Technical Committee on
Residential Sprinkler Systems
M E M O R A N D U M
DATE: May 30, 2017
TO: Principal and Alternate Members of the Technical Committee on Residential
Sprinkler Systems
FROM: Chad Duffy, Senior Fire Protection Specialist/NFPA Staff Liaison
SUBJECT: AUT-RSS AGENDA PACKAGE – A2018 Second Draft Meeting
________________________________________________________________________
Enclosed is the agenda for the Second Draft meeting for NFPA 13D, Standard for the Installation
of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes and NFPA
13R, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies..
NFPA 13D and NFPA 13R have entered the Annual 2018 revision cycle and will produce 2019
Editions. It is imperative that you review the attached public comments in advance, with your ideas
and substantiations for your views. If you have alternate suggestions for text changes, please come
prepared with the words and respective substantiation.
For administrative questions, please feel free to contact Elena Carroll at (617) 984-7952.
For technical questions, please feel free to contact Chad Duffy at (617) 984-7562. You can
also reach either of us via e-mail at [email protected] or [email protected]. We look forward to
meeting everyone in Raleigh, NC at the Renaissance Raleigh North Hills Hotel.
1
Table of Contents
Part 1 - Meeting Agenda
Part 2 - Committee Address List
Part 3 – New Process Worksheets
Part 4 – A2018 First Draft Meeting Minutes
Part 5 - A2018 Key Dates
Part 6- RSS Public Comments
2
PART 1 –
MEETING AGENDA
3
Technical Committee on
Residential Sprinkler Systems
Second Draft Meeting
June 21-22, 2017 Renaissance Raleigh North Hills Hotel
4100 Main at North Hills Street
Raleigh, NC 27609
AGENDA
Wednesday, June 21, 2017
1. Call to Order – 8:00 AM
2. Introductions of Members and Staff
3. Review and Approval of A2018 First Draft Meeting Minutes
4. Review of A2018 Revision Cycle and Meeting Schedule
5. Review of Distributed Material and Workload
b. Overview of Public Comments
c. Overview of Potential Committee Second Revisions
6. Review Public Comments
Thursday, June 22, 2017
7. Reconvene 8:00AM (Time Subject to Change)
8. Review Public Comments/Generate Second Revisions
9. Adjournment TBD
4
PART 2 –
COMMITTEE ADDRESS LIST
5
Address List No PhoneResidential Sprinkler Systems AUT-RSS
Automatic Sprinkler Systems
David R. Hague05/25/2017
AUT-RSS
Kenneth E. Isman
ChairUniversity of Maryland7402 Forests Edge CourtLaurel, MD 20707
SE 10/1/1997AUT-RSS
Roland A. Asp
PrincipalNational Fire Sprinkler Association, Inc.514 Progress Drive, Suite ALinthicum, MD 21090Design TechnicianAlternate: Jon R. Ackley
M 10/28/2014
AUT-RSS
Kerry M. Bell
PrincipalUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Alternate: Jeff Hebenstreit
RT 4/15/2004AUT-RSS
Fred Benn
PrincipalAdvanced Automatic Sprinkler, Inc.1947 San Ramon Valley BoulevardSan Ramon, CA 94583Alternate: Dan Mendoza
IM 10/10/1997
AUT-RSS
Jonathan C. Bittenbender
PrincipalREHAU Incorporated1501 Edwards Ferry RoadLeesburg, VA 20176Alternate: David A. Nickelson
M 9/30/2004AUT-RSS
Frederick C. Bradley
PrincipalFCB Engineering9470 Dominion WayAlpharetta, GA 30022-6111
SE 1/16/1998
AUT-RSS
Chase A. Browning
PrincipalMedford Fire RescueDeputy Fire Marshal200 South Ivy Street, #180Medford, OR 97501-3100
E 08/17/2015AUT-RSS
Daniel Buuck
PrincipalNational Association of Home Builders1201 15th Street, NWWashington, DC 20005-2800National Association of Home BuildersAlternate: Gary Lampella
U 03/03/2014
AUT-RSS
Bradford T. Cronin
PrincipalNewport Fire Department21 West Marlborough StreetNewport, RI 02840-2527
E 11/30/2016AUT-RSS
Thomas G. Deegan
PrincipalViking Group, Inc.3033 Orchard Vista SE, Suite 308Grand Rapids, MI 49546-7077National Fire Sprinkler AssociationManufacturerAlternate: Thomas L. Multer
M 10/10/1997
AUT-RSS
Jeffrey Feid
PrincipalState Farm Insurance CompanyOne State Farm Plaza, D-1Bloomington, IL 61710-0001
I 10/20/2010AUT-RSS
Dawn M. Flancher
PrincipalAmerican Water Works Association6666 West Quincy AvenueDenver, CO 80235American Water Works Association
U 8/9/2011
16
Address List No PhoneResidential Sprinkler Systems AUT-RSS
Automatic Sprinkler Systems
David R. Hague05/25/2017
AUT-RSS
Dana R. Haagensen
PrincipalJENSEN HUGHESSenior Fire Protection Engineer117 Metro Center BoulevardWarwick, RI 02886JENSEN HUGHESAlternate: James R. Lugar
SE 08/03/2016AUT-RSS
Charles W. Ketner
PrincipalNational Automatic Sprinkler Fitters LU 669Joint Apprenticeship & Training Committee7050 Oakland Mills RoadColumbia, MD 20732United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting IndustryAlternate: Timothy J. Skinner
L 1/10/2008
AUT-RSS
Ronald G. Nickson
PrincipalNational Multifamily Housing Council3551 White Spruce GlenSouthport, NC 28461-0078Alternate: Marshall A. Klein
U 10/10/1997AUT-RSS
Thomas William Noble
PrincipalAmerican Fire Sprinkler Association2901 Robindale LaneGrapevine, TX 76051DesignAlternate: Daniel J. Mathias
IM 04/04/2017
AUT-RSS
Michael O'Brian
PrincipalBrighton Area Fire Authority615 West Grand River AvenueBrighton, MI 48116International Association of Fire ChiefsAlternate: Robert S. Blach
E 3/2/2010AUT-RSS
Maurice M. Pilette
PrincipalMechanical Designs Ltd.67 Chouteau AvenueFramingham, MA 01701-4259
SE 4/17/1998
AUT-RSS
Milosh T. Puchovsky
PrincipalWorcester Polytechnic InstituteDepartment of Fire Protection Engineering100 Institute RoadWorcester, MA 01609
SE 8/2/2010AUT-RSS
Peter T. Schwab
PrincipalWayne Automatic Fire Sprinklers, Inc.222 Capitol CourtOcoee, FL 34761-3033Alternate: Ryan Peterson
IM 7/29/2005
AUT-RSS
George W. Stanley
PrincipalWiginton Fire Protection Engineering, Inc.699 Aero LaneSanford, FL 32771Alternate: Erne Rodriguez, Jr.
IM 10/10/1997AUT-RSS
Michael Towler
PrincipalLegacy Fire Protection Inc.#3 - 7003 30th Street SECalgary, AB T2C 1N6 CanadaCanadian Automatic Sprinkler AssociationAlternate: Jason W. Ryckman
IM 08/17/2015
AUT-RSS
Donald R. Townley
PrincipalLubrizol9911 Brecksville RoadCleveland, OH 44141-3201Alternate: Forest Hampton
M 10/23/2013AUT-RSS
Martin C. W. Trim
PrincipalBarrett Engineered Pumps1695 National AvenueSan Diego, CA 92113-1008American Society of Plumbing EngineersAlternate: Samuel S. Dannaway
SE 8/9/2012
27
Address List No PhoneResidential Sprinkler Systems AUT-RSS
Automatic Sprinkler Systems
David R. Hague05/25/2017
AUT-RSS
Ed Van Walraven
PrincipalAspen Fire Protection DistrictPO Box 1455Carbondale, CO 81623Alternate: Katherine M. Clay
E 4/3/2003AUT-RSS
Terry L. Victor
PrincipalTyco/SimplexGrinnell3621 Carrollton RoadUpperco, MD 21155Alternate: Mark E. Fessenden
M 10/10/1997
AUT-RSS
John F. Viola
PrincipalJFV Engineering, LLC10 Chestnut Hill RoadSouth Hadley, MA 01075-1718American Fire Sprinkler AssociationInstaller/MaintainerAlternate: Brent Zimiga
IM 04/05/2016AUT-RSS
Ronald N. Webb
PrincipalS.A. Comunale Company, Inc.2900 Newpark DriveBarberton, OH 44203National Fire Sprinkler AssociationContractorAlternate: William Roberts
IM 7/29/2005
AUT-RSS
Hong-Zeng Yu
PrincipalFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Alternate: Angele Morcos
I 9/30/2004AUT-RSS
Ernie Paez
Voting AlternateCAL FIRE, Office of the State Fire Marshal602 East Huntington Drive, Suite AMonrovia, CA 91016-3600
E 03/07/2013
AUT-RSS
Eric J. Skare
Voting AlternateUponor, Inc.5925 148th Street WestApple Valley, MN 55124
M 3/4/2009AUT-RSS
Jon R. Ackley
AlternateDalmatian Fire, Inc.5670 West 73rd StreetIndianapolis, IN 46278National Fire Sprinkler AssociationDesign TechnicianPrincipal: Roland A. Asp
M 10/29/2012
AUT-RSS
Robert S. Blach
AlternateMenlo Park Fire Protection District170 Middlefield RoadMenlo Park, CA 94025International Association of Fire ChiefsPrincipal: Michael O'Brian
E 3/2/2010AUT-RSS
Katherine M. Clay
AlternateJackson Hole Fire/EMSPO Box 901Jackson, WY 83001Principal: Ed Van Walraven
E 08/09/2012
AUT-RSS
Samuel S. Dannaway
AlternateCoffman Engineers/S. S. Dannaway Associates, Inc.501 Sumner Street, Suite 421Honolulu, HI 96817-5304American Society of Plumbing EngineersPrincipal: Martin C. W. Trim
SE 08/11/2014AUT-RSS
Mark E. Fessenden
AlternateTyco Fire Protection ProductsOne Stanton StreetMarinette, WI 54143-2542Principal: Terry L. Victor
M 1/14/2005
38
Address List No PhoneResidential Sprinkler Systems AUT-RSS
Automatic Sprinkler Systems
David R. Hague05/25/2017
AUT-RSS
Forest Hampton
AlternateLubrizol Advanced Materials, Inc.9911 Brecksville RoadCleveland, OH 44141-3201Principal: Donald R. Townley
M 08/17/2015AUT-RSS
Jeff Hebenstreit
AlternateUL LLC484 Tamarach DriveEdwardsville, IL 62025-5246Principal: Kerry M. Bell
RT 08/11/2014
AUT-RSS
Marshall A. Klein
AlternateMarshall A. Klein & Associates, Inc.6815 Autumn View DriveEldersburg, MD 21784-6304National Multifamily Housing CouncilPrincipal: Ronald G. Nickson
U 8/2/2010AUT-RSS
Gary Lampella
AlternateNational Association of Home Builders (NAHB)1201 15th Street NWWashington, DC 20005National Association of Home BuildersPrincipal: Daniel Buuck
U 04/05/2016
AUT-RSS
James R. Lugar
AlternateJENSEN HUGHES4918 Saint Elmo Ave.Apt 1409Bethesda, MD 20184Principal: Dana R. Haagensen
SE 08/03/2016AUT-RSS
Daniel J. Mathias
AlternateAbsolute Fire Protection, Inc.836 Ritchie Highway, Suite 1Severna Park, MD 21146-4133American Fire Sprinkler AssociationDesignPrincipal: Thomas William Noble
IM 04/05/2016
AUT-RSS
Dan Mendoza
AlternateAdvanced Automatic Sprinkler1947 San Ramon Valley BoulevardSuite 100San Ramon, CA 94583Principal: Fred Benn
IM 10/29/2012AUT-RSS
Angele Morcos
AlternateFM Global1151 Boston-Providence TurnpikeNorwood, MA 02062-9102Principal: Hong-Zeng Yu
I 07/29/2013
AUT-RSS
Thomas L. Multer
AlternateReliable Automatic Sprinkler Company, Inc.1470 Smith Grove RoadLiberty, SC 29657-4305National Fire Sprinkler AssociationManufacturerPrincipal: Thomas G. Deegan
M 4/15/2004AUT-RSS
David A. Nickelson
AlternateREHAU Incorporated1501 Edwards Ferry RoadLeesburg, VA 20176Principal: Jonathan C. Bittenbender
M 8/9/2011
AUT-RSS
Ryan Peterson
AlternateWayne Auto Fire Sprinklers4683 Laredo AvenueFort Myers, FL 33905Principal: Peter T. Schwab
IM 04/04/2017AUT-RSS
William Roberts
AlternateQuick Response Fire Protection566 Halls Mill RoadFreehold, NJ 07728National Fire Sprinkler AssociationContractorPrincipal: Ronald N. Webb
IM 12/08/2015
49
Address List No PhoneResidential Sprinkler Systems AUT-RSS
Automatic Sprinkler Systems
David R. Hague05/25/2017
AUT-RSS
Erne Rodriguez, Jr.
AlternateWiginton Fire Protection Engineering, Inc.699 Aero LaneSanford, FL 32771Principal: George W. Stanley
IM 03/05/2012AUT-RSS
Jason W. Ryckman
AlternateCanadian Automatic Sprinkler Association335 Renfrew Drive, Suite 302Markham, ON L3R 9S9 CanadaPrincipal: Michael Towler
IM 10/28/2014
AUT-RSS
Timothy J. Skinner
AlternateNational Automatic Sprinkler Fitters LU 669PO Box 89Lima, OH 45802United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting IndustryPrincipal: Charles W. Ketner
L 08/11/2014AUT-RSS
Brent Zimiga
AlternateRapid Fire Protection Inc.1805 Samco RoadRapid City, SD 57702American Fire Sprinkler AssociationInstaller/MaintainerPrincipal: John F. Viola
IM 04/05/2016
AUT-RSS
Rohit Khanna
Nonvoting MemberUS Consumer Product Safety Commission5 Research PlaceRockville, MD 02085
C 10/10/1998AUT-RSS
David R. Hague
Staff LiaisonNational Fire Protection Assocation1 Batterymarch ParkQuincy, MA 02169-7471
510
PART 3 –
NEW PROCESS WORKSHEETS
11
NEW PROCESS ACTIONS AND MOTIONS
Possible Action #1: Accept Public Comment (exactly as it is)
Action Required Sample motion
Create a Second Revision I move to create a Second Revision using PC #
______.
Possible action #2: Reject but see (revise submitted text)
Action Required Sample motion
Step 1 Create a Second Revision based on a
Public Comment
I move to create a Second Revision based on PC # _____with the following changes to the text . .
.
Step 2 If the revision is related to multiple PCs,
respond to all of them together using the cart function
I move to create a Second Revision based on PC # ____and incorporating PC #s _____with the
following changes to the text . . .
Possible action #3: Reject (no change to the standard)
Action Required Sample motion
Generate a statement (substantiation) I move to reject PC # ____ with the following
substantiation . . .
Possible Action #4: Reject but hold (new material)
Action Required Sample motion
Reject Public Comment for this cycle, but
save for next revision cycle
I move to reject PC # ____ but hold it for consideration during the First Draft meeting next
cycle.
12
PART 4 –
A2018 FIRST DRAFT MEETING MINUTES
13
Technical Committee on Residential Sprinkler Systems
First Draft Meeting
San Diego Marriott Mission Valley
San Diego, CA
July 13 - 14, 2016
1. Chairman Ken Isman called the meeting to order at 8:00am and self-introductions were
made.
2. Dave Hague gave a Staff report and presentation on general meeting procedures.
3. The committee acted on all public inputs.
4. A Task Group on Compartments was formed to review the definition of “Compartment” in
NFPA 13D as illustrated in Figures A.10.2(a) & (b).
a. Task Group members are:
i. Brad Cronin - Chair
ii. Chase Browning
iii. Roland Asp
iv. Mark Fessenden
v. Michael Towler
5. There was no old business to discuss.
6. There was no new business to discuss.
7. The meeting adjourned at 3:00pm on the 14th.
14
Residential Sprinkler Systems
NFPA 13D/R FD Meeting
July 13-14, 2016
San Diego, CA
Name Office Organization
Asp, Roland Principal National Fire Sprinkler Association
Bell, Kerry Principal UL LLC
Benn, Fred Principal Advanced Automatic Sprinkler, Inc.
Bradley, Frederick Principal FCB Engineering
Browning, Chase Principal Medford Fire Rescue
Buuck, Daniel Principal National Association of Home Builders
Deegan, Thomas Principal National Fire Sprinkler Association
Feid, Jeffrey Principal State Farm Insurance Company
Haagensen, Dana Principal Jensen Hughes
Nickson, Ronald Principal National Multifamily Housing Council
O'Brian, Michael Principal International Association of Fire Chiefs
Schwab, Peter Principal Wayne Automatic Fire Sprinklers, Inc.
Skare, Eric Principal Uponor, Inc.
15
Residential Sprinkler Systems
NFPA 13D/R FD Meeting
July 13-14, 2016
San Diego, CA
Name Office Organization
Townley, Donald Principal Lubrizol
Trim, Martin Principal American Society of Plumbing Engineers
Van Walraven, Ed Principal Aspen Fire Protection District
Victor, Terry Principal Tyco Fire Protection Products
Webb, Ronald Principal National Fire Sprinkler Association
Yu, Hong-Zeng Principal FM Global
Cronin, Bradford Voting Alternate Newport Fire Department
Mathias, Daniel Voting Alternate American Fire Sprinkler Association
Ackley, Jon Alternate National Fire Sprinkler Association
Fessenden, Mark Alternate Tyco Fire Protection Products
Hampton, Forest Alternate Lubrizol Advanced Materials, Inc.
Hebenstreit, Jeff Alternate UL LLC
Klein, Marshall Alternate National Multifamily Housing Council
Lugar, James Alternate JENSEN HUGHES
16
Residential Sprinkler Systems
NFPA 13D/R FD Meeting
July 13-14, 2016
San Diego, CA
Name Office Organization
Multer, Thomas Alternate National Fire Sprinkler Association
Roberts, William Alternate National Fire Sprinkler Association
Rodriguez, Erne Alternate Wiginton Fire Protection Engineering, Inc.
Rodriguez, Melisa Alternate Uponor
Zimiga, Brent Alternate American Fire Sprinkler Association
Khanna, Rohit Nonvoting Member US Consumer Product Safety Commission
Hague, David Staff Liaison National Fire Protection Association
17
PART 5 –
A2018 KEY DATES
18
Process
StageProcess Step Dates for TC
Dates for TC
with CC
Public Input Closing Date 6/29/2016 6/29/2016
Final date for TC First Draft Meeting 12/7/2016 9/7/2016Posting of First Draft and TC Ballot 1/25/2017 10/19/2016Final date for Receipt of TC First Draft ballot 2/15/2017 11/9/2016Final date for Receipt of TC First Draft ballot ‐ recirc 2/22/2017 11/16/2016Posting of First Draft for CC Meeting 11/23/2016Final date for CC First Draft Meeting 1/4/2017Posting of First Draft and CC Ballot 1/25/2017Final date for Receipt of CC First Draft ballot 2/15/2017Final date for Receipt of CC First Draft ballot ‐ recirc 2/22/2017Post First Draft Report for Public Comment 3/1/2017 3/1/2017
Public Comment closing date 5/10/2017 5/10/2017
Notice published on Consent Standards (Standards that receive No Comments). Note: Date varies and determined via TC ballot.
_ _
Appeal Closing Date for Consent Standards (15 Days) (Standards That Received
No Comments)_ _
Final date for TC Second Draft Meeting 11/8/2017 8/2/2017Posting of Second Draft and TC Ballot 12/20/2017 9/13/2017Final date for Receipt of TC Second Draft Ballot 1/10/2018 10/4/2017Final date for receipt of TC Second Draft ballot ‐ recirc 1/17/2018 10/11/2017Posting of Second Draft for CC Mtg 10/18/2017Final date for CC Second Draft Meeting 11/29/2017Posting of Second Draft for CC Ballot 12/20/2017Final date for Receipt of CC Second Draft ballot 1/10/2018Final date for Receipt of CC Second Draft ballot ‐ recirc 1/17/2018Post Second Draft Report for NITMAM Review 1/24/2018 1/24/2018
Notice of Intent to Make a Motion (NITMAM) Closing Date 2/21/2018 2/21/2018Posting of Certified Amending Motions (CAMs) and Consent Standards 4/4/2018 4/4/2018Appeal Closing Date for Consent Standards (15 Days after posting) 4/19/2018 4/19/2018SC Issuance Date for Consent Standards (10 Days) 4/29/2018 4/29/2018
Tech Session Association Meeting for Standards with CAMs 6/4‐7/2018 6/4‐7/2018
Appeal Closing Date for Standards with CAMs (20 Days after ATM) 6/27/2018 6/27/2018Council Issuance Date for Standards with CAMs* 8/14/2018 8/14/2018
Comment
Stage (Second
Draft)
Tech Session
Preparation
(& Issuance)
Appeals and
Issuance
2018 ANNUAL REVISION CYCLE
Public Input
Stage
(First Draft)
* Public Input Closing Dates may vary according to standards and schedules for Revision Cycles may change. Please check the
NFPA Website for the most up‐to‐date information on Public Input Closing Dates and schedules at www.nfpa.org/document # (i.e.
www.nfpa.org/101) and click on Next Edition tab.
19
PART 6 – NFPA 13D
PUBLIC COMMENTS
20
Public Comment No. 2-NFPA 13D-2017 [ Global Input ]
There is a potential conflict between the change in 5.1.2.1 and FR 47 which suggests thatnon-metallic hangers must be listed.
Additional Proposed Changes
File Name Description Approved
13D_CCN2.pdf 13D_CCN2
Statement of Problem and Substantiation for Public Comment
NOTE: This Public Comment appeared as CC Note No. 2 in the First Draft Report on First Revision No. 47.
Related Item
First Revision No. 47-NFPA 13D-2016 [Section No. 5.1.2.1]
Submitter Information Verification
Submitter Full Name: Cc On Aut-Aac
Organization: NFPA
Affilliation: CC on Automatic Sprinkler Systems
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 12:30:44 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 24 5/16/17, 12:47 PM
21
Correlating Committee Note No. 2-NFPA 13D-2016 [ Section No. 5.1.2.1 ]
Submitter Information Verification
Submitter Full Name: David Hague
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 08 10:41:26 EST 2016
Committee Statement
CommitteeStatement:
There is a potential conflict between this change and FR 47 which suggests thatnon-metallic hangers must be listed.
First Revision No. 47-NFPA 13D-2016 [Section No. 5.1.2.1]
Ballot Results
This item has passed ballot
20 Eligible Voters
3 Not Returned
16 Affirmative All
0 Affirmative with Comments
0 Negative with Comments
1 Abstention
Not Returned
Javeri, Sultan M.
Kim, Andrew
Mitchell, Brock
Affirmative All
Asp, Roland A.
Baz, Jose R.
Bell, Kerry M.
Bless, Jr., Ralph E.
Franson, Scott T.
Hilton, Luke
Hoffman, Alex
Huggins, Roland J.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 4 3/1/2017 9:56 AM
22
Ketner, Charles W.
LeBlanc, John A.
Linder, Kenneth W.
Lowrey, David O.
Palenske, Garner A.
Phillips, Lawrence Richard
Seghi, Adam
Thompson, J. Michael
Abstention
Friedman, Michael J.
absent of information that would enable me to make a decision, I abstain on all ballots on all referenceddocuments
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 4 3/1/2017 9:56 AM
23
Public Comment No. 3-NFPA 13D-2017 [ Global Input ]
There is a potential conflict between FR 16 and FR 47 which requires hangers to be listed (7.4.4).
Additional Proposed Changes
File Name Description Approved
13D_CCN1.pdf 13D_CCN1
Statement of Problem and Substantiation for Public Comment
NOTE: This Public Comment appeared as CC Note No. 1 in the First Draft Report.
Related Item
First Revision No. 16-NFPA 13D-2016 [New Section after 7.4.4]
Submitter Information Verification
Submitter Full Name: Cc On Aut-Aac
Organization: NFPA
Affilliation: CC on Automatic Sprinkler Systems
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 13:29:58 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 24 5/16/17, 12:47 PM
24
Correlating Committee Note No. 1-NFPA 13D-2016 [ New Section after 7.4.4 ]
Submitter Information Verification
Submitter Full Name: David Hague
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 08 10:39:52 EST 2016
Committee Statement
CommitteeStatement:
There is a potential conflict between this FR and FR47 which requires hangers to belisted.
First Revision No. 16-NFPA 13D-2016 [New Section after 7.4.4]
Ballot Results
This item has passed ballot
20 Eligible Voters
3 Not Returned
16 Affirmative All
0 Affirmative with Comments
0 Negative with Comments
1 Abstention
Not Returned
Javeri, Sultan M.
Kim, Andrew
Mitchell, Brock
Affirmative All
Asp, Roland A.
Baz, Jose R.
Bell, Kerry M.
Bless, Jr., Ralph E.
Franson, Scott T.
Hilton, Luke
Hoffman, Alex
Huggins, Roland J.
Ketner, Charles W.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 4 3/1/2017 9:56 AM
25
LeBlanc, John A.
Linder, Kenneth W.
Lowrey, David O.
Palenske, Garner A.
Phillips, Lawrence Richard
Seghi, Adam
Thompson, J. Michael
Abstention
Friedman, Michael J.
absent of information that would enable me to make a decision, I abstain on all ballots on all referenceddocuments
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 4 3/1/2017 9:56 AM
26
Public Comment No. 15-NFPA 13D-2017 [ Section No. 7.4.5 ]
7.4.5*
Where sprinkler piping is exposed to the sprinkler protected area, it shall be supported with metal hangersor hangers listed for this application. made of the same material as the structure.
Annex note submitted as separate PC
A.7.4.5
Wood used as part of a trapeze hanger is considered an extension of the structure and is considered acceptable to
hang sprinkler piping.
Statement of Problem and Substantiation for Public Comment
This proposal will clarify misconceptions about hanging pipe from a wooden structure. AHJ's have been disallowing this as they consider a wood trapeze to be a nonmetallic hanger.
This language will also address the concerns of the correlating committee (see CN-1)Annex note submitted as separate PCA.7.4.5Wood used as part of a trapeze hanger is considered an extension of the structure and is considered acceptable to hang sprinkler piping.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 16-NFPA 13D-2017 [New Section after A.7.4.4]
Related Item
FR-16
CN-1
Submitter Information Verification
Submitter Full Name: Roland Asp
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 16:11:53 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 24 5/16/17, 12:47 PM
27
Public Comment No. 22-NFPA 13D-2017 [ Section No. 8.1.3.1.2 ]
8.1.3.1.2*
Where construction features or other special conditions exist that are outside the scope of sprinkler listings,listed sprinklers shall be permitted to be installed beyond their listing limitations.
A.8.1.3.1.2. Technical documentation should be provided to the authority having jurisdiction thatdemonstraits that the modification is in compliance with the intent and purpose of this code and that suchmodification does not lessen health, life and fire safety requirements.
Statement of Problem and Substantiation for Public Comment
The purpose of this comment is to state that an approved report should be provided prior to installing fire sprinklers outside of their listing. The base code allows for the installation of fire sprinklers outside of their listing, but does not provide SUFFICIENT guidance on the limitations of this provision. Requiring the report will provide guidance on acceptable methods of installation, even if outside of the listing of the fire sprinkler.
Related Item
PI 84
Submitter Information Verification
Submitter Full Name: Lynn Nielson
Organization: City of Henderson
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 15:57:27 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 24 5/16/17, 12:47 PM
28
Public Comment No. 18-NFPA 13D-2017 [ Section No. 8.2.1.2 ]
8.2.1.2
Pendent-type residential sprinklers located under or adjacent to beams in accordance with 10.2.1 shall beinstalled in accordance with one of the following:
(1) Pendent, recessed pendent, and flush-type pendent sprinklers shall be permitted to be installed directlyunder a beam having a maximum depth of 14 in. (350 mm) with the sprinkler deflector 1 in. to 2 in. (25mm to 50 mm) below the beam, or in accordance with the manufacturer’s instructions for recessed orflush sprinklers if the deflector is less than 1 in. (25 mm) below the beam.
(2) Pendent sprinklers, including flush-type pendent sprinklers, shall be permitted to be installed adjacentto beams where the vertical centerline of the sprinkler is no greater than 2 in. (50 mm) from the edge ofthe beam and with the sprinkler deflector 1 in. to 2 in. (25 mm to 50 mm) below the beam, or inaccordance with the manufacturer’s instructions for flush sprinklers if the deflector is less than 1 in. (25mm) below the beam.
Add attached Figures
Additional Proposed Changes
File Name Description Approved
Beam_ceiling_figures.pdf Figures for sprinkler under beams and sprinklers adjacent to beams
Statement of Problem and Substantiation for Public Comment
This comment is in support of FR 32 and seeks to add two figures to illustrate the requirements for installing sprinklers under and adjacent to beams,Note this section and new figures have also been to submitted to NFPA 13 and the figures submitted to NFPA 13R.
Related Item
FR-32
Submitter Information Verification
Submitter Full Name: Roland Asp
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 10:54:29 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5 of 24 5/16/17, 12:47 PM
29
30
Public Comment No. 20-NFPA 13D-2017 [ Section No. 8.2.5.3.2 ]
8.2.5.3.2
Sprinklers shall be positioned with respect to continuous obstructions in accordance with Table 8.2.5.3.2and Figure 8.2.5.3.2.
Table 8.2.5.3.2 Positioning of Sprinklers to Avoid Obstructions to Discharge (Residential Upright andPendent Spray Sprinklers)
Distance from Sprinklers to
Side of Obstruction (A)
Maximum Allowable Distance of Deflector
Above Bottom of
Obstruction (in.) (B)
Less than 1 ft (300 mm) 0
1 ft (300 mm) to less Less than 1 ft 6 in. (450 mm) 0
1 ft 6 in. (450 mm) to less Less than 2 ft (600 mm) 1(25 mm)
2 ft (600 mm) to less Less than 2 ft 6 in. (750 mm) 1(25 mm)
2 ft (750 mm) 6 in. to less Less than 3 ft (900 mm) 1(25 mm)
3 ft (900 mm) to less Less than 3 ft 6 in. (1050 mm) 3(75 mm)
3 ft (1050 mm) 6 in. to less Less than 4 ft (1200 mm) 3(75 mm)
4 ft (1200 mm) to less Less than 4 ft 6 in. (1350 mm) 5(125 mm)
4 ft (1350 mm) 6 in. to less Less than 5 ft (1500 mm) 7(175 mm)
5 ft (1500 mm) to less Less than 5 ft 6 in. (1650 mm) 7(175 mm)
5 ft 6 in. (1650 mm) to less Less than 6 ft (1800 mm) 7(175 mm)
6 ft (1800 mm) to less Less than 6 ft 6 in. (1950 mm) 9(225 mm)
6 ft 6 (1950 mm) in. to less Less than 7 ft (2100 mm) 11(275 mm)
7 ft and greater (2100 mm) 14(350 mm)
Note: For A and B, refer to Figure 8.2.5.3.2.
Figure 8.2.5.3.2 Positioning of Sprinkler to Avoid Obstruction to Discharge (Residential Uprightand Pendent Spray Sprinklers).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 24 5/16/17, 12:47 PM
31
Statement of Problem and Substantiation for Public Comment
This comment is to support First Revision No 683 and to apply the same changes to relatedtables throughout NFPA 13. (Global Revision) This is what was agreed upon at the first draftmeeting and will provide consistency throughout the document.Not that similar comments have been submitted to NFPA 13R and NFPA 13D.
Related Item
FR-683 (NFPA 13)
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 14:35:19 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 24 5/16/17, 12:47 PM
32
Public Comment No. 21-NFPA 13D-2017 [ Section No. 8.2.5.4.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
8 of 24 5/16/17, 12:47 PM
33
8.2.5.4.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
9 of 24 5/16/17, 12:47 PM
34
Sprinklers shall be positioned with respect to continuous obstructions in accordance with Table 8.2.5.4.2(a),Figure 8.2.5.4.2(a), Table 8.2.5.4.2(b), Figure 8.2.5.4.2(b), and Figure 8.2.5.4.2(c).
Table 8.2.5.4.2(a) Positioning of Sprinklers to Avoid Obstructions (Residential Sidewall Sprinklers)
Distance from Sidewall
Sprinkler to Side of
Obstruction (A)
Maximum Allowable Distance of Deflector Above Bottom ofObstruction (in.) (B)
Less than 8 ft (2400 mm) Not allowed
8 ft (2400 mm) to less Less than 10 ft(3000 mm)
1 (25 mm)
10 ft (3000 mm) to less Less than 11 ft(3300 mm)
2 (50 mm)
11 ft (3300 mm) to less Less than 12 ft(3600 mm)
3 (75 mm)
12 ft (3600 mm) to less Less than 13 ft(3900 mm)
4 (100 mm)
13 ft (3900 mm) to less Less than 14 ft(4200 mm)
6 (150 mm)
14 ft (4200 mm) to less Less than 15 ft(4500 mm)
7 (175 mm)
15 ft (4500 mm) to less Less than 16 ft(4800 mm)
9 (225 mm)
16 ft (4800 mm) to less Less than 17 ft(5100 mm)
11 (275 mm)
17 ft (5100 mm) or greater 14 (350 mm)
Note: For A and B, refer to Figure 8.2.5.4.2(a).
Table 8.2.5.4.2(b) Positioning of Sprinklers to Avoid Obstructions Along Wall (Residential SidewallSprinklers)
Distance from Sidewall Sprinkler to Side of
Obstruction (A)
Maximum Allowable Distance of Deflector
Above Bottom of
Obstruction (in.) (B)
Less than 1 ft 6 in. (450 mm) 0
1 ft 6 in. (450 mm) to less Less than 3 ft (900 mm) 1 (25 mm)
3 ft (900 mm) to less Less than 4 ft (1200 mm) 3 (75 mm)
4 ft (1200 mm) to less Less than 4 ft 6 in. (1350 mm) 5 (125 mm)
4 ft 6 in. (1350 mm) to less Less than 6 ft (1850 mm) 7 (175 mm)
6 ft (1850 mm) to less Less than 6 ft 6 in. (1950 mm) 9 (225 mm)
6 ft 6 in. (1950 mm) to less Less than 7 ft (2100 mm) 11 (275 mm)
7 ft to (2100 mm) less Less than 7 ft 6 in. (2250 mm) 14 (350 mm)
Note: For A and B, refer to Figure 8.2.5.4.2(b).
Figure 8.2.5.4.2(a) Positioning of Sprinkler to Avoid Obstruction (Residential Sidewall Sprinklers).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10 of 24 5/16/17, 12:47 PM
35
Figure 8.2.5.4.2(b) Positioning of Sprinkler to Avoid Obstruction Along Wall (Residential SidewallSprinklers).
Figure 8.2.5.4.2(c) Positioning of Sprinkler to Avoid Obstructions Against Wall (ResidentialSidewall Sprinklers).
Statement of Problem and Substantiation for Public Comment
This comment is to support First Revision No 683 and to apply the same changes to relatedtables throughout NFPA 13. (Global Revision) This is what was agreed upon at the first draftmeeting and will provide consistency throughout the document.Not that similar comments have been submitted to NFPA 13R and NFPA 13D.
Related Item
FR-683 (NFPA 13)
Submitter Information Verification
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
11 of 24 5/16/17, 12:47 PM
36
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 14:37:58 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
12 of 24 5/16/17, 12:47 PM
37
Public Comment No. 23-NFPA 13D-2017 [ Section No. 8.3.4 ]
8.3.4*
Sprinklers shall not be required in garages, open attached porches, carports, and similar structures.
8.3.4.1 Attached garages with any habitable rooms above shall be required to be protected withfire sprinklers.
Statement of Problem and Substantiation for Public Comment
A fire in a garage without fire sprinklers with habitable rooms above it can undermine the structural integrity of the habitable rooms above and increase the risk of occupants within those rooms not being able to exit the structure safely.
The committees comment, "Building code requires separation. The passive protection (1 Hour) provides more time than the 10 minute limit of the FSS".
The building code passive protection is not actually 1-hour and in many situations is not even 10 minutes.
The water supply is normally in the garage. Adding sprinkler protection into the garage is easy to do.
Related Item
PI 85
Submitter Information Verification
Submitter Full Name: Lynn Nielson
Organization: City of Henderson
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 16:04:03 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
13 of 24 5/16/17, 12:47 PM
38
Public Comment No. 12-NFPA 13D-2017 [ Section No. 12.3.6.1 ]
12.3.6.1
In a detached dwelling or a manufactured home the sprinkler system shall be permitted to be put in aninactive state for any of the following reasons:
(1) After a manufactured home has been installed and tested in the factory and is being prepared forshipment
(2) When a manufactured home is being stored for future occupancy
(3) When the detached dwelling is unoccupied during renovation work, with notification and approval of theAHJ
(4) * When the detached dwelling is unoccupied for an extended period of time, with notification andapproval of the AHJ
A.12.3.6.1 (4) An example of this would be a summer home that is closed up for the winter. Since NFPA 13is a lifesfety system only and the buildig will remain unoccupied, leaving the system off and drained isacceptable.
Statement of Problem and Substantiation for Public Comment
This note clarifies that it is acceptable to turn the system off when there will not be occupants for extended periods of time.
Related Item
Public Input No. 81
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 02 10:28:23 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
14 of 24 5/16/17, 12:47 PM
39
Public Comment No. 14-NFPA 13D-2017 [ Section No. A.6.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
15 of 24 5/16/17, 12:47 PM
40
A.6.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
16 of 24 5/16/17, 12:47 PM
41
The connection to city mains for fire protection is often subject to local regulation of metering and backflowprevention requirements. Preferred and acceptable water supply arrangements are shown in FigureA.6.2(a) through Figure A.6.2(e). Where it is necessary to use a meter between the city water main andthe sprinkler system supply, an acceptable arrangement as shown in Figure A.6.2(c) and Figure A.6.2(d)can be used. Under these circumstances, the flow characteristics of the meter are to be included in thehydraulic calculation of the system [see Table 10.4.4(a)]. Where a tank is used for both domestic and fireprotection purposes, a low water alarm that actuates when the water level falls below 110 percent of theminimum quantity specified in 6.1.2 should be provided.
The effect of pressure-reducing valves on the system should be considered in the hydraulic calculationprocedures.
Figure A.6.2(a), Figure A.6.2(c), or Figure A.6.2(d) are acceptable methods for getting the water supplyinto the unit for a stand-alone sprinkler system (one that does not also provide direct connections to thecold water fixtures) because the common supply pipe for the domestic system and the sprinkler systembetween the water supply and the dwelling unit has a single control valve that shuts the sprinkler system,which helps to ensure that people who have running water to their domestic fixtures also have fireprotection. This serves as a form of supervision for the control valve and can be used to make sure thatthe valve stays open in place of other, more expensive options such as tamper switches with a monitoringservice.
Some water utilities insist on separate taps and supply pipes from the water supply to the dwelling unit forfire sprinkler systems as shown in Figure A.6.2(d), due to concerns about shutting off the water supply fornonpayment of bills and the desire not to shut off fire protection if this ever occurs. While these types ofarrangements are acceptable, they might not be cost efficient and should be discouraged due to the extracost burden this places on the building owner. It is extremely rare that the water utilities would actually shutoff water for nonpayment, and even if they do they are creating a situation in which the dwelling would beunfit for occupation.
Figure A.6.2(a) Minimum Requirements for a Stand-Alone System.
Figure A.6.2(b) Acceptable Arrangement for Stand-Alone Piping Systems — Option 1.
Figure A.6.2(c) Acceptable Arrangement for Stand-Alone Piping System — Option 2.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
17 of 24 5/16/17, 12:47 PM
42
Figure A.6.2(d) Acceptable Arrangement for Stand-Alone Piping Systems — Option 3.
Figure A.6.2(e) Acceptable Arrangement for Townhouse Stand-Alone Piping Systems.
Statement of Problem and Substantiation for Public Comment
Modify Figure (e). It appears that all the systems are connected once inside the townhouses. Use a swirly or arrow to point automatic sprinkler system
Related Item
First Revision No. 18
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
18 of 24 5/16/17, 12:47 PM
43
State:
Zip:
Submittal Date: Tue May 09 09:02:28 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
19 of 24 5/16/17, 12:47 PM
44
Public Comment No. 16-NFPA 13D-2017 [ New Section after A.7.4.4 ]
A.7.4.5
Wood used as part of a trapeze hanger is considered an extension of the structure and is considered acceptable to
hang sprinkler piping.
Statement of Problem and Substantiation for Public Comment
This proposal will clarify misconceptions about hanging pipe from a wooden structure. AHJ's have been disallowing this as they consider a wood trapeze to be a nonmetallic hanger.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 15-NFPA 13D-2017 [Section No. 7.4.5]
Related Item
FR-16
Submitter Information Verification
Submitter Full Name: Roland Asp
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 16:22:08 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
20 of 24 5/16/17, 12:47 PM
45
Public Comment No. 13-NFPA 13D-2017 [ Section No. A.7.5.6.3(3) ]
A.7.5.6.3(3)
See Figure A.7.5.6.3(3)(a) and Figure A.7.5.6.3(3)(b).
Figure A.7.5.6.3(3)(a) Recessed Fireplace.
[see two new drawings attached]
Figure A.7.5.6.3(3)(b) Open Fireplace.
[see two new drawings attached]
Additional Proposed Changes
File Name Description Approved
FRONT_Fire_Place_ORDINARY.png Improved drawing to illustrate concept accepted in FR
FRONT_Fire_Place_INTERMEDIATE.png Improved drawing to illustrate concept accepted in FR
OPEN_Fire_Place_ORDINARY.png Improved drawing to illustrate concept accepted in FR
OPEN_Fire_Place_INTERMEDIATE.png Improved drawing to illustrate concept accepted in FR
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
21 of 24 5/16/17, 12:47 PM
46
Statement of Problem and Substantiation for Public Comment
Improved drawings have been submitted to illustrate the concept accepted in the First Revision. This should be correlated across NFPA 13 and NFPA 13R.
Related Item
FR-17
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 15:00:43 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
22 of 24 5/16/17, 12:47 PM
47
48
49
50
51
Public Comment No. 11-NFPA 13D-2017 [ Section No. B.1.2.1 ]
B.1.2.1 ASTM Publications.
ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.
ASTM A135, Standard Specification for Electric-Resistance-Welded Steel Pipe, 2006.
ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2009 2016 .
ASTM F437, Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 1996.
ASTM F438, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 40, 1997.
ASTM F439, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 1997.
ASTM F442, Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe (SDR-PR),1997.
ASTM F876, Standard Specification for Crosslinked Polyethylene (PEX) Tubing, 2008.
IEEE/ASTM SI 10, Standard for Use of the International System of Units (SI): The Modern Metric System,1997.
Statement of Problem and Substantiation for Public Comment
date update
Related Item
public input 5
Submitter Information Verification
Submitter Full Name: Marcelo Hirschler
Organization: GBH International
Street Address:
City:
State:
Zip:
Submittal Date: Thu Apr 27 15:59:17 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
23 of 24 5/16/17, 12:47 PM
52
Public Comment No. 17-NFPA 13D-2017 [ New Section after B.3 ]
Annex C Press-Connect Fittings used in Fire Sprinkler Applications
(See separate document for proposed text of Annex)
Additional Proposed Changes
File Name Description Approved
NFPA_13D_Public_Comment_Annex_Information_Press_Connect_Viega_Submitted.docx
NFPA 13D Public Comment Proposed Annex C
Statement of Problem and Substantiation for Public Comment
Currently there is no definition for Press-Connect fittings in NFPA 13D. The term Press-Connect Fitting is used in both the IAPMO and ICC codes. The wide use of Mechanical type fittings has created the need to identify fittings such as Press-Connect and provide definitions to prevent confusion between mechanical fitting types and to help identify the correct standards these fittings are typically listed to. The proposed annex provides reference information which will be helpful in distinguishing between Mechanical type fittings and Press-Connect Fittings.
In the first draft review meetings our public comments 32, 33, 88, and 89 were resolved because all press-connect systems require listings and thus are not to be listed in the existing tables for standards whose products do not require separate listings.
It was suggested by a few committee members that information on Press-Connect fittings be added instead to the Annex of this code for reference and informational purposes.
Related Item
PI 32
PI 33
PI 89
PI 88
Submitter Information Verification
Submitter Full Name: Gary Morgan
Organization: Viega LLC
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 20:35:11 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
24 of 24 5/16/17, 12:47 PM
53
Proposed New Annex
Annex C Press‐Connect Fittings used in Fire Sprinkler Applications This annex is not a part of the requirements of this NFPA document but is included for informational purposes only.
This annex is intended to provide basic information and description of press‐connect fittings for metallic
piping systems used in fire sprinkler systems. All press‐connect fitting systems used in fire sprinkler
applications require listing(s) specific to the application. Because press‐connect fittings are not
specifically included in the mandatory sections of this standard the following information will discuss the
press‐connect fitting connection in more detail.
C.1 Definition of Press‐Connect Fittings
The press‐connect fitting is a permanent mechanical connection for joining copper tubing or steel pipe
typically utilizing an elastomeric seal or an elastomeric seal in conjunction with a corrosion resistant
axial biting or grip ring or rings. Fitting connections are generally pressed with an electro‐hydraulic
pressing tool utilizing pressing jaws or pressing rings approved by the fitting manufacturer for use in
accordance with their listing.
C.2 Applications of Press Connect Fittings
Press‐connect fittings are commonly used today in both dry (pre‐action) systems as well as wet systems.
Press‐connect system designs must not exceed the maximum pressure and ambient exposure
temperature ratings for fittings and piping. The maximum continuous exposure temperature is limited
by the elastomeric sealing element material. A manufacturers’ listing will specify the maximum
continuous exposure temperatures for their press‐connect system.
C.3 Standards for Press‐Connect Fittings
Press‐connect systems are generally manufactured in accordance with ASME B16.51, Copper and
Copper Alloy Press‐Connect Pressure Fittings; or IAPMO PS‐117, Press and Nail Connections; or ASTM
F3226/F326M, Standard Specification for Metallic Press‐Connect Fittings for Piping and Tubing Systems
depending on the type of piping. These standards specify the material requirements and the
performance criteria such as, but not limited to, Hydrostatic Pressure Test, Static Torque Test, Bending
Test, Vacuum Test, Pressure Cycle Test, Vibration Test, Thermocycling Test, and Dynamic Torque Test.
C.4 General Assembly Procedure for Press‐Connect Fittings
Press‐connect fittings all have an elastomeric seal that forms the seal‐tight joint. The pipe or tubing is
cut square, deburred and chamfered and, or reamed to restore the full inside diameter. The ends of the
pipe or tube that will be inserted into the fittings should be carefully inspected for any noticeable
damage or deep scratches and also checked and cleaned if any foreign matter such as dirt or tape
residue is present. The pipe or tubing is then fully inserted into the fitting until the internal shoulder
stop is reached and the tubing is then marked with a permanent marker where the tubing meets the
outer shoulder of the fitting in order to establish the full insertion depth. With the tubing fully inserted
54
and the insertion depth mark double checked, the joint can be pressed using the tool recommended by
the manufacturer. The insertion depth mark should be checked once again after pressing to insure the
joint did not slip apart during the pressing operation. Pressure testing of completed sections should
then be conducted per the manufacturer’s instructions and this code to insure all joints are seal tight.
55
PART 6A – NFPA 13R
PUBLIC COMMENTS
56
Public Comment No. 4-NFPA 13R-2017 [ Global Input ]
Note to 13R & 13 - regarding sprinklers in closets with ventless dryers (6.4.6.3.2). Coordinate with NFPA13D FR-23. See NFPA 13R-FR51 and NFPA 13 FR-891.
Additional Proposed Changes
File Name Description Approved
13R_CCN1.pdf 13R_CCN1
Statement of Problem and Substantiation for Public Comment
NOTE: This Public Comment appeared as CC Note No. 1 in the First Draft Report.
Related Item
First Revision No. 51-NFPA 13R-2016 [Section No. 6.4.6.3.2]
Submitter Information Verification
Submitter Full Name: Cc On Aut-Aac
Organization: NFPA
Affilliation: CC on Automatic Sprinkler Systems
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 13:20:22 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 71 5/16/17, 1:20 PM
57
Correlating Committee Note No. 1-NFPA 13R-2016 [ Section No. 6.4.6.3.2 ]
Submitter Information Verification
Submitter Full Name: David Hague
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Thu Dec 08 09:49:40 EST 2016
Committee Statement
CommitteeStatement:
Note to 13R & 13 - regarding sprinklers in closets with ventless dryers. Coordinate with NFPA 13DFR23. See NFPA NFPA 13R - FR51 and NFPA 13 FR891.
First Revision No. 51-NFPA 13R-2016 [Section No. 6.4.6.3.2]
Ballot Results
This item has passed ballot
20 Eligible Voters
4 Not Returned
15 Affirmative All
0 Affirmative with Comments
0 Negative with Comments
1 Abstention
Not Returned
Javeri, Sultan M.
Kim, Andrew
Mitchell, Brock
Stultz, Douglas Paul
Affirmative All
Asp, Roland A.
Baz, Jose R.
Bell, Kerry M.
Bless, Jr., Ralph E.
Franson, Scott T.
Hilton, Luke
Hoffman, Alex
Huggins, Roland J.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
1 of 2 3/1/2017 10:00 AM
58
Ketner, Charles W.
LeBlanc, John A.
Linder, Kenneth W.
Lowrey, David O.
Palenske, Garner A.
Seghi, Adam
Thompson, J. Michael
Abstention
Friedman, Michael J.
absent of information that would enable me to make a decision, I abstain on all ballots on all referenced documents
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 2 3/1/2017 10:00 AM
59
Public Comment No. 56-NFPA 13R-2017 [ Section No. 5.1.3 ]
5.1.3 Rated Pressure.
System components shall be rated for the maximum system working pressure to which they are exposedbut shall not be rated at less than 175 psi (12.1 bar) for components installed above ground and 150 psi(10.4 bar) for components installed underground between the water supply and the system riser. When theunderground piping can be supplied or pressurized by a Fire Department Connection (FDC), theunderground piping shall be designed to withstand a working pressure of not less than 200 psi (Class 200),or 50 psi greater than the system design pressure, whichever is greater.
Statement of Problem and Substantiation for Public Comment
This Comment/PI intends to require higher pressure ratings for underground lines that can be fed by Fire Department Connections. Delivery of water at Fire Department Connections can cause pressures that exceed 150 psi. Typically, use of 200 psi rated line can withstand the pressures delivered at the FDC. However, when higher pressures are required at the FDC due to system demands, the underground line is required to be listed for 50 psi above that demand pressure. The 50 psi above design pressure is to allow for pipe to be listed for the pressure used during the hydrostatic test.
The FDC has been used as the only source of water for the system when the main water source is out of service.
Related Item
IP 93
Submitter Information Verification
Submitter Full Name: Lynn Nielson
Organization: City of Henderson
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 15:49:58 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 71 5/16/17, 1:20 PM
60
Public Comment No. 53-NFPA 13R-2017 [ New Section after 5.2.1.4 ]
5.2.1.4
Nonmetallic pipe used in isolated portions of wet pipe sprinkler systems where those portions of the systemdo not exceed working pressures of 130 psi (9 bar) shall be designed to withstand a working pressure notless than 130 psi (9 bar) at 120°F (49 °C) and 100 psi (6.9 bar) at 180°F (82 °C).
Statement of Problem and Substantiation for Public Comment
This public comment is a slight revision of Public Input No. 86 eliminating the specified means of limiting pressure (thereby eliminating the committee's concern of an "additional failure point". This concept is also being resubmitted based on the committee statement for Public Input No. 93, which states "If excessive pressures are introduced to the system through the FDC, such pressures are for a limited time and are flowing pressure (fire event). Pipe can handle pressures in excess of their rating for limited time."
Related Item
PI 86
Submitter Information Verification
Submitter Full Name: Eric Skare
Organization: Uponor Inc
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 15:12:30 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 71 5/16/17, 1:20 PM
61
Public Comment No. 28-NFPA 13R-2017 [ Section No. 5.2.2.3 ]
5.2.2.3
Pipe or tube listed for light-hazard occupancies shall be permitted to be installed in concealed spacesabove ordinary-hazard rooms.
Statement of Problem and Substantiation for Public Comment
When nonmetallic pipe and tube first got listed for use in fire sprinkler systems, there was a requirement to separate the pipe and tube from the protected light hazard space using some sort of construction material (typically wood, gypsum board, or plywood). This effectively created a concealed space above the protected light hazard space that contained the pipe. No new information has come forward to show that the pipe would be able to withstand the increased heat release from an ordinary hazard fire in the same type of concealed space. There is no information on what minimum construction should be used to separate the concealed space from the ordinary hazard area and there is no information on how to seal any potential penetrations or openings to the concealed space (remember that concealed spaces are permitted to have small openings such as the return air openings in a plenum). There is no evidence that nonmetallic pipe or tube subjected to a fire likely to come from an ordinary hazard space will survive prior to sprinkler operation. And if the pipe does not survive, how will water get to the sprinkler?
Related Item
FR2
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 10:10:22 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 71 5/16/17, 1:20 PM
62
Public Comment No. 32-NFPA 13R-2017 [ Section No. 5.2.2.3 ]
5.2.2.3
Pipe or tube listed for light-hazard occupancies shall be permitted to be installed in concealed spaceswithin a fire rated assembly above ordinary-hazard rooms.
Statement of Problem and Substantiation for Public Comment
As the language stands, this would permit listed plastic pipe to be installed in concealed space without specifying a fire rating which would not meet the minimum requirements of the product. This change specifies the requirement to be within a fire rated assembly.
Related Item
FR-2
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 10:29:33 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
5 of 71 5/16/17, 1:20 PM
63
Public Comment No. 54-NFPA 13R-2017 [ New Section after 5.2.9.3 ]
5.2.9.4
Nonmetallic fittings used in isolated portions of wet pipe sprinkler systems where those portions of thesystem do not exceed working pressures of 130 psi (9 bar) shall be designed to withstand a workingpressure not less than 130 psi (9 bar) at 120°F (49°C) and 100 psi (6.9 bar) at 180°F (82°C).
Statement of Problem and Substantiation for Public Comment
This public comment is a slight revision of Public Input No. 86 eliminating the specified means of limiting pressure (thereby eliminating the committee's concern of an "additional failure point". This concept is also being resubmitted based on the committee statement for Public Input No. 93, which states "If excessive pressures are introduced to the system through the FDC, such pressures are for a limited time and are flowing pressure (fire event). Pipe can handle pressures in excess of their rating for limited time."
Related Item
PI 87
Submitter Information Verification
Submitter Full Name: Eric Skare
Organization: Uponor Inc
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 15:39:07 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
6 of 71 5/16/17, 1:20 PM
64
Public Comment No. 50-NFPA 13R-2017 [ Section No. 5.4.2 ]
5.4.2* Systems in Areas Subject to Freezing.
Where any portion of a system is subject to freezing and the temperature cannot be maintained reliably ator above 40°F (4°C), the pipe shall be protected by use of one of the following methods:
(1)
(2) Dry pipe system
(3) Preaction system
(4) Listed dry pendent, dry upright, or dry sidewall sprinklers extended from pipe in heated areas
(5) Heat tracing in accordance with 6.7.2.2
(6) Heat tracing in accordance with 6.7.2.2
Statement of Problem and Substantiation for Public Comment
APPA disagrees with adding a trust heat trace to prevent freezing. It has a habit of failing regularly and without warning. We agree with Technical Committee member Peter T. Schwab’s Affirmative Comment, “The committee statement would make excellent annex language because it indicates that the temperature of the space that the wet pipe is installed can get below 40 degrees as long as the pipe does not freeze.” We are asking the technical committee to review this subsection to ensure it is enforceable.
Related Item
FR-49
Submitter Information Verification
Submitter Full Name: Billie Zidek
Organization: APPA
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 14:08:56 EDT 2017
* Antifreeze system using a listed antifreeze solution in accordance with NFPA 13
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 71 5/16/17, 1:20 PM
65
Public Comment No. 7-NFPA 13R-2017 [ Section No. 5.4.4 ]
5.4.4 *
Water-filled piping shall be permitted to be installed in areas where the temperature is less than 40°F (4°C)when heat loss calculations performed by a professional engineer verify that the system will not freeze.
A.5.4.4
There are some geographic regions where the temperature will get below 40°F (4°C) for brief periods oftime. However the water in the pipe has sufficient thermal mass to keep it from freezing and thus freezeprotection is not required.
Statement of Problem and Substantiation for Public Comment
Adding annex language that mirrors the committee statement from the first draft.
Related Item
First Revision No. 49-NFPA 13R-2016 [Section No. 5.4.2]
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 13:52:35 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
8 of 71 5/16/17, 1:20 PM
66
Public Comment No. 43-NFPA 13R-2017 [ Section No. 6.2.2.2 ]
6.2.2.2
The following types of spaces shall be permitted to be protected by residential sprinklers in accordance withSection 7.1:
(1) Lobbies not in hotels and motels
(2) Foyers
(3) Corridors
(4) Halls
(5) Lounges
(6) Ordinary-hazard areas in accordance with 7.2.4.1
(7) Garages in accordance in accordance with 7.3.4 and 7.3.4.1(1)
(8) Porches, balconies, lanais and similar areas
(9) Other areas with fire loads similar to residential fire loads
Statement of Problem and Substantiation for Public Comment
Some AHJ's consider these areas "outside" the dwelling unit since they are exterior. Residential sprinklers should be allowed when these areas are required to be protected (Type 5 construction).
Related Item
Public Input No. 23
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 09:34:40 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
9 of 71 5/16/17, 1:20 PM
67
Public Comment No. 8-NFPA 13R-2017 [ Section No. 6.2.3.3 ]
6.2.3.3 *
The practices of 6.2.3.3.1 through 6.2.3.3.3 5 shall be observed when installing residential sprinklersunless higher expected ambient temperatures require a higher temperature rating.
6.2.3.3.1
Sprinklers under glass or plastic skylights exposed to direct rays of the sun shall be of intermediatetemperature classification.
6.2.3.3.2
Sprinklers in an unventilated concealed space under uninsulated roof or in an unventilated attic shall be ofintermediate temperature classification.
6.2.3.3.3
*
Sprinklers
in closets containing ventless clothes dryers
installed near specific heat sources that are identified in Table 6.2.3.3.3 shall be of the
intermediate-temperature classification or higher.
temperature rating indicated in Table 6.2.3.3.3 unless sprinklers are listed for positioning closer to the heatsource.
6.2.3.3.3.1
Sprinklers adjacent to diffusers shall not be required to meet 6.2.3.3.3 where the temperature from thediffuser does not exceed 100°F (38°C).
6.2.3.3.4*
Sprinklers in closets containing ventless clothes dryers shall be of the intermediate-temperatureclassification or higher.
6.2.3.3.5
All sprinklers within a compartment shall have the same temperature classification except where requiredby 6.2.3.3 for a specific location.
Additional Proposed Changes
File Name Description Approved
Table_6.2.3.3.3.docx Table 6.2.3.3.3
Statement of Problem and Substantiation for Public Comment
During the first draft, sections 6.2.3.3.3 and 6.2.3.4 and Table 6.2.3.3.3 were inadvertantly deleted. This comment simply adds back the text and table. It also renumbers the remainder of the section into a more logical progression.
Related Item
First Revision No. 11-NFPA 13R-2016 [Section No. 6.2.3.3.3]
Submitter Information Verification
Submitter Full Name: Peter Schwab
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10 of 71 5/16/17, 1:20 PM
68
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 14:25:41 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
11 of 71 5/16/17, 1:20 PM
69
`
70
Public Comment No. 27-NFPA 13R-2017 [ Section No. 6.2.3.3 [Excluding any
Sub-Sections] ]
The practices of 6.2.3.3.1 through 6.2.3.3.3 shall 5 shall be observed when installing residential sprinklersunless higher expected ambient temperatures require a higher temperature rating.
Statement of Problem and Substantiation for Public Comment
Since two additional sections have been added, the base paragraph needs to recognize those additional sections.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 25-NFPA 13R-2017 [New Section after 6.2.3.3.3.1]
Public Comment No. 26-NFPA 13R-2017 [Section No. 6.2.3.3.3.1]
Related Item
FR11
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 10:02:34 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
12 of 71 5/16/17, 1:20 PM
71
Public Comment No. 44-NFPA 13R-2017 [ Section No. 6.2.3.3.3 ]
6.2.3.3.3*
Sprinklers in closets containing ventless clothes dryers shall be of the intermediate-temperatureclassification or higher.
6.2.3.3.3.1
Sprinklers adjacent to diffusers shall not be required to meet 6.2.3.3.3 where the temperature from thediffuser does not exceed 100°F (38°C).
Statement of Problem and Substantiation for Public Comment
Restore Table 6.2.3.3.3. PI No. 91 simply added annex figures. The action did not delete the table.
Related Item
Public Input No. 91
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 09:42:40 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
13 of 71 5/16/17, 1:20 PM
72
Public Comment No. 25-NFPA 13R-2017 [ New Section after 6.2.3.3.3.1 ]
6.2.3.3.4 Sprinklers installed near specific heat sources that
are identified in Table 6.2.3.3.4 shall be of the temperature
rating indicated in Table 6.2.3.3.4 unless sprinklers are listed
for positioning closer to the heat source.
<Insert Table 6.2.3.3.4, which is Table 6.2.3.3.3 from the 2016 edition>
Additional Proposed Changes
File Name Description Approved
Table_6-2-3-3-4.pdf This is how the table should look
Statement of Problem and Substantiation for Public Comment
This section and table are important to the proper placement of sprinklers with respect to heat sources. I believe it was deleted in error in the first draft.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 26-NFPA 13R-2017 [Section No. 6.2.3.3.3.1]
Public Comment No. 27-NFPA 13R-2017 [Section No. 6.2.3.3 [Excluding anySub-Sections]]
Related Item
FR11
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 09:45:25 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
14 of 71 5/16/17, 1:20 PM
73
Table 6.2.3.3.4
74
Public Comment No. 26-NFPA 13R-2017 [ Section No. 6.2.3.3.3.1 ]
6.2.3.3.3.1 5
Sprinklers adjacent to diffusers shall not be required to meet 6.2.3.3.3 where 4 where the temperaturefrom the diffuser does not exceed 100°F (38°C).
Statement of Problem and Substantiation for Public Comment
First, the section needs to be moved because it only applies to closets with non-venting dryers if it stays where it is. Second, the reference within the section needs to be to the Table where it requires distance from diffusers, not to the section dealing with closets containing dryers.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 25-NFPA 13R-2017 [New Section after 6.2.3.3.3.1]
Public Comment No. 27-NFPA 13R-2017 [Section No. 6.2.3.3 [Excluding anySub-Sections]]
Related Item
FR11
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 09:56:51 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
15 of 71 5/16/17, 1:20 PM
75
Public Comment No. 33-NFPA 13R-2017 [ Section No. 6.2.3.3.3.1 ]
6.2.3.3.3.1 4
Sprinklers adjacent to diffusers shall not be required to meet 6.2.3.3.3 where the temperature from thediffuser does not exceed 100°F (38°C).
Statement of Problem and Substantiation for Public Comment
This is strictly renumbering as the requirements for diffusers not exceeding 100F does not directly relate to the ventless dryer section above and therefore should not be a subsection of the ventless dryer requirement.
Related Item
FR-8
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 10:37:27 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
16 of 71 5/16/17, 1:20 PM
76
Public Comment No. 47-NFPA 13R-2017 [ Section No. 6.4.6.1.1.1 ]
6.4.6.1.1.1
Pendent-type residential sprinklers located under or adjacent to beams in accordance with 7.1.1.3.1 shallbe installed in accordance with one of the following:
(1) Pendent, recessed pendent, and flush-type pendent sprinklers shall be permitted to be installed directlyunder a beam having a maximum depth of 14 in. (350 mm) with the sprinkler deflector 1 in. to 2 in. (25mm to 50 mm) below the beam, or in accordance with the manufacturer’s instructions for recessed orflush sprinklers if the deflector is less than 1 in. (25 mm) below the beam.
(2) Pendent sprinklers, including flush-type pendent sprinklers, shall be permitted to be installed adjacentto beams when the vertical centerline of the sprinkler is no greater than 2 in. (50 mm) from the edge ofthe beam and with the sprinkler deflector 1 in. to 2 in. (25 mm to 50 mm) below the beam, or inaccordance with the manufacturer’s instructions for flush sprinklers if the deflector is less than 1 in. (25mm) below the beam.
Add attached figures
Additional Proposed Changes
File Name Description Approved
Beam_ceiling_figures.pdf New Figures for positioning sprinklers below and adjacent to beams
Statement of Problem and Substantiation for Public Comment
This comment is in support of this new language and seeks to add two new figures to illustrate these requirements.
Note these figures have also been submitted to NFPA 13 and NFPA 13R.
Related Item
FR-12
Submitter Information Verification
Submitter Full Name: Roland Asp
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 11:02:08 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
17 of 71 5/16/17, 1:20 PM
77
78
Public Comment No. 45-NFPA 13R-2017 [ New Section after 6.4.6.3.4.4 ]
6.4.6.3.4.5
In hallways up to 6 ft (1.8 m) in width, pendent sprinklers shall be permitted to be located adjacent tolights without regards to obstructions where the sprinkler is installed in the allowable obstruction zone asshown in figure 6.4.6.3.4.5.
Additional Proposed Changes
File Name Description Approved
pendent_hallway_light_Model_1_.pdf
Statement of Problem and Substantiation for Public Comment
In a hallway, a light should not be an obstruction when the sprinkler is installed adjacent to the light on the with of the hallway.
Related Item
Public Input No. 50
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 10:11:37 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
18 of 71 5/16/17, 1:20 PM
79
80
Public Comment No. 51-NFPA 13R-2017 [ Section No. 6.4.6.3.6.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
19 of 71 5/16/17, 1:20 PM
81
6.4.6.3.6.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
20 of 71 5/16/17, 1:20 PM
82
Sprinklers shall be positioned with respect to continuous obstructions in accordance with Table 6.4.6.3.6.2and Figure 6.4.6.3.6.2.
Table 6.4.6.3.6.2 Positioning of Sprinklers to Avoid Obstructions to Discharge (Residential Upright andPendent Spray Sprinklers)
Distance from Sprinklers to
Side of Obstruction (A)
Maximum Allowable Distance of Deflector AboveBottom of Obstruction (in.) (B)
Less than 1 ft (0.30 m [300 mm]) 0
1 ft (0.30 m [300 mm]) to less Less than 1 ft6 in. (0.45 m [450 mm])
0
1 ft 6 in. (0.45 m [450 mm]) to less Less than2 ft (0.6 m [600 mm])
1 (25 mm)
2 ft (0.6 m [600 mm]) to less Less than 2 ft6 in. (0.75 m [750 mm])
1 (25 mm)
2 ft 6 in. (0.75 m [750 mm]) to less Less than3 ft (0.9 m [900 mm])
1 (25 mm)
3 ft (0.9 m [900 mm]) to less Less than 3 ft6 in. (1.05 m [1050 mm])
3 (75 mm)
3 ft 6 in. (1.05 m [1050 mm]) to less Less than4 ft (1.2 m [1200 mm])
3 (75 mm)
4 ft (1.2 m [1200 mm]) to less Less than 4 ft6 in. (1.35 m [1350 mm])
5 (125 mm)
4 ft 6 in. (1.35 m [1350 mm]) to less Less than5 ft (1.5 m [1500 mm])
7 (175 mm)
5 ft (1.5 m [1500 mm]) to less Less than 5 ft6 in. (1.65 m [1650 mm])
7 (175 mm)
5 ft 6 in. (1.65 m [1650 mm]) to less Less than6 ft (1.8 m [1800 mm])
7 (175 mm)
6 ft (1.8 m [1800 mm]) to less Less than 6 ft6 in. (1.95 m [1950 mm])
9 (225 mm)
6 ft 6 in. (1.95 m [1950 mm]) to less Less than7 ft (2.1 m [2100 mm])
11 (275 mm)
7 ft (2.1 m [2100 mm]) and greater 14 (350 mm)
For SI units, 1 in. = 25 mm; 1 ft = 0.30 m.
Note: For A and B, refer to Figure 6.4.6.3.6.2.
Figure 6.4.6.3.6.2 Positioning of Sprinkler to Avoid Obstruction to Discharge (Residential Uprightand Pendent Spray Sprinklers).
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
21 of 71 5/16/17, 1:20 PM
83
Statement of Problem and Substantiation for Public Comment
This comment is to support First Revision No 683 and to apply the same changes to relatedtables throughout NFPA 13. (Global Revision) This is what was agreed upon at the first draftmeeting and will provide consistency throughout the document.Not that similar comments have been submitted to NFPA 13R and NFPA 13D.
Related Item
FR-683 (NFPA 13)
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 14:27:57 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
22 of 71 5/16/17, 1:20 PM
84
Public Comment No. 52-NFPA 13R-2017 [ Section No. 6.4.6.3.7.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
23 of 71 5/16/17, 1:20 PM
85
6.4.6.3.7.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
24 of 71 5/16/17, 1:20 PM
86
Sprinklers shall be positioned with respect to continuous obstructions in accordance with Table6.4.6.3.7.2(a), Figure 6.4.6.3.7.2(a), Table 6.4.6.3.7.2(b), Figure 6.4.6.3.7.2(b), and Figure 6.4.6.3.7.2(c).
Figure 6.4.6.3.7.2(a) Positioning of Sprinkler to Avoid Obstruction (Residential SidewallSprinklers).
Figure 6.4.6.3.7.2(b) Positioning of Sprinkler to Avoid Obstruction Along Wall (Residential SidewallSprinklers).
Figure 6.4.6.3.7.2(c) Positioning of Sprinkler to Avoid Obstruction Against Wall (ResidentialSidewall Sprinklers).
Table 6.4.6.3.7.2(a) Positioning of Sprinklers to Avoid Obstructions (Residential Sidewall Sprinklers)
Distance from Sidewall Sprinkler to Sideof Obstruction (A)
Maximum Allowable Distance of Deflector AboveBottom of Obstruction (in.) (B)
Less than 8 ft (2.4 m [2400 mm]) Not allowed
8 ft (2.4 m [2400 mm]) to less than 10 ft (3 m[3000 mm])
1 (25 mm)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
25 of 71 5/16/17, 1:20 PM
87
Distance from Sidewall Sprinkler to Sideof Obstruction (A)
Maximum Allowable Distance of Deflector AboveBottom of Obstruction (in.) (B)
10 ft (3 m [3000 mm]) to less Less than 11 ft(3.3 m [3300 mm])
2 (50 mm)
11 ft (3.3 m [3300 mm]) to less Less than12 ft (3.6 m [3600 mm])
3 (75 mm)
12 ft (3.6 m [3600 mm]) to less Less than13 ft (3.9 m [3900 mm])
4 (100 mm)
13 ft (3.9 m [3900 mm]) to less Less than14 ft (4.2 m [4200 mm])
6 (150 mm)
14 ft (4.2 m [4200 mm]) to less Less than15 ft (4.5 m [4500 mm])
7 (175 mm)
15 ft (4.5 m [4500 mm]) to less Less than16 ft (4.8 m [4800 mm])
9 (225 mm)
16 ft (4.8 m [4800 mm]) to less Less than17 ft (5.1 m [5100 mm])
11 (275 mm)
17 ft (5.1 m [5100 mm]) or greater 14 (350 mm)
For SI units, 1 in. = 25 mm; 1 ft = 0.30 m.
Note: For A and B, refer to Figure 6.4.6.3.7.2(a).
Table 6.4.6.3.7.2(b) Positioning of Sprinklers to Avoid Obstructions Along Wall (Residential SidewallSprinklers)
Distance from Sidewall Sprinkler to Side ofObstruction (A)
Maximum Allowable Distance of Deflector AboveBottom of Obstruction (in.) (B)
Less than 1 ft 6 in. (0.45 m [450 mm]) 0
1 ft 6 in. (0.45 m [450 mm]) to less Less than3 ft (0.9 m [900 mm])
1 (25 mm)
3 ft (0.9 m [900 mm]) to less Less than 4 ft(1.2 m [1200 mm])
3 (75 mm)
4 ft (1.2 m [1200 mm]) to less Less than 4 ft6 in. (1.35 m [1350 mm])
5 (125 mm)
4 ft 6 in. (1.35 m [1350 mm]) to less Less than6 ft (1.8 m [1800 mm])
7 (175 mm)
6 ft (1.8 m [1800 mm]) to less Less than 6 ft6 in. (1.95 m [1950 mm])
9 (225 mm)
6 ft 6 in. (1.95 m [1950 mm]) to less Less than7 ft (2.1 m [2100 mm])
11 (275 mm)
7 ft (2.1 m [2100 mm]) to less Less than 7 ft6 in. (2.3 m [2300 mm])
14 (350 mm)
For SI units, 1 in. = 25 mm; 1 ft = 0.30 m.
Note: For A and B, refer to Figure 6.4.6.3.7.2(b).
Statement of Problem and Substantiation for Public Comment
This comment is to support First Revision No 683 and to apply the same changes to relatedtables throughout NFPA 13. (Global Revision) This is what was agreed upon at the first draftmeeting and will provide consistency throughout the document.Not that similar comments have been submitted to NFPA 13R and NFPA 13D.
Related Item
FR-683 (NFPA 13)
Submitter Information Verification
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
26 of 71 5/16/17, 1:20 PM
88
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 14:30:45 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
27 of 71 5/16/17, 1:20 PM
89
Public Comment No. 57-NFPA 13R-2017 [ New Section after 6.5.4.2 ]
6.5.5* Temporary Protection During Construction, Alteration or Demolition.
Temporary fire sprinkler protection during construction, alteration or demolition shall comply with NFPA241.
A.6.5.5 During construction, alternation and demolition, there are many hazardous conditions, such ascutting, welding, grinding and combustible or hazardous product storage that can be made safer byinstalling a temporary fire sprinkler system. Given that such protection will be supplemental to any otherprotection that would be required, NFPA 241 permits temporary fire sprinkler protection when approved bythe AHJ.
Statement of Problem and Substantiation for Public Comment
In discussing rejection of PI 107, the committee suggested that the issue of temporary sprinklers during construction was better suited for inclusion in NFPA 241. That suggestion was pursued and resulted in an addition of a new section on temporary sprinkler protection in the next edition of NFPA 241. It is appropriate for NFPA 13R to include a reference to NFPA 241 since sprinkler contractors won't ordinarily be familiar with that standard.
For reference, the NFPA 241 text is as follows:
7.9 Temporary Protection During Construction, Alteration or Demolition.During construction, alteration or demolition, the use of temporary fire sprinkler protection approved by the AHJ shall be permitted as supplemental protection.
A.7.9 During construction, alternation and demolition, there are many hazardous conditions, such as cutting, welding, grinding and combustible or hazardous product storage that can be made safer by installing a temporary fire sprinkler system. Given that such protection will besupplemental to any other protection that would be required, there is no harm in allowing this additional safety feature on a temporary basis if the design basis and installation is considered acceptable by the AHJ.
Related Item
pi 109
Submitter Information Verification
Submitter Full Name: Jeffrey Shapiro
Organization: International Code Consultants
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 22:47:19 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
28 of 71 5/16/17, 1:20 PM
90
Public Comment No. 19-NFPA 13R-2017 [ Section No. 6.6.5 ]
6.6.5 *
Except as provided for in 6.6.5.1, sprinklers shall not be required in any lanais, porches, balconies,corridors, carports, porte cocheres, and stairs that are open and attached.
6.6.5.1
Corridors that are open to the outside atmosphere and are separated from the exit stairwell shall notrequire sprinkler protection.
6.6.5.2
Where a roof or deck is provided above, sprinklers shall be installed to protect attached exterior balconies,attached exterior decks, and ground floor patios serving dwelling units in buildings of Construction Type V.
6.6.5. 1 2 .1
Where sidewall sprinklers are installed beneath decks or balconies constructed with open wood joists,sprinklers shall be permitted to be installed with deflectors not less than 1 in. (25 mm) or more than 6 in.(152 mm) below the structural members, provided that the deflector is not more than 14 in. (356 mm) belowthe underside surface of the deck.
Statement of Problem and Substantiation for Public Comment
Aligns NFPA 13R with the IBC.
Related Item
FR No. 15
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Fri Apr 21 08:31:55 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
29 of 71 5/16/17, 1:20 PM
91
Public Comment No. 34-NFPA 13R-2017 [ Section No. 6.6.5 [Excluding any
Sub-Sections] ]
Except as provided for in 6.6.5.1 , sprinklers shall not be required in any lanais, porches, balconies,corridors, carports, porte cocheres, other similar features, and stairs that are open and attached.
Statement of Problem and Substantiation for Public Comment
Different terminology is used to describe the similar building features and the use of a regional/new term should not exclude this section from being applied.
Related Item
FR-15
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 10:53:26 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
30 of 71 5/16/17, 1:20 PM
92
Public Comment No. 48-NFPA 13R-2017 [ Section No. 6.6.9 ]
6.6.9 Interior Stairwells Stairwells .
6.6.9.1 Enclosed Stairwells
6.6.9.1.1
Except as allowed by 6.6.9.2, 6.6.9.3, and 6.6.9.4, sprinklers shall be installed throughout all interior,enclosed stairwells.
6.6.9.1. 2*
Sprinklers shall not be required underneath stair risers in dwelling units where the walls and ceilings aresurfaced with noncombustible or limited-combustible finishes.
6.6.9.1. 3
Sprinklers shall not be required under intermediate landings.
6.6.9.1.4
Closets located underneath stairs shall be protected in accordance with 6.4.6.3.2, 6.6.3, 6.6.4, and 6.6.7.
6.6.9.4 1.5
Interior stairwells located outside the dwelling unit shall be protected in accordance with NFPA 13.
6.6.9.2 Unenclosed stairs
6.6.9.2.1
Sprinkler shall not be required beneath the landings or treads of exposed stairs
Additional Proposed Changes
File Name Description Approved
open_tread_stairs.jpg Picture of an open stair located inside a condominium.
Statement of Problem and Substantiation for Public Comment
Storage beneath the open tread stairs is unlikely and discharge from surrounding sprinklers will address the fire if one were to occur there. Without guidance the industry tends to refer to NFPA 13 which is extremely conservative.
Related Item
Public Input No. 27-NFPA 13R-2016
Submitter Information Verification
Submitter Full Name: Thomas Noble
Organization: AFSA
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 11:15:58 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
31 of 71 5/16/17, 1:20 PM
93
94
Public Comment No. 1-NFPA 13R-2017 [ New Section after 6.6.9.4 ]
6.6.10 Open-Ended Corridors.
6.6.10.1 Sprinkler protection shall be provided in open-ended corridors and associated stairways and
ramps where the corridor and stairway is not separated.
6.6.10.2 Exterior corridors that are 50 percent open shall not be required to be protected.
A.6.6.10.2 An example of an exterior corridor that is fifty percent open is shown in Figure A.6.6.10.2.
Statement of Problem and Substantiation for Public Comment
Reconsider PI #27 and insert the suggested language from PI #27. The title of section 6.6 is "Location of Sprinklers" so it appears to be warranted that one would go to chapter 6 to look to see how open corridors are addressed with respect to fire sprinkler protection under NFPA 13R. By not addressing this issue, the TC creates the potential for this item to be missed by the contractor and AHJ at the time of permit, then only to be caught at the time of inspection. This approach only encourages confusion and the potential for change orders that serves no one. The installation standard should strive to provide clarity and direction as to when and where fire sprinklers are required. PI #27 accomplishes that objective with no downside. The TC should reconsider the text as proposed in PI #27.
Related Item
Public Input No. 27-NFPA 13R-2016 [New Section after 6.6.9.4]
Submitter Information Verification
Submitter Full Name: Anthony Apfelbeck
Organization: Altamonte Springs Building/Fire Safety Division
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 09:40:12 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
32 of 71 5/16/17, 1:20 PM
95
Public Comment No. 2-NFPA 13R-2017 [ New Section after 6.8.8 ]
6.8.9 Multiple Occupancies
Control valve arrangements in mixed occupancy buildings with a residential occupancy shall be in
accordance with 6.8.9.
6.8.9.1
In podium/pedestal buildings, the system(s) below the podium/pedestal shall have a separate control valve.
6.8.9.2*
In buildings that are not a podium/pedestal where there are mixed occupancy/occupancies and NFPA 13 is
used for the non-residential occupancy/occupancies, a single control valve shall be permitted for the entire
building.
A.6.8.9.2
NFPA 13 requires a separate sprinkler system per floor in multi-story buildings meeting certain
requirements. It should not be necessary to follow these rules where there are mixed occupancies and the
use of NFPA 13 & NFPA 13R systems.
6.8.9.3*
In buildings with mixed occupancies and the non-residential occupancy is mercantile, it shall have a
separate control valve.
A.8.9.3
Many mercantile spaces require modifications as tenants move in and out. The addition control requirement
is to prevent the residential portion from being shut down during modifications.
Statement of Problem and Substantiation for Public Comment
Reconsider PI #57 and accept the proposed text from PI #57. The concerns raised in PI #57 are valid and should be addressed. As an example, in a mixed occupancy building with residential above mercantile, business or assembly, there will be many occasions where tenant improvement work is occurring in the non-residential occupancies. Without separate control valves, the residential portion of the building will be without fire sprinkler protection while the TI work is occurring in the non-residential spaces. This creates an unnecessary hazard within the residential occupancies when they are without protection due to the TI work.
In addition, with the TC justifying a resolution on this issue by stating there are certain situations when a single control valve would be acceptable, that then raises the inverse of the resolution statement....If the TC feels there is justification for "certain situations" where a single control valve would be acceptable, that also means there are also "certain situations" where a single control valve is clearly not acceptable. If there are truly "certain situations" where the single control valve is warranted, TC could address this concern in the PI resolution by revising the PI language to address the specific situation where the TC is envisioning a single control valve being acceptable by simply including such language in the standard under this section. (The proponent of this PC is not proposing such language and he is unable to envision a "certain situation" where single control valve would be acceptable.)
Related Item
Public Input No. 57-NFPA 13R-2016 [New Section after 6.8.8]
Submitter Information Verification
Submitter Full Name: Anthony Apfelbeck
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
33 of 71 5/16/17, 1:20 PM
96
Organization: Altamonte Springs Building/Fire Safety Division
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 09:52:07 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
34 of 71 5/16/17, 1:20 PM
97
Public Comment No. 3-NFPA 13R-2017 [ Section No. 7.4.1 ]
7.4.1 Occupied Attics and Attics Used for Storage.
Attics that are intended for occupancy or storage shall comply with Section 7. 1, where 4.1.1 Where theattic is part of the dwelling unit , or and is intended for occupancy or storage, it shall comply with Section7.2 , where 1.
7.4.1.2 Where the attic is outside of the dwelling unit, it shall comply with Section 7 .2.
7.4.1. 1 3 Sprinkler temperature ratings shall comply with 6.2.3 .
Statement of Problem and Substantiation for Public Comment
The FR language in 7.4.1 is very confusing in the current form. This PI separates the two requirements from the current 7.4.1 into separate sections for better readability so designers and AHJs can more easily understand the intent.
Related Item
First Revision No. 41-NFPA 13R-2016 [New Section after 7.4]
Submitter Information Verification
Submitter Full Name: Anthony Apfelbeck
Organization: Altamonte Springs Building/Fire Safety Division
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 10:25:03 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
35 of 71 5/16/17, 1:20 PM
98
Public Comment No. 40-NFPA 13R-2017 [ Section No. 7.4.1 [Excluding any
Sub-Sections] ]
Attics that are intended for occupancy or storage shall comply with Section 7.1 , where the attic is part ofthe dwelling unit, or Section 7.2 , where the attic is outside of the dwelling unit. NFPA 13.
Statement of Problem and Substantiation for Public Comment
An attic would most likely never be acceptable for living purposes per model building codes. See the definition below from the ICC and the commentary in regards to attics. An attic used for storage accessible from the dwelling unit or outside the dwelling unit needs to be protected in accordance with NFPA 13. Also recommend changing the title.
OCCUPIABLE SPACE. A room or enclosed spacedesigned for human occupancy in which individuals congregatefor amusement, educational or similar purposes or inwhich occupants are engaged at labor, and which is equippedwith means of egress and light and ventilation facilities meetingthe requirements of this code.
Occupiable spaces are those areas designed forhuman occupancy. It applies to both residential andnonresidential spaces alike. Most spaces in a buildingare occupiable spaces. Based on the nature ofthe occupancy, various code sections apply. All habitablespaces are also considered occupiable (see thedefinition of “Habitable space”). However, all occupiablespaces are not habitable. Additionally, somespaces are neither habitable nor occupiable. Thecode identifies crawl spaces, attics, penthouses andelevated platforms (mechanical or industrial equipment)as unoccupied spaces. Since the code generallystates how these spaces must be accessed, butdoes not specifically require means of egress, theywould not be occupiable spaces. If access is limitedto maintenance and service personnel, it is likely thata space is not occupiable.
Related Item
Public Input No. 103
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 14:51:16 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
36 of 71 5/16/17, 1:20 PM
99
Public Comment No. 41-NFPA 13R-2017 [ Section No. 7.4.3 [Excluding any
Sub-Sections] ]
Attics that are not required by 7.5 4 .1 to have sprinklers shall be permitted to have protection in accordancewith one of the following.
(1) Protection complying with NFPA 13
(2) Protection using sprinklers specifically listed to provide attic protection in residential occupancies using
a discharge density of not less than 0.05 gpm/ft2 (2.04 mm/min) and a design area of not less than foursprinklers
Statement of Problem and Substantiation for Public Comment
Reference to 4.5.1 is incorrect.
Related Item
Public Input No. 103
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 15:43:31 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
37 of 71 5/16/17, 1:20 PM
100
Public Comment No. 58-NFPA 13R-2017 [ Section No. 7.4.3 [Excluding any
Sub-Sections] ]
Attics that are not required by 7.5 4 .1 to have sprinklers shall be permitted to have protection in accordancewith one of the following.
(1) Protection complying with NFPA 13
(2) Protection using sprinklers specifically listed to provide attic protection in residential occupancies using
a discharge density of not less than 0.05 gpm/ft2 (2.04 mm/min) and a design area of not less than foursprinklers
Statement of Problem and Substantiation for Public Comment
editorial correction to match approved committee action on FR and the original submittal
Related Item
PI 103
Submitter Information Verification
Submitter Full Name: Jeffrey Shapiro
Organization: International Code Consultants
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 23:31:18 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
38 of 71 5/16/17, 1:20 PM
101
Public Comment No. 49-NFPA 13R-2017 [ New Section after 9.2.1 ]
TITLE OF NEW CONTENT
9.2.1.1 In buildings with mixed occupancies where the nonresidential occupancy/occupancies is protectedwith an NFPA 13 system,100 GPM for outside hose shall be added to the water supply flow and duration forthe NFPA 13R hydraulically calculated systems.
9.2.1.2 Water allowance for outside hose shall be added to the sprinkler requirement at the connection tothe city main or a private fire hydrant, whichever is closer to the system riser.
Statement of Problem and Substantiation for Public Comment
This correlates with new section 6.11.6 that allows a common FDC in buildings with mixed use and NFPA 13 and 13R criteria in the same building. If the FDC is common and the fire fighters will be using hose streams during a fire event, the water supply must be capable of supplying the system demand plus the hose streams.
Related Item
FR No. 23
FR No. 52
Submitter Information Verification
Submitter Full Name: Terry Victor
Organization: TycoSimplexGrinnell
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 11:53:00 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
39 of 71 5/16/17, 1:20 PM
102
Public Comment No. 11-NFPA 13R-2017 [ Section No. 9.3.2 [Excluding any
Sub-Sections] ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
40 of 71 5/16/17, 1:20 PM
103
Domestic demand shall be based upon Table 9.3.2(a) and Table 9.3.2(b).
Table 9.3.2(a) Fixture Load Values
Facility Type Unit
Private Facilities (those within individual dwelling units)
Bathroom group with flush tank (including lavatory, water closet, and bathtub with shower) 6
Bathroom group with flush valve 8
Bathtub 2
Dishwasher 1
Kitchen sink 2
Laundry trays 3
Lavatory 1
Shower stall 2
Washing machine 2
Water closet with flush valve 6
Water closet with flush tank 3
Public Facilities
Bathtub 4
Drinking fountain 0
Kitchen sink 4
Lavatory 2
Service sink 3
Shower head 4
Urinal with 1 in. (25 mm) flush valve 10
Urinal with 3⁄4 in. (20 mm) flush valve 5
Urinal with flush tank 3
Washing machine [8 lb (3.63 kg)] 3
Washing machine [16 lb (7.26 kg)] 4
Water closet with flush valve 10
Water closet with flush tank 5
Table 9.3.2(b) Total Estimated Domestic Demand
Total Demand
Total Fixture Load Units [fromTable 9.3.3(a)]
For Systems with PredominatelyFlush Tanks
For Systems with PredominatelyLoad Units
gpm L/min gpm L/min
1 3 11.5 — —
2 5 19 — —
5 10 38 15 57
10 15 57 25 95
20 20 76 35 130
35 25 95 45 170
50 30 115 50 190
70 35 130 60 225
100 45 170 70 265
150 55 210 80 305
200 65 245 90 340
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
41 of 71 5/16/17, 1:20 PM
104
Total Demand
Total Fixture Load Units [fromTable 9.3.3(a)]
For Systems with PredominatelyFlush Tanks
For Systems with PredominatelyLoad Units
250 75 285 100 380
350 100 380 125 475
500 125 475 150 570
750 175 660 175 660
1000 200 755 200 755
1500 275 1040 275 1040
2000 325 1230 325 1230
3500 500 1900 500 1900
Additional Proposed Changes
File Name Description Approved
Domestic.docx Table 9.3.2(a)
Statement of Problem and Substantiation for Public Comment
Modify the Fixture Load Values for domestic demand calculations based on current values. See the attached file as terraview and tables are not compatible. Values come from the IPC. If accepted, staff will need to convert for table b
Related Item
FR-52
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 23 10:30:49 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
42 of 71 5/16/17, 1:20 PM
105
Table 9.3.2(a) Fixture Load Values Facility Type Unit Private Facilities (those within individual dwelling units) Bathroom group with flush tank (including 63.6 lavatory, water closet, and bathtub with shower) Bathroom group with flush valve 8 Bathtub 21.4 Dishwasher 11.4 Kitchen sink 21.4 Laundry trays (1 to 3) 31.4 Lavatory 10.7 Shower stall head 21.4 Washing machine 21.4 Water closet with flush valve 6 Water closet with flush tank 32.2 Public Facilities Bathtub 4 Drinking fountain 0 Kitchen sink 4 Lavatory 2 Service sink 3 Shower head 4 Urinal with 1 in. (25 mm) flush valve 10 Urinal with 3⁄4 in. (20 mm) flush valve 5 Urinal with flush tank 3 Washing machine [8 lb (3.63 kg)] 3 Washing machine [16 lb (7.26 kg)] 4 Water closet with flush valve 10 Water closet with flush tank 5
106
Public Comment No. 20-NFPA 13R-2017 [ Section No. 9.3.2 [Excluding any
Sub-Sections] ]
Domestic demand shall be based upon Table 9.3.2(a) and Table 9.3.2(b) .
Table 9.3.2(a) Fixture Load Values
Facility Type Unit Private Facilities (those within individual dwelling units) Bathroom group with flushtank (including lavatory, water closet, and bathtub with shower) 6 Bathroom group with flush valve 8Bathtub 2 Dishwasher 1 Kitchen sink 2 Laundry trays 3 Lavatory 1 Shower stall 2 Washing machine 2Water closet with flush valve 6 Water closet with flush tank 3 Public Facilities Bathtub 4 Drinkingfountain 0 Kitchen sink 4 Lavatory 2 Service sink 3 Shower head 4 Urinal with 1 in. (25 mm) flush valve
10 Urinal with 3 ⁄ 4 in. (20 mm) flush valve 5 Urinal with flush tank 3 Washing machine [8 lb (3.63 kg)] 3Washing machine [16 lb (7.26 kg)] 4 Water closet with flush valve 10 Water closet with flush tank 5
Table 9.3.2(b) Total Estimated Domestic Demand
Total Demand Total Fixture Load Units [from Table 9.3.3(a)] For Systems with Predominately FlushTanks For Systems with Predominately Load Units gpm L/min gpm L/min 1 3 11.5 — — 2 5 19— — 5 10 38 15 57 10 15 57 25 95 20 20 76 35 130 35 25 95 45 170 50 30 115 50 190 70 35 130 60 225 100 45 17
Statement of Problem and Substantiation for Public Comment
These tables are old and do not reflect the newer low flow technology of plumbing fixtures. It is one thing to have them in the annex as suggestions. It is another thing to have them in the body of the standard, making them mandatory. If the committee wants mandatory values for combined domestic demand, the values need to be more representative of current fixtures.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 21-NFPA 13R-2017 [Section No. 9.3.2.1]
Public Comment No. 22-NFPA 13R-2017 [Section No. 9.3.3]
Public Comment No. 23-NFPA 13R-2017 [Section No. A.9.3]
Related Item
FR52
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Wed Apr 26 16:13:51 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
43 of 71 5/16/17, 1:20 PM
107
Public Comment No. 35-NFPA 13R-2017 [ Section No. 9.3.2 [Excluding any
Sub-Sections] ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
44 of 71 5/16/17, 1:20 PM
108
Domestic demand shall be based upon Table 9.3.2(a) and Table 9.3.2(b).
Table 9.3.2(a) Fixture Load Values
Facility Type Unit
Private Facilities (those within individual dwelling units)
Bathroom group with flush tank (including lavatory, water closet, and bathtub with shower) 3. 6
Bathroom group with flush valve 8
Bathtub 2 1.4
Dishwasher 1.4
Kitchen sink 2 1.4
Laundry trays (1 to 3 ) 1.4
Lavatory 1 0.7
Shower stall head 2 1.4
Washing machine 2 1.4
Water closet with flush valve 6
Water closet with flush tank 3 2.2
Public Facilities
Bathtub 4
Drinking fountain 0
Kitchen sink 4
Lavatory 2
Service sink 3
Shower head 4
Urinal with 1 in. (25 mm) flush valve 10
Urinal with 3⁄4 in. (20 mm) flush valve 5
Urinal with flush tank 3
Washing machine [8 lb (3.63 kg)] 3
Washing machine [16 lb (7.26 kg)] 4
Water closet with flush valve 10
Water closet with flush tank 5
Table 9.3.2(b) Total Estimated Domestic Demand
Total Demand
Total Fixture Load Units[from Table 9.3.3(a)]
For Systems withPredominately Flush Tanks
For Systems withPredominately Load Units
gpm L/min gpm L/min
1 3 11.5 — —
2 5 19 — —
5 10 38 15 57
10 15 57 25 95
20 20 76 35 130
35 25 95 45 170
50 30 115 50 190
70 35 130 60 225
100 45 170 70 265
150 55 210 80 305
200 65 245 90 340
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
45 of 71 5/16/17, 1:20 PM
109
Total Demand
Total Fixture Load Units[from Table 9.3.3(a)]
For Systems withPredominately Flush Tanks
For Systems withPredominately Load Units
250 75 285 100 380
350 100 380 125 475
500 125 475 150 570
750 175 660 175 660
1000 200 755 200 755
1500 275 1040 275 1040
2000 325 1230 325 1230
3500 500 1900 500 1900
Statement of Problem and Substantiation for Public Comment
These are updated ficture load tables used by the industry. The existing tables in the standard are 20 years old and are no longer accurate.
Related Item
FR-52
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 10:58:35 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
46 of 71 5/16/17, 1:20 PM
110
Public Comment No. 24-NFPA 13R-2017 [ Sections 9.3.2, 9.3.3 ]
Sections 9.3.2, 9.3.3
9.3.2
Domestic demand shall be based upon Table 9.3.2(a) and Table 9.3.2(b) .
Table 9.3.2(a) Fixture Load Values
Facility Type Unit Private Facilities (those within individual dwelling units) Bathroom group with flushtank (including lavatory, water closet, and bathtub with shower) 6 Bathroom group with flush valve 8Bathtub 2 Dishwasher 1 Kitchen sink 2 Laundry trays 3 Lavatory 1 Shower stall 2 Washing machine2 Water closet with flush valve 6 Water closet with flush tank 3 Public Facilities Bathtub 4 Drinkingfountain 0 Kitchen sink 4 Lavatory 2 Service sink 3 Shower head 4 Urinal with 1 in. (25 mm) flush
valve 10 Urinal with 3 ⁄ 4 in. (20 mm) flush valve 5 Urinal with flush tank 3 Washing machine [8 lb(3.63 kg)] 3 Washing machine [16 lb (7.26 kg)] 4 Water closet with flush valve 10 Water closet with flushtank 5
Table 9.3.2(b) Total Estimated Domestic Demand
Total Demand Total Fixture Load Units [from Table 9.3.3(a)] For Systems with Predominately FlushTanks For Systems with Predominately Load Units gpm L/min gpm L/min 1 3 11.5 — — 2 5 19— — 5 10 38 15 57 10 15 57 25 95 20 20 76 35 130 35 25 95 45 170 50 30 115 50 190 70 35 130 60 225 100 45 17
9.3.2.1
Interpolation of Table 9.3.2(b) shall be allowed when calculating domestic demand.
9.3.3
Where more demanding domestic demands are specified, they shall be used.
(Delete these sections on the domestic demand and their Tables from the body of the Code. Notethat the Annex Note to Section 9.3 still has these two Tables listed and shown in the Annex Notewhere they should be based on my Committee notes I took during the First Draft Meeting.)
Statement of Problem and Substantiation for Public Comment
I distinctly remember at the First Draft Meeting we had discussion about moving the old Fixture Load Values (Table A.9.6(a)) and Total Estimated Domestic Demand (Table A.9.6(b)) from the Annex to the body of the Code under this FR. We discussed that these Tables were from more than 30 years ago and that the recent Model Plumbing Codes have revised similar Tables in their Codes to reflect modern, more energy and water saving efficient fixture loads and water demands. The Committee agreed that moving these Tables at this time into the body of the Code was not a good move and voted not to move them from the Annex. We voted on deleting the proposed new Section 9.3.2 from this rewrite of Chapter 9 and it passed. However on the ballot this Section is shown as being part of the First Revision. To confirm my understanding that the Committee did indeed agree to leave these Tables in the Annex, Staff did place these Tables in the Annex Note to New Section 9.3 but forgot to delete these two Sections from the body of the Code. So since the Tables are shown in the Annex Note for Section 9.3, I conclude that my notes were correct and it was the intent of the Committee to leave the Tables in the Annex. To further the argument to leave these Tables in the Annex is the fact that both these Tables are only in the Appendix of each of the Model Plumbing Codes (IPC and UPC), not in their body of the Code. It would be poor code practice to place Appendix Items from the plumbing codes into the body of the NFPA 13R Standard. Also, it is my understanding that the Model Plumbing Codes are reviewing code proposals based on research and a study that was conducted at the University of Cincinnati that is a new method for sizing the water piping based on flow rate and probability of simultaneous use.The sizing method uses Hunter's concepts and updates the sizing based on a study conducted throughout the US (See http://tinyurl.com/kxcevr7 for detailed information on this new method). To lock users of NFPA 13R into only one method to calculate domestic demand based on old technology would not be in the best interest of the fire protection and plumbing communities. We should leave these Tables in the NFPA 13R Annex so the code user can continue to rely on the Model Plumbing Codes to address the domestic water demand options in our modern buildings.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
47 of 71 5/16/17, 1:20 PM
111
Related Item
SR #52
Submitter Information Verification
Submitter Full Name: Marshall Klein
Organization: Marshall A Klein Associates
Street Address:
City:
State:
Zip:
Submittal Date: Thu May 04 16:26:27 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
48 of 71 5/16/17, 1:20 PM
112
Public Comment No. 21-NFPA 13R-2017 [ Section No. 9.3.2.1 ]
9.3.2.1
Interpolation of Table 9.3.2(b) shall be allowed when calculating domestic demand.
Statement of Problem and Substantiation for Public Comment
This is related to the deletion of the tables in PC-20. If you get rid of the tables, you have to get rid of this statement as well.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 20-NFPA 13R-2017 [Section No. 9.3.2 [Excluding any Sub-Sections]]
Related Item
FR52
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Wed Apr 26 16:22:19 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
49 of 71 5/16/17, 1:20 PM
113
Public Comment No. 22-NFPA 13R-2017 [ Section No. 9.3.3 ]
9.3.3
Where more demanding domestic demands are specified, they shall be used.
Statement of Problem and Substantiation for Public Comment
This is related to PC-20. If the tables are removed, this section needs to be removed as well.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 20-NFPA 13R-2017 [Section No. 9.3.2 [Excluding any Sub-Sections]]
Related Item
FR52
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Wed Apr 26 16:24:17 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
50 of 71 5/16/17, 1:20 PM
114
Public Comment No. 31-NFPA 13R-2017 [ Section No. 9.3.5 ]
9.3.5
The flow and pressure of a public water supply shall be determined from waterflow test data or otherapproved method.
9.3.
5.1
Water supply fluctuations must be addressed in the design of sprinkler systems, as required by theauthority having jurisdiction.
9.3.5.2
Safety factors must be addressed in the design of sprinkler systems, as required by the authority havingjurisdiction.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
51 of 71 5/16/17, 1:20 PM
115
6 Where a waterflow test was conducted to determine the strength of a water supply and knowledge ofthe water supply is available, the volume and pressure available for use for a fire protection system shallbe determined from 9.3.6.1. Where a waterflow test was conducted to determine the strength of a watersupply and knowledge of the water supply is not available, the volume and pressure available for use fora fire protection system shall be determined from 9.3.6.2.
9.3.6.1* Water supply adjustments shall be based on knowledge of the water supply and engineeringjudgment taking into account reasonable daily and seasonal fluctuations not extreme conditions.
9.3.6.2* If knowledge of the water supply is unavailable, the following formula shall be used to determineavailable flow and pressure:
P = The pressure available from the water supply to use for a fire protection system that will becalculated for a given flow (Q)
Q = The flow that will be used to calculate the available pressure from the water supply.
P R = The residual pressure measured during the waterflow test while the flow Q R was
discharging from the water supply.
P S = The static pressure measured during the waterflow test.
Q R = The flow discharging from the water supply when P R was measured.
P L = The expected low static pressure at the location of the test results accounting for daily and
seasonal fluctuations (not extreme conditions) obtained from the water utility. Where the waterauthority does not provide P L , see 9.3.6.3.
9.3.6.3 Where the water authority does not provide a value for P L , the value of P L shall be calculated
from the following formula:
P L = 0.9P S
A.9.3.6.1 The purpose of the adjustment is to take into account reasonable daily and seasonal variationsin the water supply, which are easily predicted and tracked by a water utility. It is not the intent to use thissection to account for unusual conditions such as 100 year droughts or water main breaks. Theseunusual conditions are handled through the Impairment Procedures of NFPA 25 and should not beconsidered when determining the ability of a water supply to meet the demand of a fire protection systemunder more normal circumstances.
A.9.3.6.2 Consider the following example. A waterflow test is conducted at a location where a city watermain is going to be tapped for a new sprinkler system. During the test, the static pressure is measured at70 psi, the residual pressure is measured at 50 psi while 1300 gpm was discharging from a nearbyhydrant. The water utility is contacted and they indicate that a reasonable low static pressure accountingfor typical daily and seasonal fluctuations in this area is 55 psi. The equation that describes the watersupply available for a fire sprinkler system would be:
There are two ways to use this formula. One would be to assume two different values for Q, calculate Pand then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling on or below the lineon this graph would be acceptable in accordance with NFPA 13 to work with this water supply. In thiscase, the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can be plotted on log 1.85 paper as shown in FigureA.9.3.6.2.
The second way to use this formula would be to calculate the fire protection system and determine theflow necessary to make the system work. Plug this flow into the formula above and see what theavailable pressure from the water supply will be at that flow. For example, if a sprinkler system connectedto this water supply had a demand of 580 gpm, the available pressure from the water supply would be:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
52 of 71 5/16/17, 1:20 PM
116
Additional Proposed Changes
File Name Description Approved
Safety_Margin_Proposal-NFPA_13R.docx
This is how the proposal should look with the formulas and figures in place
Statement of Problem and Substantiation for Public Comment
The committee was looking for correlation information at the first draft meeting. The Discharge Criteria accepted the proposal with a few changes, which should provide the committee with the correlation information they were seeking.
Related Item
PI53
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 12:17:05 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
53 of 71 5/16/17, 1:20 PM
117
Water Supply Adjustment Proposals Put Together Insert new sections as follows: 9.3.6 Where a waterflow test was conducted to determine the strength of a water supply and knowledge of the water supply is available, the volume and pressure available for use for a fire protection system shall be determined from 9.4.1. Where a waterflow test was conducted to determine the strength of a water supply and knowledge of the water supply is not available, the volume and pressure available for use for a fire protection system shall be determined from 9.4.2. 9.3.6.1* Water supply adjustments shall be based on knowledge of the water supply and engineering judgment taking into account reasonable daily and seasonal fluctuations not extreme conditions. 9.3.6.2* If knowledge of the water supply is unavailable, the following formula shall be used to determine available flow and pressure:
LR
SR PQ
QPPP
85.1
P = The pressure available from the water supply to use for a fire protection system that will be calculated for a given flow (Q) Q = The flow that will be used to calculate the available pressure from the water supply. PR = The residual pressure measured during the waterflow test while the flow QR was discharging from the water supply. PS = The static pressure measured during the waterflow test. QR = The flow discharging from the water supply when PR was measured. PL = The expected low static pressure at the location of the test results accounting for daily and seasonal fluctuations (not extreme conditions) obtained from the water utility. Where the water authority does not provide PL, see 9.4.3.
9.3.6.3 Where the water authority does not provide a value for PL, the value of PL shall be calculated from the following formula:
PL = 0.9PS A.9.3.6.1 The purpose of the adjustment is to take into account reasonable daily and seasonal variations in the water supply, which are easily predicted and tracked by a water utility. It is not
118
the intent to use this section to account for unusual conditions such as 100 year droughts or water main breaks. These unusual conditions are handled through the Impairment Procedures of NFPA 25 and should not be considered when determining the ability of a water supply to meet the demand of a fire protection system under more normal circumstances. A.9.3.6.2 Consider the following example. A waterflow test is conducted at a location where a city water main is going to be tapped for a new sprinkler system. During the test, the static pressure is measured at 70 psi, the residual pressure is measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. The water utility is contacted and they indicate that a reasonable low static pressure accounting for typical daily and seasonal fluctuations in this area is 55 psi. The equation that describes the water supply available for a fire sprinkler system would be:
551300
705085.1
QP
There are two ways to use this formula. One would be to assume two different values for Q, calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling on or below the line on this graph would be acceptable in accordance with NFPA 13 to work with this water supply. In this case, the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can be plotted on log 1.85 paper as shown in Figure A.9.3.6.2. The second way to use this formula would be to calculate the fire protection system and determine the flow necessary to make the system work. Plug this flow into the formula above and see what the available pressure from the water supply will be at that flow. For example, if a sprinkler system connected to this water supply had a demand of 580 gpm, the available pressure from the water supply would be:
551300
5807050
85.1
P
P = (-20)(0.225) + 55
P = 50.5 psi
So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will work with this water supply.
119
Figure A.9.3.6.2 Available Water Supply Curve for Example in Section A.9.3.6.2
Sprinkler system demand can be anywhere in shaded region
120
Public Comment No. 29-NFPA 13R-2017 [ Section No. 9.7 ]
9.7 Fire Pump.
9.7.1* A single automatically controlled fire pump in accordance with NFPA 20 shall be an acceptablewater supply source.
9.7.2 Fire pumps shall be designed and installed in accordance with NFPA 20.
A.9.7.1 A separate fire pump is not required for every building. It is a common and acceptable practice toprovide a single fire pump for multiple buildings where the buildings are under the control of the sameowner or management firm, or where the multiple owners of the buildings have enterred into a cooperativeagreement for the maintenance and care of the fire pump system. In the case where a fire pump servesmultiple buildings, it must be sized so that it can meet the demand of the largest single fire that might occurin any of the buildings, but it is not required to meet the demand of multiple fires simultaneously.
Statement of Problem and Substantiation for Public Comment
There are two separate and distinct ideas being provided in section 9.7. It is better to separate them so that there is no confusion. If section 9.7 is left as it was in the first draft, it implies that a fire pump that does not meet NFPA 20 might be acceptable, which has not been the position of the committee. Also, clarification of the single fire pump for multiple buildings is important to the concept of having a single fire pump as proposed in the first draft.
Related Item
FR52
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 10:21:41 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
54 of 71 5/16/17, 1:20 PM
121
Public Comment No. 42-NFPA 13R-2017 [ Section No. A.1.1 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
55 of 71 5/16/17, 1:20 PM
122
A.1.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
56 of 71 5/16/17, 1:20 PM
123
NFPA 13R is appropriate for use as an alternative to NFPA 13 only in those residential occupancies, asdefined in this standard, up to and including four aboveground stories in height. It should be noted thatmodel building codes contain special allowances for pedestal or podium-style buildings, which permit thestory height for structures above the pedestal to be measured from the top surface of the pedestal, ratherthan from grade plane, and it is the intent of NFPA 13R to follow this model building code method fordetermining the number of stories. Accordingly, it is possible for a four-story residential structure to bewithin the scope of NFPA 13R even when that structure is constructed on top of a one-story pedestal.However, where this is allowed, model building codes will require the pedestal portion to be constructedusing Type I construction, and the pedestal portion will be required to be protected by an NFPA13–compliant sprinkler system.
Regardless of whether a building does or does not involve a pedestal, NFPA 13R systems are alwayslimited to structures that do not exceed 60 ft (18 m) in height above grade plane. Note that model buildingcodes do not allow building height to be measured from the top of a pedestal. That allowance only appliesto determining the number of stories. The 60-foot overall height limit is consistent with limits established bymodel building codes for buildings of Type V construction. The height of a structure above grade plane isdetermined by model building codes, which base the height on the average height of the highest roofsurface above grade plane. For further information on the building height story limits, see model buildingcodes.
Buildings that contain multiple occupancies (either separated or nonseparated), accessory occupancies, orincidental uses are often subject to special rules that might restrict the use of NFPA 13R. In buildingscontaining a residential occupancy properly separated from other occupancies, the use of NFPA 13R in theresidential occupancy and NFPA 13 in the non residential occupancy(s) is appropriate. Refer to theadopted building code to determine whether such restrictions are applicable.
The criteria in this standard are based on full-scale fire tests of rooms containing typical furnishings found inresidential living rooms, kitchens, and bedrooms. The furnishings were arranged as typically found indwelling units in a manner similar to that shown in Figure A.1.1(a), Figure A.1.1(b), and Figure A.1.1(c).Sixty full-scale fire tests were conducted in a two-story dwelling in Los Angeles, California, and 16 testswere conducted in a 14 ft (4.3 m) wide mobile home in Charlotte, North Carolina. Sprinkler systemsdesigned and installed according to this standard are expected to prevent flashover within the compartmentof origin where sprinklers are installed in the compartment. A sprinkler system designed and installedaccording to this standard cannot, however, be expected to completely control a fire involving fuel loads
that are significantly higher than average for dwelling units [10 lb/ft2 (49 kg/m2)], configurations of fuelsother than those with typical residential occupancies, or conditions where the interior finish has anunusually high flame spread index (i.e., greater than 225).
To be effective, sprinkler systems installed in accordance with this standard need to open the sprinklersclosest to the fire before the fire exceeds the ability of the sprinkler discharge to extinguish or control thefire. Conditions that allow the fire to grow beyond that point before sprinkler activation or that interfere withthe quality of water distribution can produce conditions beyond the capabilities of the sprinkler systemdescribed in this standard. Unusually high ceilings or ceiling configurations that tend to divert the rising hotgases from sprinkler locations or change the sprinkler discharge pattern from its standard pattern canproduce fire conditions that cannot be extinguished or controlled by the systems described in this standard.
NFPA 13R references NFPA 13 in many aspects (i.e., hanging and bracing, design densities and spacingoutside of dwelling unit, painting and finish of sprinklers, welding, and so on). If this standard does notspecifically address a situation, NFPA 13 is a good resource that can be utilized by the installer and theauthority having jurisdiction for a solution. It is not the intent of this standard to require compliance withNFPA 13 when NFPA 13R is silent on a subject. Only AHJ approval should be required.
Figure A.1.1(a) Bedroom.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
57 of 71 5/16/17, 1:20 PM
124
Figure A.1.1(b) Manufactured Home Bedroom.
Figure A.1.1(c) Living Room.
Statement of Problem and Substantiation for Public Comment
Further clarifies that NFPA 13 and NFPA 13R systems can be located in the same building if properly separated.
Related Item
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
58 of 71 5/16/17, 1:20 PM
125
Public Input No. 37
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 09:26:39 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
59 of 71 5/16/17, 1:20 PM
126
Public Comment No. 6-NFPA 13R-2017 [ Section No. A.3.3.10 ]
A.3.3.10 Residential Occupancies.
Buildings that contain multiple occupancies, either separated or nonseparated; accessory occupancies; orincidental uses are often subject to special rules that could restrict the use of NFPA 13R. Refer to theadopted building code to determine whether such restrictions are applicable. NFPA 13R is appropriate foruse in a residential occupancy. In the list of building types included in this definition, there are situationswhere there will be mixed occupancies and NFPA 13R might not be the appropriate sprinkler system forthe non-residential occupancies.
Statement of Problem and Substantiation for Public Comment
Adding additional explanatory language that mirrors the committee statement from the first draft.
Related Item
Public Input No. 19-NFPA 13R-2016 [Section No. 3.3.9]
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 13:44:21 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
60 of 71 5/16/17, 1:20 PM
127
Public Comment No. 39-NFPA 13R-2017 [ Section No. A.6.2.3.3.3 ]
A.6.2.3.3.3
See Figure A.6.2.3.3.3(a) and Figure A.6.2.3.3.3(b).
Figure A.6.2.3.3.3(a) Clearance Around Recessed Fireplace.
[see two new drawings attached]
Figure A.6.2.3.3.3(b) Clearance Around Open Fireplace.
[see two new derawings attached]
Additional Proposed Changes
File Name Description Approved
FRONT_Fire_Place_ORDINARY.png Improved drawing to illustrate concept accepted in FR
FRONT_Fire_Place_INTERMEDIATE.png Improved drawing to illustrate concept accepted in FR
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
61 of 71 5/16/17, 1:20 PM
128
OPEN_Fire_Place_ORDINARY.png Improved drawing to illustrate concept accepted in FR
OPEN_Fire_Place_INTERMEDIATE.png Improved drawing to illustrate concept accepted in FR
Statement of Problem and Substantiation for Public Comment
Improved drawings have been submitted to illustrate the concept accepted in the First Revision. This should be correlated across NFPA 13 and NFPA 13D.
Related Item
PI-91
Submitter Information Verification
Submitter Full Name: Robert Upson
Organization: National Fire Sprinkler Association
Affilliation: NFSA Engineering and Standards Committee
Street Address:
City:
State:
Zip:
Submittal Date: Mon May 08 14:12:19 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
62 of 71 5/16/17, 1:20 PM
129
Public Comment No. 30-NFPA 13R-2017 [ Section No. A.6.6.5 ]
A.6.6.5
An example of an open or exterior corridor, stair, or breezeway is one that is exposed to the outsideatmosphere (temperature). Another example is an exterior wraparound corridor that is typical in a two- tothree-story motel.
Note that although NFPA 13R does not require sprinklers in corridors that are open and attached, theadopted building code might require sprinkler protection in certain open-ended corridors.
The 2015 IBC has added section 903.3.1.2.2, which requires sprinklers in open-ended corridors andassociated stairways that are not separated. This requirement has been included in 1027.6, but the ICC feltit needed to flag the requirement in NFPA 13R. As this committee did with the sprinklers on porches inbuildings of Type 5 construction, it should align with what is found in the IBC.
Statement of Problem and Substantiation for Public Comment
This appears to have been substantiation text and not annex material.
Related Item
FR15
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Fri May 05 10:29:41 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
63 of 71 5/16/17, 1:20 PM
130
Public Comment No. 59-NFPA 13R-2017 [ Section No. A.6.6.6 ]
A.6.6.6
Concealed spaces are permitted to have small openings such as grilles for return air when the space isbeing used as a plenum. Such small openings do not disqualify the space from being considered as aconcealed space, and sprinklers are still permitted to be omitted. (See Section 7.5 for 4 for additionalinformation on attic sprinklers.)
Statement of Problem and Substantiation for Public Comment
Editorial to match FR approved by the committee and the original submittal
Related Item
pi 104
Submitter Information Verification
Submitter Full Name: Jeffrey Shapiro
Organization: International Code Consultants
Affilliation: Self
Street Address:
City:
State:
Zip:
Submittal Date: Wed May 10 23:37:22 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
64 of 71 5/16/17, 1:20 PM
131
Public Comment No. 9-NFPA 13R-2017 [ Section No. A.7.4.3 ]
A.7.4.3
NFPA 13R does not require installation of sprinklers in attics that are not intended for occupancy orstorage. However storage. Model building codes do not allow habitation in attics. The presence of an atticaccess or scuttle hole does not determine that the attic is intended for storage. However , model buildingcodes sometimes require protection of attics in tall, combustible-framed residential occupancies that areotherwise allowed to follow NFPA 13R. Such protection is permitted to be provided by sprinklers or othermeans allowed by the model building code or NFPA 13, as specified for protection of combustibleconcealed spaces. Common methods of protection in lieu of sprinklers include filling the space withnoncombustible insulation, using fire-retardant-treated wood, or using noncombustible materials. Eventhough sprinklers are not mandatory for attic protection under NFPA 13R, NFPA 13R offers appropriatedesign requirements for cases where sprinklers are provided and sets design benchmarks that parallelwhat is permitted for garages.
Statement of Problem and Substantiation for Public Comment
Clarification is needed that the presence of an attic access does not mean the attic will be used for occupancy or storage.
Related Item
First Revision No. 41-NFPA 13R-2016 [New Section after 7.4]
Submitter Information Verification
Submitter Full Name: Peter Schwab
Organization: Wayne Automatic Fire Sprinkler
Street Address:
City:
State:
Zip:
Submittal Date: Thu Mar 02 14:41:55 EST 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
65 of 71 5/16/17, 1:20 PM
132
Public Comment No. 23-NFPA 13R-2017 [ Section No. A.9.3 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
66 of 71 5/16/17, 1:20 PM
133
A.9.3 .1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
67 of 71 5/16/17, 1:20 PM
134
Table A.9.3.1 (a) and Table A.9.3.1 (b) can be reresent one conservative method that can be used todetermine a domestic design demand. Using The method is conservative because the tables date back toa time before low low fixtures were in common use. Starting with Table A.9.3.1 (a), the total number ofwater supply fixture units downstream of any point in the piping serving both sprinkler and domestic needsis determined. Using Then, using Table A.9.3(b), the appropriate total flow allowance is determined andadded to the sprinkler demand at the total pressure required for the sprinkler system at that point. If lowflow fixtures are used, the Authority having jurisdiction is permitted to approve other methods of detemininga reasonable domestic demand to add to the sprinkler demand.
Table A.9.3(a) Fixture Load Values
Facility Type Unit
Private Facilities (those within individual dwelling units)
Bathroom group with flush tank (including lavatory, water closet, and bathtub with shower) 6
Bathroom group with flush valve 8
Bathtub 2
Dishwasher 1
Kitchen sink 2
Laundry trays 3
Lavatory 1
Shower stall 2
Washing machine 2
Water closet with flush valve 6
Water closet with flush tank 3
Public Facilities
Bathtub 4
Drinking fountain 0
Kitchen sink 4
Lavatory 2
Service sink 3
Shower head 4
Urinal with 1 in. (25 mm) flush valve 10
Urinal with 3 ⁄ 4 in. (20 mm) flush valve 5
Urinal with flush tank 3
Washing machine [8 lb (3.63 kg)] 3
Washing machine [16 lb (7.26 kg)] 4
Water closet with flush valve 10
Water closet with flush tank 5
Table A.9.3(b) Total Estimated Domestic Demand
Total Fixture
Load Units
[from Table A.9.6(a)]
Total Demand
For Systems
with Predominately
Flush Tanks
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
68 of 71 5/16/17, 1:20 PM
135
For Systems
with Predominately
Flush Valves
gpm L/min
gpm L/min
1 3 11.5
— —
2 5 19
— —
5 10 38
15 57
10 15 57
25 95
20 20 76
35 130
35 25 95
45 170
50 30 115
50 190
70 35 130
60 225
100 45 170
70 265
150 55 210
80 305
200 65 245
90 340
250 75 285
100 380
350 100 380
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
69 of 71 5/16/17, 1:20 PM
136
125 475
500 125 475
150 570
750 175 660
175 660
1000 200 755
200 755
1500 275 1040
275 1040
2000 325 1230
325 1230
3500 500 1900
500 1900
Statement of Problem and Substantiation for Public Comment
This is connected to PC20. The fixture load tables should be in the annex, not the body of the standard. This proposal provides a little more information for the user.
Related Public Comments for This Document
Related Comment Relationship
Public Comment No. 20-NFPA 13R-2017 [Section No. 9.3.2 [Excluding any Sub-Sections]]
Related Item
FR52
Submitter Information Verification
Submitter Full Name: Kenneth Isman
Organization: University of Maryland
Street Address:
City:
State:
Zip:
Submittal Date: Wed Apr 26 16:36:44 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
70 of 71 5/16/17, 1:20 PM
137
Public Comment No. 46-NFPA 13R-2017 [ New Section after B.3 ]
Annex C Press-Connect Fittings used in Fire Sprinkler Applications
(See separate document for proposed text of Annex)
Additional Proposed Changes
File Name Description Approved
NFPA_13R_Public_Comment_Annex_Information_Press_Connect_Viega_Submitted.docx
NFPA 13R Public Comment Proposed Annex C
Statement of Problem and Substantiation for Public Comment
Currently there is no definition for Press-Connect fittings in NFPA 13R. The term Press-Connect Fitting is used in both the IAPMO and ICC codes. The wide use of Mechanical type fittings has created the need to identify fittings such as Press-Connect and provide definitions to prevent confusion between mechanical fitting types and to help identify the correct standards these fittings are typically listed to. The proposed annex provides reference information which will be helpful in distinguishing between Mechanical type fittings and Press-Connect Fittings.
In the first draft review meetings our public comments 60, 71, 72, 98, and 99 were resolved because all press-connect systems require listings and thus are not to be listed in the existing tables for standards whose products do not require separate listings.
It was suggested by a few committee members that information on Press-Connect fittings be added instead to the Annex of this code for reference and informational purposes.
Related Item
PI 60
PI 71
PI 72
PI 98
PI 99
Submitter Information Verification
Submitter Full Name: Gary Morgan
Organization: Viega LLC
Street Address:
City:
State:
Zip:
Submittal Date: Tue May 09 20:47:10 EDT 2017
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
71 of 71 5/16/17, 1:20 PM
138
Proposed New Annex
Annex C Press‐Connect Fittings used in Fire Sprinkler Applications This annex is not a part of the requirements of this NFPA document but is included for informational purposes only.
This annex is intended to provide basic information and description of press‐connect fittings for metallic
piping systems used in fire sprinkler systems. All press‐connect fitting systems used in fire sprinkler
applications require listing(s) specific to the application. Because press‐connect fittings are not
specifically included in the mandatory sections of this standard the following information will discuss the
press‐connect fitting connection in more detail.
C.1 Definition of Press‐Connect Fittings
The press‐connect fitting is a permanent mechanical connection for joining copper tubing or steel pipe
typically utilizing an elastomeric seal or an elastomeric seal in conjunction with a corrosion resistant
axial biting or grip ring or rings. Fitting connections are generally pressed with an electro‐hydraulic
pressing tool utilizing pressing jaws or pressing rings approved by the fitting manufacturer for use in
accordance with their listing.
C.2 Applications of Press Connect Fittings
Press‐connect fittings are commonly used today in both dry (pre‐action) systems as well as wet systems.
Press‐connect system designs must not exceed the maximum pressure and ambient exposure
temperature ratings for fittings and piping. The maximum continuous exposure temperature is limited
by the elastomeric sealing element material. A manufacturers’ listing will specify the maximum
continuous exposure temperatures for their press‐connect system.
C.3 Standards for Press‐Connect Fittings
Press‐connect systems are generally manufactured in accordance with ASME B16.51, Copper and
Copper Alloy Press‐Connect Pressure Fittings; or IAPMO PS‐117, Press and Nail Connections; or ASTM
F3226/F326M, Standard Specification for Metallic Press‐Connect Fittings for Piping and Tubing Systems
depending on the type of piping. These standards specify the material requirements and the
performance criteria such as, but not limited to, Hydrostatic Pressure Test, Static Torque Test, Bending
Test, Vacuum Test, Pressure Cycle Test, Vibration Test, Thermocycling Test, and Dynamic Torque Test.
C.4 General Assembly Procedure for Press‐Connect Fittings
Press‐connect fittings all have an elastomeric seal that forms the seal‐tight joint. The pipe or tubing is
cut square, deburred and chamfered and, or reamed to restore the full inside diameter. The ends of the
pipe or tube that will be inserted into the fittings should be carefully inspected for any noticeable
damage or deep scratches and also checked and cleaned if any foreign matter such as dirt or tape
residue is present. The pipe or tubing is then fully inserted into the fitting until the internal shoulder
stop is reached and the tubing is then marked with a permanent marker where the tubing meets the
outer shoulder of the fitting in order to establish the full insertion depth. With the tubing fully inserted
139
and the insertion depth mark double checked, the joint can be pressed using the tool recommended by
the manufacturer. The insertion depth mark should be checked once again after pressing to insure the
joint did not slip apart during the pressing operation. Pressure testing of completed sections should
then be conducted per the manufacturer’s instructions and this code to insure all joints are seal tight.
140