSTALLATION DIAGRAMS FOR DIRECT EXPANSION MACHINES WITHREMOTE AIR COOLED CONDENSER 

WARNINGIt is necessary to provide the refrigerant charge for the connection pipes and for the

remote air cooled condenser.Charge refrigerant in the suitable quantity and lubricant oil in 10% ratio of chargedrefrigerant.Lubricant oil must be the same type as the charged one as shown on the compressorplate.

1) Air conditioner2) Remote air cooled condenser3) Gas discharge line4) Liquid line5) Non - return valve.6) Additional liquid receiver external to the conditioner with valves and safety valve.

Install the liquid receiver close to the air conditioner.7) Solenoid valve of the liquid line. It is an optional accessory of the air conditioner for refrigeration plants with

refrigerant pipe longer than 10m

THIS DIAGRAM APPLIES TO EACH REFRIGERANT CIRCUIT OF THE UNIT. 

Page 31: t Nxtmtr 0511 Gb

8/10/2019 t Nxtmtr 0511 Gb

http://slidepdf.com/reader/full/t-nxtmtr-0511-gb 31/32

neXt mtr

31RC GROUP S.p.A. ● T_NXTMTR_0511_IT ● R407C

EXAMPLE FOR MACHINES NOISE EMISSION CALCULATION

IMPORTANTThe declared noise levels are intended in free field conditions.The noise pressure level of an installed unit is affected by the room acousticcharacteristics. Please consider an average noise increase of +4/+6 dB(A).

NEXT MTR WITH DUCT

Lp A = Air intake Over catalogue value

Lp B = Air delivery Over catalogue value

The point B do not influence the point A 

NEXT MTR WITH PLENUM ON AIR DELIVERY

Lp A = Air intake Over catalogue value

Lp B = Air delivery Over catalogue value – plenum noise reduction

Lp A+B = 10 log10(10 +10 )LpA10

LpC10 

NEXT MTR WITH DUCT AND PLENUM ON AIR DELIVERY

Lp A = Radiated Over catalogue value 

Lp B = Air delivery Over catalogue value

Lp C = Lp A + 6dB(A) – plenum noise reduction

Lp A+C = 10 log10(10 +10 )

The point B do not influence the point A+C 

LpA10

LpC10 

NEXT MTR WITH DUCT AND PLENUM ON AIR SUCTION

Lp A = Radiated Over catalogue value

Lp B = Air delivery Over catalogue value

Lp C = Lp D = Lp A + 6 dB(A) – plenum noise reduction

The points B, C and D do not influence the point A 

Blind front panel

Blind front panel