FDQ-B7 Concealed Ceiling Unit technical data Split Sky Air air conditioning systems
Transcript
Page 1: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

FDQ-B7

Concealed Ceiling Unit

technical data

SplitSky Air

air co

nd

ition

ing

system

s

Page 2: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

Split - Sky Air

EE

DE0

5-1

/3 •

05/2

005

Prepar

ed in

Belg

ium

by

Goeki

nt

Gra

phic

s

Zandvoordestraat 300

B - 8400 Ostend Belgium

Specifications are subject to change without prior notice.

ISO14001 assures an effective environmental management system in order to help protecthuman health and the environment from the potentialimpact of our activities, products and services and toassist in maintaining and improving the quality ofthe environment

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

www.daikineurope.com

Page 3: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

TABLE OF CONTENTSFDQ125-250B7

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Nominal capacity, capacity steps and nominal input

Technical specifications

3 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6 Sound level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Sound pressure spectrum

Sound power spectrum

7 Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Standard accessories

Optional accessories

For capacity tables, please refer to part II: outdoor units

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

1• Split - Sky Air • Indoor Units

Page 4: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

1 Features

1 3 x 3 6 6Optional Optional 2 steps:

FDQ250,3 steps:

FDQ125,200

+ Leaves maximum floor and wall space for furniture, decorationand fittings

+ Blends unobtrusively with any interior decor: only the suctionand discharge grilles are visible

+ Extremely quiet in operation.+ Easy to install+ High external static pressure facilitates unit use with flexible

ducts of varying lengths+ Daikin remote controls give you easy control at your fingertips.

+ The wired remote control provides you with a schedule timer,enabling to program the air conditioning daily or weekly.

+ The optional remote ON/OFF enables you to start/stop the airconditioning from a mobile phone via a telephone remotecontrol (field supply).

+ The optional forced OFF enables you to switch off the unitautomatically. E.g. when a window is opened, the unit switchesoff.

+ The ’home leave’ operation button prevents large temperaturedifferences by continuously operating at a minimum (heatingmode) or maximum (cooling mode) preset level while you’reout or sleeping. It also allows the indoor temperature to returnquickly to your favourite comfort level.

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

11

2 • Split - Sky Air • Indoor Units

Page 5: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

2 Specifications

NOMINAL CAPACITY and NOMINAL INPUTFDQ125B7V3B FDQ200B7V3B FDQ250B7V3B

RZQ125B8V3B/B7W1B RZQ200B7W1B RZQ250B7W1BNOMINAL CAPACITY Cooling kW 12.5 20 25

Heating kW 14.0 23 27NOMINAL INPUT Cooling kW 4.15 6.43 8.31

Heating kW 3.69 7.54 8.85EER 3.01 3.11 3.01COP 3.79 3.05 3.05ENERGY LABEL Cooling B B B

Heating A D DANNUAL ENERGYCONSUMPTION

Cooling kWh 2,075 3,215 4,155

TECHNICAL SPECIFICATIONSFDQ125B7V3B FDQ200B7V3B FDQ250B7V3B

DIMENSIONS Unit H mm 350 450 450W mm 1,400 1,400 1,400D mm 662 900 900

WEIGHT Machine weight kg 59.0 93.0 93.0REQUIRED CEILING VOID mm 350 450 450HEAT EXCHANGER Specifications Length mm 1,150 1,255 1,255

No. of rows 3 3 3Fin pitch mm 1.75 2.00 2.00N° of passes 10 13 13Face area m2 0.338 0.634 0.634N° of stages 14 24 24

Tube type Hi-XSS (7) Hi-XSS (8) Hi-XSS (8)Fin Type Rhombus Non-symmetric fin

Treatment HydrophilicFAN Type Sirocco fan

Quantity 2 2 2Air flow rate Cooling medium m3/min 43.0 69.0 89.0

Heating medium m3/min 43.0 69.0 89.0External staticpressure (Max.)

High Pa 150 250 250Standard Pa 150 250 250Low Pa 150 250 250

Motor Quantity 1 1 1Model DPA216-178NB DPC241-241NBNumber of steps 3 3 2Output (high) W 500 650 1000Drive Direct drive

SOUND LEVEL Cooling Sound power medium dBA 75.0 81.0 82.0Sound pressure High dBA 44.0 45.0 47.0

Heating Sound pressure Low dBA 44.0 45.0 47.0REFRIGERANT Type R-410APIPING CONNECTIONS Liquid Type Flare connection

φ (O.D.) mm 9.52 9.52 12.7Gas Type Flare connection

φ (O.D.) mm 15.9 22.2 22.2Drain φ (O.D.) mm 25 25Heat insulation Both liquid and gas pipes

AIR FILTER As option (see notes) Resin net with mold resistanceAIR DIRECTION CONTROL Up and downwardsTEMPERATURE CONTROL Microprocessor thermostat for cooling and heatingSAFETY DEVICES Fan motor thermal fuseSTANDARD ACCESSORIES Item Installation and operation manual

Quantity 1 1 1

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

12

3• Split - Sky Air • Indoor Units

Page 6: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

ELECTRICAL SPECIFICATIONSFDQ125B7V3B FDQ200B7V3B FDQ250B7V3B

POWER SUPPLY Name V3 V3 V3Phase 1∼ 1∼ 1∼Frequency Hz 50 50 50Voltage V 230 230 230

VOLTAGE RANGE Minimum -10% -10% -10%Maximum +10% +10% +10%

Power supply intake Both indoor and outdoor unit

NOTES1 Nominal cooling capacities are based on: indoor temperature: 27°CDB/19°CWB * outdoor temperature: 35°CDB * equivalent refrigerant piping

length: 7.5m * level difference: 0m

2 Nominal heating capacities are based on: indoor temperature: 20°CDB * outdoor temperature: 7°CDB/6°CWB * refrigerant piping length: 7.5m *level difference 0m.

3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

4 Sound values are measured in an anechoic room.

5 The sound pressure level is measured via a microphone at 1m distance of the unit.

6 Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound leveldrawings of this chapter.

7 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.

8 For more details, refer to wiring diagram, name plate and installation manual.

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

2 Specifications

12

4 • Split - Sky Air • Indoor Units

Page 7: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

3 Dimensional drawings

FDQ125B7

view A

view A

Notes:

P : Service space

1 Power supply intake2 Drain connection J25 O.D.3 Liquid pipe connection single union joint 3/8’’4 Filter

3TW26054-1

3TW22814-1C

FDQ200-250B

view A

view A

1 Power supply intake2 Drain connection J25 O.D.3 Gas pipe connection FDQ200/250 : 7/8″ O.D. or 22.2 mm O.D.4 Liquid pipe connection FDQ200 : Single union joint 3/8″ or 9.52mm

FDQ250 : Single union joint 1/2″ or 12.7mm5 Filter

Model A BFDQ200 830 285FDQ250 890 255

Service space

Extra service space for optional drain pump

Notes:

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

13

5• Split - Sky Air • Indoor Units

Page 8: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

4 Piping diagrams

3TW26055-1AO Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Heat exchanger

Refrigerant flow

CoolingHeating

Liquid pipe connection port

FDQ125-250B

Gas pipe connection port

Refrigerant pipe connection port diameters

Model Gas LiquidFDQ125 J15.90

J9.52FDQ200

J 22.2FDQ250 J 12.7

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

14

6 • Split - Sky Air • Indoor Units

Page 9: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

5 Wiring diagrams

2TW26036-1B

FDQ125-250

A1P Printed circuit boardA3P Printed circuit boardT1R Transformer(230V / 218V)C1R Capacitor (fan)F1T Thermal fuse (M1F embedded)HAP Light emitting diode (service monitor

green)K1F Magnetic contactor (M1F)M1F Motor (Fan)

R1T Thermistor (air)R2T Thermistor (coil)RyF1 Magnetic relay (fan)SS1 Selector switch (emergency)X1M Terminal stripRC Signal receiver circuitTC Signal transmission circuitF5U Power setting faultQ1DI Earth leakage breaker

Wired remote controlBS1 On/Off buttonBS2 Timer mode start/stop buttonBS3,BS8 Programming time buttonBS4 Temperature setting button upBS9 Temperature setting button downBS6 Operation mode selector buttonBS7 Timer on/off buttonBS12 Inspection/test operation button

Adapter for wiringRyC,RyF Magnetic relayConnector for optional partsX60AX61A

Connector (interface adaptor for SKY AIR /US series)

X33A Connector (adapter for wiring)X35A Connector (group control adapter)X40A Connector (remote ON/OFF, forced off, only

SKY-AIR Pàseries)

IndoorOutdoorWired remotecontrol

Terminals foroperation indicator

Switch box

Details of wired remote control(optional accessory)

Adapter for wiring

Fano

perat

ion

com

pres

sor

opera

tion

Notes

1. When using the central remote control, see manual for connectionto the unit.

2. Be sure that the power supply is switched off before opening theswitch box.* L-tap is not available for 250 class.

g Field wiring D Terminala : Connectorc : Wire clampb : Protective earth (screw)ColoursBLK: Black / BRN: brown / WHT: WhiteRED: Red / BLU: Blue / GRY: GreyORG: Orange / YLW: Yellow

BS14 Filter sign reset buttonH1P Light emitting diode (service monitor

red)LCD Liquid crystal displaySS1 Selector switch (main/sub)

Remote ON/OFF,forced OFF

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

15

7• Split - Sky Air • Indoor Units

Page 10: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

6 Sound level6-1 Sound pressure spectrum

Soun

dpr

essu

rele

vel(

dB)

Soun

dpr

essu

rele

vel(

dB)

Octave band center frequency (Hz) Octave band center frequency (Hz)

Octave band center frequency (Hz)

FDQ125B7 FDQ200B7

3TW22817-13TW22807-1

3TW22827-1

Legend

High speed

Low speed

Soun

dpr

essu

rele

vel(

dB)

FDQ250B7

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition (at 62 Pa ESP, 90m3/min)3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20µPa5 the indicated sound pressure is the casing radiated sound pressure.

Suction unit Unit Discharge unit

Microphone

Metalducts insulated inside

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

16

6-1

8 • Split - Sky Air • Indoor Units

Page 11: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

6 Sound level6-2 Sound power spectrum

FDQ125B7

FDQ250B7

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Oct

ave

band

soun

dpr

essu

rele

vel

Oct

ave

band

soun

dpr

essu

rele

vel

Oct

ave

band

soun

dpr

essu

rele

vel

FDQ200B7

Octave band center frequency (Hz)

Low speed

3TW26057-1 3TW26957-1

3TW26967-1

High speed

Legend

NOTES

1 Data is valid at free field condition2 Data is valid at nominal operation condition (at 62

Pa ESP, 90m3/min)3 dB(A) = A-weighted sound pressure level (A-scale

according to IEC)4 Reference acoustic pressure 0dB = 20µPa5 the indicated sound pressure is the casing

radiated sound pressure.

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

16

6-2

9• Split - Sky Air • Indoor Units

Page 12: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

7 Fan characteristics

3TW22808-1

FDQ125B7

highmedium

low

FDQ200B7

FDQ250B7

3TW22818-1

3TW22828-1

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

17

10 • Split - Sky Air • Indoor Units

Page 13: technical data - daikintech.co.ukFDA)/2005/FDQ-B...Split Sky Air air conditioning systems. Split - Sky Air ... Daikin Europe N.V. is approved by LRQA for its Quality ... K1F Magnetic

8 Accessories8-1 Standard accessories

Option Option name FDQ125B FDQ200B FDQ250B

Wiring adaptor for electrical appendices KRP4A51 X X X

Adaptor for wiring (interlock for fresh air intake) KRP1B54 X X X

Interface adaptor for Sky Air series DTA112B51 X X X

Central remote control DCS302B51 X X X

Unified ON/OFF control DCS301B51 X X X

Schedule timer DST301B51 X X X

Option PCB for external electrical heater, humidifier and/or hour meter EKRP1B2 X X X

Drain pump EKDU125A1 X X X

Wired remote control BRC1D527 X X X

Remote ’’On/Off’’ and ’’Forced Off’’ kit EKRORO X X X

3TW22809-1D

Note: Connection with hour meter is possible by using the EKRP1B2. (Onlyavailable for FDQ125,200,250B-types).

• Concealed Ceiling, Inverter Controlled Unit • R-410A • FDQ125-250B7V3B

18

8-1

11• Split - Sky Air • Indoor Units