July 2016
Project: Customer: Engineer: Pump Manufacturer:
Model GPA + GPUFull Service Full Voltage
Across the Line StartElectric Fire Pump Controller
with Automatic Power Transfer Switch
Technical Data Submittal Document
Contents:• Data Sheets • Dimensional Data• Wiring Schematics• Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 2
Standard,Listings,
Approvals andCertifications
Built to NFPA 20 (latest edition)
Underwriters Laboratory (UL)• UL218 - Fire Pump Controllers• UL 1008 - Automatic power transfer switches for fire pump controllers• CSA C22.2 No. 14 Industrial Control Equipment
FM Global Class 1321/1323New York City Accepted for use in the City of New York by the Department of BuildingsSeismic Certification See page 6 for detailsOptional□ CE Mark Various EN, IEC & CEE directives and standards
Enclosure
Protection Rating□ Standard: NEMA 2 (IP31)Optional□ NEMA 12□ NEMA 3□ NEMA 3R□ NEMA 4
Accessories• Bottom entry gland plate• Lifting Lugs• Keylock handle
*Please see Disconnecting Means details on page 3.
□ NEMA 4X-304 sst painted□ NEMA 4X-304 sst brushed finish□ NEMA 4X-316 sst painted□ NEMA 4X-316 sst brushed finish
□ IP54□ IP55□ IP65□ IP66
Paint Specifications• Red RAL3002• Powder coating• Glossy textured finish
Starting Method: Full Voltage Across the line (Direct on line)Typical Voltage Applied at Start: 100%Inrush Current: 6 x normal load currentStarting Torque: 100%Motor Type: Across the line (Direct on line)No. of Contactors: 1 at 100% of horsepowerMin. ampacity of motor conductors: 3 at 125% x 100% of Full Load Current (FLC)
MT2
T1
T31M
1M
CR4
3L1 3L2
3L1
3L2
3L3
600Across-the-line starting
Locked rotor current
Full load current
Percent of motor speed (%)
Line
cur
rent
% o
f ful
l loa
d
20 40 60 80 100
450
300
150
GPA
From Automatic Power Transfer Switch*
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 3
Surge Suppression Surge arrestor rated to suppress surges above line voltage
Disconnecting Means
• Isolating switch and circuit breaker assembly:- Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current- Circuit breaker continuous rating not less than 115% of motor full load current- Overcurrent sensing non-thermal type, magnetic only- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle Service Entrance
Rating Suitable as service entrance equipment
Emergency Start Handle
• Flange mounted • Integrated limit switch• Pull and latch activation • Across the line start (direct on line)
Locked Rotor Protector
• Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds• Factory set at 600% of motor full load current
Electrical Readings
• Voltage phase to phase (normal power)• Amperage of each phase when motor is running
Pressure Readings
• Continuous system pressure display• Cut-in and Cut-out pressure settings
Pressure and Event recorder
• Pressure readings with date stamp• Event recording with date stamp• Under regular maintained operation, events can be stored in memory for up to 5 years.• Data viewable on operator interface display screen• Downloadable by USB port to external memory device
Pressure Sensing
• Pressure transducer and run test solenoid valve assembly for fresh water application• Pressure sensing line connection 1/2” Female NPT• Drain connection 3/8”• Rated for 0-500PSI working pressure (standard display at 0-300psi)• Externally mounted with protective cover
Ambient Temperature
Rating
Standard: □ 5°C to 40°C / 41°F to 104°F
Optional: □ 5°C to 55°C / 41°F to 131°F
Shortcircuit Withstand
Rating
200V to 208V 60Hz
220V to 240V 60Hz
380V to 416V 50 Hz / 60Hz
440V to 480V 60Hz
575V to 600V 60Hz
Normal Power
Alternate Power
Normal Power
Alternate Power
Normal Power
Alternate Power
Normal Power
Alternate Power
Normal Power
Alternate Power
HP (kw)
� Standard 100kA5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a
� Optional 150kA
� Standard 50kA 200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373) 5-500 (3.7- 373)� Optional 100kA n/a n/a n/a n/a
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 4
Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)
Visual Indications & Alarms
• Power available• Phase reversal• Motor run• Pump room alarm• Motor trouble• Phase loss• Phase unbalance• Low water level
Remote Alarm Contacts
SPDT-8A-250V.AC• Power available• Phase reversal• Motor run• Common pump room alarm (field re-assignable)**
• Overvoltage • Undervoltage • Phase unbalance• Low pump room temperature • High Pump room temperature
• Common motor trouble (field re-assignable)**• Overcurrent • Fail to start• Undercurrent • Ground fault
• Free (field programmable)**
ViZiTouch Operator Interface
• Embedded microcomputer with software PLC logic• 4.2” color touch screen (HMI technology)• Upgradable software• Expandable storage• Multi-language
Communication Protocol
Capability
• Protocol: Modbus• Connection type: Shielded female connector RJ45• Frame Format: TCP/IP• Addresses: See bulletin MOD-GPx
Operation
Automatic Start • Start on pressure drop• Remote start signal from automatic device
Manual Start
• Start pushbutton• Run test pushbutton• Deluge valve start• Remote start from manual device
Stopping • Manual with Stop pushbutton• Automatic after expiration of minimum run timer ***
Timers Field Adjustable & Visual Countdown
• Minimum run timer ***(off delay)• Sequential start timer (on delay)• Periodic test timer
ActuationVisual Indication
• Pressure• Non-pressure
Mode • Automatic• Non-automatic
• Manual start • Deluge valve start• Remote automatic start• Remote manual start• Overcurrent • Undercurrent• Undervoltage• Overvoltage
• Locked rotor• Periodic test• Fail to start• Low discharge pressure• Low pump room temperature • Pump room temperature (ºF or ºC)• Pump on demand/Automatic start• Emergency start
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.***Can only be used if approved by the AHJ
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 5
Automatic Power Transfer Switch
Surge Suppression Surge arrestor rated to suppress surges above line voltage
Disconnecting Means
• Isolating switch and circuit breaker assembly:- Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current- Circuit breaker continuous rating not less than 115% of motor full load current- Overcurrent sensing non-thermal type, magnetic only- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Locked Rotor Protector
• Operate shunt trip to open circuit breaker• Factory set at 600% of motor full load current• Trip between 8 and 20 seconds
Visual Indications
• Alternate (emergency) isolating switch in the OFF position• Alternate (emergency) voltage phase to phase• Transfer switch in normal position• Transition timers
Transfer switch test pushbuttonBypass for re-transfer and generator shutdownElectrically operated and mechanically held in the normal or alternate positionProvision for manual operation
Remote Alarm ContactsSPDT-8A-250VAC
• Isolating switch in the OFF position• Transfer switch in normal position• Transfer switch in alternate (emergency) position
Time Delays• Momentary normal power outage override (factory set at 3 sec - field adjustable 1 to 3 sec)• Alternate (emergency) power available delay (factory set at 3 sec - field adjustable 1 to 3 sec)• Transfer trouble delay (factory set at 20 sec - field adjustable 1 to 60 sec)• Retransfer to normal (factory set at 5 min - field adjustable 1 to 20 min)• Generator cooldown (factory set at 5 min - field adjustable 1 to 20 min)
Voltage Sensing• Transfer to alternate (normal power dropout) 85% of nominal - field adjustable 0 to 100%• Phase reversal transfer to alternate• Retransfer to normal (normal power pickup) 90% of nominal - field adjustable 0 to 100%
Audible Alarm (AIS Open)4” alarm bell - 85 dB at 10ft. (3m)
Generator Start ConnectionSPDT-8A-250V.AC
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 6
Seismic Certification
Seismic Certification Company
TRU Compliance, LLCA Tobalski Watkins Affiliate TWEI Project No.: 15014
Mounting details Rigid base and wall mounting
Seismic Information
Building Code
Test Criteria
Seismic Parameters SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
IBC 2015, CBC 2016
ICC-ES
AC156
ASCE 7-10 Chapter 13
2.0 1.0 1.5 3.20 2.40 1.33 0.53
3.2 0.0 1.5 3.20 1.28 2.13 0.85
0.1
1.0
10.0
0.1 1.0 10.0
Spe
ctra
l Res
pons
e A
ccel
erat
ion
(g)
Frequency, f (Hz)
RRS for Nonstructural Components Testing
Horiz. Level 1 Vert. Level 1
Notes:• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016. • OSHPD Special Seismic Certification Preapproval (OSP)
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 7
A4 Flow switch provision
A8 Foam pump application w/o pressure transducer and run test solenoid valve
A9 Low zone pump control function
A10 Middle zone pump control function
A11 High zone pump control function
A13 Non-pressure actuated controller w/o pressure transducer and run test solenoid valve
A16 Lockout/interlock circuit from equipment installed inside the pump room
B11
Built in alarm panel (120V.AC supervisory power) providing indication for:• Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase.• Pilot lights for loss of phase & supervisory power available
B11BBuilt in alarm panel same as B11 but 220-240VAC supervisory power
B19A High motor temperature c/w thermoster relay and alarm contacts (Form C-SPDT)
B19B High motor temperature c/w PT100 relay and alarm contacts (Form C-SPDT)
B21 Ground fault alarm detection c/w visual indication and alarm contact (Form C-SPDT)
C1 Extra motor run alarm contact (Form C-SPDT)
C4 Periodic test alarm contact (Form C-SPDT)
C6 Low discharge pressure alarm contact (Form C-SPDT)
C7 Low pump room temperature alarm contact (Form C-SPDT)
C10 Low water reservoir level alarm contact (Form C-SPDT)
C11 High electric motor temperature alarm contact (Form C-SPDT)
C12 High electric motor vibration c/w visual indication and alarm contact (Form C-SPDT)
C14 Pump on demand / automatic start alarm contact(Form C-SPDT)
C15 Pump fail to start alarm contact (Form C-SPDT)
C16 Control voltage healthy alarm contact (Form C-SPDT)
C17 Flow meter valve loop open c/w visual indication and alarm contact (Form C-SPDT)
C18 High water reservoir level c/w visual indication and alarm contact (Form C-SPDT)
C19 Emergency start alarm contact (Form C-SPDT)
C20 Manual start alarm contact (Form C-SPDT)
C21 Deluge valve start alarm contact (Form C-SPDT)
C22 Remote automatic start alarm contact (Form C-SPDT)
C23 Remote manual start alarm contact (Form C-SPDT)
C24 High pump room temperature alarm contact (Form C-SPDT)
C25 Second set of standard alarm contacts (Form C-SPDT) (Typical for city of Los Angeles and Denver)
Cx Additional visual and alarm contact (Specify function) (Form C-SPDT)
D1 Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact
D1A Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact
D5 Pressure transducer and run test solenoid valve for fresh water rated for 0-500PSI (for factory calibration purposes only)
D5D Pressure transducer and run test solenoid valve for sea water rated for 0-500PSI
D10 Omit mounting feet (when applicable)
D13 High withstand rating for (normal power section) • 208V to 480V = 150kA • 600V = 100kA
D14 Anti-condensation heater & thermostat
D14A Anti-condensation heater & humidistat
D14B Anti-condensation heater & thermostat & humidistat
D15 Tropicalization
D18 CE Mark with factory certificate
D26 Modbus with RTU frame format and RS485 connection
D27 Motor heater connection (external single phase power source and heater on/off contact)
D27A Motor heater connection (internal single phase power source and heater on/off contact)
D28 Customized drawing set
D34 Field programmable I/O board - 8 Input / 5 output
D35 Field programmable I/O board - 8 Input / 10 output
D36 Redundant pressure transducer for fresh water rated for 0-500PSI
D36ARedundant pressure transducer for sea water rated for 0-500PSI
D37 Window kit for operator interface
E1 Permanent load shedding contacts
E2 Temporary pump motor start period load shedding contacts
E3 Temporary & permanent load shedding contacts
F2 Anti condensation heater & thermostat (alternate power section)
F2A Anti condensation heater & humidistat (alternate power section)
F2B Anti condensation heater & thermostat & humidistat (alternate power section)
F6 High withstand rating for (model GPU only) :• 208V to 480V=150kA • 600V=100kA
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 8
L01 Other language and English (bilingual)
L02 French
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Technical Data Model GPA + GPU Electric Fire Pump Controller with Automatic Power Transfer Switch
July 2016 9
??
4
9 10
12 13
11
14
5 6 7
3
2
1
8
PMS 295 PMS 361 Noir
ViZiTouch Operator Interface
1 - Power on LED2 - Color touch screen3 - Alarm LED4 - HOME page button 5 - ALARM page button6 - CONFIGURATION page button7 - HISTORY page button
8 - USB port9 - START button10 - TRANSFER SWITCH TEST button11- Contextual navigation pad12 - STOP button13 - RUN TEST button14 - HELP button
Dimensions Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
10 GENERAL REVISION 16/06/14
Drawing number
Model:GPA/GPP/GPY+GPU
Electric Fire Pump ControllerWith Automatic Transfer Switch
DI112 /EGPX-11 ADDED SEISMIC LOGO 19/08/1512 MODIFIED TORNATECH & SEISMIC LOGO 14/04/16
CDL2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Voltage Min HP Max HP
208 5 30
220 - 240 5 30
380 - 400 - 415 5 60
440 - 480 5 60
600 5 75
Projection
Voltage / Power Table
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
36" [914]
38 1/4" [972]
12" [305]
15 7/8" [403]
Ø7/8" [Ø23] X2
Sensing Line Connection - 1/2 " F.NPT
Drain - 3/8 " M.TUBE
36" [914]
7" [178]
7" [178]
19" [483]
2 1/2" [64]
34 3/4" [883]
38 3/8" [976]
39 3/8" [999]
30" [763]
7" [179]8 5/8" [218]
Ø3/8" [Ø10] X4
42" [1068]
7" [178]
6" [152]
NormalPower and
Motor LeadsEntrance
EmergencyPower
Entrance
5" [127]7" [178]
3 1/4" [83]
1 1/4" [31]
6" [152]
Ø1/2" [Ø13] X3
3" [76]1" [25]
37 3/8" [949]37 3/8" [949]
5" [127]
See Notes
Notes:
- Protect Equipment Against Drilling Chips.- Door Swing Equal to Door Width.
- Use Watertight Conduit and Connector Only.- Bottom Conduit Entrance Through Removable Gland Plate Recommended.
- Standard Paint : Textured Red RAL 3002.- All Dimensions are in Inches [Millimeters].
- Standard NEMA: NEMA 2
- Center of ViZiTouch Screen: 30-5/8" [7778] from Bottom (No Feet).
17 5/8" [448] 13 5/8" [348]
- Seismic mounting to be rigid wall and base only.
2L2
2L1
2L3SeeGPU
Drawing 3L1
3L3
3L2
1M*
Blac
k
Whi
te
Whi
te
Red
Blac
k
Blac
k
Whi
te
Whi
te
Blac
k
PowerAvailable
PhaseReversal
CommonPump Room
MotorTrouble
Alarm
MotorRunning
IS CB
1L1
1L2
1L3
1MCR4
17
SA
To J453 2
ST
3L23L1
CT1
CT3CT2
6465
6667
6869
* Contact closed when Emergency Start is in ON position
J40
J42
J37
J39Common
11
12
14J19 J18
J41
11
14
12J36
11
14
12J38
AI4-IN
(-)
(+)J14
J15
J16
J17
PT1Black
Red
White
SV1
N
GJ43
GND
ST2J45 2
3To shunt trip
+
REC
GNDJ44
N
LJ47
24VAC3
1
3L1
3L2XTR1
X1
X2
H2
H13
1
J8
6
5
7
J57
3
2
4
1
68
67
65
64
66
696
5
7
J76
3
2
4
1
8
To J76
31
32
30
J25
34
35
33
36
29
23
27
25
21
24
22
26
28
LS1*
2
1J53
J1
I/O RELAY BOARD
P1
37
38
AB1+ -Red
AI3-IN
(-)
(+)
PT1-IN
(-)
(+)
PT2-IN
(-)
(+)
TB1
TB2
TB3
TB4
TB5
Pressuretransducertype 0-5V
P2
DI0
CO
M
CO
M
J14
DI1
CO
M
DI2
CO
M
DI3
CO
M
DI4
CO
M
DI5
CO
M
DI6
CO
M
DI7
24V
GN
D
J13
(+)
(-)J16
J6P1
J3
J11
MAIN BOARD
SV1
Blue
Brown
Green / Yellow
LOCKOUT
REMOTEMANUAL START
DELUGEVALVE
WATER RESERVOIRLOW
REMOTEAUTOMATIC START
TM1Probe 1
Temperature
SeeDwgGPU
VIZITOUCH
J2*
J1*
* REMOVE JUMPER TO USE THIS FEATURE
11
12
14
11
12
14
11
12
14
11
12
14
11
12
14
11
12
14
Wiring schematic Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPA+GPU
WS510 /EGPA-
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
Full Voltage / Across the LineWith Automatic Transfer Switch
1M
1M
1M-2
1M-3
1M-1
CR4CR4-1
CR4-2
SV1-1
SV1-2
LS1-2
LS1-1
To J57
To CT1-2-3
To 3L1-2-3
3L3
3L2
3L1
BlackRed
Black
2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.CDL
4 Added Seismic Logo 19/08/153 General Revision 07/01/15
5 Modified Tornatech & Seismic Logo 14/04/16
24Vdc
24Vrect
COMJ38
J8
6
5
7
J57
3
2
4
1I/O BOARD Tr. Sw.
DESCRIPTIONDATEREV.
2L2
2L1
2E2
2E3
2E1
2L1
2L3
2L2
M
GPU-
Drawing No.
APP.
VER.
DES.
BUILT TO LATEST NFPA 20 STANDARD EDITION
2E2
2E1
2E3
Wiring schematic
3L2
3L1
3L3
MODEL :
LSN1NO
C
CNC
NOLSN2
CNOLSE1
CNC
NOLSE3
50Normal Power fromPump ControllerSection
Normal / Alternate Powerto Pump Controller Section
TSP : Shown in normal position
/EWS500
GPU
Red
Whi
te
Blac
k
Red
Whi
te
Blac
k
Blac
kBl
ack
AL1
AL2
AL3
ACB
J49-4
Red
Green
Black
WhiteJ49-1
J49-2
J49-5J49-3 Brown
J50-1White
WhiteBlack J54-2J54-1
J50-2Black
X2 H1
XTR3
X2
X1
X1
H1
H2
H2
XTR2
24VAC
24VAC
51
52
54
53
53 5154 52
2L1
2E2
2E1
2L2
ADDED SEISMIC LOGO2. 15/08/20
J20
6
5
7
J64
3
2
4
1
J53 2
1
J47 2
1
J50
J1
J49
14
J46
12
11
11
14
12
11
14
11
14
J45 COM
ST2
J55 LN11
LN12
J52 M+
M-
J54 LE11
LE12
11
12
14
J3914
12
11
14
11
12
ALT.
PO
S.N
OR
. PO
S.AC
BG
EN
12
11
14
CNC
NOLSE2
J50-4
Red
GreenJ50-5
J50-3 Brown
LSN3NO
CNC WhiteBlack J55-2
J55-1
24Va
c224
Vac1
J58 GND
COM
I/O BOARD Tr. Sw.
Green
Brown
Black
White
Red
Green
Brown
Black
White
Red To LSE1 / LSE2
To LSN3
To LSE3
White
White
Black
Black
To LSN1 / LSN2
5655
From AST
From PumpControllerSection
2L2
2L1
50
2E2
2E3
2E1
White
Black
White
Black
ACB
LSA1
LSA2
LSA3
11
14
14
12
11
LSN
1LS
E1LS
E2LS
N2
11
14
14
12
11
Red
Whi
te
Drawing for information only.Manufacturer reserves the right to modify this drawing whitout notice.Contact manufacturer for "As Built" drawing.
ASA
NYCDpt of Building
Approved
AUTOMATIC POWER TRANSFER SWITCH
MODIFIED SEISMIC LOGO3. 16/04/14
AIS
CNC
NOLSA2
J46-6
Red
GreenJ46-5
J46-7 Brown
CNOLSA1
J46-3WhiteJ46-4
Black
CNOLSA4
J46-1WhiteJ46-2
Black
CNC
NOLSA3
J46-9
Red
GreenJ46-10
J46-8 Brown
55 56
AST
Green
Brown
Red To LSA
Black
White
Green
Brown
Red
Black
White
1E2
1E1
1E3
CDL
2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPX
TD500 1/3 /EGPX-
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.
GPA, GPR & GPS
M
GndT1 T2 T3
1M
Incoming Power3 Phases
Bonding
Gnd L2L1IS
Ground
L3Power Terminals Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC(Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer ormotor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABCsequence.5 - Field wiring and lug sizes base on copper conductors only. Do not use aluminium conductors.
Models :
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (10)
1x (10)
1x (14 to 10)
1x (12 to 10)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x ( 10)
1x (10)
1x (8 to 2)
1x (6 to 2)
1x (6 to 2)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 2)
1x (8 to 2)
1x (6 to 2)
1x (4 to 1/0)
1x (3 to 1/0)
1x (8 to 2)
1x (6 to 2)
1x (6 to 1/0)
1x (3 to 1/0)
1x (2 to 1/0)
1x (6 to 2)
1x (6 to 2)
1x (4 to 1/0)
1x (1 to 3/0)
1x (1/0 to 3/0)
1x (6 to 2)
1x (4 to 1/0)
1x (3 to 1/0)
1x (2/0 to 3/0)
1x (3/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (3/0)
1x (4/0 to 300)
1x (3 to 1/0)
1x (1 to 2/0)
1x (1/0 to 3/0)
1x (250 to 300)
1x (300)
1x (1 to 2/0)
1x (2/0 to 3/0)
1x (3/0)
2x (2/0 to 300)
2x (2/0 to 300)
1x (3/0)
1x (2/0 to 3/0)
1x (250 to 300)
2x (3/0 to 300)
2x (4/0 to 300)
1x (3/0)
1x (4/0 to 300)
1x (300)
2x (4/0 to 300)
2x (250 to 300)
1x (250 to 300)
2x (1/0 to 300)
2x (3/0 to 300)
2x (350 to 500)
2x (2/0 to 300)
2x (3/0 to 300)
2x (4/0 to 300)
2x (3/0 to 300)
2x (4/0 to 300)
2x (300)
--------
--------
--------
2x (4/0 to 300)
2x (300)
--------
--------
2x (250 to 300)
--------
--------
2x (300)
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1/0)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (250 to 500)
1x (300 to 500)
1x (1 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (350 to 500)
1x (500)
1x (3/0 to 250)
1x (2/0 to 250)
1x (250)
2x (3/0 to 500)
2x (4/0 to 500)
1x (3/0 to 250)
1x (4/0 to 250)
1x (300 to 500)
2x (4/0 to 500)
2x (250 to 500)
1x (250 to 500)
1x (350 to 500)
2x (3/0 to 250)
1x (350 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (300 to 500)
--------
--------
--------
2x (4/0 to 500)
2x (300 to 500)
--------
--------
2x (250 to 500)
--------
--------
2x (300 to 500)
--------
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 " (127 mm) 8 " (203 mm)
12 " (305 mm)
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (3 to 1/0)
1x (2 to 1/0)
1x (4 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (3/0 to 250)
1x (4/0 to 250)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
Wiring Size for motor connection for Models GPA, GPR & GPS (AWG or MCM). TERMINALS T1 - T2 - T3
Voltage
Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3
BendingSpace
HP
HP
HP
HP
(Use Copper Conductors Only)
(Use Copper Conductors Only)
2x (400 to 500)
2x (400 to 600)
2x (500 to 600)
2x (500 to 600) 2x (600)
2x (400 to 600) 2x (500 to 600)
2x (400 to 500)
16 " (406 mm)
2x (400 to 600)
2x (400 to 500)
2x (500 to 600)
2x (500 to 600) 2x (600)
2x (400 to 600) 2x (500 to 600)
BendingSpace
BendingSpace
Voltage
BendingSpace
Voltage
Voltage
2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.6 Added Seismic Logo 19/08/157 Added Terminal Torque Ratings 14/09/158 Modified Tornatech & Seismic Logo 14/04/16
Terminals Diagram and Sizing
Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of Building
Approved
Drawing number
Electric Fire Pump ControllerModel:GPX
TD500 2/3 /EGPX-
Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
For drawing for approval or installation, please contact manufacturer.
GPP
Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC
(Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
4 - Controller is phase sensitive. Incoming lines must be connected in ABC
sequence.
5 - Field wiring and lug sizes base on copper conductors only.
Do not use aluminium conductors.
Models :
M
Gnd
T7 T8 T9
2M
Incoming Power
3 Phases
Bonding
Gnd
L2L1
IS
Ground
L3
T1 T2 T3
1M
M
Gnd
T6 T4 T5
2M
Incoming Power
3 Phases
Bonding
Gnd
L2L1
IS
Ground
L3
T1 T2 T3
1M
Power Terminals
GPW & GPYModels :
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208
1x (14 to 10)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (12 to 10)
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (10)
1x (10)
1x (14 to 10)
1x (12 to 10)
1x (12 to 10)
1x (8 to 2)
1x (8 to 2)
1x (12 to 10)
1x (12 to 10)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (12 to 10)
1x (10)
1x (10)
1x (6 to 2)
1x (6 to 2)
1x (10)
1x (10 to 2)
1x (8 to 2)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 2)
1x (8 to 2)
1x (6 to 2)
1x (4 to 2/0)
1x (4 to 2/0)
1x (8 to 2)
1x (6 to 2)
1x (6 to 2)
1x (3 to 2/0)
1x (2 to 3/0)
1x (8 to 2)
1x (6 to 2)
1x (4 to 1/0)
1x (2 to 3/0)
1x (1 to 3/0)
1x (6 to 2)
1x (4 to 2/0)
1x (4 to 2/0)
1x (1/0 to 3/0)
1x (2/0 to 3/0)
1x (4 to 2/0)
1x (3 to 2/0)
1x (2 to 2/0)
1x (3/0)
1x (3/0)
1x (2 to 3/0)
1x (3 to 2/0)
1x (1/0 to 3/0)
1x (4/0 to 300)
1x (250 to 300)
1x (2 to 3/0)
1x (1/0 to 3/0)
1x (2/0 to 3/0)
1x (300)
2x (1/0 to 300)
1x (1/0 to 3/0)
1x (2/0 to 3/0)
2x (2/0 to 300)
1x (2/0 to 3/0)
1x (300)
1x (300)
2x (2/0 to 300)
--------
--------
--------
1x (250 to 300)
2x (1/0 to 300)
--------
--------
1x (300)
2x (2/0 to 300)
--------
--------
2x (1/0 to 300)
--------
--------
2x (2/0 to 300)
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208
1x (10 to 1/0)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (250 to 500)
1x (300 to 500)
1x (1 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (350 to 500)
1x (500)
1x (3/0 to 250)
1x (2/0 to 250)
1x (250)
2x (3/0 to 500)
2x (4/0 to 500)
1x (3/0 to 250)
1x (4/0 to 250)
1x (300 to 500)
2x (4/0 to 500)
2x (250 to 500)
1x (250 to 500)
1x (350 to 500)
2x (3/0 to 250)
1x (350 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (300 to 500)
--------
--------
--------
2x (4/0 to 500)
2x (300 to 500)
--------
--------
2x (250 to 500)
--------
--------
2x (300 to 500)
--------
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 " (127 mm) 8 " (203 mm)
12 " (305 mm)
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (3 to 1/0)
1x (2 to 1/0)
1x (4 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (3/0 to 250)
1x (4/0 to 250)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
1x (4/0 to 300)
1x (4/0 to 300)
1x (4/0 to 300)
Wiring Size for motor connection for Models GPP, GPW & GPY (AWG or MCM). TERMINALS T1 - T2 - T3 - T4 - T5 - T6 - T7 - T8 - T9
HP
HP
HP
HP
2x (3/0 to 300)
2x (3/0 to 350)
2x (4/0 to 350)
2x (4/0 to 350) 2x (4/0 to 350)
2x (3/0 to 350) 2x (4/0 to 350)
2x (400 to 500)
2x (400 to 600)
2x (500 to 600)
2x (500 to 600) 2x (600)
2x (400 to 600) 2x (500 to 600)
2x (400 to 500)
Voltage
Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3
Bending
Space
(Use Copper Conductors Only)
(Use Copper Conductors Only)
Bending
Space
Bending
Space
Voltage
Bending
Space
Voltage
Voltage
16 " (406 mm)
2016Copyright © Tornatech Inc.
All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
6
Added Seismic Logo
19/08/15
7 Added Terminal Torque Ratings14/09/15
8 Modified Tornatech & Seismic Logo14/04/16
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Electric Fire Pump Controller Model:GPX
TD500 3/3 /EGPX-
Control Terminals (I/O board)
Close to start pump 2324 J25
Remote Manual Start
Open to start pump 2728 J25
Automatic Start
Signal
DelugeValve Open to start pump 29
30 J25
Deluge Valve
Signal
Water ReservoirLow Close to signal alarm 31
32 J25
Water Reservoir Low
Signal
Flow / ZoneStart / Stop 33
34 J25
Flow / Zone
(I/O board)
Close to signal alarm
SignalLockout Close to block start 25
26 J25
Lockout
J1If used, remove jumper J1
J2If used, remove jumper J2
Field Connections for External Devices
RunningMotor
TroubleMotor
Reversal Phase
AvailablePower
Remote Alarm Terminals (I/O board)
(Fail Safe)
AlarmRoomPump
J19 - 14J19 - 11J19 - 12
Normally closedOpens to alarm
Closes to alarmNormally open
J40 - 14J40 - 11J40 - 12
Normally openCloses to alarm
Opens to alarmNormally closed
J42 - 14J42 - 11J42 - 12
Normally closedOpens to alarm
Closes to alarmNormally open
J37 - 14J37 - 11J37 - 12
Normally closedOpens to alarm
Closes to alarmNormally open
J39 - 14J39 - 11J39 - 12
Normally closedOpens to alarm
Closes to alarmNormally open
TB1
TB2
TB3
TB4
MO
TOR
RU
N
Programmable)(Field*
J41 - 14J41 - 11J41 - 12
Normally closedOpens to alarm
Closes to alarmNormally open
TB5
(RE-ASSIGNABLE)
(RE-ASSIGNABLE)
*Not Available in GPS Models
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.
RemoteManualStart
RemoteAutomaticStart
6 Added Seismic Logo 19/08/15
0.5 Nm12 - 24 AWG
Terminals Wire Size:
0.5 Nm12 - 24 AWG
Terminals Wire Size:
0.5 Nm12 - 24 AWG
Terminals Wire Size:
7 Added Terminal Torque Ratings 14/09/15
2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
8 Modified Tornatech & Seismic Logo 14/04/16
BondingGround
3 PhasesIncoming Power
Power Terminals
Gnd AL1 AL2 AL3
AIS
Remote Alarm Terminal (I/O board Tr. Sw.)
12
11
14
J39
14
12
11
14
11
12
ALT.
PO
S.N
OR
. PO
S.AC
BG
EN
12
11
14
Closes to start generatorNormally open
Opens to start generatorNormally closed
SetGenerator
is in OFF or TrippedCloses when ACB
is in OFF or TrippedOpens when ACB
OFF or TrippedACB in
Closes when Tr. Sw.in Normal Position
Opens when Tr. Sw.in Normal Position
Tr. Sw. inNormalPosition
Closes when Tr. Sw.in Alternate Position
Opens when Tr. Sw.in Alternate Position
Tr. Sw. inAlternatePosition
(I/O board Tr. Sw.)
J39
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1/0)
30 40 50 60
75 100 125 150 200 250 300 350 400 450 500
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (3 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (250 to 500)
1x (300 to 500)
1x (1 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (350 to 500)
1x (500)
1x (3/0 to 250)
1x (2/0 to 250)
1x (250)
2x (3/0 to 500)
2x (4/0 to 500)
1x (3/0 to 250)
1x (4/0 to 250)
1x (300 to 500)
2x (4/0 to 500)
2x (250 to 500)
1x (250 to 500)
1x (350 to 500)
2x (3/0 to 250)
1x (350 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (3/0 to 250)
2x (4/0 to 500)
2x (300 to 500)
--------
--------
--------
2x (4/0 to 500)
2x (300 to 500)
--------
--------
2x (250 to 500)
--------
--------
2x (300 to 500)
--------
--------
--------
--------
--------
220 to 240
380 to 416
600
440 to 480
208
5 " (127 mm) 8 " (203 mm)
12 " (305 mm)
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (10 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (10 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (4 to 1/0)
1x (4 to 1/0)
1x (8 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (4 to 1/0)
1x (3 to 1/0)
1x (8 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (3 to 1/0)
1x (2 to 1/0)
1x (4 to 1/0)
1x (6 to 1/0)
1x (6 to 1/0)
1x (1 to 250)
1x (1/0 to 250)
1x (2/0 to 250)
1x (3/0 to 250)
1x (3/0 to 250)
1x (4/0 to 250)
2x (350 to 500)
2x (350 to 500)
2x (350 to 500)
Voltage
Voltage
Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS AL1 - AL2 - AL3
BendingSpace
BendingSpace
HP
HP
Field Connections for External Devices
Notes:1 - Controller is phase sensitive. Incoming lines must be connected in ABC2 - Field wiring and lug sizes base on copper conductors only. Do not use aluminium conductors.
(Use Copper Conductors Only)
2x (400 to 600)
2x (400 to 500)
2x (500 to 600)
2x (500 to 600) 2x (600)
2x (400 to 600) 2x (500 to 600)
2x (400 to 500)
16 " (406 mm)
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
3 General Revision 09/01/15
Drawing number
Transfer Switch Model:GPU
TD500 /EGPU-
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.
4 Added Seismic Logo 19/08/15
2016Copyright © Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.CDL
5 Modified Tornatech & Seismic Logo 14/04/16