ION8650
PowerLogic power-monitoring units
Technical data sheet
2011
2
ION8650 Functions and characteristics
Advanced revenue meteringP
B10
7500
PowerLogic ION8650 socket meter
Used to monitor electric energy provider networks, service entrances and substations, PowerLogic ION8650 meters are ideal for independent power producers and cogeneration applications that need to accurately measure energy bi-directionally in both generation and stand-by modes. These meters give utilities the tools to manage complex energy supply contracts that include commitments to power quality. Integrate them with our ION Enterprise™ operations software or other energy management and SCADA systems through multiple communication channels and protocols, including Itron MV-90.
ApplicationsRevenue meteringCo-generation and IPP monitoringCompliance monitoringPower quality analysisDemand and power factor controlLoad curtailmentEquipment monitoring and controlEnergy pulsing and totalisationInstrument transformer correction
Main characteristicsANSI Class 0.2 and IEC 62053-22/23 Class 0,2S meteringFor interconnection points on medium, high, and ultra-high voltage networks; twice as accurate as current IEC and ANSI Class 0.2 standards over all conditions and including single wide range current measurement.Power quality compliance monitoringMonitor compliance with international quality-of-supply standards (IEC 61000-4-30 Class A/S, EN50160, IEC 61000-4-7, IEC 61000-4-15, IEEE 1159, IEEE 519).Digital fault recordingSimultaneous capture of voltage and current channels for sub-cycle disturbance transients.Complete communicationsMulti-port, multi-protocol ports including serial, infrared, modem and ethernet. Simultaneously supports multiple industry standard protocols including: Itron MV-90, Modbus, Modbus Master, DNP 3.0 and IEC 61850.Multiple tariffs and time-of-useApply tariffs, seasonal rate schedules to measure energy and demand values for time periods with specific billing requirements.Multiple setpoints for alarm and control functionsA total of 65 setpoints are configurable for 1-second or ½ - cycle operation.Power quality summaryConsolidation of all the power quality characteristics into a single trendable index.Integrate with softwareEasily integrate with ION Enterprise operations software or other energy management systems; MV90, DNP, Modbus, IEC 61850.Transformer/line loss compensationDetermine technical system losses in real time.Instrument transformer correctionSave money and improve accuracy by correcting for less accurate transformers.Alarm notification via emailHigh-priority alarms, data logs sent directly to the user’s PC. Instant notification of power quality events by email.
Part numbersION8650 meters
ION8650A M8650AION8650B M8650BION8650C M8650C
See page 6 for complete part number descriptions.
OptionsSee page 7.
3
ION8650 Functions and characteristics (cont.)
Advanced revenue meteringPE
8630
2-95
PowerLogic ION8650 socket meter.
1 Terminals2 Optical port3 Main display status bar4 Watt LED5 Navigation, ALT/Enter buttons6 VAR LED7 Nameplate label8 Demand reset switch
Selection guide ION8650 A
ION8650 B
ION8650 C
GeneralUse on LV and HV systems b b b
Current accuracy 0.1 % reading 0.1 % reading 0.1 % reading
Voltage accuracy 0.1 % reading 0.1 % reading 0.1 % reading
Power accuracy 0.1 % reading 0.1 % reading 0.1 % reading
Samples/cycle 1024 1024 1024Instantaneous values
Current, voltage, frequency b b b
Active, reactive, apparent power Total & per phase b b b
Power factor Total & per phase b b b
Current measurement range (autoranging) 0.01 - 20A 0.01 - 20A 0.01 - 20A Energy values
Active, reactive, apparent energy b b b
Settable accumulation modes b b b
Demand valuesCurrent Present & max. values b b b
Active, reactive, apparent power Present & max. values b b b
Predicted active, reactive, apparent power b b b
Synchronisation of the measurement window b b b
Demand modes: Block (sliding), thermal (exponential) b b b
Power quality measurements Harmonic distortion Current & voltage b b b
Individual harmonics Via front panel 63 63 31Waveform and transient capture b - -Harmonics: magnitude, phase, and interharmonics 50 40 -Detection of voltage sags and swells b b b
IEC 61000-4-30 class A /S A S -IEC 61000-4-15 (Flicker) b b -High speed data recording (down to 10 ms) b b -EN50160 compliance reporting b b -Programmable (logic and math functions) b b b
Data recording
PE
8600
2
Disturbance waveform capture and power quality report
Onboard Memory (in Mbytes) 128 64 32Revenue logs b b b
Event logs b b b
Historical logs b b b
Harmonics logs b b b
Sag/swell logs b b b
Transient logs b - -Time stamping to 1 ms b b b
GPS synchronisation (IRIG-B standard) b b b
Display and I/OFront panel display b b b
Wiring self-test (requires PowerLogic ION Setup) b b b
Pulse output (front panel LED) 2 2 2Digital or analogue inputs(1)(max) 11 11 11Digital or analogue outputs(1)(max, including pulse output) 16 16 16Direct connection voltage 277V(2) 277V(2) 277V(2)
CommunicationInfrared port 1 1 1RS 485 / RS 232 port 1 1 1(3)
RS 485 port 1 1 1(3)
Ethernet port (Modbus/TCP/IP protocol) with gateway 1 1 1(3)
Internal modem with gateway (ModemGate) 1 1 1(3)
HTML web page server (WebMeter) b b b
IRIG-B port (unmodulated IRIG B00x time format) 1 1 1Modbus TCP Master / Slave (Ethernet port) b / b b / b - / bModbus RTU Master / Slave (Serial ports) b / b b / b - / bDNP 3.0 through serial, modem, and I/R ports b b b
(1) With optional I/O Expander.(2) For 9S, and 36S only. For 35S system up to 480V line-to-line.(3) Infrared port plus two other communications ports maximum
4
ION8650Functions and characteristics (cont.)
Advanced revenue meteringP
E86
041
PowerLogic ION8650 front panel harmonic display.
Electrical characteristics Type of measurement True rms 1024 samples per cycleMeasurement accuracy
Current and voltage 0.1 % ReadingPower 0.1%Frequency ±0.001 HzPower factor 0.1% Energy 0.1%, twice as accurate as ANSI Class 0.2 and
IEC 62053-22/23 (0,2S)Data update rate 0.5 cycle or 1 second (depending on value)Input-voltage characteristics (1)
Nominal voltage 57V to 277VLL rms autoranging (9S) 100V to 480VLL rms autoranging (35S)
Maximum voltage 347 VLN rms, 600 VLL rms (9S)600 VLL rms (35S)
Impedance 5 MW /phase (phase-Uref/Ground)Inputs V1, V2, V3, VREF
Input-current characteristics
Rated nominal/current class
1A, 2 A, 5 A and/or 10 A (Class 1/2/10/20)
Accuracy range 0.01 - 20 A autoranging (standard range)Measurement range 0 001 - 24 A
Permissible overload 500A rms for 1 second, non-recurring (standard)
Burden per phase Socket - 0.05VA at 5A (0.002 Ω max)Switchboard - 0.05VA at 1A (0.05 Ω max)
Power supply Standard power supply, 120-277 VAC
120-277 VLN RMS (-15%/+20%) 47-63 Hz or120-480 VLL RMS (-15%/+20%) 47-63 Hz (35S)
Auxiliary power cable assembly, 65-120 VAC
AC: 65-120 (+/- 15%) VLN RMS, 47-63 HzDC: 80-160 (+/- 20%) VDC
Auxiliary power cable assembly, 160-277 VAC
AC: 160-277 (+/- 20%) VLN RMS, 47-63 HzDC: 200-300 (+/- 20%) VDC
Ride-through time, 120-277 VAC(Standard power supply)
Min 100 ms (6 cycles at 60 Hz at 96 VAC),200 ms (12 cycles at 60 Hz at 120 VAC),800 ms (48 cycles at 60 Hz at 240 VAC)
Input/outputs Digital outputs (Form C) 4 Solid state relays (130 V AC/ 200 V DC) 50 mA AC/DC
Digital outputs (Form A) 4 Solid state relays (via optional I/O Expander)Digital inputs 4 Solid state inputs (via optional I/O Expander)
PE
8604
2
ION8650 front panel phasor display and table.
Mechanical characteristicsWeight 7.0 kg IP degree of protection
Socket Front IP65, back IP51Switchboard Front IP50, back IP30
Dimensions Socket 178 x 237 mmSwitchboard 285 x 228 x 163 mm
Environmental conditionsOperating temperature -40°C to +85°CDisplay operating range -20°C to +60°CStorage temperature -40°C to +85°CHumidity rating 5 to 95 % RH non-condensingPollution degree 2Installation category Cat IIIDielectric withstand 2.5kV, 50Hz, 1 minElectromagnetic compatibility
Electrostatic discharge IEC 61000-4-2Immunity to radiated fields IEC 61000-4-3Immunity to fast transients IEC 61000-4-4Immunity to surge IEC 61000-4-5Immunity conducted IEC61000-4-6Damped oscillatory waves immunity IEC61000-4-12Conducted and radiated emissions CISPR 22 (class B)Safety
Europe As per IEC62052-11North America As per ANSI C12.1(1)Specifications are limited by the operating range of the power supply if a non-aux power supply is used.
5
ION8650Functions and characteristics (cont.)
Advanced revenue meteringP
E86
004-
C
Example embedded webserver page (WebMeter) showing realtime values.
CommunicationRS 232 / RS 485 port (COM1) User-selectable RS 232 or RS 485.
300 - 115,200 bauds (RS485 limited to 57,600 bps); protocols: ION, Modbus/RTU/Mastering, DNP 3.0, GPSTRUETIME/DATUM.
Internal modem port (COM2) 300 bps-57,600 bauds (automatic detection supported)ANSI 12.18 Type II optical port (COM3)
Up to 19200 bauds
RS 485 port (COM4) Up to 57,600 bauds, Modbus, direct connection to a PC or modem
Ethernet port 10/100 BaseT, RJ45 connector, protocols: DNP, ION, Modbus/TCP/Mastering, IEC 61850
EtherGate Up to 31 slave devices via serial portsModemGate Up to 31 slave devicesEmbedded web server (WebMeter) 4 standard pages, up to 5 customisable pages
Firmware characteristicsHigh-speed data recording Up to 1/2-cycle interval burst recording, stores detailed
characteristics of disturbances or outages. Trigger recording by a user-defined setpoint, or from external equipment. Can log data only during critical event to conserve memory
Harmonic distortion Up to 63rd harmonic for all voltage and current inputs
Dip/swell detection Analyse severity/potential impact of dips and swells:magnitude and duration data suitable for plotting on
voltage tolerance curvesper phase triggers for waveform recording or control
operations
-
-
Instantaneous High accuracy (1s) and high-speed (1/2 cycle) measurements, including true rms per phase / total for:
voltage and currentactive power (kW) and reactive power (kVAR)apparent power (kVA)power factor and frequencyvoltage and current unbalancephase reversal
------
Load profiling Channel assignments are user configurable:800 channels via 50 data recorders (feature set A), 720 channels via 45 data recorders (feature set B), 64 channels via 4 data recorders (feature set C).
Configure for historical trend recording of energy, demand, voltage, current, power quality, other measured parameter. Recorders can trigger on time interval basis, calendar schedule, alarm/event condition, manually.
---
Waveform captures Simultaneous capture of all voltage and current channelssub-cycle disturbance capture (16 to 1024 samples/
cycle)-
PE
8600
5-C
Alarms Threshold alarms:adjustable pickup and dropout setpoints and time
delays, numerous activation levels possible for a given type of alarm
user-defined priority levelsboolean combination of alarms possible
-
--
Advanced security Up to 16 users with unique access rights. Perform resets, time syncs, or meter configurations based on user priviledges.
Transformer correction Correct for phase / magnitude inaccuracies in current transformers (CTs), potential transformers (PTs)
Memory 32 Mbytes (C), 64 Mbytes (B), 128 Mbytes (A)Firmware update Update via the communication portsDisplay characteristics
Type FSTN transreflective LCDBacklight LEDLanguages English
6
ION8650 Functions and characteristics (cont.)
Advanced revenue metering
Part NumbersItem Code Description
PE
8604
3-C
Example product part number.
1 Model M8650 Schneider Electric advanced tariff meter.2 Feature Set A 128MB Memory Class A power quality analysis, waveforms and
transient capture with 1024 samples/cycle.
B 64MB memory, energy meter Class S EN50160 power quality monitoring.
1 Model.2 Feature set.3 Form factor.4 Current Inputs.5 Voltage inputs.6 Power supply.7 System frequency.8 Communications.9 Input/output options.10 Security.11Special order options.
C 32MB memory, basic tariff/energy metering (4 data recorders, 64 channels).
3 Form Factor (1) 0 Form 9S/29S/36S Base, 57-277 VLN (autoranging) 3-Element, 4-Wire / 2 1/2-Element, 4-Wire
1 Form 35S Base - 120-480 VLL (autoranging) 2-Element, 3-Wire
4 Form 9/29/35/36S FT21 Switchboard (meter + case) with break out panel
7 Form 9/29/35/36S FT21 Switchboard (meter + case) with break out cable
4 Current Inputs C 1, 2 or 5 Amp nominal, 20 Amp full scale (24 Amp fault capture, start at 0.001 A)
5 Voltage Inputs 0 Standard (see Form Factor above)
6 Power Supply E Form 9/29/35/36S, (socket) and Form 9, 36 (FT21 switchboard): 120-277 VAC. Form 35S (socket) and Form 35 (FT21 switchboard): 120-480 VAC. Powered from the meter’s voltage connections, low end measurement range limited to 120 V LL.
H Auxiliary Power Pigtail: 65-120 VAC or 80-160 VDC (power from external source)
J Auxiliary Power Pigtail: 160-277 VAC or 200-300 VDC (power from external source)
7 System Frequency 5 Calibrated for 50 Hz systems.
6 Calibrated for 60 Hz systems.
8 Communications A 0 Infrared optical port, RS 232/RS 485 port, RS 485 port
PowerLogic ION8650 meter with switchboard case C 1 Infrared optical port, Ethernet (10/100 BaseT), RS 232/485 port, RS 485 port (note: in addition to infrared optical port, Feature Set C can use any two ports (configurable)), 56k universal internal modem (RJ11)
PB
1075
07
M 1 Infrared optical port, RS 232/485 port, RS 485 port (note: in addition to infrared optical port, Feature Set C can use any two ports (configurable)), 56k universal internal modem (RJ11)
E 0 Infrared optical port, Ethernet (10/100 BaseT), RS 232/485 port, RS 485 port (note: in addition to infrared optical port, Feature Set C can use any two ports (configurable)).
9 Onboard I/O A None.
B 4 Form C digital outputs, 3 Form A digital inputs.
C 4 Form C digital outputs, 1 Form A digital output, 1 digital input.
10 Security 0 Password protected, no security lock
1 Password protected with security lock enabled (requires removal of outer cover to configure billing parameters)
3 RMICAN (Measurement Canada approved)
4 RMICAN-SEAL (Measurement Canada approved, and factory sealed)**
11 Special Order A None
(1)Specifications are limited by the operating range of the power supply if a non-aux power supply is used.
7
ION8650 Functions and characteristics (cont.)
Advanced revenue metering
Part numbers (cont.)
PE
8604
4
I/O ExpanderDigital/Analog I/O P850E Schneider Electric I/O Expander for ION8600 meters: Inputs and
Outputs for energy pulsing, control, energy counting, status monitoring, and analog interface to SCADA.
Example order code. Use this group of codes when ordering the I/O Expander.
I/O option A External I/O box with 8 digital inputs and 8 digital outputs (4 Form A, 4 Form C)
1 Digital / Analog I/O.2 I/O option.3 Cable option.
B External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (0 to 20mA)
C External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (-1mA to 1mA)
PE
8613
1
D External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (two -1 to 1 mA, and two 0 to 20 mA outputs)
Cable option 0 No cable - cables for the I/O box are no ordered as a separate part number. Refer to part numbers: CBL-8X00IOE5FT, CBL-8X00IOE15FT and CBL-8XX0-BOP-IOBOX under Connector cables, below.
A-base adaptersA-BASE-ADAPTER-9 Form 9S to Form 9A adapterA-BASE-ADAPTER-35 Form 35S to Form 35A adapterOptical communication interface
OPTICAL-PROBE Optical communication interfaceConnector cables
CBL-8X00BRKOUT 5ft Breakout Cable: 24-pin female Molex connector to one DB9 female connector for RS 232, and 2 sets of twisted pair wires for two RS 485 port connections
CBL-8X00IOE5FT 5ft extension cable, mates with 24-pin male Molex connector from the meter to the 24-pin female Molex connector on the I/O Expander box (not for use with breakout panel E8, F8 & G8 form factors)
CBL-8X00IOE15FT 15ft extension cable, mates with 24-pin male Molex connector from the meter to the 24-pin female Molex connector on the I/O Expander box (not for use with breakout panel E8, F8 & G8 form factors)
CBL-8XX0-BOP-IOBOX 6ft connector cable, 24-pin male to 14-pin male Molex connector for connecting an ION8650 meter with breakout panel to an I/O Expander Box
A 2P 8 5 0 E A 2P 8 5 0 E
8
ION8650 Installation and connections
ION8650 socket dimensions
PE
8630
3
PE
8630
4
ION8650 switchboard dimensions
PE
8630
5
PE
8630
6
I/O Expander dimensions
PE
8630
7
PE
8630
8
Advanced revenue metering
9
ION8650 Installation and connections (cont.)
ION8650 suggested switchboard mounting dimensions
PE
8605
2
ION8650 switchboard mounting
PE
8630
9
Advanced revenue metering
10
ION8650 Installation and connection (cont.)
4-Wire 3 element direct connection
PE
8631
0
Connection representation only. Other types of connection are possible. See product installation guide for complete wiring and communication connection details.
4-Wire 3 element, 3 PT connection
PE
8631
1
Connection representation only. Other types of connection are possible. See product installation guide for complete wiring and communication connection details.
Protection(3A)
Protection(2A)
Shortingblock
N L1 L2 L3
L/+ N/-
For auxiliary powered units only
I4 optionalfor ION8600A,ION8600B only}
I11
I12
I21
I22
I32
I42
I31
I41
V1
V2
V3
Connect G terminalto ground for AC power source
Vref
Protection(3A)
Protection(2A)
Shortingblock
N L1 L2 L3
L/+ N/-
For auxiliary powered units only
I4 optionalfor ION8600A,ION8600B only}
I11
I12
I21
I22
I32
I42
I31
I41
V1
V2
V3
Connect G terminalto ground for AC power source
Vref
Connect G terminalto ground for AC power sourceProtection
(3A)
Shortingblock
N L1 L2 L3
L/+ N/-
}
I11
I12
I21
I22
I32
I42
I31
I41
V1
Vref
Protection(2A) V2
V3
I4 optionalfor ION8600A,ION8600B only
For auxiliary powered units only
Connect G terminalto ground for AC power sourceProtection
(3A)
Shortingblock
N L1 L2 L3
L/+ N/-
}
I11
I12
I21
I22
I32
I42
I31
I41
V1
Vref
Protection(2A) V2
V3
I4 optionalfor ION8600A,ION8600B only
For auxiliary powered units only
Advanced revenue metering
ART 8
2125
4 / ©
201
1 - S
chne
ider
Elec
tric -
All
right
s res
erve
d
Schneider Electric35 Rue Joseph Monier, CS 3032392506 Rueil Malmaison CedexTel : +33 (0)1 41 29 70 00http://www.schneider-electric.com
PLSED310027EN
As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication. PowerLogic, ION, ION Enterprise, MeterM@il and Modbus are either trademarks or registered trademarks of Schneider Electric. Printed on recycled paper Publishing : Schneider Electric Production : Schneider Electric PMCPrinting : Imprimerie du Pont de Claix - made in France June-2011