+ All Categories
Home > Documents > TA-COMPACT-P - IMI Hydronic Engineering - ESC · The pressure independent balancing and control...

TA-COMPACT-P - IMI Hydronic Engineering - ESC · The pressure independent balancing and control...

Date post: 28-Aug-2018
Category:
Upload: vungoc
View: 253 times
Download: 4 times
Share this document with a friend
8
TA-COMPACT-P Combined control & balancing valves for small terminal units Pressure independent balancing and control valve (PIBCV)
Transcript

TA-COMPACT-P

Combined control & balancing valves for small terminal unitsPressure independent balancing and control valve (PIBCV)

IMI TA / Control valves / TA-COMPACT-P

2

TA-COMPACT-PThe pressure independent balancing and control valve TA-COMPACT-P ensures optimum performance over a long life. Adjustable maximum fl ow enables design fl ow and eliminates over fl ows for accurate hydronic control. The TA-COMPACT-P together with our balancing instruments enables advanced measuring and diagnostics.

Key features

> Precise hydronic balancingSmoothly adjustable setting of max. fl ow prevents over fl ow through terminal unit.

> Installations without limitsSlim and compact shape simplifi es installation, one side access to all functions simplifi es operation.

> Full control of the systemExact fl ow measuring and unique diagnostic functions for ultimate energy savings and highly reliable system.

> High reliability AMETAL® and stainless steel guarantees high corrosion resistance and reduces the risk of leakage.

Technical description

Application:Heating and cooling systems.

Functions:ControlPre-setting (max. fl ow)Differential pressure controlMeasuring (ΔH, T, q)Shut-off (for isolation during system maintenance – see also Leakage rate)

Dimensions:DN 10-32

Pressure class:PN 16

Differential pressure (ΔpV):Max. differential pressure (ΔpVmax):400 kPa = 4 barMin. differential pressure (ΔpVmin):DN 10-20: 15 kPa = 0,15 barDN 25-32: 23 kPa = 0,23 bar(Valid for position 10, fully open. Other positions will require lower differential pressure, check with the software HySelect.)ΔpVmax = The maximum allowed pressure drop over the valve, to fulfi ll all stated performances.ΔpVmin = The minimum recommended pressure drop over the valve, for proper differential pressure control.

Flow range:The fl ow (qmax) can be set within the range:DN 10: 21,5 - 120 l/hDN 15 LF: 44 - 245 l/hDN 15: 88 - 470 l/hDN 20: 210 - 1150 l/hDN 25: 370 - 2150 l/hDN 32: 800 - 3700 l/hqmax = l/h at each setting and fully open valve plug.LF = Low fl ow

Temperature:Max. working temperature: 90°CMin. working temperature: 0°C

Media:Water or neutral fl uids, water-glycol mixtures.

Lift:4 mm

Leakage rate:Leakage fl ow ≤ 0,01% of max. qmax

(setting 10) and correct fl ow direction. (Class IV according to EN 60534-4).

Characteristics:Linear, best suited for on/off control.

Material:Valve body: AMETAL®

Valve insert: AMETAL®

Valve plug: Stainless steelSpindle: Stainless steelSpindle seal: EPDM O-ringΔp insert: PPSMembrane: EPDM and HNBRSprings: Stainless steelO-rings: EPDM

AMETAL® is the dezincifi cation resistant alloy of IMI Hydronic Engineering.

Marking:TA, IMI, PN 16, DN and fl ow direction arrow.Grey handwheel: TA-COMPACT-P and DN. For low fl ow version also LF.

Connection:Male thread according to ISO 228.

Connection to actuator:M30x1,5

Actuators:See separate information on EMO T.

3

Measuring accuracy

Maximum fl ow deviation at different settings

*) Setting (%) of fully open valve.

Correction factors

The fl ow calculations are valid for water (+20°C). For other liquids with approximately the same viscosity as water (≤20 cSt = 3°E=100S.U.), it is only necessary to compensate for the specifi c density. However, at low temperatures, the viscosity increases and laminar fl ow may occur in the valves. This causes

a fl ow deviation that increases with small valves, low settings and low differential pressures. Correction for this deviation can be made with the software HySelect or directly in our balancing instruments.

Noise

In order to avoid noise in the installation the valve must be correctly installed and the water de-aerated.

Actuators

Actuator EMO TFor more details of EMO T, see separate catalogue leafl et.TA-COMPACT-P is developed to work together with the EMO T actuator. Actuators of other brands require;Working range: X (closed - fully open) = 11,6 - 15,8Closing force: Min. 125 N (max. 500 N)

IMI Hydronic Engineering will not be held responsible for the control function if actuators other brand than IMI TA are used.

Max. recommended pressure drop (ΔpV) for valve and actuator combinationThe maximum recommended pressure drop over a valve and actuator combination for close off (ΔpVclose) and to fulfi ll all stated performances (ΔpVmax).

DN EMO T * [kPa]

10

40015202532

*) Closing force 125 N.ΔpVclose = The maximum pressure drop that the valve can close against from an opened position, with a specifi ed force (actuator) without exceeding stated leakage rate.ΔpVmax = The maximum allowed pressure drop over the valve, to fulfi ll all

stated performances.

02468

1012141618202224

0 20 40 60 80 100[%] *

± %

10 30 50 70 90

Ø22

10X

M30x1,5

IMI TA / Control valves / TA-COMPACT-P

4

Sizing

1. Choose the smallest valve size that can obtain the design fl ow with some safety margin, see “qmax values”. The setting should be as open as possible.

2. Check that the available ΔpV is within the working range 15-400 kPa or 23-400 kPa.

qmax values

Position

1 2 3 4 5 6 7 8 9 10 DN 10 21,5 39,5 54,0 68,5 80,0 91,0 99,0 107 113 120DN 15 LF 44,0 71,0 97,0 123 148 170 190 210 227 245DN 15 88,0 150 200 248 295 340 380 420 450 470DN 20 210 335 460 575 680 780 890 990 1080 1150DN 25 370 610 830 1050 1270 1490 1720 1870 2050 2150DN 32 800 1220 1620 2060 2450 2790 3080 3350 3550 3700

qmax = l/h at each setting and fully open valve plug.

LF = Low fl ow

Installation

Application example

Flow direction

Installation of actuator EMO TApprox. 15 mm of free space is required above the actuator.

TA-COMPACT-P + EMO T

TA-COMPACT-P TA-COMPACT-P

TA-COMPACT-P TA-COMPACT-P

TA-COMPACT-P TA-COMPACT-P

~15 mm

DN 10-20: 107 mmDN 25-32: 113 mm

IP54 IP54 IP54 IP54

5

Operating function

Setting

1. Turn the setting wheel to desired value, e.g. 5.0.

Shut-off

1. Turn the setting wheel clockwise to X.

Measuring q1. Remove any actuator.2. Connect IMI TA balancing instrument to the measuring points.3. Input the valve type, size and setting and the actual fl ow is displayed.

Measuring ΔH

1. Remove any actuator.2. Close the valve according to “Shut-off”.3. Bypass the Δp part by opening the bypass spindle ≈1 turn anticlockwise, with a 5 mm Allen key.4. Connect IMI TA balancing instrument to the measuring points and measure.Important! Close the bypass spindle after the measurement is completed.

IMI TA / Control valves / TA-COMPACT-P

6

Articles

Male threadThreads according to ISO 228

DN D L H1 H2 B qmax [l/h]

Kg EAN Article No

10 G1/2 74 55 55 54 120 0,53 7318794013308 52 164-01015 LF G3/4 74 55 55 54 245 0,54 7318794025202 52 164-11515 G3/4 74 55 55 54 470 0,54 7318794013407 52 164-01520 G1 85 64 55 64 1150 0,69 7318794013506 52 164-02025 G1 1/4 93 64 61 64 2150 0,79 7318794013605 52 164-02532 G1 1/2 112 78 61 78 3700 1,5 7318794013704 52 164-032

LF = Low fl ow

*) Connection to actuator.

→ = Flow direction

Connections

With female threadThreads according to ISO 228. Thread length according to ISO 7-1.Swivelling nut

Valve DN D D1 L* EAN Article No

10 G1/2 G3/8 21 7318794016804 52 163-01015 G3/4 G1/2 21 7318794016903 52 163-01520 G1 G3/4 23 7318794017009 52 163-02025 G1 1/4 G1 23 7318794017108 52 163-02532 G1 1/2 G1 1/4 31 7318794017207 52 163-032

With male threadThreads according to ISO 7-1.Swivelling nut

Valve DN D D1 L* EAN Article No

10 - - - - -15 G3/4 R1/2 29 4024052516612 0601-02.35020 G1 R3/4 32,5 4024052516810 0601-03.35025 G1 1/4 R1 35 4024052517015 0601-04.35032 - - - - -

Welding connectionSwivelling nut

Valve DN D Pipe DN L* EAN Article No

10 G1/2 10 30 7318792748400 52 009-01015 G3/4 15 36 7318792748509 52 009-01520 G1 20 40 7318792748608 52 009-02025 G1 1/4 25 40 7318792748707 52 009-02532 G1 1/2 32 40 7318792748806 52 009-032

*) Fitting length (from the gasket surface to the end of the connection).

L

D

H2

M30x1,5*

ØB

H1

D D1

L

D D1

L

L

7

Soldering connectionSwivelling nut

Valve DN D Pipe Ø L* EAN Article No

10 G1/2 10 10 7318792749100 52 009-51010 G1/2 12 11 7318792749209 52 009-51215 G3/4 15 13 7318792749308 52 009-51515 G3/4 16 13 7318792749407 52 009-51620 G1 18 15 7318792749506 52 009-51820 G1 22 18 7318792749605 52 009-52225 G1 1/4 28 21 7318792749704 52 009-52832 G1 1/2 35 26 7318792749803 52 009-535

Connection with smooth endFor connection with press couplingSwivelling nut

Valve DN D Pipe Ø L* EAN Article No

10 G1/2 12 35 7318793810502 52 009-31215 G3/4 15 39 7318793810601 52 009-31520 G1 18 44 7318793810700 52 009-31820 G1 22 48 7318793810809 52 009-32225 G1 1/4 28 53 7318793810908 52 009-32832 G1 1/2 35 59 7318793811004 52 009-335

Compression connectionSupport bushes shall be used, for more information see catalogue leafl et FPL.Should not be used with PEX-pipes.Chrome plated

Valve DN D Pipe Ø L** EAN Article No

10 G1/2 8 16 7318793620002 53 319-20810 G1/2 10 17 7318793620101 53 319-21010 G1/2 12 17 7318793620200 53 319-21210 G1/2 15 20 7318793620309 53 319-21510 G1/2 16 25 7318793620408 53 319-21615 G3/4 15 27 7318793705006 53 319-61515 G3/4 18 27 7318793705105 53 319-61815 G3/4 22 27 7318793705204 53 319-62220 G1 28 29 7318793705402 53 319-928

*) Fitting length (from the gasket surface to the end of the connection).

**) Over all length L refers to unassembled coupling.

Accessories

Protection capFor TBV-C, TBV-CM, TBV-CMP, KTCM 512, TA-COMPACT-P. Red.

EAN Article No

7318793961105 52 143-100

L

L

D

L

IMI TA / Control valves / TA-COMPACT-P

The products, texts, photographs, graphics and diagrams in this document may be subject to alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up

to date information about our products and specifi cations, please visit www.imi-hydronic.com.

5-5-45 TA-COMPACT-P 01.2015