+ All Categories
Home > Documents > Technical Manual Whole

Technical Manual Whole

Date post: 10-Feb-2018
Category:
Upload: vincent-mutambirwa
View: 218 times
Download: 0 times
Share this document with a friend

of 93

Transcript
  • 7/22/2019 Technical Manual Whole

    1/93

    Brick Properties1.1

  • 7/22/2019 Technical Manual Whole

    2/93

    Section 1.1 relates to the properties of bricks made to meet the requirements of Australian Standard AS4455 Part

    1 Masonry Units. This information is provided as a guide only to the properties of interest to a masonry designer

    or builder.

    Brick Dimensions

    The work size of a standard brick is: 76 mm high x 230 mm long x 110 mm wide.

    Some bricks are made with different work sizes. For example brick heights of 119 mm and 162 mm to match 1.5

    and 2 standard size brick heights, including mortar joint, respectively. 50 mm and 90 mm high bricks, 90 mm wide

    bricks and 290 mm long bricks are made for different structural and aesthetic effect. Larger bricks are often used

    for more economical laying and as a design feature either on their own or combined with smaller bricks.

    In cyclonic areas larger (140 mm wide x 90 mm high x 290 mm long) hollow bricks are used to allow for

    reinforcement and grouting in the wall. Wider (150 mm wide) bricks can also be used in walls requiring lower

    sound transmission, higher fire resistance levels and higher load bearing capacity depending on the specific brick

    properties.

    Clay brick sizes may vary after they are fired but size variation between units averages out when blended properly

    during laying. Brick dimensions are measured by dry stacking 20 units, measuring the total length, width and

    height and comparing that measurement to 20 times the work size.

    Bricks are classified according to how much 20 bricks together deviate from 20 times the work size.

    For standard bricks, Dimensional Category DW1 means the height and width will differ by less than plus or

    minus 50 mm from 20 times the work size, and the length will differ less than plus or minus 90 mm.

    For standard bricks, Dimensional Category DW2 means the height and width will differ by less than plus or

    minus 40 mm from 20 times the work size, and the length will differ less than plus or minus 60 mm.

    Dimensional Category, DW0 means there are no requirements. This is usually reserved for non-standard

    shaped bricks and bricks that have been rumbled or otherwise distorted during the manufacturing process

    for aesthetic reasons.

    Bricks & Pavers Technical Manual

    Section 1.1 Brick Properties 1.101

    ADV03743

  • 7/22/2019 Technical Manual Whole

    3/93

    Brick Strength

    Brick strength is defined as resistance to load per unit area and is expressed in mega Pascals (MPa).

    Characteristic Unconfined Compressive Strength (fuc)

    The characteristic unconfined compressive strength is used by engineers in the design of masonry to calculate

    the strength of a wall. Bricks in any one batch have a range of strengths that would usually follow a normal

    distribution. In a wall the different strength bricks contribute to the strength of the whole and the weakest brick

    does not determine the strength of the wall. For safety, engineering practice has been to use characteristic

    unconfined compressive strength. This is the strength 95% of the bricks will exceed and is typically 0.86 times

    the lowest unconfined compressive strength found when measuring the compressive strengths of 10 samples.

    Boral bricks usually have characteristic unconfined compressive strengths in the range 15 to 35 MPa.

    Unconfined Compressive Strength

    The unconfined compressive strength is a calculated number based on the compressive strength. To measure the

    compressive strength of a brick, steel platens are used above and below. This constrains the surface and where

    all other factors are equal, a shorter brick will have a higher compressive strength than a taller brick. To remove

    this test effect, the compressive strength is multiplied by a factor, which varies with the height of the brick. The

    resulting number is called the unconfined compressive strength and reflects the performance of the brick in a

    wall. Theoretically, bricks which are identical except for their height should produce the same unconfined

    compressive strength. This figure is not now used in masonry design, but is used to calculate Characteristic

    Unconfined Compressive Strength.

    Compressive Strength of Bricks

    Brick strength is measured according to AS4456.4 Determining Compressive Strength of Masonry Units.

    Individually crushing 10 bricks gives the compressive strength of each brick and the mean compressive strength

    of the lot. These figures are not used in masonry design, but are used to calculate Unconfined Compressive

    Strength.

    Bricks & Pavers Technical Manual

    Section 1.1 Brick Properties 1.102

    ADV03744

  • 7/22/2019 Technical Manual Whole

    4/93

    Water Absorption

    Cold Water Absorption

    The amount of water that a brick can absorb is measured by the cold water absorption test. There is no distinct

    relationship between water absorption and the water-tightness of walls. The results of water absorption tests

    are used by the brick manufacturer for quality assurance.

    Initial Rate of Absorption

    The initial rate of absorption (IRA) is the amount of water absorbed in one minute through the bed face of the

    brick. It is a measure of the bricks suction and can be used as a factor in the design of mortars that will bond

    strongly with units. As mortars other than the deemed to comply mortars are rarely used, the impact of the IRA

    is primarily on the bricklayer. Bricklayers, through practical experience, adjust the mortar, the height of a wall

    built in a day and the length of time before ironing the joints, according to the suction.

    The bond between the masonry unit and mortar is largely influenced by the capacity of the brick to absorb water

    and the ability of the mortar to retain the water that is needed for the proper hydration of cement. If the brick

    sucks the water too quickly from the mortar, the next course may not be properly bedded. If the mortar retains

    too much water, the units tend to float on the mortar bed, making it difficult to lay plumb walls at a reasonable

    rate. In either case there will be poor bond.

    The optimum value of IRA is considered to be between 0.5 and 1.5 kg/m 2/min. However, IRAs can exceed

    these limits. The mortars water retentivity should be matched to the brick type where good bond strength is

    critical.

    Bricks & Pavers Technical Manual

    Section 1.1 Brick Properties 1.103

    ADV03745

  • 7/22/2019 Technical Manual Whole

    5/93

    Durability

    Salt attack is the most common durability problem affecting bricks. In the form of a solution, salt can be absorbed

    into masonry. As the water evaporates, the salt is drawn towards the outside face. The evaporating water leaves

    the solution super-saturated so salt crystals begin to form. The salt crystals grow in the pores just below the

    surface and depending on the texture of the brick, the amount of salt, the rate of drying and the temperature, the

    salt may fill the pores, exerting very high pressures on the matrix. The energy in the constrained salt crystal

    increases and if sufficient pops a piece of the outer surface off and salt attack has begun.

    Bricks are assessed and classed into three grades according to AS/NZS4456.10 Resistance to Salt Attack. In

    summary the three grades of brick that can be used are as follows:

    Protected Grade (PRO)

    Suitable for use in elements above the damp-proof course in non-marine exterior environments. Elements

    above the damp-proof course in all exterior environments, with a waterproof coating, properly flashed

    junctions with other building elements and a top covering (roof or coping) protecting the masonry.

    General Purpose Grade (GP)

    Suitable for use in an external wall, excluding walls in severe marine environments or in contact with

    aggressive soils and environments (see AS3700 Appendix E). General purpose grade bricks can also be used

    in PRO applications.

    Exposure Grade (EXP)

    Suitable for use in external walls exposed to severe marine environments, i.e. up to one kilometre from a

    surf coast or up to 100 metres from a non-surf coast or in contact with aggressive soils and environments.

    The distances are specified from mean high water mark. Exposure grade bricks can also be used in PRO and

    GP applications.

    Boral bricks are classified as either EXP or GP.

    Bricks & Pavers Technical Manual

    Section 1.1 Brick Properties 1.104

    ADV03746

  • 7/22/2019 Technical Manual Whole

    6/93

    Moisture Expansion

    Clay products expand over time as they absorb water into their structure. This is well known and documented

    and must be consider when designing brickwork. The expansion is not uniform (it is logarithmic) over time. In the

    first six months one quarter of the expansion occurs, one half in the first two years and three quarters in the first

    5 years. The Characteristic Expansion is estimated from an accelerated test and expressed as a coefficient of

    expansion (em) that for Boral bricks is usually between 0.8 and 1.2 mm/m/15 years.

    Efflorescence

    Bricks may contain soluble salts that come to the surface when the brick dries. The source of these soluble salts

    is the raw materials used in the brick production process.

    Brick efflorescence should not be confused with the efflorescence that is seen on masonry walls after

    construction. This form of efflorescence is caused mainly from the raw materials and water used in the wall

    construction process (eg. Mortar).

    Brick efflorescence is usually white but there is a special form of efflorescence (known as vanadium staining) that

    is coloured yellow, green or reddish-brown and is therefore particularly visible on light coloured bricks.

    All efflorescence is more or less visible depending on the colour and surface texture of the brick.

    Boral bricks have a nil to slight efflorescence.

    Pitting due to Lime

    If brickmaking raw materials contain particles of calcium carbonate, these will be converted into quicklime in the

    kiln. Water subsequently combines with the quicklime to form hydrated lime and in the process expands. If lime

    particles are sufficiently large and sufficiently near the surface they pop off a piece of the brick, leaving a

    generally circular pit.

    Boral Bricks rarely show lime pitting.

    Bricks & Pavers Technical Manual

    Section 1.1 Brick Properties 1.105

    ADV03747

  • 7/22/2019 Technical Manual Whole

    7/93

    Brick Masonry Design1.2

  • 7/22/2019 Technical Manual Whole

    8/93

    The following design information is based on Australian Standard AS3700: 2001 Masonry Structures. Reference

    to Clauses and Formulae are those used in AS3700. This information is provided as a guide only to the processes

    involved in designing masonry. All masonry should be designed by a suitably qualified structural engineer.

    Robustness

    AS3700, Clause 4.6.1 requires walls to have an adequate degree of Robustness. Robustness is a minimum

    design requirement, and may be overridden by fire, wind, snow, earthquake or live and dead load requirements.

    In robustness calculations (AS3700 Clause 4.6.2), there are height, length, and panel action formulae. By reworking

    the standard formulae and inserting known data, it is possible to determine whether a chosen design and Boral brick

    will provide adequate robustness, as in the tables below and the charts on pages 1.202 to 1.204.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.201

    ADV03749

    Maximum Wall Length (m)

    Wall Thickness (mm) Lateral Support One End Lateral Support Both Ends

    90 1.08 3.24

    110 1.32 3.96

    150 1.80 5.40

    230 2.76 8.28

    Table 3. Maximum Wall Length where One or Both Ends are Laterally Restrained

    Table 2. Maximum Height of Walls with Free Ends

    Maximum Wall Height (m)

    Wall Thickness (mm) No Lateral Support at Top Lateral Support at Top Concrete Slab on Top

    90 0.54 2.43 3.24

    110 0.66 2.97 3.96

    150 0.90 4.05 5.40

    230 1.38 6.21 8.28

    Pier Thickness (mm) Maximum Height (m)

    230 x 230 3.105

    350 x 350 4.725

    Table 1. Maximum Height of Isolated Piers

    In the situation depicted in Table 3 above, height is not limited although length is. This typically applies to lift

    shafts and stairwells. Control joints and openings greater than one fifth of the wall height are treated as free

    ends unless specific measures are taken to provide adequate lateral support.

    Where wall lengths exceed those in Table 3 above, AS 3700 Equation 4.6.2 (4) must be used to determine the maximum

    height for a wall of the required length. Should the initial choice of product not provide a suitable solution, then a thicker

    Boral brick or increased masonry width or extra restraints should be evaluated.t

  • 7/22/2019 Technical Manual Whole

    9/93

    Robustness (continued)

    How to Use the Boral Robustness Graphs

    These charts determine the minimum brick thickness for a known wall height, length and restraint criteria.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.202

    ADV03750

    1. Select the graph for the chosen wall restraint

    (support) criteria. In this example there is

    support on one side and the top is supported by

    other than a concrete slab. Typically this would

    be a wall supporting roof frames, joined into

    another wall at one end and with a door at the

    other end.

    2. Plot the intersection of the design Wall Height

    and the Wall Length on the graph. (For this

    example 3 m height x 5 m length).

    3. The lines ABOVE the intersection point indicate

    wall thickness that are acceptable. In this

    example, the intersection point is just below the

    line for 110 mm bricks. Therefore a single leaf of

    110 mm bricks would be suitable and the most

    economical.

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    ALL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    230mm

    90x90mm

    110mm

    90mm

    150mm

    110x110mm

    FR

    S

    R

    Laterally supported one end

    and top laterally supported

    by other than concrete slab

  • 7/22/2019 Technical Manual Whole

    10/93

    Robustness Limits

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.203

    ADV03751

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    90x90mm

    110mm

    90mm

    150mm

    110x110mm

    RR

    R

    R

    Laterally supported both ends

    and top laterally supported

    by a concrete slab

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    90x90mm

    110mm

    90mm

    150mm

    110x110mm

    RR

    S

    R

    Laterally supported both ends

    and top laterally supported

    by other than concrete slab

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    90x90mm

    110mm90mm

    150mm

    110x110mm

    RR

    F

    R

    Laterally supported

    both ends and

    top unsupported

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    230mm

    90x90mm110mm

    90mm

    150mm110x110mm

    FR

    F

    R

    Laterally supportedone end andtop unsupported

  • 7/22/2019 Technical Manual Whole

    11/93

    ADV03752

    1.204

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Robustness Limits

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    90x90mm110mm

    90mm

    150mm

    110x110mm

    FR

    R

    R

    Laterally supported one end

    and top laterally supported

    by a concrete slab

    8

    7

    6

    5

    4

    3

    2

    1

    01 22 3 4 5 6 7 8

    W

    A

    LL

    HEIG

    HT

    (m

    )

    W A L L L E N G T H ( m )

    230mm

    90x90mm

    110mm

    90mm

    150mm

    110x110mm

    FR

    S

    R

    Laterally supported one endand top laterally supported

    by other than a concrete slab

  • 7/22/2019 Technical Manual Whole

    12/93

    Masonry Strength

    Masonry Strength is defined as resistance to load per unit area. It must be remembered that thicker masonry will

    support more load than thinner masonry of the same strength.

    Characteristic Compressive Strength of Masonry fm

    fm = km kh fuc

    km is a mortar strength factor and kh is a factor for the amount of mortar joints.

    km is 1.4 for M3 mortar and 1.5 for the stronger M4 mortar (see AS 3700 Table 3.1 for a full list of factors).

    kh is 1 for 76 mm high units with 10 mm mortar beds and is 1.24 for 162 mm high bricks with 10 mm mortar

    beds (see AS 3700 Table 3.2 to derive factors for other unit and joint heights). In other words, a wall of

    double height bricks is more than 20% stronger than a wall of 76 mm high bricks of the same fuc.

    fuc is the characteristic unconfined compressive strength of bricks.

    Characteristic Flexural Tensile Strength of Masonry fmt

    In flexing, the top of the arc is in tension and the bottom of the arc is in compression. Masonry is good in

    compression but poor in tension. Flexural strength depends on the mortar/brick bond and for design purposes is

    generally taken to be zero. Using up to 0.2 MPa is permitted when designing for transient loads such as wind,

    earthquake, etc. Higher bending forces may be used for design but these require site testing to verify

    construction meets the stated values.

    Characteristic Shear Strength of Masonry fms

    Shear strength, like flexural strength, is related to the mortar/brick bond. For design purposes, at the damp

    course, it is taken to be zero unless testing shows another value. Elsewhere, mortar joints have f ms values of

    between 0.15 and 0.35 MPa.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.205

    ADV03753

  • 7/22/2019 Technical Manual Whole

    13/93

    Durability of Masonry

    AS3700 requires masonry to be designed to continue functioning satisfactorily throughout its design life without

    undue maintenance. That is, all masonry materials, including bricks, mortar and all built-in components, must be

    sufficiently durable for the exposure classification of the site (see AS3700 Appendix E). Masonry designed to

    meet the requirements of AS3700 Section 5, is deemed to comply with the durability requirements and Table 5.1

    defines the durability requirements for bricks, built-in components and mortar in different environments.

    Salt attack is the most common durability problem. In the form of a solution, salt can be absorbed into masonry.

    As the water evaporates, the salt is drawn towards the outside face. The evaporating water leaves the solution

    super-saturated so salt crystals begin to form. The salt crystals grow in the pores just below the surface and

    depending on the texture of the brick, the amount of salt, the rate of drying and the temperature, the salt may

    fill the pores, exerting very high pressures on the matrix. The energy in the constrained salt crystal increases and

    if sufficient pops a piece of the outer surface off and salt attack has begun.

    Boral bricks graded General Purpose (GP) are suitable for use in all walls, excluding external walls in severe

    marine environments or in all walls in contact with aggressive soils and environments.

    Boral bricks graded Exposure Grade (EXP) are suitable for use in all walls including external walls exposed to

    severe marine environments, i.e. up to 1 km from a surf coast or up to 100 m from a non surf coast or walls in

    contact with aggressive soils and environments. The distances are specified from mean high water mark.

    Walls below damp proof course often require greater durability, even if they are well away from the coast, as

    they may be subjected to saline, acidic or alkaline soils. If unsure of the corrosive nature of the site, an

    inexpensive total soluble salt content test for soil is available in most areas. Remember it is the designers

    responsibility to specify the appropriate durability grade of bricks, mortar and built-in components and it is the

    builders responsibility to order bricks, etc. of appropriate durability grade specified by the designer. Brick

    manufacturers cannot take any responsibility in this decision as they are not aware of the design requirements

    of each site. t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.206

    ADV03754

  • 7/22/2019 Technical Manual Whole

    14/93

    Durability of Masonry (continued)

    Refer to Section 1.4 Property Tables for tabulated properties of individual brick types for their salt attack

    resistance category.

    Mortar mix requirements for durability are referred in Table 11, page 1.301 of this manual and are detailed in

    AS3700 Table 10.1.

    M4 mortars are required and mortar joints must be tooled in all situations requiring exposure grade materials.

    Concrete floors, paths and steps are a source of sulfate salts that if dissolved in water may enter the brickwork and

    cause salt attack. Exposed slabs supported on external brickwork should clear the brickwork by 50 mm and

    incorporate a drip groove to prevent the run-off from the slab running down the brickwork. A damp proof course

    (usually a double layer) is also used under the slab on top of the bricks to prevent water passing through the slab

    into the bricks and as a slip joint to prevent a build up of forces as the concrete shrinks and the bricks expand

    over time.

    Landscaping and gardening practices are also possible sources of salt attack. Care must be taken to not bridge

    the damp proof course when landscaping at the base of walls. Watering gardens and lawns, against walls, may

    cause salts (fertilisers) to splash up on to the wall where they are absorbed and may cause salt attack.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.207

    ADV03755

  • 7/22/2019 Technical Manual Whole

    15/93

    Brick Ties

    In brick veneer construction, ties are used to pass all the lateral out-of-plane loads and forces (such as from wind)

    to the structural backing. In cavity brick construction ties either pass the lateral out-of-plane loads and forces to

    the stronger leaf or share them between the leaves.

    The design of ties in masonry for structural purposes must comply with AS3700 Clause 7.7 for veneer or Clause

    7.8 for cavity construction. For small buildings the tie requirements are covered in AS3700 Clause 12.3.4 for brick

    veneer construction and Clause 12.3.3.2 for cavity brick construction.

    Type A ties are those that have no specific seismic design characteristics. It is difficult to find brick ties other

    than Type A in Australia. Ties are available in heavy, medium and light duty in galvanised steel, stainless steel

    and plastic. Plastic ties are usually reserved for acoustic applications. Stainless steel ties are used in situations

    requiring exposure grade materials or very long life. Galvanised steel ties are those most commonly used.

    The Newcastle (NSW) earthquake which occurred in 1989 showed masonry survived well except where the ties

    were deficient. Problems found included:

    galvanised ties rusted through;

    ties only built into one leaf during construction;

    loose ties;

    absent ties; and,

    incorrect duty ties used.

    Ties are required to meet the durability requirement of the site for the design life of the building. Should the

    design life of the building be exceeded and the ties begin to fail, they can be replaced with remedial ties but this

    is a very expensive process and as ties are hidden it is unlikely they will be seen until a catastrophic failure

    occurs. As sustainability considerations become more important, the life of buildings is likely to be extended.

    Properly maintained, brick buildings may last for centuries. It should be remembered that stainless steel brick

    ties offer a longer service life and, although more expensive as a proportion of the overall building cost, the

    difference is trivial.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.208

    ADV03756

  • 7/22/2019 Technical Manual Whole

    16/93

    Movement in Masonry Walls

    To allow for movements in masonry (expansion and contraction and footing movement) control joints are

    required. These can usually be constructed so that the expansion joint and the articulation joint are one and

    the same.

    Expansion Joints

    Expansion and contraction must be allowed for in masonry design by inserting control joints at spacings designed

    to suit the magnitude of the movement.

    Clay products expand permanently over time. This is the opposite of cement-based products, which permanently

    shrink. For this reason it is unwise to use clay and concrete units in the same band in a wall. If clay bricks are

    used in concrete framed buildings, control joint spacing and workmanship are critical, as the bricks will expand

    as the concrete frame shrinks.

    The magnitude of thermal changes varies from brick to brick depending on the many factors, however, allowing

    0.008 mm/m/C is usually recommended. Expansion and contraction from wetting and drying of clay bricks is less

    than for concrete and calcium silicate products and usually can be ignored in brick masonry design.

    AS3700, Clause 4.8 requires expansion joints to be spaced to limit panel movement so that movement from both

    sides closes joints by less than 15 mm and joints are at least 5 mm wide when closed. This means the gap, when

    constructed, should be 20-25 mm. However, in most buildings articulation joints are used and these are closer

    than required for expansion making separate expansion joints unnecessary.

    Articulation Joints

    Articulation joints are vertical gaps that allow for minor footing movements, to prevent distress or significant

    wall cracking. Articulation joints provide the flexibility needed when building on reactive clay soils and usually

    are not required for masonry on stable sites (classified according to AS2870). Spacing of articulation joints

    depends on the site classification and the slab or footing design, but where used must be placed no closer than

    0.5 metres and no further than 3 metres from all corners. The width of articulation joints depends on the height

    of the masonry: 10 mm for masonry up to 3 metres and 15 mm for masonry up to 6 metres high. t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.209

    ADV03757

  • 7/22/2019 Technical Manual Whole

    17/93

    Movement in Masonry Walls (continued)

    Control Joints (General)

    Control joints should be used beside large openings, where wall thickness changes (except where this is for

    support eg. engaged piers), where wall height changes by more than 20%, at changes of level in footings and at

    other points of potential cracking. Control joints must not continue through bond beams.

    Ideally, control joints are located near a corner and concealed behind a down pipe. The bricklayer and renderer

    must keep the control joint clean, otherwise, bridging mortar or render will induce cracks as the masonry moves.

    External control joints should be finished with a soft flexible sealant to prevent moisture penetration.

    The design and construction of control gaps in the external leaf of a full brick wall is identical to that in brick

    veneer. In internal masonry, control gaps are not usually required, except at re-entrant angles in long walls.

    However, where an internal control joint is required the design is as for external leaves but the thermal

    component may be ignored in calculations. Internal control joints can usually be located at a full-height opening

    such as a door or window.

    Ties are required on both sides of a control joint, but where it is not possible to use them masonry flexible

    anchors (MFAs) must be used across the joint. Where MFAs are used in walls over 3 metres or in walls exposed

    to high winds, MFAs must be built in at half height and every seventh course (600 mm) above. MFAs are ties that

    are of a type that only allows movement in one plane. Unless ties are used, control joints create a free end in

    terms of Robustness and Fire Resistance Level calculations for structural adequacy, so their positioning is critical

    to the overall design of the structure.

    In portal frame construction, the control

    joint is positioned at a column so that

    both ends can be tied to the columns

    flanges.

    The principles of control joint

    construction are illustrated in the

    adjacent figure.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.210

    ADV03758

    Articulation joints withcompressible backingand mastic sealant

    Dividing wall witharticulation joint andMFA's at intersectionwith cavity wall

    Brick ties on each sideof articulation joint

    Articulationjoint

  • 7/22/2019 Technical Manual Whole

    18/93

    Thermal Properties

    As at 2004, the Building Code of Australia (BCA) requires energy efficiency performance for housing (BCA Vol 2).

    Australia is divided into 8 climatic zones. (Sydney and Perth are in Zone 5, Adelaide and Melbourne are in Zone

    6, Brisbane is in Zone 2 and Canberra is in Zone 7). The zones and Local Government boundaries are detailed on

    a map, which is available from the Australian Building Codes Board (www.abcb.gov.au) but the Local Council

    should be able to provide the information where there is any doubt.

    The BCA set the minimum energy efficiency requirement of 3.5 stars for Zones 1-3 and 4 stars for Zones 4-8. While

    the BCA sets these minimum requirements, State governments may adopt these minimums or may opt for different

    requirements. Local authorities may adopt higher star ratings but may not opt for lower ratings than the State adopts.

    The ABCB has indicated they are considering requiring 5 stars in line with Victoria and ACT.

    Victoria requires a 5 star rating on the building fabric from July 2005 using FirstRate or NatHERS software.

    Pre-July 2004, the requirement was 4 stars on the building fabric. Post July 2004, the requirement is either 5 stars

    on the building fabric; or 4 stars on the building fabric plus water saving measures and a solar hot water system;

    or 4 stars on the building fabric plus water saving measures and a rain water tank.

    ACT requires 5 stars from ACTHERS software.

    South Australia requires 4 stars from NatHERS or FirstRate software.

    The NSW situation is complex. From 1 July 2004 in the Sydney Metropolitan area and 1 July 2005 eleswhere in the

    State all new housing, dual occupancies and small (under 300 m2) hostel type accommodation will be required to

    have a BASIX rating. From 1 February 2005 in the Sydney Metropolitan area and 1 October 2005 elsewhere in the

    state this will apply to all new residential developments. From 1 July 2005 these measures apply to alterations to

    residences in Sydney and from 1 October 2005 elsewhere in the State. BASIX is a comprehensive sustainability

    rating software, incorporating energy and water efficiency initially with the intention of including stormwater,

    transport, site ecology, waste and recycling and materials at a later date. It is a web-based system in which you

    enter data about the development in boxes and the whole has to meet targets to get Development Application

    approval. BASIX is aimed at achieving energy reductions of 25% (going up to 40% in July 2006) and potable water

    savings of 40%.

    Different star rating software can produce different ratings. To overcome this, the Australian Building Codes Board

    has developed a protocol to ensure all star rating software, as nearly as practical, produces the same rating for the

    same design.t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.211

    ADV03759

  • 7/22/2019 Technical Manual Whole

    19/93

    Thermal Properties (continued)

    The requirements to meet a star rating are complex because the rating is based on the total building design for a

    given site. It is important to remember that roof insulation, shading, orientation and window size and placement

    have a much greater impact on energy efficiency than the walls. Heat enters and leaves buildings more readily

    through the windows and roof and greater insulation in the roof space is usually the most cost-effective measure

    to increase star ratings. Although there is not an exact relationship, to meet the star ratings walls generally have

    to meet the following requirements:

    Table 4. Wall Insulation Requirements

    The BCA states that brick veneer construction made with a single leaf of 110 mm wide bricks has an R value of

    0.54 and must incorporate insulation to produce the values above.

    Cavity clay masonry is treated differently and is deemed to satisfy wall insulation requirements if it achieves a

    mass of 220 kg per square metre of wall in Zones 5 and 6 and in the ACT. In Zone 6 the masonry must be

    constructed on a concrete slab in contact with the ground. In the ACT the masonry must be constructed on a

    concrete slab in contact with the ground or having an insulated timber floor.

    Cavity clay masonry is deemed to satisfy because heavy mass walling has a high thermal inertia (thermal lag).

    Heat is slowly absorbed during the day and slowly lost during the cool night. Most thermal requirements focus

    on thermal insulation, denoted as R value. When dealing with heavy mass walling and typical non-tropical

    diurnal temperature cycles, R value is misleading as it assumes a steady state (constant temperature difference

    across the wall) which is not the case because of the day-night temperature cycle. Cavity brick houses are well

    known to have a lower temperature fluctuation than lighter weight construction and the deemed-to-satisfy

    provision is in recognition of this fact.

    In February 2004 the ABCB released a proposal to impose energy efficiency requirements in the BCA Volume 1

    for Class 2, 3 & 4 buildings, (residential buildings other than houses). ACT currently has requirements on these

    classes of building and Victoria has requirements on these classes and on Class 9c buildings. The requirements

    are essentially the same as for Class 1 buildings.

    Zones Wall insulation value1, 2, 3 & 5 R1.4

    Qld Zones 1, 2 & 3 R1.0

    4 & 6 R1.7

    7 R1.9

    8 R2.8

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.212

    ADV03760

  • 7/22/2019 Technical Manual Whole

    20/93

    Masonry Design for Fire Resistance

    Fire Resistance Levels (FRL)

    FRLs come from the Building Code of Australias (BCA) Volume 1 tables for Type A, B or C construction. The Type of

    construction depends on the Class of building and the number of stories or floors. FRLs for housing come from BCA

    Volume 2.

    There are three figures in the Fire Resistance Level.

    Eg: FRL 120/60/90 means that the wall must achieve Structural Adequacy for 120 minutes / Integrity for 60 minutes /

    Insulation for 90 minutes.

    Structural Adequacy

    This governs the walls height, length, thickness and restraints. Brick suppliers do not control the wall height,

    length or restraints so therefore do not control Structural Adequacy.

    Integrity

    This is the resistance to the passage of flame or gas. To provide integrity, walls must be structurally adequate

    and they must maintain insulation. Extensive fire testing of masonry has shown integrity to be closely related to

    structural adequacy or insulation. AS 3700 therefore allows Integrity to be equal to the lesser of the Structural

    Adequacy or the Insulation periods.

    Insulation

    This is resistance to the passage of heat through the wall. Insulation is a function of the thickness of the brick

    as shown in Table 5, page 1.222 of this manual.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.213

    ADV03761

  • 7/22/2019 Technical Manual Whole

    21/93

    Masonry Design for Structural Adequacy FRL

    Structural Adequacy is a minimum provision and may be overridden by design for robustness, wind, live or

    earthquake loads.

    A fire on one side of a wall will heat that side, making it expand and lean towards the fire. When the lean or bow

    reaches half the thickness of the original wall, the wall becomes structurally inadequate. The formulae in

    AS3700, Clause 6.3.2.2 limits the panel size, depending on its restraints and thickness.

    The Slenderness ratio (Srf) of a proposed wall is calculated according to AS 3700 Clause 6.3.2.2. If this value is

    less than the maximum Srf

    in Table 6.1 of the Standard [or the Srf

    calculated from Fire Tests and AS 3700 Clause

    6.3.3(b)(ii)], then the wall complies. If the S rf of the wall is greater than the maximum permissible, it must be

    recalculated for an increased thickness and/or extra restraints.

    There are 3 formulae for calculating Srf.

    AS 3700 Formula 6.3.2.2 (1) and (2) are the formulae for vertically spanning walls (with no support along either

    vertical edge).

    Formula (1) and (2) always govern where there is no end restraint, and often govern where walls are long, relative

    to their height. Projects with multiple wall lengths (eg: home units) can use this formula as a one size fits all

    method of calculating the wall thickness.

    AS 3700 Formula 6.3.2.2 (3) allows a wall to exceed the height given by formula (1) and (2) provided the top and

    at least one end is supported.

    AS 3700 Formula 6.3.2.2 (4) allows a wall to exceed the height given in formula (3) where walls are short, relative

    to their height (eg: a lift well or vent shaft). Short walls with no top restraint often occur in situations like portal

    frame factories.

    For cavity walls where both leaves are equally loaded (within 10 per cent of each other, including where there is

    no load on either leaf) the thickness is equal to two-thirds of the sum of the thicknesses of both leaves and the

    edge restraint condition is that for the leaf not exposed to the fire. Where one leaf is more heavily loaded than

    the other, the thickness and edge restraint condition is that of the more heavily loaded leaf. Where cavity walls

    are constructed with leaves of different masonry unit types, the structural adequacy is based on the less fire

    resistant material.t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.214

    ADV03762

  • 7/22/2019 Technical Manual Whole

    22/93

    Masonry Design for Structural Adequacy FRL (continued)

    Refer to the Structural Adequacy Graphs on the following pages for maximum height and length values for walls

    of different thicknesses and restraint conditions.

    An appropriately qualified engineer should check all calculations. Other loads may supersede Structural

    Adequacy requirements.

    How to Use the Boral Structural Adequacy FRL Graphs

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.215

    ADV03763

    1. Select the graph with Structural Adequacy for

    the required minutes. (240 minutes for this

    example).

    2. Select the graph for the chosen wall restraint

    (support) criteria. (Support on both vertical

    edges, top and bottom for this example).

    3. Plot the intersection of the design Wall Height

    and the Wall Length on the graph. (For this

    example 3 m height x 5 m length).

    4. The line ABOVE the intersection indicates the

    minimum brick thickness required for the wall.

    In this example, 150 mm bricks would be

    suitable and the most economical.

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supportedon all sides

  • 7/22/2019 Technical Manual Whole

    23/93

    ADV03764

    1.216

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Structural Adequacy for 60 Minutes FRL

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm

    90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supported

    on all sides

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm

    90mm

    150mm

    230mm

    FS

    S

    S

    Laterally supported

    on three sides,

    one end unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm

    90mm

    150mm

    230mm

    SS

    F

    S

    Laterally supported

    on three sides,

    top unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm

    90mm

    150mm

    230mm

    FS

    F

    S

    Laterally supported

    one end and bottom,

    one end and top unsupported

  • 7/22/2019 Technical Manual Whole

    24/93

    ADV03765

    1.217

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Structural Adequacy for 90 Minutes FRL

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supported

    on all sides

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIGHT

    BETWE

    EN

    SUPPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110m m90mm

    150m m

    230mm

    FS

    S

    S

    Laterally supported

    on three sides,

    one end unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    F

    S

    Laterally supported

    on three sides,

    top unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    FS

    F

    S

    Laterally supportedone end and bottom,

    one end and top unsupported

  • 7/22/2019 Technical Manual Whole

    25/93

    ADV03766

    1.218

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Structural Adequacy for 120 Minutes FRL

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supported

    on all sides

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    FS

    S

    S

    Laterally supported

    on three sides,

    one end unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm230mm

    SS

    F

    S

    Laterally supported

    on three sides,

    top unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    FS

    F

    S

    Laterally supportedone end and bottom,

    one end and top unsupported

  • 7/22/2019 Technical Manual Whole

    26/93

    ADV03767

    1.219

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Structural Adequacy for 180 Minutes FRL

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supported

    on all sides

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    FS

    S

    S

    Laterally supported

    on three sides,

    one end unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm230mm

    SS

    F

    S

    Laterally supported

    on three sides,

    top unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm230mm

    FS

    F

    S

    Laterally supportedone end and bottom,

    one end and top unsupported

  • 7/22/2019 Technical Manual Whole

    27/93

    ADV03768

    1.220

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Structural Adequacy for 240 Minutes FRL

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    SS

    S

    S

    Laterally supported

    on all sides

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETW

    EE

    N

    SU

    PPORTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm

    230mm

    FS

    S

    S

    Laterally supported

    on three sides,

    one end unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm230mm

    SS

    F

    S

    Laterally supported

    on three sides,

    top unsupported

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    01 2 3 4 5 6 7 12111098

    HEIG

    HT

    BETWE

    EN

    SU

    PPO

    RTS

    (m

    )

    L E N G T H B E T W E E N S U P P O R T S ( m )

    110mm90mm

    150mm230mm

    FS

    F

    S

    Laterally supportedone end and bottom,

    one end and top unsupported

  • 7/22/2019 Technical Manual Whole

    28/93

    Structural Adequacy for Panels with Unsupported Ends

    This figure shows the situation where there is support top and bottom but none on the sides. This applies

    where there are control joints, large openings, long walls, etc. To use this graph select the desired FRL in

    minutes and the height of the wall. The line above the intersection shows the brick thickness required.

    Maximum Wall Heights for Structural Adequacy for any Wall Length

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.221

    ADV03769

    7

    6

    5

    4

    3

    2

    1

    060 90 120 240180

    M

    A

    XIM

    UM

    W

    ALL

    HEIGHT

    (m

    )

    F R L F O R S T R U C T U R A L A D E Q U A C Y

    ( m i n u t e s )

    110mm

    90mm

    150mm

    230mm

    FF

    S

    S

    Top and bottom supported,

    ends not supported.

  • 7/22/2019 Technical Manual Whole

    29/93

    Masonry Design for Integrity FRL

    It is impractical to provide test results for all possible wall designs, and therefore Integrity must be proved in

    some other way. The most practical way to prove Integrity is to prove Structural Adequacy and Insulation

    equal to or better than the Integrity requirement. Logically, if the wall is designed to minimise bowing it will

    not crack and therefore resist the passage of flame and gas for the specified time.

    This method is also the best way to prove Integrity even when a wall may not be required to comply with a

    Structural Adequacy FRL value, such as is the case with non-load bearing walls. Eg. If the BCA requires an FRL

    of -/90/90, the wall has no actual Structural Adequacy requirement, but to prove Integrity of 90 minutes, the

    wall must be structurally adequate for at least 90 minutes.

    Masonry Design for Insulation FRL

    Insulation is the one FRL component that a brick manufacturer does control. It is governed by the type of

    material and material thickness.

    Material thickness (t) is defined in AS3700, Clause 6.5.2 as the overall thickness for bricks with cores not more

    than 30% of the bricks overall volume.

    For cavity walls, t = the sum of material thicknesses in both leaves.

    Effect of Recesses for Services on FRLs

    Recesses that are less than half of the masonry thickness and are less than 10,000 mm2 (0.01 m2) for both sides

    within any 5 m2 of the wall area do not have an effect on fire ratings.

    If these limits are exceeded, the masonry design thickness must be reduced by the depth of the recess.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.222

    ADV03770

    Wall thickness (mm) 90 110 140 or 150160 (150 plus 10 mm

    230180 220

    render on both sides) (90/90 cavity) (110/110 cavity)

    Insulation period (minutes) 60 90 120 180 240 240 240

    Table 5. Insulation periods for standard bricks (minutes)

    Note: Wall thickness excludes render on side of wall exposed to fire.

  • 7/22/2019 Technical Manual Whole

    30/93

    Effect of Chases on Fire Rated Masonry

    Structural Adequacy FRL

    To assess the effect of chases on Structural Adequacy FRLs, the direction in which the wall spans must be taken

    into account.

    Walls spanning vertically may be chased vertically to full height but horizontal chases are limited in length

    to 4 times the walls thickness.

    Walls spanning vertically and horizontally may be chased either horizontally up to half the walls length or

    vertically up to half the walls height.

    If these limits are exceeded, the masonry design thickness must be reduced by the depth of the chase or, in the

    case of vertical chases, designed as 2 walls with unsupported ends at the chase. Horizontal chases in all walls

    should be kept to a bare minimum.

    Note: Chases affect the sound reduction capacity of walls. See Acoustic Design page 1.225 of this manual.

    Integrity and Insulation FRLs

    AS3700 limits the maximum depth of chase to 30 mm and the maximum area of chase to 1,000 mm2. The

    maximum total area of chases on both sides of any 5 m2 of wall is limited to 100,000 mm2 (0.1 m2). If these limits

    are exceeded, the masonry design thickness must be reduced by the depth of the chase.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.223

    ADV03771

  • 7/22/2019 Technical Manual Whole

    31/93

    Options for Increasing FRLs

    Structural Adequacy FRLs can be increased by adding wall stiffeners, by increasing the overall thickness, by

    adding reinforcement or by protecting the wall, e.g. with Boral Plasterboards FireStop board, fixed to furring

    channels (on both sides of the wall if a fire rating is required from both sides). Note: Be careful of the effect of

    plasterboard on sound reduction in party walls. See Acoustic Design page 1.225 of this manual.

    Integrity FRLs are increased by increasing the other two FRL values to the required Integrity FRL.

    Insulation FRLs can be increased by adding another leaf of masonry, by rendering both sides of the wall if the fire

    can come from either side. Note: Only ONE thickness of render is added to the material thickness and that must

    be on the cold side because the render on the exposed face will drop off early in a fire.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.224

    ADV03772

  • 7/22/2019 Technical Manual Whole

    32/93

    ACOUSTIC DESIGN

    Acoustic Performance Rating

    The BCA requirements for Class 1, 2, 3 and 9c buildings changed in May 2004 with the issue of Amendment 14.

    Amendment 14 has been adopted by all jurisdictions other than Queensland, Northern Territory and Western

    Australia where Amendment 13 continues in force. It must be remembered that the BCA requirements are the

    minimum requirements and some Local Authorities may require better performance. Check with Local Councils

    for specific requirements above the BCA minimums. Note: Incremental improvements in sound insulation come

    at an ever-increasing cost.

    The BCA Amendment 14 requirements are met by:

    1. Testing a sample of constructed walls to verify that they meet the Weighted Standardised Level Difference

    (Dnt,w explained further in Acoustic Performance On-Site on page 1.231 of this manual) requirements; or

    2. Constructing walls using the same materials and techniques as walls that have been constructed and tested in a

    laboratory and shown to meet the Weighted Sound Reduction Index (Rw) requirements; or,

    3. Constructing walls using the materials and techniques in the Acceptable Construction Practice section of

    the BCA; and,

    4. Where impact sound reduction is required, it is to be achieved by discontinuous construction; and,

    5. Except where the requirements are verified by on-site testing, chasing of services into masonry walls is not

    allowed and electrical outlets on either side of the wall must be offset by no less than 100 mm. t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.225

    ADV03773

  • 7/22/2019 Technical Manual Whole

    33/93

    ADV03774

    1.226

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Building service Adjacent room Barrier rating

    A duct, soil, waste, water supplySole occupancy unit habitable room

    Rw40

    or stormwater pipe passingother than a kitchen

    through a separating wall Sole occupancy unit kitchen or Rw25non habitable room

    Table 9. BCA Amendment 14 Service separation* in Class 1, 2, 3 & 9c buildings.

    * In Class 1 buildings the requirements apply to those services that pass through more than one building. In Class 2, 3 & 9c requirements apply

    to all stormwater pipes and other services that pass through more than one sole occupancy unit.

    Wall Separating Wall Rating

    Sole occupancy unit all areas Sole occupancy unitRw45 all areas except those below

    Sole occupancy unit all areas Laundry, kitchen Rw45

    and

    discontinuous construction

    or

    No less resistant to impact

    noise than a deemed-to-

    satisfy wall

    Sole occupancy unit al l areas Bathroom, sanitary compartment (but not anRw45

    associated ensuite), plant room, utilities room

    Table 8. BCA Volume 1 Amendment 14 Requirements for walls separating sole occupancy units from otherparts of the building in Class 9c Buildings (aged care facilities).

    Table 6. BCA Volume 2 Amendment 14 Requirements for walls separating two or more Class 1 Buildings

    Wall Separating Wall Rating

    Sole occupancy unit Sole occupancy unit

    all areas all areas except those belowRw+Ctr50

    Sole occupancy unit bathroom, sanitary Sole occupancy unit Rw+Ctr50

    compartment, laundry or kitchen habitable room except a kitchen and

    discontinuous construction

    Wall Separating Wall RatingSole occupancy unit Sole occupancy unit

    Rw+Ctr50 all areas except those below all areas except those below

    Sole occupancy unit bathroom, Sole occupancy unit Rw+Ctr50

    sanitary compartment, laundry or kitchen habitable room except a kitchen and

    discontinuous construction

    Sole occupancy unit all areas Plant room or lift shaft Rw+Ctr50

    and

    discontinuous construction

    Sole occupancy unit al l areas Stairway, public corridor, publ ic lobbyRw50or areas of different classification

    Table 7. BCA Volume 1 Amendment 14 Requirements for walls separating sole occupancy units from otherparts of the building in Class 2&3 Buildings.

    Acoustic Performance Rating (continued)

  • 7/22/2019 Technical Manual Whole

    34/93

    Weighted Sound Reduction Index (Rw)

    Rw is a single-number rating of the sound reduction through a wall or other building element. Since the sound

    reduction may be different at different frequencies, test measurements are subjected to a standard procedure

    that yields a single number that is about equal to the average sound reduction in the middle of the human hearing

    range. Two spectral corrections can be applied to Rw: C and Ctr. C compensates for medium to high

    frequency noise and Ctr compensates for low frequency noise. C and Ctr are both negative numbers.

    Impact Sound Resistance

    The BCA Amendment 14 says there is no appropriate test for impact sound reduction in walls. However, in the

    case of Class 9c buildings the BCA allows impact sound reduction to be demonstrated by showing a wall

    performs no worse than a deemed-to-satisfy wall. To achieve impact sound resistance, the BCA requires walls

    consist of two leaves with at least a 20 mm cavity between them and if ties are needed in masonry walls they

    must be of the resilient type. Except for the resilient ties in masonry walls there are to be no mechanical linkages

    between the walls, except at the periphery (i.e. through walls, floors and ceilings).

    BCA Deemed-to-Satisfy Walls

    BCA Volume 1 Amendment 14 Specification F5.2 Table 2 gives deemed-to-satisfy walls for sound insulation for

    walls separating sole occupancy units.

    BCA Volume 2 Amendment 14 Table 3.8.6.2 gives deemed-to-satisfy walls for sound insulation for walls

    separating two or more Class 1 Buildings. These walls are the same as those in Volume 1 except only walls

    achieving Rw+Ctr50 are allowed.

    Deemed-to-satisfy clay brick walls are detailed on the following pages. t

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.227

    ADV03775

  • 7/22/2019 Technical Manual Whole

    35/93

    ADV03776

    1.228

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Two leaves of 110 mm clay brick masonry with:

    (a) A cavity not less than 50 mm between leaves; and

    (b) 50 mm thick glass wool insulation with a density of 11

    kg/m3 or 50 mm thick polyester insulation with a density

    of 20 kg/m3 in the cavity.

    Construction Rating

    Table 10. BCA Volume 1 Amendment 14 Deemed-to-Satisfy Brick Walls

    BCA Deemed-to-Satisfy Walls (continued)

    Rw+Ctr50

    Two leaves of 110 mm clay brick masonry with:

    (a) A cavity not less than 50 mm between leaves;

    and

    (b) 13 mm cement render on each outside face.

    Rw+Ctr50

    Single leaf of 110 mm clay brick masonry with:

    (a) A row of 70 mm x 35 mm timber studs or 64 mm steel studs

    at 600 mm centres, spaced 20 mm from the masonry wall;

    and

    (b) 50 mm thick mineral insulation or glass wool insulation with

    a density of 11 kg/m3 positioned between studs; and,

    (c) one layer of 13 mm plasterboard fixed to outside face of

    studs and outside face of masonry.

    Rw+Ctr50

    Single leaf of 90 mm clay brick masonry with:

    (a) A row of 70 mm x 35 mm timber studs or 64 mm steels studs

    at 600 mm centres, spaced 20 mm from each face of the

    masonry wall; and

    (b) 50 mm thick mineral insulation or glass wool insulation with

    a density of 11 kg/m3 positioned between studs in each row;

    and

    (c) one layer of 13 mm plasterboard fixed to studs on each

    outside face.

    Rw+Ctr50

  • 7/22/2019 Technical Manual Whole

    36/93

    ADV03777

    1.229

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design

    Single leaf of 150 mm brick masonry with

    13 mm cement render on each face.

    Construction Rating

    Table 10. BCA Volume 1 Amendment 14 Deemed-to-Satisfy Brick Walls (continued)

    BCA Deemed-to-Satisfy Walls (continued)

    Rw50

    Single leaf of 220 mm brick masonry with

    13 mm cement render on each face.Rw50

    Single leaf of 110 mm brick masonry with

    13 mm cement render on each face.Rw45

  • 7/22/2019 Technical Manual Whole

    37/93

    Solid v. Cavity Walls

    Acoustic performance with single leaf masonry follows the Mass Law. The acoustic performance of these walls

    depends on their mass. More mass gives better performance, however, the relationship is logarithmic: If a 110

    mm wall gives Rw = 45, a 230 mm wall of the same brick may give Rw = 57.

    Cavity walls behave differently because sound waves can resonate in cavities. The narrower the cavity becomes,

    the more resonance occurs. Insulation in the cavity helps absorb resonating sound and narrow cavities should

    have bond breaker board, to prevent mortar from providing a bridge for sound to travel between the leaves.

    Brick Walls with Render

    Render on one side of a brick wall adds 2 or 3 to the walls R w but adding render to the second side only adds

    1 to the walls Rw. The render appears to fill defects in the wall surface reducing the sound transmission, but this

    is a one-off benefit.

    Brick Walls with Plasterboard

    Cornice cement daubs, used to fix plasterboard directly to brick walls, create a small cavity in which resonance

    occurs. Brick walls with daub fixed plasterboard on both sides stop less noise than the same walls, bare. Adding

    extra daubs (halving spacing) gives lower performances, presumably due to extra bridges through the daubs.

    Plasterboard on furring channel is marginally better than daub fixed. A bigger cavity between the wall and the

    plasterboard makes it harder for resonating energy to build up pressure on the board. When standard furring

    channel clips are used, this system transfers vibrations to the plasterboard via the channels and clips. Boral

    Impact Clips (BICs) have a rubber shank on their masonry anchor that isolates the vibrations from the masonry.

    The use of BIC mounts can add 3 or 4 dB to the walls Rw. Polyester and glass wool in the cavity helps prevent

    resonance and further decreases the sound transmission. Denser grades of plasterboard and additional layers of

    plasterboard (fixed with grab screws and leaving no cavities) also decrease sound transmission.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.230

    ADV03778

  • 7/22/2019 Technical Manual Whole

    38/93

    Points to Consider When Designing Wallsfor Acoustic Performance

    The BCA specifies minimum levels for sound isolation but experience shows that achieving the minimum

    standards is not always sufficient to satisfy occupants. In view of this it is recommended that architects,

    developers, builders, etc., consider a higher level of sound insulation, commensurate with the expectations of

    the end user. End user expectations are frequently related to the cost of occupying the unit.

    Wall design is a balance between acoustical performance, thickness, weight and cost. Frequently it is not

    possible to optimise one factor without seriously compromising the others.

    Acoustic Performance On-Site

    The Rw ratings on walling systems are obtained from tests carried out in accredited laboratories, under

    controlled conditions. When identical partitions in buildings are tested in-situ, it is often found that the actual

    result obtained, called the Weighted Standardised Level Difference (Dnt,w), is lower than the laboratory Rw. This

    reduction in performance can be due to rooms being too small, varying size of the element being tested, flanking

    paths (noise passing through other parts of the building) or background noise. The allowance in the BCA for a

    difference of 5 between the laboratory test and the field test is not to allow for poor construction practice. To

    repeat the performance in the field, attention to detail in the design and construction of the partition and its

    adjoining floor/ceiling and associated structure is of prime importance. Even the most basic elements, if ignored,

    can seriously downgrade the sound insulation performance.

    The most common field faults include bricklayers not completely filling all mortar joints, poor sealing between

    walls and other building elements, electrical power outlets being placed back to back, chasing masonry and

    concrete walls, leaving gaps in insulation, screwing into insulation and winding it around the screw when

    attaching sheet materials, not staggering joints in sheet materials and poor sealing of penetrations.

    Boral Bricks cannot guarantee that field performance ratings will match laboratory performance. However, with

    careful attention during construction of the wall, correct installation to specification and proper caulking/sealing,

    the assembly should produce a field performance close to and comparable with tested values. The following

    items can also affect the acoustic performance on site.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.231

    ADV03779

  • 7/22/2019 Technical Manual Whole

    39/93

    Perimeter Acoustical Sealing

    As the Rw of a wall increases, the control of flanking paths becomes more critical. Consequently, the perimeter

    sealing requirements for a low sound rating wall, such as Rw = 45, are much less than for a high sound rating

    wall, such as Rw = 60. Note: it is neither necessary, nor is it cost effective, to provide very high perimeter

    acoustic sealing for a low Rw wall.

    Effective sealants have the following properties:

    Good flexibility, (elastic set);

    Low hardness;

    Excellent adhesion, usually to concrete, timber, plaster and galvanised steel;

    Minimal shrinkage (less than 5%);

    Moderate density (greater than 800 kg/m3); and are,

    Fire rated where required (All walls required by the BCA to be sound rated also have fire ratings).

    All of the above properties must be maintained over the useful life of the building, that is, greater than 20 years.

    Note: Use of expanding foam sealants is not acceptable.

    Refer to the manufacturer to ensure the particular type or grade of sealant is suitable for the purpose.

    Doors

    Hollow, cored and even solid doors generally provide unsatisfactory sound insulation. Doors can provide direct

    air leaks between rooms lowering the overall Rw of the wall in which they are inserted. Where sound insulation

    is important, specialised heavyweight doors or, preferably, two doors separated by an absorbent lined airspace

    or lobby should be used.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.232

    ADV03780

  • 7/22/2019 Technical Manual Whole

    40/93

    Lightweight Panels Above Doors

    Panels are often incorporated for aesthetic reasons, however, they should not be used unless they have an R w

    equal to or better than the walls requirement.

    Air Paths Through Gaps, Cracks or Holes

    Seal all gaps, cracks or openings, however small, with an acoustic sealant. Holes readily conduct airborne

    sounds and can considerably reduce the Rw of a wall.

    Appliances

    Noise producing fixtures or appliances such as water closets, cisterns, water storage tanks, sluices,

    dishwashers, washing machines and pumps should be isolated from the structure with resilient mountings and

    flexible service leads and connections.

    Electrical Outlets & Service Pipes

    Penetrations of all sorts should be avoided but if unavoidable, seal around them effectively. If possible introduce

    a discontinuity in pipe work between fittings, such as a flexible connection within or on the line of a partition.

    Use acoustically rated boxes for all general power outlets, light switches, telephone connections, television

    outlets, etc. Seal the sides of electrical boxes and the perimeter of all penetrations with acoustic sealant. Offset

    all power outlets on either side of a wall by at least 100 mm.

    Bricks & Pavers Technical Manual

    Section 1.2. Brick Masonry Design 1.233

    ADV03781

  • 7/22/2019 Technical Manual Whole

    41/93

    Brick Masonry Construction1.3

  • 7/22/2019 Technical Manual Whole

    42/93

    The following information relates to the construction of brick walls to meet AS3700, the design and aesthetic

    requirements.

    Mortar

    AS3700: 2001, Table 10.1 gives the options for mortar mixes classified as M1 to M4. M1 mortars are for

    restoration applications. M2 mortars are for use in interior walls above dampcourse or in exterior walls above

    dampcourse if more than one km from a body of salt water and 10 km from a surf coast and the wall has

    protection from water ingress above. M3 and M4 mortars are those most commonly used in construction. Table

    11 gives the proportions of the most commonly used mortars. Other deemed-to-satisfy compositions are given in

    AS3700. Special mortars that are tested and shown to meet requirements are allowed with verification on site.

    Note: Proportions are by volume and should be measured with a bucket or gauge box, NOT A SHOVEL.

    Table 11. Typical Mortar Mixes

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.301

    ADV03783

    Refer to page 1.104 for description of Durability Class. *Methylcellulose type, not air entrainers such as detergent.

    Where masonry strength is crucial, trial walls should be constructed with the bricks and mortar to be used on

    the job, then tested before construction commences. Masonry bond strength is related to the suction of the

    bricks, the particle size distribution of the sand, cement content, additive contents, etc. For many jobs these

    panels can also be used as physical samples of the required quality of the bricklaying and cleaning.

    Note: AS 3700 allows the use of:

    Cements complying with AS 3972 or AS 1316

    Lime complying with AS 1672.1

    Sand that is free of any deleterious materials

    Water that is free from deleterious materials and

    Admixtures including plasticisers, air entraining agents and set retarders complying with AS1478.1,

    cellulose-type water thickeners, colouring pigments complying with BS EN 12878 and bonding polymers.t

    Mortar DurabilityMix proportions by volume

    Type Class Portland or Hydrated WaterBlended Cement Lime Sand Thickener*

    M1 PRO 0 1 3 No

    M2 PRO 1 2 9 No

    M3 GP 1 1 6 No

    M3 GP 1 0 5 Yes

    M4 EXP 1 12 412 No

    M4 EXP 1 0 4 Yes

  • 7/22/2019 Technical Manual Whole

    43/93

    Mortar (continued)

    No other material may be used until tests on masonry constructed with the mortar, made with the material or

    admixture shows the masonry complies with the standards requirements for compressive strength, flexural

    strength and durability.

    Deleterious materials are those reducing the strength or durability of the masonry and including anything that

    attacks the built-in components. This means the use of fire clay, detergent, sugar, soft drink, etc., are banned.

    Most of these materials severely reduce mortar strength and durability. Water thickener must be used only

    according to the manufacturers directions because overuse severely reduces mortar strength.

    Mortar Estimator

    Table 12. Estimated Material Requirements to Lay 1,000 Standard Bricks

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.302

    ADV03784

    Mix Composition 40 kg bags 25 kg bags Cubic metres Tonnes of

    (C:L:S) of cement of lime of sand damp sand

    M3 1 : 1 : 6 4 2.4 0.64 1.2

    M3 1 : 0 : 5 4 0 0.64 1.2

    M4 1 : 0 : 4 6.5 0 0.64 1.2

    M4 1 : 12 : 412 5.3 1.6 0.64 1.2

    This table assumes partial filling of cores and typical site wastage.

    Only make sufficient mortar for immediate use. If mortar starts to set, it may be re-tempered once only.

    Where bricklaying is interrupted, the mortar should be covered to prevent evaporation and mixed with the trowel

    before continuing. t

  • 7/22/2019 Technical Manual Whole

    44/93

    Mortar (continued)

    Mortar Colour

    The mortar colour can dramatically affect the overall look. The colour of mortar is influenced by the colour of the

    cement and the aggregates (sand). Many pigments are also available ranging in colour through red, yellow,

    brown, green, blue and black (mainly oxides but carbon black can be used to give black mortar). The cheapest

    way of colouring mortar is to use coloured sand. White and yellow sands are commonly available but red and

    brown sands are also available. Sands are normally natural materials which vary considerably even in the one

    deposit. To ensure colour consistency, sufficient sand from the one batch should be set aside for the whole job.

    Where colour is crucial to the look of the masonry, before accepting the sand, a trial wall should be built (4 bricks

    x 10 courses). After the mortar dries assess the colour. Where oxides or carbon black are used as colours never

    use more than 10% by weight of the cement content.

    Colours are additive in their effect and it is possible to get different shades and tones of mortar using different

    combinations of cement, sands and oxides.

    Table 13: Typical Coloured Mortar Components

    Note: The colour of mortar can be severely degraded by incorrect or poor brick cleaning.

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.303

    ADV03785

    Mortar Colour Cement Sand Oxide

    Red Grey White or Yellow or Red Red

    Yellow Off-white or Grey Yellow Yellow & Brown

    Cream Off-white Yellow None

    Tan Grey White or Yellow Brown

    Black Grey Yellow Black

  • 7/22/2019 Technical Manual Whole

    45/93

    Joint Types

    The type of joint can dramatically affect the overall look of brick masonry. Joints can be used to create a casual,

    rustic or formal look to brickwork. There are many different joints; the most common ones used in Australia are

    shown below.

    Terminology and joint preference differs in different countries and within Australia. Where there is any

    confusion, always use a drawing or physical sample to avoid misunderstandings.

    Shallow ironed joints are recommended in areas requiring exposure grade bricks and mortar. Tooling the joint to

    produce ironed and struck joints is equivalent to steel trowelling concrete and produces a dense smooth surface

    which sheds water and dirt better than other types of joint. Ironed and struck joints should always be used for

    bricks with straight sharp edges such as Smooth Face and Velour bricks.

    Raked joints may be used with any type of brick but they tend to retain dirt and may lead to streaks down the

    masonry in dirty environments. Raking must not come closer than 5 mm to any core. This usually limits raking to

    less than 10 mm, however it is best to check the bricks that are being used before raking. AS3700 specifies that

    joints in walls in marine, severe marine or aggressive environments or on aggressive soils must be tooled to a

    dense smooth surface. This precludes raking and in practice ironed joints are the only ones that consistently

    meet the requirement.

    Flush joints may be used with any type of brick. However, flush joints are particularly effective with rumbled

    bricks as flush joints make the joints look to be of variable thickness that gives a pleasing rustic look.

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.304

    ADV03786

    Flush Joint Raked Joint Ironed Joint Weathered JointStruck Joint

  • 7/22/2019 Technical Manual Whole

    46/93

    Joint Sizes

    Mortar bed joints are required to be less than 10 mm unless the design specifies another thickness. A different

    thickness may only be specified after the designer considers the effect on compressive and flexural strength of

    the masonry. During construction mortar bed joints are allowed to deviate by 3mm. Because of poor practice

    or lack of proper direction some slabs and footings are finished at the wrong height. Mortar joints up to 50 mm

    thick have been used to get the correct coursing, however, this is not allowed under AS3700.

    Perpends are to have a minimum design thickness of 5 mm. In structural brickwork perpends may be up to 10 mm

    thicker than the specified thickness but no thinner. In face brickwork perpends may deviate by 5 mm from the

    average width but in any one wall the maximum difference allowable between any two perpends is 8 mm.

    The preceding tolerances do not apply in the case of thin bed mortars and perpend tolerances do not apply where

    perpends are not filled with mortar.

    Weepholes

    Weepholes are to allow moisture that collects in the cavity to escape. Weepholes should be spaced at less than

    1200 mm centres wherever flashing is built into the masonry to shed water from the cavity. Weepholes are

    usually empty perpends (10 mm wide) but proprietary products are available to prevent the entry of insects. In

    high wind areas it has been known for water to be blown up the cavity onto the inner wall and as this is very

    undesirable, more, narrower weepholes are usually built into the wall. It is essential that weepholes remain open

    and render and other applied coatings, where used, must be raked out of the joint.

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.305

    ADV03787

  • 7/22/2019 Technical Manual Whole

    47/93

    Brick Estimator

    Brickwork is based on the 600 mm unit, (seven courses high and two and a half bricks long). This unit fits in with

    doors, windows and other building materials. The number of bricks required for a wall can be determined from

    the Brick Coursing Height and Brick Gauge tables on pages 1.310-1.312 of this manual. Select the height of the

    wall and from the following page for the brick height chosen determine the number of courses. From the next

    page for 230 mm long bricks or the one after for 290 mm bricks, determine the number of bricks for the length of

    your wall. A half brick should be calculated as 1 whole brick, due to site wastage. Multiply the number of bricks

    by the number of courses to give the number of bricks for the wall. Saw cutting bricks may mean getting two

    halves from a brick but this is not usual practice because of the cost of cutting.

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.306

    ADV03788

  • 7/22/2019 Technical Manual Whole

    48/93

    Brick bonds and other decorative effects

    A bond is the pattern in which bricks are laid. The most common bond is Stretcher Bond which consists of courses

    of full bricks where every course is offset half a brick from the course below. When following the mortar joint,

    stretcher bond has the longest vertical pathway and therefore the best bend strength.

    Stretcher bond is used in walls one brick wide. Where walls are two or more bricks wide then stretcher bond

    needs ties to hold the leaves together to give it a monolithic action. To avoid the use of ties traditional practice

    has been to lay some of the bricks sideways. This has usually been either full courses of headers with full

    courses of stretcher (English) or courses of alternating header and stretcher (Flemish). A variation of Flemish

    Bond is Garden Wall Bond where courses are made of a header and three stretchers alternating.

    Corner treatment can be different in these bonds. English corners end in full stretchers or full headers, and any

    part brick required to make up the course is set inside the corner. Dutch corners end in the part bricks.

    Variations on these bonds are common in particular a header course every three or six courses with stretcher

    courses between.

    Although these bonds have traditionally been developed for thick walls, they can be used in single leaf walls as

    a decorative effect using cut bricks for the headers. Such walls are usually non-load bearing. Cutting costs are

    high but not excessive as the headers have the cut side turned in and the bricks can be bolstered.

    Other decorative bonds may be used in non-load bearing applications, particularly in the form of panels. The

    limitations are strengths lower than Stretcher Bond and the cost of cutting and slower brick laying. The

    decorative effect of bonds is highlighted by using a mortar in a contrasting colour to the brick.

    Other bonds include:

    Stack Bond Bricks laid horizontally in vertical columns so all vertical joints align.

    Soldier Stack Bond Bricks laid vertically in vertical columns so all vertical joints align.

    1/3 Bond Every course is offset by 1/3 of a brick.

    Zigzag Bond, Vertical Zigzag Bond, 45 Stretcher Bond, Chevron Bond, Basket Weave Bond, 45 Basket

    Weave Bond and virtually any pattern that tessellates.t

    Bricks & Pavers Technical Manual

    Section 1.3. Brick Masonry Construction 1.307

    ADV03789

  • 7/22/2019 Technical Manual Whole

    49/93

    Brick bonds and other decorative effects (continued)

    Other decorative effects are available such as:

    Laying bands of bricks of the same colour with different textures eg smooth faced and rock faced;

    Laying bands of bricks with different (contrasting or complimentary) colours;

    Corbelling (bricks set out from the wall);

    Racking (bricks set back into the wall);

    Quoining (corner bricks in different colours or set out from the wall);

    Soldiers above openings or as a single course;

    Copings on piers and parapet walls;

    Sills in different colours or textures, using sill bricks, etc.; or,

    In the late 1800s bricks of contrasting colours were laid in patterns such as diamonds or crosses


Recommended