+ All Categories
Home > Documents > Technical Assessment of Solar PV System for Health Club Islamabad

Technical Assessment of Solar PV System for Health Club Islamabad

Date post: 26-Feb-2018
Category:
Upload: muhammad-saeed
View: 220 times
Download: 0 times
Share this document with a friend

of 19

Transcript
  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    1/19

    Technical Assessment of SolarPV System for Health Club

    Islamabad

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    2/19

    Contents1 Introduction .......................................................................................................................................... 3

    1.1 Background ................................................................................................................................... 3

    1.2 Site Description ............................................................................................................................. 3

    2 General Design ...................................................................................................................................... 4

    3 Load profile ........................................................................................................................................... 4

    4 System Design ....................................................................................................................................... 4

    5 Cost Assessment ................................................................................................................................... 6

    6 Conclusion ............................................................................................................................................. 7

    7 Annexure 1 ............................................................................................................................................ 88 Annexure 2 .......................................................................................................................................... 11

    9 Annexure 3 .......................................................................................................................................... 16

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    3/19

    1 Introduction

    1.1 Background

    1.2 Site DescriptionThe following site has been visited where the proposed Solar PV System will be

    installed:

    Health Club,

    Blue Area, Islamabad

    Coordinates:

    Latitude: 33.725470Longitude: 73.086826

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    4/19

    2 General DesignThe Solar PV System will provide electricity to the Health Club during load shedding

    hours with Figure 1 showing the design of the proposed Solar PV System. Electricity to

    the Health Club shall be provided either from the grid or by the battery bank, which

    will be charged through the PV generator, thus working essentially as a solar powered

    UPS.

    Figure 1: Possible Solar PV System Design

    3 Load profileThe Health Club has different electrical appliances and 2 kW constant load has been

    requested by the owner of the premises.

    4 System DesignLoad profile described above was input to the solar simulation software PV Sol*

    5.5 expert. Since the solar system will be designed as a UPS, thus the system has been

    designed as an off grid application.

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    5/19

    The model system is only example for possible system design and should not be

    considered as a final system recommendation. Prior to implementation of the project,

    detailed planning and designing will be required by the contractor. The model systems

    assumed for this study are poly-crystalline PV modules Yingli Solar YL240 P and 12 V

    165 Ah Sonnenschein Model Dryfit Solar Block SB 12/185 AS batteries are selected to

    provide electricity for load during the load shedding hours on daily basis.

    The Yingli modules represent the middle class standard for cost-efficient yet quality

    modules and are widely used for typical PV installations. The modules are rated at 240

    Wp, are TV certified according to IEC-standards and are delivered with a positive

    power tolerance of -0 W to +5 W. Power output warranty based on Nominal Power is 5

    years at 95%, 12 years at 90%, 18 years at 85% and 80% for 25 years. The completedatasheet can be found in the annex to this study.

    The following assumptions were made for the yield calculation:

    0 % row-to-row shading loses assumed Losses due to deviation from the standard solar spectrum 1 % Losses in diodes 0.5 % Losses due to mismatch or deviation of power rating from the manufacturers

    info 2% Losses in AC cabling were not considered Power degradation of PV modules 0.5 % of the original value per year One day of autonomy has been taken while a battery lower threshold of 30%

    has been selected

    Simulation report for a 2 kW load scenario is provided as Annexure 1.

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    6/19

    5 Cost AssessmentPreliminary cost analysis has been conducted to assess the potential Capital andOperating Costs for the designed solar PV system for 25 years and 10 years basis. Theresults of this analysis are provided in Table 1 below. It should be mentioned that these

    cost estimates are based on installation of the specific equipment mentioned earlier.Costs can vary considerably if different equipment is selected.

    Table 1: Cost Analysis for Solar PV System at Health Club

    10 Years 25 Years

    Load Requested Load: 2 kW Requested Load: 2 kW

    Club Timings (daily) From 0900 hours to 2100 hours From 0900 hours to 2100 hours)

    Load Requested2 kW constant load during plannedload shedding hours

    2 kW constant load duringplanned load shedding hours

    Planned Load Sheddinghours

    6 hours daily (one hour power cutafter each hour)

    6 hours daily (one hour powercut after each hour)

    Solar PV System Capacity 4.32 kWp 4.32 kWp

    Area Requirement 29.40 M2 29.40 M2

    Total Cost for 3.4 kWpSolar PV System

    1,702,150 1 1,702,150

    Total Cost Including ofO&M & Batteryreplacement over 25years (PKR)

    5,352,550 3,162,310

    Cost per kilowatt hour(kWh) (PKR)

    53.58 76.10

    1 Solar PV Modules, Solar Charger and Power Inverter and batteries Costs have been taken through internet andalso attached as annexures at the end of the document.

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    7/19

    6 Conclusion

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    8/19

    7 Annexure 1

    PV Sol Simulation Results

    Location: IslamabadClimate Data Record: Islamabad (1961-1990)

    PV Output: 4.32 kWpGross/Active PV Surface Area: 29.40 / 29.40 m

    PV Array Irradiation: 61,559 kWhEnergy Produced by PV Array: 7,048.8 kWh

    Converter Energy: 5,557.8 kWhConsumption Requirement: 4,380.0 kWh

    Consumption Covered by Solar Energy: 4,252.1 kWhConsumption Not Covered by System: 127.9 kWh

    Solar Fraction: 97.1 %Performance Ratio: 47.0 %

    Specific Annual Yield: 984.3 kWh/kWpCO2 Emissions Avoided: 2,612 kg/a

    System Efficiency: 6.9 %PV Array Efficiency: 11.5 %

    The results are determined by a mathematical model calculation. The actual yields of the photovoltaic systemcan deviate from these values due to fluctuations in the weather, the efficiency of modules and inverters, and other factors.The System Diagram above does not represent and cannot replace a full technical drawing of the solar system.

    2

    9

    18 x Yingli Solar YL240P-29b_IEC_2012-01 240 W

    30; 0

    8 x Sonnenscheindryfit solar block SB 12/185 AS165.0 Ah (C20); 2 x 12.0 V

    STUDER INNOTEC COMPACT 23242.3 kW

    Annual Energy Reqirement: 4380 kWhMax. Hourly Value: 2.00 kW

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    9/19

    System in Stand-Alone OperationLocation: Islamabad PV Output: 4.32 kWpClimate Data Record: Islamabad Gross/Active PV Surface Area: 29.4 m / 29.4 mNumber of Arrays: 1

    Array 1: Array NameOutput: 4.32 kW Ground Reflection: 20.0 %Gross/Active Solar SurfaceArea:

    29.4 m / 29.4 m Output Losses due to...

    PV Module 18 x deviation from AM 1.5: 1.0 %Manufacturer: Yingli Solar deviation from Manufacturer's

    Specification:2.0 %

    Model: YL240P-29b_IEC_2012-01 in Diodes: 0.5 %Nominal Output: 240 W due to Pollution: 0.0 %Power Rating Deviation: 0 % MPP TrackerEfficiency (STC): 14.7 % Hersteller-Typ-LeistungNo. of Modules in Series: 2 AC Power Rating: 5.0 kWMPP Voltage (STC): 59 V MPP Tracking Range: 14.8 V To 118.0 VOrientation: 0.0 Efficiency at Nominal Output: 92.0 %

    Inclination: 30.0 MPP Matching Efficiency: 85.0 %Mount: with VentilationShade: No

    BatteryManufacturer: Sonnenschein Mean Charge Efficiency: 85.0 %Model: dryfit solar block SB

    12/185 ASMean Discharge Efficiency: 99.0 %

    Nominal Voltage: 12.0 V Charge ControllerC20 Capacity: 165.0 Ah Lower Battery Discharge

    Threshold:30.0 %

    Self Discharge: 0.1 %/Tag

    Simulation Results for Total SystemIrradiation onto Horizontal: 54,610 kWh Battery Charge: 2,395 kWhPV Array Irradiation: 61,559 kWh Battery Losses: 384 kWhIrradiation minus Reflection: 59,166 kWh Charge Condition at Simulattion

    Start:55.4 %

    Energy Produced by PV Array: 7,049 kWh Charge Condition at SimulattionEnd:

    55.4 %

    Converter Energy: 5,558 kWh Solar Fraction: 97.1 %Consumption Requirement: 4,380 kWh Performance Ratio: 47.0 %Direct Use of PV Energy: 2,491 kWh Final Yield: 2.7 h/dConsumption Not Covered by

    System:128 kWh Specific Annual Yield: 984 kWh/kWp

    PV Array Surplus: 671 kWh System Efficiency: 6.9 %Consumption Covered by Solar

    Energy:4,252 kWh Array Efficiency: 11.5 %

    Battery Discharge: 2,012 kWh Inverter Efficiency: 94.4 %Battery Efficiency: 84.0 %

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    10/19

    Solar Energy Consumption as Percentage of Total Cosumption

    Electricity Requirement - Appliance 4,380 kWhConsumption Covered by Solar Energy 4,252 kWh

    Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

    k W h

    350300250200150100

    500

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    11/19

    8 Annexure 2Equipment Data Sheets

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    12/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    13/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    14/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    15/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    16/19

    9 Annexure 3Equipment Prices

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    17/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    18/19

  • 7/25/2019 Technical Assessment of Solar PV System for Health Club Islamabad

    19/19


Recommended