+ All Categories
Home > Documents > Technical instruction - Communication protocol MODBUS RTU ......Doc: AD507921.doc 28/04/2009 p. 1 /...

Technical instruction - Communication protocol MODBUS RTU ......Doc: AD507921.doc 28/04/2009 p. 1 /...

Date post: 02-Feb-2021
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
21
Doc: AD507921.doc 28/04/2009 p. 1 / 21 577 RGK60 RGK60 Controllo gruppi elettrogeni Gen-set control Addendum del Addendum of the manuale operativo instruction manual Protocollo comunicazione Communication protocol MODBUS RTU MODBUS RTU I 150 I GB 0409
Transcript
  • Doc: AD507921.doc 28/04/2009 p. 1 / 21

    577 RGK60 RGK60 Controllo gruppi elettrogeni Gen-set control

    Addendum del Addendum of the manuale operativo instruction manual

    Protocollo comunicazione Communication protocol

    MODBUS RTU MODBUS RTU

    I 150

    I GB 0409

  • Doc: AD507921.doc 28/04/2009 p. 2 / 21

    PROTOCOLLO MODBUS® A partire dalla revisione software 18, gli RGK60 supportano il protocollo Modbus® RTU sulla porta seriale RS-232 e RS485. Grazie a questa funzione e’ possibile leggere lo stato della centralina e controllare gli stessi tramite software di supervisione standard forniti da terze parti oppure tramite apparecchiature dotate di interfaccia Modbus® quali PLC e terminali intelligenti. IMPOSTAZIONE DEI PARAMETRI Per configurare il protocollo Modbus®, accedere al Menu funzioni ed agire sui parametri riportati nella seguente tabella: TABELLA PARAMETRI

    PAR Funzione Range Default

    P1001 Indirizzo porta seriale RS-232

    1 - 255 1

    P1002 Baud-rate porta RS-232

    OFF/1200-38400

    9600

    P1003 Baud-rate porta RS-485

    OFF/1200-38400

    9600

    P1004 Canale Modem RS232-RS485 RS232

    P1005 Parità Nessuna Even (pari) Odd (dispari)

    Nessuna

    P1006 Protocollo RS232

    Proprietario Modbus®RTU

    Proprietario

    P1007 Protocollo RS485

    Proprietario Modbus®RTU

    Proprietario

    PROTOCOLLO MODBUS® RTU Se si seleziona il parametro P1006 come protocollo Modbus® RTU, la struttura del messaggio di comunicazione è così costituita:

    T1 T2 T3

    Indirizzo ( 8 bit)

    Funzione (8 bit)

    Dati

    (N x 8 bit)

    CRC (16 bit)

    T1 T2 T3

    •••• il campo Indirizzo contiene l’indirizzo dello strumento slave cui il messaggio viene inviato.

    •••• il campo Funzione contiene il codice della funzione che deve essere eseguita dallo slave.

    •••• il campo Dati contiene i dati inviati allo slave o quelli inviati dallo slave come risposta ad una domanda.

    •••• il campo CRC consente sia al master che allo slave di verificare se ci sono errori di trasmissione. Questo consente, in caso di disturbo sulla linea di trasmissione, di ignorare il messaggio inviato per evitare problemi sia dal lato master che slave.

    •••• la sequenza T1 T2 T3 corrisponde al tempo durante il quale non devono essere scambiati dati sul bus di comunicazione, per consentire agli strumenti collegati di riconoscere la fine di un messaggio e l’inizio del successivo. Questo tempo deve essere pari a 3.5 caratteri. L’RGK60 misura il tempo trascorso tra la ricezione di un carattere e il successivo e se questo tempo supera quello necessario per trasmettere 3.5 caratteri, riferiti al baud-rate impostato, il prossimo carattere viene considerato l’inizio di un nuovo messaggio.

    MODBUS® PROTOCOL Starting from software revision 18, RGK60 series support the Modbus® protocol on their RS-232 serial port and RS485. Using this feature it is possible to read the status of the device and to control it from a standard third-party supervision software or from other intelligent devices with standard Modbus® interface, such as PLCs and intelligent terminals. PARAMETER SETTING To configure the Modbus® protocol, enter Function menu and set the parameters listed in the following table: PARAMETERS TABLE

    PAR Function Range Default

    P1001 RS-232 port serial address

    1 - 255 1

    P1002 RS-232 port baud rate

    OFF/1200-38400

    9600

    P1003 RS-485 port baud-rate

    OFF/1200-38400

    9600

    P1004 Modem channel RS232-RS485 RS232

    P1005 Parity None Even Odd

    None

    P1006 RS232 Protocol Proprietary

    Modbus®RTU Proprietary

    P1007 RS485 Protocol Proprietary

    Modbus®RTU Proprietary

    MODBUS® RTU PROTOCOL If one selects the parameter P1006 as Modbus® RTU protocol, the communication message has the following structure:

    T1 T2 T3

    Address ( 8 bit)

    Function (8 bit)

    Data

    (N x 8 bit)

    CRC (16 bit)

    T1 T2 T3

    •••• The Address field holds the serial address of the slave destination device.

    ••••The Function field holds the code of the function that must be executed by the slave.

    •••• The Data field contains data sent to the slave or data received from the slave in response to a query

    •••• The CRC field allows the master and slave devices to check the message integrity. If a message has been corrupted by electrical noise or interference, the CRC field allows the devices to recognize the error and thereby to ignore the message.

    •••• The T1 T2 T3 sequence corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 times the time required to send one character. The RGK60 measures the time that elapse from the reception of one character and the following. If this time exceeds the time necessary to send 3.5 characters at the selected baud-rate, then the next character will be considered as the first of a new message.

  • Doc: AD507921.doc 28/04/2009 p. 3 / 21

    FUNZIONI MODBUS® Le funzioni disponibili sono:

    04 = Read input register

    Consente la lettura delle misure disponibili nell’RGK60 .

    06 = Preset single register

    Permette di modificare i parametri del setup

    07 = Read exception Permette di leggere lo stato dell’RGK60

    17 = Report slave ID Permette di leggere informazioni relative all’RGK60

    Per esempio, se si vuole leggere dall ‘RGK60 con indirizzo 8 il valore della tensione di linea che si trova alla locazione 2 (02 Hex), il messaggio da spedire è il seguente:

    08 04 00 01 00 02 20 92 Dove: 08 = indirizzo slave. 04 = funzione di lettura locazione. 00 01 = indirizzo della locazione diminuito di un’unità, contenete il valore di tensione media di linea 00 02 = numero di registri da leggere a partire dall’indirizzo 01. 2092 = checksum CRC. La risposta dell’ RGK60 è la seguente:

    08 04 04 00 00 00 64 63 6A Dove: 08 = indirizzo dell’ RGK60 (Slave 08). 04 = funzione richiesta dal Master. 04 = numero di byte inviati dall’RGK60 . 00 00 00 64 = valore esadecimale della tensione di linea = 100 V. 63 6A = checksum CRC. FUNZIONE 04: READ INPUT REGISTER La funzione 04 permette di leggere una o più grandezze consecutive in memoria. L’indirizzo di ciascuna grandezza e’ indicato nelle Tabelle 2..7 riportate nelle ultime pagine del presente manuale. Come da standard Modbus®, l’indirizzo specificato nel messaggio va diminuito di 1 rispetto a quello effettivo riportato nella tabella. Se l’indirizzo richiesto non è compreso nella tabella o il numero di registri richiesti è maggiore di 20 l’RGK60 ritorna un messaggio di errore ( vedi tabella errori). Richiesta Master:

    Indirizzo slave 08h

    Funzione 04h

    MSB Indirizzo registro 00h

    LSB Indirizzo registro 0Fh

    MSB Numero registri 00h

    LSB Numero registri 08h

    MSB CRC 21h

    LSB CRC 57h

    Nell’esempio vengono richiesti allo slave numero 8 n. 8 registri consecutivi a partire dall’indirizzo 10h. Quindi vengono letti i registri dall’ 10h al 17h.Il comando termina sempre con il valore di checksum CRC.

    MODBUS® FUNCTIONS The available functions are:

    04 = Read input register

    Allows to read the RGK60 measures.

    06 = Preset single register

    Allows to set the setup parameters

    07 = Read exception

    Allows to read the device status

    17 = Report slave ID

    Allows to read information about the RGK60 .

    For instance, to read the value of the line voltage, which resides at location 2 (02 Hex) from the RGK60 with serial address 08, the message to send is the following:

    08 04 00 01 00 02 20 92 Whereas: 08 = slave address 04 = Modbus® function ‘Read input register’ 00 01 = Address of the required register (line voltage) decreased by one 00 02 = Number of registers to be read beginning from address 0001 2092 = CRC Checksum The RGK60 answer is the following:

    08 04 04 00 00 00 64 63 6A Where: 08 = RGK60 address (Slave 08) 04 = Function requested by the master 04 = Number of bytes sent by the RGK60 00 00 00 64 = Hex value of the equivalent phase-to-phase voltage (100 V) 63 6A = CRC checksum FUNCTION 04: READ INPUT REGISTER The Modbus® function 04 allows to read one or more consecutive registers from the slave memory. The address of each measure is given in the tables 2..7 reported in the final pages of this manual. As for Modbus® standard, the address in the query message must be decreased by one from the effective address reported in the table. If the measure address is not included in the table or the number of requested registers exceeds 20 the RGK60 will return an error code (see error table). Master query:

    Slave address 08h

    Function 04h

    MSB address 00h

    LSB address 0Fh

    MSB register number 00h

    LSB register number 08h

    MSB CRC 21h

    LSB CRC 57h

    In the above example slave 08 is requested for 8 consecutive registers beginning with address 10h. Thus, registers from 10h to 17h will be returned. As usual, the message ends with the CRC checksum.

  • Doc: AD507921.doc 28/04/2009 p. 4 / 21

    Risposta Slave:

    Indirizzo slave 08h

    Funzione 04h

    Numero di byte 10h

    MSB Dato 10h 00h

    LSB Dato 10h 00h

    --------------------------------------------------- ----

    MSB Dato 17h 00h

    LSB Dato 17h 00h

    MSB CRC 5Eh

    LSB CRC 83h

    La risposta è composta sempre dall’indirizzo dello slave, dalla funzione richiesta dal Master e dai dati dei registri richiesti. La risposta termina sempre con il valore di checksum CRC. FUNZIONE 06: PRESET SINGLE REGISTER Questa funzione permette di scrivere nei registri. Essa può essere utilizzata solo con i registri di indirizzo superiore a 1000 Hex, e solo quando il motore e’ fermo. E’ possibile ad esempio impostare i parametri del setup. I parametri di setup modificati vengono automaticamente salvati nella memoria ritenitiva (eeprom) e qualora il valore impostato non rientri nel valore minimo e massimo della tabella l’ RGK60 risponderà con un messaggio di errore. Se viene richiesto un parametro ad un indirizzo inesistente verrà risposto con un messaggio di errore. L’indirizzo ed il range valido per i vari parametri può essere trovato nelle Tabelle 5, 6 e 7. Con la funzione 06 e’ inoltre possibile eseguire dei comandi utilizzando gli indirizzi ed i valori riportati nella Tabella 4. Richiesta Master:

    Indirizzo slave 08h

    Funzione 06h

    MSB Indirizzo registro 21h

    LSB Indirizzo registro 04h

    MSB Dato 01h

    LSB Dato 90h

    MSB CRC C3h

    LSB CRC 52h

    Nell’esempio viene richiesto di modificare il parametro P0204 all’indirizzo 2105 Hex ( tensione nominale ) con il valore 400. Risposta Slave: La risposta è un eco della domanda, cioè viene inviato al master l’indirizzo del dato da modificare e il nuovo valore del parametro.

    Slave response:

    Slave address 08h

    Function 04h

    Byte number 10h

    MSB register 10h 00h

    LSB register 10h 00h

    --------------------------------------------------- ----

    MSB register 17h 00h

    LSB register 17h 00h

    MSB CRC 5Eh

    LSB CRC 83h

    The response is always composed of the slave address, the function code requested by the master and the contents of the requested registers. The answer ends with the CRC. FUNCTION 06: PRESET SINGLE REGISTER This function allows to write in the registers. It can be used only with registers with address higher than 1000 Hex, and only when the motor is stopped. For instance it is possible to change setup parameters. Modified parameters are automatically saved in the non-volatile eeprom memory. If the value is not in the correct range, the RGK60 will answer with an error message. In the same way, if the parameter address is not recognised, the RGK60 will send an error response. The address and the valid range for each parameter are indicated in Tables 5, 6 and 7. With function 06, some commands can be possibly executed sending the addresses and the values reported in Table 4. Master message:

    Slave address 08h

    Function 06h

    MSB register address 21h

    LSB register address 04h

    MSB data 01h

    LSB data 90h

    MSB CRC C3h

    LSB CRC 52h

    In the above message, the master wants to set parameter P0204 at address 2105 Hex (Nominal Voltage) with value 400. Slave response: The slave response is an echo to the query, that is the slave sends back to the master the address and the new value of the variable.

  • Doc: AD507921.doc 28/04/2009 p. 5 / 21

    FUNZIONE 07: READ EXCEPTION STATUS Tale funzione permette di leggere lo stato in cui si trova l’RGK60. Richiesta Master:

    Indirizzo slave 08h

    Funzione 07h

    MSB CRC 47h

    LSB CRC B2h

    La tabella seguente riporta il significato del byte inviato dall’ RGK60 come risposta:

    BIT SIGNIFICATO

    0 Reset/OFF mode

    1 Man mode

    2 Aut mode

    3 Test mode

    4 Status Rete

    5 Status generatore

    6 Status motore

    7 Status teleruttore rete

    8 Status teleruttore generatore

    9 Status Allarme

    FUNZIONE 17: REPORT SLAVE ID Questa funzione permette di identificare il tipo di RGK60. Richiesta Master.

    Indirizzo slave 08h

    Funzione 11h

    MSB CRC C6h

    LSB CRC 7Ch

    Risposta Slave:

    Indirizzo slave 08h

    Funzione 11h

    Numero byte 06h

    Dato 1 (Rev. Software) 11h

    Dato 2 (Rev. hardware) 02h

    Dato 3 (Rev. Testi) 0Ah

    Dato 4 (Rev. Parametri) 08h

    Dato 5 (Mod. Scheda Slot A) 01h

    Dato 6 (Mod. Scheda Slot B) 15h

    MSB CRC F3h

    LSB CRC 34h

    ERRORI Nel caso lo slave riceva un messaggio errato, segnala la condizione al master rispondendo con un messaggio composto dalla funzione richiesta in OR con 80 Hex, seguita da un codice di errore. Nella seguente tabella vengono riportati i codici di errore inviati dallo slave al master TABELLA 1: CODICI ERRORE

    COD ERRORE

    01 Funzione non valida

    02 Indirizzo registro illegale

    03 Valore del parametro fuori range

    04 Impossibile effettuare operazione

    06 Slave occupato, funzione momentaneamente non disponibile (es. motore in marcia)

    FUNCTION 07: READ EXCEPTION STATUS This function allows to read the status of the RGK60. Master query:

    Slave address 08h

    Function 07h

    MSB CRC 47h

    LSB CRC B2h

    The following table gives the meaning of the status byte sent by the RGK60 as answer:

    BIT MEANING

    0 Reset/OFF mode

    1 Man mode

    2 Aut mode

    3 Test mode

    4 Mains status

    5 Generator status

    6 Motor status

    7 Mains breaking status

    8 Generator breaking status

    9 Alarm status

    FUNZIONE 17: REPORT SLAVE ID This function allows to identify the RGK60 type. Master query.

    Slave address 08h

    Function 11h

    MSB CRC C6h

    LSB CRC 7Ch

    Slave response:

    Slave address 08h

    Function 11h

    Byte number 06h

    Data 1 (Software revision) 11h

    Data 2 (Hardware revision) 02h

    Data 3 (Labels revision) 0Ah

    Data 4 (Parameters revision) 08h

    Dato 5 (Mod. Interface Slot A) 01h

    Dato 6 (Mod. Interface Slot B) 15h

    MSB CRC F3h

    LSB CRC 34h

    ERRORS In case the slave receives an incorrect message, it answers with a massage composed by the queried function ORed with 80 Hex, followed by an error code byte. In the following table are reported the error codes sent by the slave to the master: TABLE 1: ERROR CODES

    CODE ERROR

    01 Invalid function

    02 Invalid address

    03 Parameter out of range

    04 Function execution impossible

    06 Slave busy, function momentarily not available (e.g. motor is running)

  • Doc: AD507921.doc 28/04/2009 p. 6 / 21

    Algoritmo di calcolo del CRC CRC calculation algorithm

    CALCOLO DEL CRC (CHECKSUM) Esempio di calcolo: Frame = 0207h Inizializzazione CRC 1111 1111 1111 1111 Carica primo byte 0000 0010 Esegue xor con il primo 1111 1111 1111 1101 Byte della frame Esegue primo shift a dx 0111 1111 1111 1110 1 Carry=1,carica polinomio 1010 0000 0000 0001 Esegue xor con il 1101 1111 1111 1111 polinomio Esegue secondo shift dx 0110 1111 1111 1111 1 Carry=1,carica polinomio 1010 0000 0000 0001 Esegue xor con il 1100 1111 1111 1110 polinomio Esegue terzo shift 0110 0111 1111 1111 0 Esegue quarto shift 0011 0011 1111 1111 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con il 1001 0011 1111 1110 Polinomio Eseque quinto shift dx 0100 1001 1111 1111 0 Eseque sesto shift dx 0010 0100 1111 1111 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con polinomio 1000 0100 1111 1110 Esegue settimo shift dx 0100 0010 0111 1111 0 Esegue ottavo shift dx 0010 0001 0011 1111 1 Carry=1, carica polinomio 1010 0000 0000 0001 Carica secondo byte 0000 0111 della frame Esegue xor con il 1000 0001 0011 1001 Secondo byte della frame Esegue primo shift dx 0100 0000 1001 1100 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con il 1110 0000 1001 1101 polinomio Esegue secondo shift dx 0111 0000 0100 1110 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con il 1101 0000 0100 1111 polinomio Esegue terzo shift dx 0110 1000 0010 0111 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con il 1100 1000 0010 0110 polinomio Esegue quarto shift dx 0110 0100 0001 0011 0 Esegue quinto shift dx 0010 0100 0000 1001 1 Carry=1, carica polinomio 1010 0000 0000 0001 Esegue xor con il 1001 0010 0000 1000 polinomio Esegue sesto shift dx 0100 1001 0000 0100 0 Esegue settimo shift dx 0010 0100 1000 0010 0 Esegue ottavo shift dx 0001 0010 0100 0001 0 Risultato CRC 0001 0010 0100 0001 12h 41h Nota: Il byte 41h viene spedito per primo (anche se e’ il LSB), poi viene trasmesso 12h.

    CRC CALCULATION (CHECKSUM) Example of CRC calculation: Frame = 0207h CRC initialization 1111 1111 1111 1111 Load the first byte 0000 0010 Execute xor with the first 1111 1111 1111 1101 Byte of the frame Execute 1st right shift 0111 1111 1111 1110 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1101 1111 1111 1111 polynomial Execute 2nd right shift 0110 1111 1111 1111 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1100 1111 1111 1110 polynomial Execute 3rd right shift 0110 0111 1111 1111 0 Execute 4th right shift 0011 0011 1111 1111 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1001 0011 1111 1110 polynomial Execute 5th right shift 0100 1001 1111 1111 0 Execute 6th right shift 0010 0100 1111 1111 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1000 0100 1111 1110 polynomial Execute 7th right shift 0100 0010 0111 1111 0 Execute 8th right shift 0010 0001 0011 1111 1 Carry=1,load polynomial 1010 0000 0000 0001 Load the second byte 0000 0111 of the frame Execute xor with the 1000 0001 0011 1001 Second byte of the frame Execute 1st right shift 0100 0000 1001 1100 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1110 0000 1001 1101 polynomial Execute 2nd right shift 0111 0000 0100 1110 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1101 0000 0100 1111 polynomial Execute 3rd right shift 0110 1000 0010 0111 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1100 1000 0010 0110 polynomial Execute 4th right shift 0110 0100 0001 0011 0 Execute 5th right shift 0010 0100 0000 1001 1 Carry=1,load polynomial 1010 0000 0000 0001 Execute xor with the 1001 0010 0000 1000 polynomial Execute 6th right shift 0100 1001 0000 0100 0 Execute 7th right shift 0010 0100 1000 0010 0 Execute 8th right shift 0001 0010 0100 0001 0 CRC Result 0001 0010 0100 0001 12h 41h Note: The byte 41h is sent first(even if it is the LSB), then12h is sent.

    CRC xor BYTE = CRC

    n = 0

    CRC right shift

    carry over

    CRC xor POLY = CRC

    n = n + 1

    next BYTE

    end message

    End

    n > 7

    Hex FFFF = CRC

    no

    no

    yes

    yes

  • Doc: AD507921.doc 28/04/2009 p. 7 / 21

    TABELLA 2: TABLE 2: MISURE FORNITE DAL PROTOCOLLO DI COMUNICAZIONE MEASURES SUPPLIED BY SERIAL COMMUNICATION PROTOCOL (Utilizzabili con funzione 04) (To be used with function 04)

    INDIRIZZO ADDRESS

    WORDS MISURA MEASURE UNITA’ UNIT

    FORMATO FORMAT

    02h 2 Tensione di fase rete L1 Mains phase voltage L1 V Unsigned long

    04h 2 Tensione di fase rete L2 Mains phase voltage L2 V Unsigned long

    06h 2 Tensione di fase rete L3 Mains phase voltage L3 V Unsigned long

    08h 2 Tensione di linea rete L1-L2 Mains phase to phase voltage L1-L2 V Unsigned long

    0Ah 2 Tensione di linea rete L2-L3 Mains phase to phase voltage L2-L3 V Unsigned long

    0Ch 2 Tensione di linea rete L3-L1 Mains phase to phase voltage L3-L1 V Unsigned long

    0Eh 2 Tensione di fase generatore L1 Generator phase voltage L1 V Unsigned long

    10h 2 Tensione di fase generatore L2 Generator phase voltage L2 V Unsigned long

    12h 2 Tensione di fase generatore L3 Generator phase voltage L3 V Unsigned long

    14h 2 Tensione di linea generatore L1-L2 Generator phase to phase voltage L1-L2 V Unsigned long

    16h 2 Tensione di linea generatore L2-L3 Generator phase to phase voltage L2-L3 V Unsigned long

    18h 2 Tensione di linea generatore L3-L1 Generator phase to phase voltage L3-L1 V Unsigned long

    1Ah 2 Corrente L1 Current L1 A Unsigned long

    1Ch 2 Corrente L2 Current L2 A Unsigned long

    1Eh 2 Corrente L3 Current L3 A Unsigned long

    20h 2 Potenza attiva rete L1 Mains active power L1 W Unsigned long

    22h 2 Potenza attiva rete L2 Mains active power L2 W Unsigned long

    24h 2 Potenza attiva rete L3 Mains active power L3 W Unsigned long

    26h 2 Potenza reattiva rete L1 Mains reactive power L1 Var Unsigned long 28h 2 Potenza reattiva rete L2 Mains reactive power L2 Var Unsigned long 2Ah 2 Potenza reattiva rete L3 Mains reactive power L3 Var Unsigned long 2Ch 2 Potenza apparente rete L1 Mains apparent power L1 VA Unsigned long

    2Eh 2 Potenza apparente rete L2 Mains apparent power L2 VA Unsigned long

    30h 2 Potenza apparente rete L3 Mains apparent power L3 VA Unsigned long

    32h 2 Potenza attiva generatore L1 Generator active power L1 W Unsigned long

    34h 2 Potenza attiva generatore L2 Generator active power L2 W Unsigned long

    36h 2 Potenza attiva generatore L3 Generator active power L3 W Unsigned long

    38h 2 Potenza reattiva generatore L1 Generator reactive power L1 Var Unsigned long 3Ah 2 Potenza reattiva generatore L2 Generator reactive power L2 Var Unsigned long 3Ch 2 Potenza reattiva generatore L3 Generator reactive power L3 Var Unsigned long 3Eh 2 Potenza apparente generatore L1 Generator apparent power L1 VA Unsigned long

    40h 2 Potenza apparente generatore L2 Generator apparent power L2 VA Unsigned long

    42h 2 Potenza apparente generatore L3 Generator apparent power L3 VA Unsigned long

    44h 2 Potenza attiva totale di rete Mains total active power W Unsigned long

    46h 2 Potenza reattiva totale di rete Mains total reactive power Var Unsigned long

    48h 2 Potenza apparente totale di rete Mains total apparent power VA Unsigned long

    4Ah 2 Potenza attiva totale di generatore Generator total active power W Unsigned long

    4Ch 2 Potenza reattiva totale di generatore Generator total reactive power Var Unsigned long

    4Eh 2 Potenza apparente totale di generatore Generator total apparent power VA Unsigned long

    50h 2 Fattore di potenza rete L1 Mains power factor L1 Unsigned long

    52h 2 Fattore di potenza rete L2 Mains power factor L2 Unsigned long

    54h 2 Fattore di potenza rete L3 Mains power factor L3 Unsigned long

    56h 2 Fattore di potenza totale rete Mains total power factor Unsigned long

    58h 2 Fattore di potenza generatore L1 Generator power factor L1 Unsigned long

    5Ah 2 Fattore di potenza generatore L2 Generator power factor L2 Unsigned long

    5Ch 2 Fattore di potenza generatore L3 Generator power factor L3 Unsigned long

    5Eh 2 Fattore di potenza totale generatore Generator total power factor Unsigned long

    60h 2 Energia attiva rete Mains total active energy Kwh*10 Unsigned long

    62h 2 Energia reattiva rete Mains total reactive power Kvarh*10 Unsigned long

    64h 2 Energia attiva generatore Generator total active energy Kwh*10 Unsigned long

    66h 2 Energia reattiva generatore Generator total reactive energy Kvarh*10 Unsigned long

    68h 2 Frequenza di rete Mains frequency Hz*10 Unsigned long

    6Ah 2 Frequenza di generatore Generator frequency Hz*10 Unsigned long

  • Doc: AD507921.doc 28/04/2009 p. 8 / 21

    6Ch 2 Velocità W Speed W Rpm/min Unsigned long

    6Eh 2 Velocità calcolata della frequenza generatore Speed calculated from generator frequency Rpm/min Unsigned long

    70h 2 Velocità Pick-UP Sensor Speed Pick-UP Rpm/min Unsigned long

    72h 2 Temperatura Temperature °C o F Unsigned long

    74h 2 Pressione Pressure Bar o psi * 100 Unsigned long

    76h 2 Carburante Fuel % Unsigned long

    78h 2 Batteria Battery V Unsigned long

    7Ah 2 Ore lavoro motore (da rev. 30) Engine working hours (rev. 30 onwards) sec Unsigned long

    7Ch 2 Numero tale avviamenti (da rev. 30) Total cranks (rev. 30 onwards) n. Unsigned long

    7Eh 2 Numero di avviamenti corretti (da rev. 30) Good cranks (rev. 30 onwards) n. Unsigned long

    100h 2 Contatore dei primi 255 eventi memorizzati (da rev. 37)

    Counter of the first 255 stored events (rev. 37 onwards)

    n. Unsigned long

    102h 2 Contatore totale degli eventi (da rev. 37) Total counter of the events (rev. 37 onwards) n. Unsigned long

    TABELLA 3: TABLE 3: BIT DI STATO STATUS BITS (Utilizzabili con funzione 04) (To be used with function 04)

    INDIRIZZO ADDRESS

    WORDS MISURA MEASURE UNITA’ UNIT

    FORMATO FORMAT

    160h 2 Stato bits di errore � Error bits status � (bit) Unsigned long

    162h 2 Stato bits di errore � Error bits status � (bit) Unsigned long

    170h 2 Uscite standard + espansioni � Standard output + expansion � (bit) Unsigned long

    180h 2 Ingressi standard + espansioni (tutte programmabili) �

    Standard input + expansion (all programmable) �

    (bit) Unsigned long

    190h 2 Status � Status � (bit) Unsigned long

    1A0h 2 Status � (da rev. 39) Status � (rev. 39 onwards) (bit) Unsigned long

    � Leggendo la word all’indirizzo 160h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 160h will return 32 bits with the following meaning:

    Bit Codice Allarme Code Alarm

    0 A01 Preallarme temperatura motore (sensore analogico) A01 Engine temperature warning (analog sensor)

    1 A02 Alta temperatura motore (sensore analogico) A02 High engine temperature (analog sensor)

    2 A03 Guasto sensore analogico temperatura A03 Temperature analog sensor fault

    3 A04 Alta temperatura motore (sensore digitale) A04 High engine temperature (digital sensor)

    4 A05 Preallarme pressione olio (sensore analogico) A05 Oil pressure warning (analog sensor)

    5 A06 Bassa pressione olio (sensore analogico) A06 Low oil pressure (analog sensor)

    6 A07 Guasto sensore analogico pressione A07 Pressure analog sensor fault

    7 A08 Bassa pressione olio (sensore digitale) A08 Low oil pressure (digital sensor)

    8 A09 Guasto sensore digitale pressione A09 Pressure digital sensor fault

    9 A10 Preallarme livello carburante (sensore analogico) A10 Fuel level warning (analog sensor)

    10 A11 Basso livello carburante (sensore analogico) A11 Low fuel level (analog sensor)

    11 A12 Guasto sensore analogico livello A12 Level analog sensor fault

    12 A13 Basso livello carburante (sensore digitale) A13 Low fuel level (digital sensor)

    13 A14 Tensione batteria alta A14 High battery voltage

    14 A15 Tensione batteria bassa A15 Low battery voltage

    15 A16 Batteria inefficiente A16 Inefficient battery

    16 A17 Avaria alternatore carica batteria A17 Charger alternator failure

    17 A18 Avaria segnale “W” A18 “W” signal failure

    18 A19 Bassa velocità motore “W” A19 Low engine “W” speed

    19 A20 Alta velocità motore “W” A20 High engine “W” speed

    20 A21 Mancato avviamento A21 Starting failure

    21 A22 Arresto di emergenza A22 Emergency stop

    22 A23 Arresto inaspettato A23 Unexpected stop

    23 A24 Mancato arresto A24 Engine stop failure

    24 A25 Bassa frequenza generatore A25 Low generator frequency

    25 A26 Alta frequenza generatore A26 High generator frequency

    26 A27 Bassa tensione generatore A27 Low generator voltage

    27 A28 Alta tensione generatore A28 High generator voltage

    28 A29 Asimmetria generatore A29 Generator asymmetry

    29 A30 Corto circuito generatore A30 Generator short-circuit

    30 A31 Sovraccarico generatore A31 Generator overload

    31 A32 Intervento protezione esterna generatore A32 External generator protection tripping

  • Doc: AD507921.doc 28/04/2009 p. 9 / 21

    � Leggendo la word all’indirizzo 162h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 162h will return 32 bits with the following meaning: Bit Codice Allarme Code Alarm

    0 A33 Errata sequenza fasi generatore A33 Incorrect generator phase sequence

    1 A34 Errata sequenza fasi rete A34 Incorrect mains phase sequence

    2 A35 Errata impostazione frequenza di sistema A35 Wrong system frequency setting

    3 A36 Anomalia contattore generatore A36 Generator contactor failure

    4 A37 Anomalia contattore rete A37 Mains contactor failure

    5 A38 Richiesta manutenzione A38 Maintenance requested

    6 A39 Errore di sistema A39 System error

    7 A40 Serbatoio travaso vuoto A40 Fuel transfer empty

    8 A41 Serbatoio travaso troppo pieno A41 Fuel transfer too full

    9 A42 Ore di noleggio esaurite A42 Rent hours exhausted

    10 A43 Basso livello liquido radiatore (da rev. 15) A43 Low radiator liquid level (rev. 15 onwards)

    11 A44 Interruttore chiuso (da rev. 15) A44 Circuit breaker closet (rev. 15 onwards)

    12 A45 Interruttore aperto (da rev. 15) A45 Circuit breaker open (rev. 15 onwards)

    13 A46 Bassa temperatura motore (sensore analogico) (da rev. 36) A46 Low engine temperature (analog sensor) (rev. 36 onwards)

    14 A47 Allarme da carica batteria (da rev. 36) A47 Battery charger alarm (rev. 36 onwards)

    15 A48 Allarme lampada rossa da CAbus (da rev. 36) A48 Red light alarm from CANbus (rev. 36 onwards)

    16 A49 Allarme lampada gialla da CAN bus (da rev. 36) A49 Amber light alarm from CANbus (rev. 36 onwards)

    17 A50 Allarme CANbus scollegato (da rev. 36) A50 CANbus disconnected alarm (rev. 36 onwards)

    18 U01 Allarme utente 1 U01 User’s alarm 1

    19 U02 Allarme utente 2 U02 User’s alarm 2

    20 U03 Allarme utente 3 U03 User’s alarm 3

    21 U04 Allarme utente 4 U04 User’s alarm 4

    22 U05 Allarme utente 5 (da rev. 18) U05 User’s alarm 5 (rev. 18 onwards)

    23 U06 Allarme utente 6 (da rev. 18) U06 User’s alarm 6 (rev. 18 onwards)

    24 U07 Allarme utente 7 (da rev. 18) U07 User’s alarm 7 (rev. 18 onwards)

    25 U08 Allarme utente 8 (da rev. 18) U08 User’s alarm 8 (rev. 18 onwards)

    26-31 Bit liberi 21-31 Free bits

    � Leggendo la word all’indirizzo 170h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 170h will return 32 bits with the following meaning:

    Bit Significato Meaning

    0 Teleruttore rete Mains contactor

    1 Teleruttore generatore Generator contactor

    2 Uscita programmabile 1 Programmable output 1

    3 Uscita programmabile 2 Programmable output 2

    4 Uscita programmabile 3 Programmable output 3

    5 Motore Start Engine Start

    6 Uscita programmabile 4 Programmable output 4

    7 Uscita elettrovalvola carburante Fuel valve output

    8 Uscita programmabile 1 espansione Expansion Programmable output 1

    9 Uscita programmabile 2 espansione Expansion Programmable output 2

    10 Uscita programmabile 3 espansione Expansion Programmable output 3

    11 Uscita programmabile 4 espansione Expansion Programmable output 4

    12 Uscita programmabile 5 espansione Expansion Programmable output 5

    13 Uscita programmabile 6 espansione Expansion Programmable output 6

    14 Uscita programmabile 7 espansione Expansion Programmable output 7

    15 Uscita programmabile 8 espansione Expansion Programmable output 8

    16 Uscita programmabile 9 espansione Expansion Programmable output 9

    17 Uscita programmabile 10 espansione Expansion Programmable output 10

    18 Uscita programmabile 11 espansione Expansion Programmable output 11

    19 Uscita programmabile 12 espansione Expansion Programmable output 12

    20..31 Bit liberi Free bits

  • Doc: AD507921.doc 28/04/2009 p. 10 / 21

    � Leggendo la word all’indirizzo 180h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 180h will return 32 bits with the following meaning

    � Leggendo la word all’indirizzo 190h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 190h will return 32 bits with the following meaning:

    Bit Significato Meaning

    0 Allarme Alarm

    1 Motore Start Engine Start

    2 Motore Stop Engine Stop

    3 Raffreddamento Cooling

    4 Test Test

    5 Start esterno External Start

    6 Stop esterno External Stop

    7 Start per soglia kw Start kw trip

    8 Start EJP Start EJP

    9 Start SCR Start SCR

    10..31 Bit liberi Free bits

    � Leggendo la word all’indirizzo 1A0h vengono restituiti 32 bit con significato come da tabella: Reading the word starting at address 1A0h will return 32 bits with the following meaning:

    Bit Significato Meaning

    0 Modalità Reset Reset mode

    1 Modalità Manuale Manual mode

    2 Modalità Automatico Automatic mode

    3 Modalità Test Test mode

    4 Presenza Rete Main voltage

    5 Presenza Generatore Generator voltage

    6 Motore Avviato Motor Running

    7 Teleruttore Rete Breaker Main

    8 Teleruttore Generatore Breaker Generator

    9 Allarme Attivo Alarm on

    10..31 Bit liberi Free bits

    Bit Significato Meaning

    0 Ingresso programmabile 1 Programmable input 1

    1 Ingresso programmabile 2 Programmable input 2

    2 Ingresso programmabile 3 Programmable input 3

    3 Ingresso programmabile 4 Programmable input 4

    4 Ingresso programmabile 5 Programmable input 5

    5 Ingresso programmabile 6 Programmable input 6

    6 Ingresso programmabile 7 Programmable input 7

    7 Ingresso programmabile 8 Programmable input 8

    8 Ingresso programmabile 9 Programmable input 9

    9 Ingresso programmabile 10 Programmable input 10

    10 Ingresso programmabile 11 Programmable input 11

    11 Ingresso programmabile 12 Programmable input 12

    12 Ingresso programmabile espansione 1 Expansion programmable input 1

    13 Ingresso programmabile espansione 2 Expansion programmable input 2

    14 Ingresso programmabile espansione 3 Expansion programmable input 3

    15 Ingresso programmabile espansione 4 Expansion programmable input 4

    16 Ingresso programmabile espansione 5 Expansion programmable input 5

    17 Ingresso programmabile espansione 6 Expansion programmable input 6

    18 Ingresso programmabile espansione 7 Expansion programmable input 7

    19 Ingresso programmabile espansione 8 Expansion programmable input 8

    20 Ingresso programmabile espansione 9 Expansion programmable input 9

    21 Ingresso programmabile espansione 10 Expansion programmable input 10

    22 Ingresso programmabile espansione 11 Expansion programmable input 11

    23 Ingresso programmabile espansione 12 Expansion programmable input 12

    24 Ingresso programmabile espansione 13 Expansion programmable input 13

    25 Ingresso programmabile espansione 14 Expansion programmable input 14

    26-31 liberi free

  • Doc: AD507921.doc 28/04/2009 p. 11 / 21

    TABELLA 4: TABLE 4: COMANDI COMMANDS (Utilizzabili con funzione 06) (To be used with function 06)

    INDIRIZZO ADDRESS

    WORDS FUNZIONE FUNCTION FORMATO FORMAT

    1000h 1 Modalità OFF � Operating mode OFF � Unsigned integer

    1001h 1 Modalità MAN � Operating mode MAN � Unsigned integer

    1002h 1 Modalità AUT � Operating mode AUT � Unsigned integer

    1003h 1 Modalità TEST � Operating mode TEST � Unsigned integer

    1004h 1 Chiusura / Apertura teleruttore rete � Opening / Closing mains contactor � Unsigned integer

    1005h 1 Chiusura / Apertura teleruttore generatore � Opening / Closing generator contactor � Unsigned integer

    1006h 1 Start motore � Engine start � Unsigned integer

    1007h 1 Stop motore � Engine stop � Unsigned integer

    1100h 1 Scrittura tutta memoria eeprom � Write all memory eeprom � Unsigned integer

    1200h 1 Menu comandi � Command menu � Unsigned integer

    1300h 1 Salva RTC (Real time clock) Save RTC (Real time clock) Unsigned integer

    � Per eseguire il comando e’ necessario usare la funzione 06 Preset single register e scrivere il valore 0001 hex all’indirizzo specificato. � To execute the command, the user must use the function 06 Preset single register, writing value 0001Hex to the address specified.. � Per eseguire una delle funzioni disponibili nel menu comandi e’ necessario scrivere il valore 00xx Hex all’indirizzo 1200, dove xx rappresenta il numero della voce del menu comandi. Ad esempio per eseguire il comando C02 Reset ore manutenzione sara’ necessario scrivere il valore 0002 Hex all’indirizzo 1200 Hex utilizzando la funzione Modbus® 06. Per la lista delle funzioni disponibili nel menu comandi fare riferimento al manuale operativo.

    � To execute one of the functions available in the Command menu, it is necessary to write value 00xxHex to address 1200 Hex, where xx represents the number of the command menu item. For instance, to execute the command C.02 Maintenance hour reset , the user must write value 0002 hex to the address 1200 hex using Modbus® function 06. See the operating manual for the complete list of the command menu functions.

    IMPOSTAZIONE PARAMETRI Tramite il protocollo Modbus® e’ possibile accedere ai parametri dei menu base, esteso e funzioni. Nelle seguenti tabelle e’ riportato il range di impostazione in formato numerico. Per interpretare correttamente la corrispondenza fra valore numerico e funzione selezionata e/o unita’ di misura, fare riferimento al manuale operativo dell’RGK60 . I seguenti parametri sono sempre disponibili in lettura, mentre possono essere modificati solo quando lo strumento è in modalità OFF.

    PARAMETER SETTING Using the Modbus® protocol it is possible to access the base, advanced and function menu parameters. In the following tables it is reported the numerical range for each parameter. To correctly understand the correspondence between the numeric value and the selected function and/or the unit of measure, please see the RGK60 operating manual. The following parameters can be read at any time, while the write-access is possible only when the RGK60 is OFF mode.

    PARAMETRI MENU UTILITA’ UTILITY PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATO FORMAT

    2002h 1 P0101 Lingue English/Italiano/

    Francais/Pourtugues/Espanol

    P0101 Languages Unsigned integer

    2003h 1 P0102 Anno 1989-2089 P0102 Year Unsigned integer

    2004h 1 P0103 Mese 1-12 P0103 Month Unsigned integer

    2005h 1 P0104 Giorno Mese 1-31 P0104 Day of the month Unsigned integer

    2006h 1 P0105 Giorno Settimana 1-7 P0105 Day of the week Unsigned integer

    2007h 1 P0106 Ora 0-23 P0106 Hour Unsigned integer

    2008h 1 P0107 Minuti 0-59 P0107 Minutes Unsigned integer

    2009h 1 P0108 Secondi 0-59 P0108 Seconds Unsigned integer

    200Ah 1 P0109 Set orologio all’alimentazione OFF/ON P0109 Clock setting at power-up Unsigned integer

    200Bh 1 P0110 Ritorno pagina principale (sec) OFF/5-999 P0110 Default page return (sec) Unsigned integer

    200Ch 1 P0111 Contrasto display (%) 0-100 P0111 Display contrast (%) Unsigned integer

    200Dh 1 P0112 Retroilluminazione dispaly (%) 0-100 P0112 Display Backlight (%) Unsigned integer

    200Eh 1 P0113 Ritardo spegnimento (min) retroilluminazione

    OFF/1-900 P0113 Delay backlight off (min) Unsigned integer

    PARAMETRI MENU GENERALI GENERAL PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2102h 1 P0201 Rapporto TA 1.0-2000.0 P0201 CT ratio Unsigned integer

    2103h 1 P0202 Rapporto TV 1.0-500.0 P0202 VT ratio Unsigned integer

    2104h 1 P0203 Tipo di collegamento 3N-3-2N-1N P0203 Wiring configuration Unsigned integer

    2105h 1 P0204 Tensione nominale (V) 100-50000 P0204 Rated voltage (V) Unsigned integer

    2106h 1 P0205 Frequenza (Hz) 50/60 P0205 Frequency (Hz) Unsigned integer

  • Doc: AD507921.doc 28/04/2009 p. 12 / 21

    2107h 1 P0206 Rapporto RPM / “W” 0.001-50.000 P0206 RPM / “W” ratio Unsigned integer

    2108h 1 P0207 Giri nominale Motore (RPM) 750-3600 P0207 Rated engine speed (RPM) Unsigned integer

    2109h 1 P0208 Scelta unità di misura °C/bar-°F/psi P0208 Unit of measure Unsigned integer

    210Ah 1 P0209 Interbloccco rete/generatore (sec) 0.0-60.0 P0209 MAINS/GEN interlock (sec) Unsigned integer

    210Bh 1 P0210 Ritardo ON/OFF rete/generatore (sec)

    1-60 P0210 M/G feedback delay (sec) Unsigned integer

    210Ch 1 P0211 Modo OFF/RESET all’alimentazione OFF/ON P0211 RESET mode at power-up Unsigned integer

    210Dh 1 P0212 Tempo sirena (sec) OFF/1-60 P0212 Siren time (sec) Unsigned integer

    210Eh 1 P0213 Sirena prima di avviamento (sec) OFF/1-60 P0213 Siren before starting (sec) Unsigned integer

    210Fh 1 P0214 Sirena PC in linea (sec OFF/1-60 P0214 Siren PC on line (sec) Unsigned integer

    2110h 1 P0215 Capacità serbatoio OFF/1-30000 P0215 Fuel capacity Unsigned integer

    2111h 1 P0216 Controllo tensione LL/LN/LL-N P0216 Voltage control Unsigned integer

    2112h 1 P0217 Apertura interruttore motorizzato (sec)

    0-600 P0217 Motorised circuit breaker opening (sec)

    Unsigned integer

    2113h 1 P0218 Chiusura interruttore motorizzato (sec)

    0-600 P0218 Motorised circuit breaker closing (sec)

    Unsigned integer

    2114h 1 P0219 Tempo integrazione Max Demand (min)

    OFF/1-60 P0219 Integration time Max Demand (min) Unsigned integer

    PARAMETRI MENU BATTERIA BATTERIA PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2202h 1 P0301 Tensione batteria (V) 1.0-2000.0 P0301 Battery voltage (V) Unsigned integer

    2203h 1 P0302 Limite tensione MAX (%) 1.0-500.0 P0302 MAX voltage limit (%) Unsigned integer

    2204h 1 P0303 Limite tensione MIN (%) 3N-3-2N-1N P0303 MIN voltage limit (%) Unsigned integer

    2205h 1 P0304 Ritardo tensione MIN/MAX (sec) 100-50000 P0304 MIN/MAX voltage delay (sec) Unsigned integer

    PARAMETRI MENU AVVIAMENTO MOTORE ENGINE START PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2302h 1 P0401 Tensione alternatore motore avviato (V)

    OFF/3-30 P0401 Alternator voltage engine started (V) Unsigned integer

    2303h 1 P0402 Tensione generatore motore avviato (%)

    OFF/10-100% P0402 Generator voltage engine started (%) Unsigned integer

    2304h 1 P0403 Frequenza generatore motore avviato (%)

    OFF/10-100% P0403 Generator frequency engine started (%)

    Unsigned integer

    2305h 1 P0404 Segnale “W” motore avviato (RPM) OFF/10-100% P0404 “W” signal engine started (RPM) Unsigned integer

    2306h 1 P0405 Preriscaldo candelette (sec) OFF/1-60 P0405 Glow-plugs preheating (sec) Unsigned integer

    2307h 1 P0406 Numero tentativi avviamento 1-10 P0406 Starting attempts number Unsigned integer

    2308h 1 P0407 Durata tentativo avv. (sec) 1-30 P0407 Attempts starting time (sec) Unsigned integer

    2309h 1 P0408 Pausa tentativi avviamento (sec) 1-30 P0408 Pause between starting (sec) Unsigned integer

    230Ah 1 P0409 Pausa avviamento interrotto e successivo (sec)

    OFF/1-20 P0409 Aborted starting & subsequent (sec) Unsigned integer

    230Bh 1 P0410 Tempo decelerazione (sec) OFF/1-180 P0410 Deceleration time (sec) Unsigned integer

    230Ch 1 P0411 Tempo raffreddamento (sec) 1-3600 P0411 Cooling time (sec) Unsigned integer

    230Dh 1 P0412 Tempo magnete arresto (sec) OFF/1-60 P0412 Stop magnet time (sec) Unsigned integer

    230Eh 1 P0413 Ritardo valvola gas (sec) OFF/1-10 P0413 Gas valve delay (sec) Unsigned integer

    230Fh 1 P0414 Tempo cicchetto (sec) OFF/1-10 P0414 Priming time (sec) Unsigned integer

    2310h 1 P0415 Tempo valvola aria (sec) OFF/1-10 P0415 Choke valve time (sec) Unsigned integer

    2311h 1 P0416 Limite stacco aria (%) 0-100 P0416 Choke OFF limit (%) Unsigned integer

    2312h 1 P0417 Tempo di preriscaldo valvola (sec)

    0-900 P0417 Valve preheating (sec) Unsigned integer

    2313h 1 P0418 Temperatura preriscaldo OFF/20-285 P0418 Preheating temperature Unsigned integer PARAMETRI MENU CONTROLLO MOTORE ENGINE CONTROL PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2402h 1 P0501 Scelta sensore pressione (1) P0501 Pressure sensor selection Unsigned integer

    2403h 1 P0502 Scelta sensore temperatura (1) P0502 Temperature sensor selection Unsigned integer

    2404h 1 P0503 Scelta sensore carburante (1) P0503 Fuel sensor selection Unsigned integer

    2405h 1 P0504 Preallarme pressione MIN 0.1-180.0 P0504 MIN pressure warning Unsigned integer

    2406h 1 P0505 Limite pressione MIN 0.1-180.0 P0505 MIN pressure limit Unsigned integer

    2407h 1 P0506 Preallarme temperatura MAX 40-285 P0506 MAX temperature warning Unsigned integer

    2408h 1 P0507 Limite temperatura MAX 40-285 P0507 MAX temperature limit Unsigned integer

    2409h 1 P0508 Preallarme carburante MIN (%) 0-100 P0508 MIN fuel warning (%) Unsigned integer

    240Ah 1 P0509 Livello carburante MIN (%) 0-100 P0509 MIN fuel level (%) Unsigned integer

    240Bh 1 P0510 Inibizione allarmi all’avviamento (sec) 1-30 P0510 Alarms inhibition at starting (sec) Unsigned integer

    240Ch 1 P0511 Limite velocità “W” MAX (%) 100-120 P0511 MAX “W” speed limit (%) Unsigned integer

    240Dh 1 P0512 Ritardo velocità “W” MAX (sec) 3-20 P0512 MAX “W” speed delay (sec) Unsigned integer

    240Eh 1 P0513 Limite velocità ”W” MIN (%) 80-100 P0513 MIN “W” speed limit (%) Unsigned integer

    240Fh 1 P0514 Ritardo velocità “W” MIN (sec) 0-600 P0514 MIN “W” speed delay (sec) Unsigned integer

    2410h 1 P0515 Ritardo A03 (min) OFF/1-60 P0515 Delay A03 (min) Unsigned integer

    2411h 1 P0516 Limite temperatura minima OFF/20-285 P0516 Low engine temperature Unsigned integer

    (1) Prima di impostare il tipo di sensore, verificare la curva di risposta mediante il software di set-up. (1) Before setting the type of sensor, it is advisable to check the curve characteristic by means of the set-up software

  • Doc: AD507921.doc 28/04/2009 p. 13 / 21

    PARAMETRI MENU CONTROLLO RETE MAINS CONTROL PARAM ETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2502h 1 P0601 Limite tensione MIN (%) 70-100 P0601 MIN voltage limit (%) Unsigned integer

    2503h 1 P0602 Ritardo tensione MIN (sec) 0-600 P0602 MIN voltage delay (sec) Unsigned integer

    2504h 1 P0603 Limite tensione MAX (%) 100-120 P0603 MAX voltage limit (%) Unsigned integer

    2505h 1 P0604 Ritardo tensione MAX (sec) 0-600 P0604 MAX voltage delay (sec) Unsigned integer

    2506h 1 P0605 Ritardo rete nei limiti (sec) 1-600 P0605 MAINS into limits delay(sec) Unsigned integer

    2507h 1 P0606 Isteresi limiti MIN/MAX (%) 0.0-5.0 P0606 MIN/MAX hysteresis limits (%) Unsigned integer

    2508h 1 P0607 Limite asimmetria MAX (%) 5-20 P0607 MAX asymmetry limit (%) Unsigned integer

    2509h 1 P0608 Ritardo asimmetria MAX (sec) 0-600 P0608 MAX asymmetry delay (sec) Unsigned integer

    250Ah 1 P0609 Limite frequenza MAX (%) 100-120/OFF P0609 MAX frequency limit (%) Unsigned integer

    250Bh 1 P0610 Limite frequenza MIN (%) OFF/80-100 P0610 MIN frequency limit (%) Unsigned integer

    250Ch 1 P0611 Ritardo frequenza MIN/MAX (sec) 0-600 P0611 MIN/MAX frequency delay (sec) Unsigned integer

    250Dh 1 P0612 Controllo RETE OFF/interno/esterno OFF/INT/EXT P0612 MAINS control OFF/internal/external) Unsigned integer

    250Eh 1 P0613 Controllo RETE in modo RESET/OFF

    OFF/ON/OFF+GLOB/ON+GLOB

    P0613 MAINS control in RESET/OFF mode Unsigned integer

    250Fh 1 P0614 Controllo RETE in modo MAN OFF/ON/OFF+G

    LOB/ON+GLOB P0614 MAINS control in MAN mode Unsigned integer

    PARAMETRI MENU CONTROLLO GENERATORE ENGINE CONTROL PARAMETERS MEN U (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2602h 1 P0701 Limite tensione MIN (%) 70-100 P0701 MIN voltage limit (%) Unsigned integer

    2603h 1 P0702 Ritardo tensione MIN (sec) 0-600 P0702 MIN voltage delay (sec) Unsigned integer

    2604h 1 P0703 Limite tensione MAX (%) 100-120 P0703 MAX voltage limit (%) Unsigned integer

    2605h 1 P0704 Ritardo tensione MAX (sec) 0-600 P0704 MAX voltage delay (sec) Unsigned integer

    2606h 1 P0705 Ritardo generatore nei limiti (sec) 0-600 P0705 Generator into limits delay (sec) Unsigned integer

    2607h 1 P0706 Isteresi limiti MIN/MAX(%) 0.0-5.0 P0706 MIN/MAX hysteresis limits (%) Unsigned integer

    2608h 1 P0707 Limite asimmetria MAX(%) 5-20 P0707 MAX asymmetry limit (%) Unsigned integer

    2609h 1 P0708 Ritardo asimmetria MAX (sec) 0-600 P0708 MAX asymmetry delay (sec) Unsigned integer

    260Ah 1 P0709 Limite frequenza MAX (%) 100-120/OFF P0709 MAX frequency limit (%) Unsigned integer

    260Bh 1 P0710 Ritardo frequenza MAX (sec) 0-200 P0710 MAX frequency delay (sec) Unsigned integer

    260Ch 1 P0711 Limite frequenza MIN (%) OFF/80-100 P0711 MIN frequency limit (%) Unsigned integer

    260Dh 1 P0712 Ritardo frequenza MIN (sec) 0-600 P0712 MIN frequency delay (sec) Unsigned integer

    260Eh 1 P0713 Controllo gen. OFF/interno/esterno OFF/INT/EXT P0713 Gen. Control (OFF/internal/external) Unsigned integer

    260Fh 1 P0714 Ritardo allarmi A27 A28 (sec) 5-240 P0714 A27 A28 alarms delay (sec) Unsigned integer PARAMETRI MENU PROTEZIONE GENERATORE ENGINE PROTECTION PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2702h 1 P0801 Corrente nominale generatore (A) OFF/5-10000 P0801 Rated generator current (A) Unsigned integer

    2703h 1 P0802 Limite corrente max. (%) 100-500/OFF P0802 MAX current limit (%) Unsigned integer

    2704h 1 P0803 Ritardo corrente max (sec) 0.0-60.0 P0803 MAX current delay (sec) Unsigned integer

    2705h 1 P0804 Scelta curva di protezione (1) P0804 Thermal protection curve selection Unsigned integer

    2706h 1 P0805 Tempo di ripristino protezione (sec) 0-5000 P0805 Generator protection reset time(sec) Unsigned integer

    (1) Prima di impostare la classe di protezione, verificare la caratteristica d’intervento mediante il software di set-up. Attenzione!! Il TA esterno deve essere scelto in funzione della corrente massima definita nel parametr1 P0802 e P0804. 1) Before setting the protection class, it is advisable to check the trip characteristic by means of the set-up software. Caution!! The external CT must be chosen on the basis of the maximum current defined by the parameters P0802 and P0804. PARAMETRI MENU TEST E MANUTENZIONE TEST E MAINTENANCE PARA METERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2802h 1 P0901 Giorno inizio TEST 1-7 P0901 TEST beginning day Unsigned integer

    2803h 1 P0902 Ora inizio TEST (h) 00-23 P0902 TEST beginning hour (h) Unsigned integer

    2804h 1 P0903 Minuti inizio test (min) 00-59 P0903 TEST beginning Minutes (min) Unsigned integer

    2805h 1 P0904 Intervallo tra i TEST (giorni) 1-30 P0904 Interval between TESTS (days) Unsigned integer

    2806h 1 P0905 Durata TEST (min) OFF/1-60 P0905 TEST duration (min) Unsigned integer

    2807h 1 P0906 Test con carico OFF/ON P0906 Test with load Unsigned integer

    2808h 1 P0907 Intervallo di manutenzione (h) OFF/1-999 P0907 Maintenance interval (h) Unsigned integer

    2809h 1 P0908 Test automatico con stop esterno OFF/ON P0908 Automatic test with external stop Unsigned integer

    PARAMETRI MENU PORTA DI COMUNICAZIONE COMUNICATION PORT PARAMETER S MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2902h 1 P1001 Indirizzo porta seriale 1-99 P1001 Serial port address Unsigned integer

    2903h 1 P1002 Baud-Rate RS232 OFF/1200-

    38400 P1002 RS-232 baud rate Unsigned integer

  • Doc: AD507921.doc 28/04/2009 p. 14 / 21

    2904h 1 P1003 Baud-Rate RS485 OFF/1200-

    38400 P1003 RS-485 baud rate Unsigned integer

    2905h 1 P1004 Canale modem RS232/RS485 P1004 Modem channel Unsigned integer

    2906h 1 P1005 Parità 0=no 1=pari

    2=dispari P1005 Parity Unsigned integer

    2907h 1 P1006 Protocollo Rs2332 0=Lovato

    1=Modbus RTU P1006 Protocol Rs232 Unsigned integer

    2908h 1 P1007 Protocollo Rs2485 0=Lovato

    1=Modbus RTU P1007 Protocol Rs485 Unsigned integer

    PARAMETRI MENU VARIE MISCELLANEOUS PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2A02h 1 P1101 Start su limite max OFF/ON P1101 Max engine power starting Unsigned integer

    2A03h 1 P1102 Limite max avviamento (kW) 0-9999 P1102 Engine start threshold (kW) Unsigned integer

    2A04h 1 P1103 Ritardo limite max avviamento (sec) 0-999 P1103 Engine start threshold delay (sec) Unsigned integer

    2A05h 1 P1104 Limite minimo arresto (kW) 0-9999 P1104 Engine stop threshold (kW) Unsigned integer

    2A06h 1 P1105 Ritardo limite minimo arresto (sec) 0-999 P1105 Engine stop threshold delay (sec) Unsigned integer

    2A07h 1 P1106 Carico fittizio OFF/ON P1106 Dummy load Unsigned integer

    2A08h 1 P1107 Carico ON (kW) 0-9999 P1107 Dummy load ON (kW) Unsigned integer

    2A09h 1 P1108 Ritardo carico ON (sec) 0-999 P1108 Dummy load ON delay (sec Unsigned integer

    2A0Ah 1 P1109 Carico OFF (kW) 0-9999 P1109 Dummy load OFF (kW) Unsigned integer

    2A0Bh 1 P1110 Ritardo carico OFF (sec) 0-999 P1110 Dummy load OFF delay (sec) Unsigned integer

    2A0Ch 1 P1111 Ore di noleggio (h) 0-60000 P1111 Rent hours (h) Unsigned integer

    2A0Dh 1 P1112 Scelta modo Normal/EJP/

    EJP-T/SCR P1112 Mode select Unsigned integer

    2A0Eh 1 P1113 Ritardo start motore (EJP) 0-99 P1113 Start motor delay (EJP) Unsigned integer

    2A0Fh 1 P1114 Ritardo commutazione 0-30 P1114 Changeover delay Unsigned integer

    2A10h 1 P1115 Blocco ricommutazione OFF/ON P1115 Changeover block Unsigned integer

    2A11h 1 P1116 Tempo di ciclo on dummy load (min) OFF/1-600 P1116 Dummy load cycle duration ON

    (min) Unsigned integer

    2A12h 1 P1117 Tempo di ciclo off dummy load (min) OFF/1-600 P1117 Dummy load cycle duration OFF

    (min) Unsigned integer

    2A13h 1 P1118 Carico fittizio ON step 2 (kW) 0-9999 P1118 Dummy load ON step 2 (kW) Unsigned integer

    2A14h 1 P1119 Carico fittizio OFF step 2 (kW) 0-9999 P1119 Dummy load OFF step 2 (kW) Unsigned integer

    2A15h 1 P1120 Carico fittizio ON step 3 (kW) 0-9999 P1120 Dummy load ON step 3 (kW) Unsigned integer

    2A16h 1 P1121 Carico fittizio OFF step 3 (kW) 0-9999 P1121 Dummy load OFF step 3 (kW) Unsigned integer

  • Doc: AD507921.doc 28/04/2009 p. 15 / 21

    PARAMETRI MENU INPUT PROGRAMMABILI INPUT PROGRAMMABLE PARAM ETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    (1) Vedi l’elenco delle funzioni disponibili nella tabella “Ingressi programmabili”. (1) See the list of the available functions in the “Programmable inputs” table. PARAMETRI MENU USCITE PROGRAMMABILI OUTPUT PROGRAMMABLE PARAME TERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2C02h 1 P1301 Uscita morsetto 5.3-5.4-5.5 (Funzione..)

    (1) P1301 Output terminal 5.3-5.4-5.5 (Function..)

    Unsigned integer

    2C03h 1 P1302 Uscita morsetto 6.2 (Funzione..)

    (1) P1302 Output terminal 6.2 (Function..)

    Unsigned integer

    2C04h 1 P1303 Uscita morsetto 6.3 (Funzione..)

    (1) P1303 Output terminal 6.3 (Function..)

    Unsigned integer

    2C05h 1 P1304 Uscita morsetto 6.5 (Funzione..)

    (1) P1304 Output terminal 6.5 Function..)

    Unsigned integer

    (1) Vedi l’elenco delle funzioni disponibili nella tabella “Uscite programmabili (1) See the list of the available functions in the “Programmable outputs” table.

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2B02h 1 P1201 Ingresso morsetto 8.1 (1) P1201 Input terminal 8.1 Unsigned integer

    2B03h 1 8.1 Tipo contatto NO/NC 8.1 Contact type Unsigned integer

    2B04h 1 8.1 Ritardo chiusura (sec) 0.0-6000.0 8.1 Opening delay (sec) Unsigned integer

    2B05h 1 8.1 Ritardo apertura (sec) 0.0-6000.0 8.1 Closing delay (sec) Unsigned integer

    2B06h 1 P1202 Ingresso morsetto 8.2 (1) P1202 Input terminal 8.2 Unsigned integer

    2B07h 1 8.2 Tipo contatto NO/NC 8.2 Contact type Unsigned integer

    2B08h 1 8.2 Ritardo chiusura (sec) 0.0-6000.0 8.2 Opening delay (sec) Unsigned integer

    2B09h 1 8.2 Ritardo apertura (sec) 0.0-6000.0 8.2 Closing delay (sec) Unsigned integer

    2B0Ah 1 P1203 Ingresso morsetto 8.3 (1) P1203 Input terminal 8.3 Unsigned integer

    2B0Bh 1 8.3 Tipo contatto NO/NC 8.3 Contact type Unsigned integer

    2B0Ch 1 8.3 Ritardo chiusura (sec) 0.0-6000.0 8.3 Opening delay (sec) Unsigned integer

    2B0Dh 1 8.3 Ritardo apertura (sec) 0.0-6000.0 8.3 Closing delay (sec) Unsigned integer

    2B0Eh 1 P1204 Ingresso morsetto 8.4 (1) P1204 Input terminal 8.4 Unsigned integer

    2B0Fh 1 8.4 Tipo contatto NO/NC 8.4 Contact type Unsigned integer

    2B10h 1 8.4 Ritardo chiusura (sec) 0.0-6000.0 8.4 Closing delay (sec) Unsigned integer

    2B11h 1 8.4 Ritardo apertura (sec) 0.0-6000.0 8.4 Opening delay (sec) Unsigned integer

    2B12h 1 P1205 Ingresso morsetto 8.5 (1) P1205 Input terminal 8.5 Unsigned integer

    2B13h 1 8.5 Tipo contatto NO/NC 8.5 Contact type Unsigned integer

    2B14h 1 8.5 Ritardo chiusura (sec) 0.0-6000.0 8.5 Closing delay (sec) Unsigned integer

    2B15h 1 8.5 Ritardo apertura (sec) 0.0-6000.0 8.5 Opening delay (sec) Unsigned integer

    2B16h 1 P1206 Ingresso morsetto 8.6 (1) P1206 Input terminal 8.6 Unsigned integer

    2B17h 1 8.6 Tipo contatto NO/NC 8.6 Contact type Unsigned integer

    2B18h 1 8.6 Ritardo chiusura (sec) 0.0-6000.0 8.6 Closing delay (sec) Unsigned integer

    2B19h 1 8.6 Ritardo apertura (sec) 0.0-6000.0 8.6 Opening delay (sec) Unsigned integer

    2B1Ah 1 P1207 Ingresso morsetto 8.7 (1) P1207 Input terminal 8.7 Unsigned integer

    2B1Bh 1 8.7 Tipo contatto NO/NC 8.7 Contact type Unsigned integer

    2B1Ch 1 8.7 Ritardo chiusura (sec) 0.0-6000.0 8.7 Closing delay (sec) Unsigned integer

    2B1Dh 1 8.7 Ritardo apertura (sec) 0.0-6000.0 8.7 Opening delay (sec) Unsigned integer

    2B1Eh 1 P1208 Ingresso morsetto 8.8 (1) P1208 Input terminal 8.8 Unsigned integer

    2B1Fh 1 8.8 Tipo contatto NO/NC 8.8 Contact type Unsigned integer

    2B20h 1 8.8 Ritardo chiusura (sec) 0.0-6000.0 8.8 Closing delay (sec) Unsigned integer

    2B21h 1 8.8 Ritardo apertura (sec) 0.0-6000.0 8.8 Opening delay (sec) Unsigned integer

    2B22h 1 P1209 Ingresso morsetto 8.9 (1) P1209 Input terminal 8.9 Unsigned integer

    2B23h 1 8.9 Tipo contatto NO/NC 8.9 Contact type Unsigned integer

    2B24h 1 8.9 Ritardo chiusura (sec) 0.0-6000.0 8.9 Closing delay (sec) Unsigned integer

    2B25h 1 8.9 Ritardo apertura (sec) 0.0-6000.0 8.9 Opening delay (sec) Unsigned integer

    2B26h 1 P1210 Ingresso morsetto 9.1 (1) P1210 Input terminal 9.1 Unsigned integer

    2B27h 1 9.1 Tipo contatto NO/NC 9.1 Contact type Unsigned integer

    2B28h 1 9.1 Ritardo chiusura (sec) 0.0-6000.0 9.1 Closing delay (sec) Unsigned integer

    2B29h 1 9.1 Ritardo apertura (sec) 0.0-6000.0 9.1 Opening delay (sec) Unsigned integer

    2B30h 1 P1211 Ingresso morsetto 9.2 (1) P1211 Input terminal 9.2 Unsigned integer

    2B31h 1 9.2 Tipo contatto NO/NC 9.2 Contact type Unsigned integer

    2B32h 1 9.2 Ritardo chiusura (sec) 0.0-6000.0 9.2 Closing delay (sec) Unsigned integer

    2B33h 1 9.2 Ritardo apertura (sec) 0.0-6000.0 9.2 opening delay (sec) Unsigned integer

    2B34h 1 P1212 Ingresso morsetto 9.3 (1) P1212 Input terminal 9.3 Unsigned integer

    2B35h 1 9.3 Tipo contatto NO/NC 9.3 Contact type Unsigned integer

    2B36h 1 9.3 Ritardo chiusura (sec) 0.0-6000.0 9.3 Closing delay (sec) Unsigned integer

    2B37h 1 9.3 Ritardo apertura (sec) 0.0-6000.0 9.3 Opening delay (sec) Unsigned integer

  • Doc: AD507921.doc 28/04/2009 p. 16 / 21

    PARAMETRI MENU INPUT OPTIONAL OPTIONAL INPUT PARAMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    (1) Vedi l’elenco delle funzioni disponibili nella tabella “Ingressi programmabili”. (1) See the list of the available functions in the “Programmable inputs” table.

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2D02h 1 P1401 Ingresso morsetto I.01 (1) P1401 Input terminal I.01 Unsigned integer

    2D03h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D04h 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D05h 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D06h 1 P1402 Ingresso morsetto I.02 (1) P1402 Input terminal I.02 Unsigned integer

    2D07h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D08h 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D09h 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D0Ah 1 P1403 Ingresso morsetto I.03 (1) P1403 Input terminal I.03 Unsigned integer

    2D0Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D0Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D0Dh 1 Ritardo apertura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D0Eh 1 P1404 Ingresso morsetto I.04 (1) P1404 Input terminal I.04 Unsigned integer

    2D0Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D10h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D11h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D12h 1 P1405 Ingresso morsetto I.05 (1) P1405 Input terminal I.05 Unsigned integer

    2D13h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D14h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D15h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D16h 1 P1406 Ingresso morsetto I.06 (1) P1406 Input terminal I.06 Unsigned integer

    2D17h 1 8.6 Tipo contatto NO/NC Contact type Unsigned integer

    2D18h 1 8.6 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D19h 1 8.6 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D1Ah 1 P1407 Ingresso morsetto I.07 (1) P1407 Input terminal I.07 Unsigned integer

    2D1Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D1Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D1Dh 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D1Eh 1 P1408 Ingresso morsetto I.08 (1) P1408 Input terminal I.08 Unsigned integer

    2D1Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D20h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D21h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D22h 1 P1409 Ingresso morsetto I.09 (1) P1409 Input terminal I.09 Unsigned integer

    2D23h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D24h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D25h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D26h 1 P1410 Ingresso morsetto I.10 (1) P1410 Input terminal I.10 Unsigned integer

    2D27h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D28h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D29h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D2Ah 1 P1411 Ingresso morsetto I.11 (1) P1411 Input terminal I.11 Unsigned integer

    2D2Bh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D2Ch 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D2Dh 1 Ritardo apertura (sec) 0.0-6000.0 opening delay (sec) Unsigned integer

    2D2Eh 1 P1412 Ingresso morsetto I.12 (1) P1412 Input terminal I.12 Unsigned integer

    2D2Fh 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D30h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D31h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

    2D32h 1 P1413 Ingresso morsetto I.13 (1) P1413 Input terminal I.13 Unsigned integer

    2D33h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D34h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D35h 1 Ritardo apertura (sec) 0.0-6000.0 opening delay (sec) Unsigned integer

    2D36h 1 P1414 Ingresso morsetto I.14 (1) P1414 Input terminal I.14 Unsigned integer

    2D37h 1 Tipo contatto NO/NC Contact type Unsigned integer

    2D38h 1 Ritardo chiusura (sec) 0.0-6000.0 Closing delay (sec) Unsigned integer

    2D39h 1 Ritardo apertura (sec) 0.0-6000.0 Opening delay (sec) Unsigned integer

  • Doc: AD507921.doc 28/04/2009 p. 17 / 21

    PARAMETRI MENU USCITE OPTIONAL OPTIONAL OUTPUT PAR AMETERS MENU (Utilizzabili con funzioni 04 e 06) (To be used with functions 04 and 06)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO RANGE PARAMETER FORMATO FORMAT

    2E02h 1 P1501 Uscita morsetto O.01 (Funzione..)

    (1) P1501 Output terminal O.01 (Function..)

    Unsigned integer

    2E03h 1 P1502 Uscita morsetto O.02 (Funzione..)

    (1) P1502 Output terminal O.02 (Function..)

    Unsigned integer

    2E04h 1 P1503 Uscita morsetto O.03 (Funzione..)

    (1) P1503 Output terminal O.03 (Function..)

    Unsigned integer

    2E05h 1 P1504 Uscita morsetto O.04 (Funzione..)

    (1) P1504 Output terminal O.04 (Function..)

    Unsigned integer

    2E06h 1 P1505 Uscita morsetto O.05 (Funzione..)

    (1) P1505 Output terminal O.05 (Function..)

    Unsigned integer

    2E07h 1 P1506 Uscita morsetto O.06 (Funzione..)

    (1) P1506 Output terminal O.06 (Function..)

    Unsigned integer

    2E08h 1 P1507 Uscita morsetto O.07 (Funzione..)

    (1) P1507 Output terminal O.07 (Function..)

    Unsigned integer

    2E09h 1 P1508 Uscita morsetto O.08 (Funzione..)

    (1) P1508 Output terminal O.08 (Function..)

    Unsigned integer

    2E0Ah 1 P1509 Uscita morsetto O.09 (Funzione..)

    (1) P1509 Output terminal O.09 (Function..)

    Unsigned integer

    2E0Bh 1 P1510 Uscita morsetto O.10 (Funzione..)

    (1) P1510 Output terminal O.10 (Function..)

    Unsigned integer

    2E0Ch 1 P1511 Uscita morsetto O.11 (Funzione..)

    (1) P1511 Output terminal O.11 (Function..)

    Unsigned integer

    2E0Dh 1 P1512 Uscita morsetto O.12 (Funzione..)

    (1) P1512 Output terminal O.12 (Function..)

    Unsigned integer

    (1) Vedi l’Eelenco delle funzioni disponibili nella tabella “Uscite programmabili (1) See the list of the available functions in the “Programmable outputs” table.

    Ingressi programmabili – (Funzione…) Programmable inputs – (Function…)

    0 Disabilitato Disable

    1 Pressione olio Oil pressure

    2 Temperatura acqua motore Water engine temperature

    3 Livello carburante Fuel level

    4 Arresto di emergenza Emergency stop

    5 Stop a distanza Remote stop

    6 Avviamento a distanza Remote starting

    7 Avviamento a distanza senza stop Remote starting without cooling

    8 Avvia test automatico Start automatic test

    9 Protezione termica generatore Generator thermal protection

    10 Supervisione OFF Supervision Off

    11 Blocco setup Set-up block

    12 Controllo RETE esterno External MAINS control

    13 Controllo GEN esterno External GEN control

    14 Telecommutazione Automatic changeover

    15 Feed-back contattore RETE MAINS contactor feed-back

    16 Feed-back contattore GEN GEN contactor feed-back

    17 Serbatoio vuoto Fuel tank empty

    18 Start rabbocco Filling start

    19 Stop rabbocco Filling stop

    20 Serbatoio troppo pieno Fuel tank too full

    21 Blocco tastiera (1) Keyboard lock (1)

    22 Liquido radiatore Radiator liquid

    23 Sirena off Siren off

    24 Allarme stato interruttore Circuit breaker status alarm

    25 Allarme carica batteria Battery charger alarm

    26 Inibizione Allarmi (CANbus) Alarm inhibition (CANbus)

    27 Abilitazione droop (CANbus) Droop enable (CANbus)

    28 Incremento velocità (CANbus) Increase speed (CANbus)

    29 Decremento velocità (CANbus) Decrease speed (CANbus)

    30 Allarme utente 1 User’s alarm 1

    31 Allarme utente 2 User’s alarm 2

    32 Allarme utente 3 User’s alarm 3

    33 Allarme utente 4 User’s alarm 4

    34 Allarme utente 5 User’s alarm 5

    35 Allarme utente 6 User’s alarm 6

    36 Allarme utente 7 User’s alarm 7

    37 Allarme utente 8 User’s alarm 8

    (1) Con la funzione “ Blocco tastiera” abilitata i tasti Off/Reset – Man – Aut – Test – Start – Stop – Mains – Gen – Enter non sono operativi. (1) When the “Keyboard lock” is enabled, OFF/RESET - MAN – AUT – TEST- START – STOP – MAINS – GEN – ENTER keys are inoperative.

  • Doc: AD507921.doc 28/04/2009 p. 18 / 21

    Uscite programmabili – (Funzione…) Programmable outputs – (Function…)

    TABELLA 9: TABLE 9: LISTA EVENTI � EVENT LOG � (Utilizzabili con funzione 04) (Da rev. firmware 18 a 21) (To be used with function 04) (From firmware rev. 18 to 21)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATO FORMAT

    6002h 1 Codice evento nr. 32 (piu’ recente) � Code of event nr. 32 (most recent) � 0..62 Unsigned integer

    6003h 1 Ore evento nr. 32 Event nr. 32 - Hours 0..59 Unsigned integer

    6004h 1 Minuti evento nr. 32 Event nr. 32 - Minutes 0..59 Unsigned integer

    6005h 1 Secondi evento nr. 32 Event nr. 32 - Seconds 0..23 Unsigned integer

    6006h 1 Giorno evento nr.32 Event nr. 32 - Day 0..31 Unsigned integer

    6007h 1 Mese evento nr. 32 Event nr. 32 - Month 1..12 Unsigned integer

    6008h 1 Anno evento nr. 32 Event nr. 32 - Year 0..99 Unsigned integer

    6009h 1 Codice evento nr. 31 � Code of event nr. 31 � 0..62 Unsigned integer

    600Ah 1 Ore evento nr. 31 Event nr. 31 - Hours 0..59 Unsigned integer

    600Bh 1 Minuti evento nr. 31 Event nr. 31 - Minutes 0..59 Unsigned integer

    600Ch 1 Secondi evento nr. 31 Event nr. 31 - Seconds 0..23 Unsigned integer

    600Dh 1 Giorno evento nr. 31 Event nr. 31 - Day 0..31 Unsigned integer

    600Eh 1 Mese evento nr. 31 Event nr. 31 - Month 1..12 Unsigned integer

    600Fh 1 Anno evento nr. 31 Event nr. 31 - Year 0..99 Unsigned integer

    … … … … … …

    60DBh 1 Codice evento nr. 01 (piu’ vecchio) � Code of event nr. 01 (oldest) � 0..62 Unsigned integer

    60DCh 1 Ore evento nr. 01 Event nr. 01 - Hours 0..59 Unsigned integer

    60DDh 1 Minuti evento nr. 01 Event nr. 01 - Minutes 0..59 Unsigned integer

    60DEh 1 Secondi evento nr. 01 Event nr. 01 - Seconds 0..23 Unsigned integer

    60DFh 1 Giorno evento nr. 01 Event nr. 01 - Day 0..31 Unsigned integer

    60E0h 1 Mese evento nr. 01 Event nr. 01- Month 1..12 Unsigned integer

    60E1h 1 Anno evento nr. 01 Event nr. 01 - Year 0..99 Unsigned integer

    � Il significato del codice dell’evento puo’ essere determinato nella seguente tabella. In caso non siano registrati eventi viene ritornato il codice 0. � The meaning of the event code can be found in the following table. In case there is no recorded event code 0 will be returned

    0 Disabilitata Disable

    1 Allarme globale Global alarm

    2 Elettrovalvola carburante Fuel solenoid valve

    3 Sirena Siren

    4 Deceleratore Decelerator

    5 Magnete stop Stop magnet

    6 Candelette Glow-plugs

    7 Valvola gas Gas valve

    8 Valvola aria Air valve

    9 Valvola cicchetto Priming valve

    \0 Pompa rabbocco Topping-up pump

    11 Carico fittizio Dummy load

    12 Aria compressa Compressed air

    13 Modo funzionamento Operating mode

    14 Rete non presente Mains not present

    15 Motore in moto Engine running

    16 Motore in allarme Engine failure

    17 Basso carburante Low fuel level

    18 Carico fittizio L1 Dummy load L1

    19 Carico fittizio L2 Dummy load L2

    20 Carico fittizio L3 Dummy load L3

    21 Allarme globale 1 Global alarm 2

    22 Allarme globale 2 Global alarm 3

    23 Teleruttore Rete Mains contactor

    24 Teleruttore Generatore Generator contactor

    25 Apertura motorizzata interruttore rete Mains motorised circuit breaker opening

    26 Chiusura motorizzata interruttore rete Mains motorised circuit breaker closing

    27 Apertura motorizzata interruttore generatore Generator motorised circuit breaker opening

    28 Chiusura motorizzata interruttore generatore Generator motorised circuit breaker closing

    29 Valvola preriscaldo Valve preheating

    30 Set/Reset Relè 1 da supervisione Relay 1 set/reset via remote control software

    31 Set/Reset Relè 2 da supervisione Relay 2 set/reset via remote control software

    32 Set/Reset Relè 3 da supervisione Relay 3 set/reset via remote control software

    33 Set/Reset Relè 4 da supervisione Relay 4 set/reset via remote control software

    34 Uscita fase L1 entro i limiti impostati Output phase L1 within preset limits

    35 Uscita fase L2 entro i limiti impostati e fase L1 fuori dai limti Output phase L2 within preset limits and phase L1 outside the limits

    36 Uscita fase L3 entro i limiti impostati e fase L1 e L2 fuori dai limiti Output phase L3 within preset limits and phase L1 and L2 outside the limits

    37-95 Allarmi A1-A50 e UA1-UA8 A1-A50 and UA1-UA8 alarms

  • Doc: AD507921.doc 28/04/2009 p. 19 / 21

    TABELLA 9: TABLE 9: LISTA EVENTI � EVENT LOG � (Utilizzabili con funzione 04) (Da rev. firmware 22 a 35) (To be used with function 04) (From firmware rev. 22 to 35)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATO FORMAT

    6002h 1 Codice evento nr. 255 (piu’ recente) � Code of event nr. 255 (most recent) � 0..62 Unsigned integer

    6003h 1 Ore evento nr. 255 Event nr. 255 - Hours 0..59 Unsigned integer

    6004h 1 Minuti evento nr. 255 Event nr. 255 - Minutes 0..59 Unsigned integer

    6005h 1 Secondi evento nr. 255 Event nr. 255 - Seconds 0..23 Unsigned integer

    6006h 1 Giorno evento nr.255 Event nr. 255 - Day 0..31 Unsigned integer

    6007h 1 Mese evento nr. 255 Event nr. 255 - Month 1..12 Unsigned integer

    6008h 1 Anno evento nr. 255 Event nr. 255 - Year 0..99 Unsigned integer

    6009h 1 Codice evento nr. 254 � Code of event nr. 254 � 0..62 Unsigned integer

    600Ah 1 Ore evento nr. 254 Event nr. 254 - Hours 0..59 Unsigned integer

    600Bh 1 Minuti evento nr. 254 Event nr. 254 - Minutes 0..59 Unsigned integer

    600Ch 1 Secondi evento nr. 254 Event nr. 254 - Seconds 0..23 Unsigned integer

    600Dh 1 Giorno evento nr. 254 Event nr. 254 - Day 0..31 Unsigned integer

    600Eh 1 Mese evento nr. 254 Event nr. 254 - Month 1..12 Unsigned integer

    600Fh 1 Anno evento nr. 254 Event nr. 254 - Year 0..99 Unsigned integer

    … … … … … …

    66F4h 1 Codice evento nr. 01 (piu’ vecchio) � Code of event nr. 01 (oldest) � 0..62 Unsigned integer

    66F5h 1 Ore evento nr. 01 Event nr. 01 - Hours 0..59 Unsigned integer

    66F6h 1 Minuti evento nr. 01 Event nr. 01 - Minutes 0..59 Unsigned integer

    66F7h 1 Secondi evento nr. 01 Event nr. 01 - Seconds 0..23 Unsigned integer

    66F8h 1 Giorno evento nr. 01 Event nr. 01 - Day 0..31 Unsigned integer

    66F9h 1 Mese evento nr. 01 Event nr. 01- Month 1..12 Unsigned integre

    66FAh 1 Anno evento nr. 01 Event nr. 01 - Year 0..99 Unsigned integre

    TABELLA 9: TABLE 9: LISTA EVENTI � EVENT LOG � (Utilizzabili con funzione 04) (Da rev. firmware 36) (To be used with function 04) (From firmware rev. 36)

    INDIRIZZO ADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATO FORMAT

    6002h 1 Codice evento nr. 255 (piu’ recente) � Code of event nr. 255 (most recent) � 0..62 Unsigned integer

    6003h 1 Ore evento nr. 255 Event nr. 255 - Hours 0..59 Unsigned integer

    6004h 1 Minuti evento nr. 255 Event nr. 255 - Minutes 0..59 Unsigned integer

    6005h 1 Secondi evento nr. 255 Event nr. 255 - Seconds 0..23 Unsigned integer

    6006h 1 Giorno evento nr.255 Event nr. 255 - Day 0..31 Unsigned integer

    6007h 1 Mese evento nr. 255 Event nr. 255 - Month 1..12 Unsigned integer

    6008h 1 Anno evento nr. 255 Event nr. 255 - Year 0..99 Unsigned integer

    6009h 1 Codice DTC CANbus (4th byte) evento nr.255 Event nr. 255 - DTC code CANbus (4th byte) 0…255 Unsigned integer

    600Ah 1 Codice DTC CANbus (3th byte) evento nr.255 Event nr. 255 - DTC code CANbus (3th byte) 0…255 Unsigned integer

    600Bh 1 Codice DTC CANbus (2th byte) evento nr.255 Event nr. 255 - DTC code CANbus (2th byte) 0…255 Unsigned integer

    600Ch 1 Codice DTC CANbus (1th byte) evento nr.255 Event nr. 255 - DTC code CANbus (1th byte) 0…255 Unsigned integer

    600Dh 1 Codice evento nr. 254 � Code of event nr. 254 � 0..62 Unsigned integer

    600Eh 1 Ore evento nr. 254 Event nr. 254 - Hours 0..59 Unsigned integer

    600Fh 1 Minuti evento nr. 254 Event nr. 254 - Minutes 0..59 Unsigned integer

    6010h 1 Secondi evento nr. 254 Event nr. 254 - Seconds 0..23 Unsigned integer

    6011h 1 Giorno evento nr. 254 Event nr. 254 - Day 0..31 Unsigned integer

    6012h 1 Mese evento nr. 254 Event nr. 254 - Month 1..12 Unsigned integer

    6013h 1 Anno evento nr. 254 Event nr. 254 - Year 0..99 Unsigned integer

    6014h 1 Codice DTC CANbus (4th byte) ) evento nr.254 Event nr. 254 - DTC code CANbus (4th byte) 0…255 Unsigned integer

    6015h 1 Codice DTC CANbus (3th byte) evento nr.254 Event nr. 254 - DTC code CANbus (3th byte) 0…255 Unsigned integer

    6016h 1 Codice DTC CANbus (2th byte) evento nr.254 Event nr. 254 - DTC code CANbus (2th byte) 0…255 Unsigned integer

    6017h 1 Codice DTC CANbus (1th byte) evento nr.254 Event nr. 254 - DTC code CANbus (1th byte) 0…255 Unsigned integer

    … … … … … …

    continua……… continue………..

  • Doc: AD507921.doc 28/04/2009 p. 20 / 21

    ...continua ….continue

    INDIRIZZO ADDRESS

    WORDS PARAMETRO PARAMETER RANGE FORMATO FORMAT

    6AECh 1 Codice evento nr. 01 (piu’ vecchio) � Code of event nr. 01 (oldest) � 0..62 Unsigned integer

    6AEDh 1 Ore evento nr. 1 Event nr. 1 - Hours 0..59 Unsigned integer

    6AEEh 1 Minuti evento nr. 1 Event nr. 1 - Minutes 0..59 Unsigned integer

    6AEFh 1 Secondi evento nr. 1 Event nr. 1 - Seconds 0..23 Unsigned integer

    6AF0h 1 Giorno evento nr. 1 Event nr. 1 - Day 0..31 Unsigned integer

    6AF1h 1 Mese evento nr. 1 Event nr. 1 - Month 1..12 Unsigned integer

    6AF2h 1 Anno evento nr. 1 Event nr. 1 - Year 0..99 Unsigned integer

    6AF3h 1 Codice DTC CANbus (4th byte) evento nr. 1 Event nr. 1 - DTC code CANbus (4th byte) 0…255 Unsigned integer

    6AF4h 1 Codice DTC CANbus (3th byte) evento nr. 1 Event nr. 1 - DTC code CANbus (3th byte) 0…255 Unsigned integer

    6AF5h 1 Codice DTC CANbus (2th byte) evento nr. 1 Event nr. 1 - DTC code CANbus (2th byte) 0…255 Unsigned integer

    6AF6h 1 Codice DTC CANbus (1th byte) evento nr. 1 Event nr. 1 - DTC code CANbus (1th byte) 0…255 Unsigned integer

    � Il significato del codice dell’evento puo’ essere determinato nella seguente tabella. In caso non siano registrati eventi viene ritornato il codice 0. � The meaning of the event code can be found in the following table. In case there is no recorded event code 0 will be returned. � Per conoscere il numero dell’ultimo evento registrato, è necessario interrogare all’indirizzo 100h e 102h. Verrà ritornato per ciascun indirizzo un valore tra 1 e 255. Il primo indirizzo indica il contatore dei primi 255 eventi memorizzati (una volta arrivato a 255 il contatore non si incrementa fino a quando si esegue un azzeramento degli eventi). Il secondo indirizzo indica il contatore che si incrementa ad ogni evento memorizzato e si azzera dopo il 255 evento registrato. � To identify the number of the latest stored event, the user must write to address 100h and 102h. A response from each address will be provided with a value between 1 and 255. The first address indicates the counter of the first 255 stored events; once the counter reaches 255, it will no longer increase the count until the events are cleared. The second address indicates the counter which increases at each stored events and clears after the 255th stored event.

    Num Cod. Messaggio Cod. Message 0 E01 Modalità selezionata RESET E01 RESET mode select

    1 E02 Modalità selezionata MAN E02 MAN mode select

    2 E03 Modalità selezionata AUT E03 AUT mode select

    3 E04 Modalità selezionata TEST E04 TEST mode select

    4 E05 Mot


Recommended