Date post: | 10-Feb-2018 |
Category: |
Documents |
Upload: | vincent-mutambirwa |
View: | 218 times |
Download: | 0 times |
of 93
7/22/2019 Technical Manual Whole
1/93
Brick Properties1.1
7/22/2019 Technical Manual Whole
2/93
Section 1.1 relates to the properties of bricks made to meet the requirements of Australian Standard AS4455 Part
1 Masonry Units. This information is provided as a guide only to the properties of interest to a masonry designer
or builder.
Brick Dimensions
The work size of a standard brick is: 76 mm high x 230 mm long x 110 mm wide.
Some bricks are made with different work sizes. For example brick heights of 119 mm and 162 mm to match 1.5
and 2 standard size brick heights, including mortar joint, respectively. 50 mm and 90 mm high bricks, 90 mm wide
bricks and 290 mm long bricks are made for different structural and aesthetic effect. Larger bricks are often used
for more economical laying and as a design feature either on their own or combined with smaller bricks.
In cyclonic areas larger (140 mm wide x 90 mm high x 290 mm long) hollow bricks are used to allow for
reinforcement and grouting in the wall. Wider (150 mm wide) bricks can also be used in walls requiring lower
sound transmission, higher fire resistance levels and higher load bearing capacity depending on the specific brick
properties.
Clay brick sizes may vary after they are fired but size variation between units averages out when blended properly
during laying. Brick dimensions are measured by dry stacking 20 units, measuring the total length, width and
height and comparing that measurement to 20 times the work size.
Bricks are classified according to how much 20 bricks together deviate from 20 times the work size.
For standard bricks, Dimensional Category DW1 means the height and width will differ by less than plus or
minus 50 mm from 20 times the work size, and the length will differ less than plus or minus 90 mm.
For standard bricks, Dimensional Category DW2 means the height and width will differ by less than plus or
minus 40 mm from 20 times the work size, and the length will differ less than plus or minus 60 mm.
Dimensional Category, DW0 means there are no requirements. This is usually reserved for non-standard
shaped bricks and bricks that have been rumbled or otherwise distorted during the manufacturing process
for aesthetic reasons.
Bricks & Pavers Technical Manual
Section 1.1 Brick Properties 1.101
ADV03743
7/22/2019 Technical Manual Whole
3/93
Brick Strength
Brick strength is defined as resistance to load per unit area and is expressed in mega Pascals (MPa).
Characteristic Unconfined Compressive Strength (fuc)
The characteristic unconfined compressive strength is used by engineers in the design of masonry to calculate
the strength of a wall. Bricks in any one batch have a range of strengths that would usually follow a normal
distribution. In a wall the different strength bricks contribute to the strength of the whole and the weakest brick
does not determine the strength of the wall. For safety, engineering practice has been to use characteristic
unconfined compressive strength. This is the strength 95% of the bricks will exceed and is typically 0.86 times
the lowest unconfined compressive strength found when measuring the compressive strengths of 10 samples.
Boral bricks usually have characteristic unconfined compressive strengths in the range 15 to 35 MPa.
Unconfined Compressive Strength
The unconfined compressive strength is a calculated number based on the compressive strength. To measure the
compressive strength of a brick, steel platens are used above and below. This constrains the surface and where
all other factors are equal, a shorter brick will have a higher compressive strength than a taller brick. To remove
this test effect, the compressive strength is multiplied by a factor, which varies with the height of the brick. The
resulting number is called the unconfined compressive strength and reflects the performance of the brick in a
wall. Theoretically, bricks which are identical except for their height should produce the same unconfined
compressive strength. This figure is not now used in masonry design, but is used to calculate Characteristic
Unconfined Compressive Strength.
Compressive Strength of Bricks
Brick strength is measured according to AS4456.4 Determining Compressive Strength of Masonry Units.
Individually crushing 10 bricks gives the compressive strength of each brick and the mean compressive strength
of the lot. These figures are not used in masonry design, but are used to calculate Unconfined Compressive
Strength.
Bricks & Pavers Technical Manual
Section 1.1 Brick Properties 1.102
ADV03744
7/22/2019 Technical Manual Whole
4/93
Water Absorption
Cold Water Absorption
The amount of water that a brick can absorb is measured by the cold water absorption test. There is no distinct
relationship between water absorption and the water-tightness of walls. The results of water absorption tests
are used by the brick manufacturer for quality assurance.
Initial Rate of Absorption
The initial rate of absorption (IRA) is the amount of water absorbed in one minute through the bed face of the
brick. It is a measure of the bricks suction and can be used as a factor in the design of mortars that will bond
strongly with units. As mortars other than the deemed to comply mortars are rarely used, the impact of the IRA
is primarily on the bricklayer. Bricklayers, through practical experience, adjust the mortar, the height of a wall
built in a day and the length of time before ironing the joints, according to the suction.
The bond between the masonry unit and mortar is largely influenced by the capacity of the brick to absorb water
and the ability of the mortar to retain the water that is needed for the proper hydration of cement. If the brick
sucks the water too quickly from the mortar, the next course may not be properly bedded. If the mortar retains
too much water, the units tend to float on the mortar bed, making it difficult to lay plumb walls at a reasonable
rate. In either case there will be poor bond.
The optimum value of IRA is considered to be between 0.5 and 1.5 kg/m 2/min. However, IRAs can exceed
these limits. The mortars water retentivity should be matched to the brick type where good bond strength is
critical.
Bricks & Pavers Technical Manual
Section 1.1 Brick Properties 1.103
ADV03745
7/22/2019 Technical Manual Whole
5/93
Durability
Salt attack is the most common durability problem affecting bricks. In the form of a solution, salt can be absorbed
into masonry. As the water evaporates, the salt is drawn towards the outside face. The evaporating water leaves
the solution super-saturated so salt crystals begin to form. The salt crystals grow in the pores just below the
surface and depending on the texture of the brick, the amount of salt, the rate of drying and the temperature, the
salt may fill the pores, exerting very high pressures on the matrix. The energy in the constrained salt crystal
increases and if sufficient pops a piece of the outer surface off and salt attack has begun.
Bricks are assessed and classed into three grades according to AS/NZS4456.10 Resistance to Salt Attack. In
summary the three grades of brick that can be used are as follows:
Protected Grade (PRO)
Suitable for use in elements above the damp-proof course in non-marine exterior environments. Elements
above the damp-proof course in all exterior environments, with a waterproof coating, properly flashed
junctions with other building elements and a top covering (roof or coping) protecting the masonry.
General Purpose Grade (GP)
Suitable for use in an external wall, excluding walls in severe marine environments or in contact with
aggressive soils and environments (see AS3700 Appendix E). General purpose grade bricks can also be used
in PRO applications.
Exposure Grade (EXP)
Suitable for use in external walls exposed to severe marine environments, i.e. up to one kilometre from a
surf coast or up to 100 metres from a non-surf coast or in contact with aggressive soils and environments.
The distances are specified from mean high water mark. Exposure grade bricks can also be used in PRO and
GP applications.
Boral bricks are classified as either EXP or GP.
Bricks & Pavers Technical Manual
Section 1.1 Brick Properties 1.104
ADV03746
7/22/2019 Technical Manual Whole
6/93
Moisture Expansion
Clay products expand over time as they absorb water into their structure. This is well known and documented
and must be consider when designing brickwork. The expansion is not uniform (it is logarithmic) over time. In the
first six months one quarter of the expansion occurs, one half in the first two years and three quarters in the first
5 years. The Characteristic Expansion is estimated from an accelerated test and expressed as a coefficient of
expansion (em) that for Boral bricks is usually between 0.8 and 1.2 mm/m/15 years.
Efflorescence
Bricks may contain soluble salts that come to the surface when the brick dries. The source of these soluble salts
is the raw materials used in the brick production process.
Brick efflorescence should not be confused with the efflorescence that is seen on masonry walls after
construction. This form of efflorescence is caused mainly from the raw materials and water used in the wall
construction process (eg. Mortar).
Brick efflorescence is usually white but there is a special form of efflorescence (known as vanadium staining) that
is coloured yellow, green or reddish-brown and is therefore particularly visible on light coloured bricks.
All efflorescence is more or less visible depending on the colour and surface texture of the brick.
Boral bricks have a nil to slight efflorescence.
Pitting due to Lime
If brickmaking raw materials contain particles of calcium carbonate, these will be converted into quicklime in the
kiln. Water subsequently combines with the quicklime to form hydrated lime and in the process expands. If lime
particles are sufficiently large and sufficiently near the surface they pop off a piece of the brick, leaving a
generally circular pit.
Boral Bricks rarely show lime pitting.
Bricks & Pavers Technical Manual
Section 1.1 Brick Properties 1.105
ADV03747
7/22/2019 Technical Manual Whole
7/93
Brick Masonry Design1.2
7/22/2019 Technical Manual Whole
8/93
The following design information is based on Australian Standard AS3700: 2001 Masonry Structures. Reference
to Clauses and Formulae are those used in AS3700. This information is provided as a guide only to the processes
involved in designing masonry. All masonry should be designed by a suitably qualified structural engineer.
Robustness
AS3700, Clause 4.6.1 requires walls to have an adequate degree of Robustness. Robustness is a minimum
design requirement, and may be overridden by fire, wind, snow, earthquake or live and dead load requirements.
In robustness calculations (AS3700 Clause 4.6.2), there are height, length, and panel action formulae. By reworking
the standard formulae and inserting known data, it is possible to determine whether a chosen design and Boral brick
will provide adequate robustness, as in the tables below and the charts on pages 1.202 to 1.204.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.201
ADV03749
Maximum Wall Length (m)
Wall Thickness (mm) Lateral Support One End Lateral Support Both Ends
90 1.08 3.24
110 1.32 3.96
150 1.80 5.40
230 2.76 8.28
Table 3. Maximum Wall Length where One or Both Ends are Laterally Restrained
Table 2. Maximum Height of Walls with Free Ends
Maximum Wall Height (m)
Wall Thickness (mm) No Lateral Support at Top Lateral Support at Top Concrete Slab on Top
90 0.54 2.43 3.24
110 0.66 2.97 3.96
150 0.90 4.05 5.40
230 1.38 6.21 8.28
Pier Thickness (mm) Maximum Height (m)
230 x 230 3.105
350 x 350 4.725
Table 1. Maximum Height of Isolated Piers
In the situation depicted in Table 3 above, height is not limited although length is. This typically applies to lift
shafts and stairwells. Control joints and openings greater than one fifth of the wall height are treated as free
ends unless specific measures are taken to provide adequate lateral support.
Where wall lengths exceed those in Table 3 above, AS 3700 Equation 4.6.2 (4) must be used to determine the maximum
height for a wall of the required length. Should the initial choice of product not provide a suitable solution, then a thicker
Boral brick or increased masonry width or extra restraints should be evaluated.t
7/22/2019 Technical Manual Whole
9/93
Robustness (continued)
How to Use the Boral Robustness Graphs
These charts determine the minimum brick thickness for a known wall height, length and restraint criteria.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.202
ADV03750
1. Select the graph for the chosen wall restraint
(support) criteria. In this example there is
support on one side and the top is supported by
other than a concrete slab. Typically this would
be a wall supporting roof frames, joined into
another wall at one end and with a door at the
other end.
2. Plot the intersection of the design Wall Height
and the Wall Length on the graph. (For this
example 3 m height x 5 m length).
3. The lines ABOVE the intersection point indicate
wall thickness that are acceptable. In this
example, the intersection point is just below the
line for 110 mm bricks. Therefore a single leaf of
110 mm bricks would be suitable and the most
economical.
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
ALL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
230mm
90x90mm
110mm
90mm
150mm
110x110mm
FR
S
R
Laterally supported one end
and top laterally supported
by other than concrete slab
7/22/2019 Technical Manual Whole
10/93
Robustness Limits
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.203
ADV03751
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
90x90mm
110mm
90mm
150mm
110x110mm
RR
R
R
Laterally supported both ends
and top laterally supported
by a concrete slab
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
90x90mm
110mm
90mm
150mm
110x110mm
RR
S
R
Laterally supported both ends
and top laterally supported
by other than concrete slab
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
90x90mm
110mm90mm
150mm
110x110mm
RR
F
R
Laterally supported
both ends and
top unsupported
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
230mm
90x90mm110mm
90mm
150mm110x110mm
FR
F
R
Laterally supportedone end andtop unsupported
7/22/2019 Technical Manual Whole
11/93
ADV03752
1.204
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Robustness Limits
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
90x90mm110mm
90mm
150mm
110x110mm
FR
R
R
Laterally supported one end
and top laterally supported
by a concrete slab
8
7
6
5
4
3
2
1
01 22 3 4 5 6 7 8
W
A
LL
HEIG
HT
(m
)
W A L L L E N G T H ( m )
230mm
90x90mm
110mm
90mm
150mm
110x110mm
FR
S
R
Laterally supported one endand top laterally supported
by other than a concrete slab
7/22/2019 Technical Manual Whole
12/93
Masonry Strength
Masonry Strength is defined as resistance to load per unit area. It must be remembered that thicker masonry will
support more load than thinner masonry of the same strength.
Characteristic Compressive Strength of Masonry fm
fm = km kh fuc
km is a mortar strength factor and kh is a factor for the amount of mortar joints.
km is 1.4 for M3 mortar and 1.5 for the stronger M4 mortar (see AS 3700 Table 3.1 for a full list of factors).
kh is 1 for 76 mm high units with 10 mm mortar beds and is 1.24 for 162 mm high bricks with 10 mm mortar
beds (see AS 3700 Table 3.2 to derive factors for other unit and joint heights). In other words, a wall of
double height bricks is more than 20% stronger than a wall of 76 mm high bricks of the same fuc.
fuc is the characteristic unconfined compressive strength of bricks.
Characteristic Flexural Tensile Strength of Masonry fmt
In flexing, the top of the arc is in tension and the bottom of the arc is in compression. Masonry is good in
compression but poor in tension. Flexural strength depends on the mortar/brick bond and for design purposes is
generally taken to be zero. Using up to 0.2 MPa is permitted when designing for transient loads such as wind,
earthquake, etc. Higher bending forces may be used for design but these require site testing to verify
construction meets the stated values.
Characteristic Shear Strength of Masonry fms
Shear strength, like flexural strength, is related to the mortar/brick bond. For design purposes, at the damp
course, it is taken to be zero unless testing shows another value. Elsewhere, mortar joints have f ms values of
between 0.15 and 0.35 MPa.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.205
ADV03753
7/22/2019 Technical Manual Whole
13/93
Durability of Masonry
AS3700 requires masonry to be designed to continue functioning satisfactorily throughout its design life without
undue maintenance. That is, all masonry materials, including bricks, mortar and all built-in components, must be
sufficiently durable for the exposure classification of the site (see AS3700 Appendix E). Masonry designed to
meet the requirements of AS3700 Section 5, is deemed to comply with the durability requirements and Table 5.1
defines the durability requirements for bricks, built-in components and mortar in different environments.
Salt attack is the most common durability problem. In the form of a solution, salt can be absorbed into masonry.
As the water evaporates, the salt is drawn towards the outside face. The evaporating water leaves the solution
super-saturated so salt crystals begin to form. The salt crystals grow in the pores just below the surface and
depending on the texture of the brick, the amount of salt, the rate of drying and the temperature, the salt may
fill the pores, exerting very high pressures on the matrix. The energy in the constrained salt crystal increases and
if sufficient pops a piece of the outer surface off and salt attack has begun.
Boral bricks graded General Purpose (GP) are suitable for use in all walls, excluding external walls in severe
marine environments or in all walls in contact with aggressive soils and environments.
Boral bricks graded Exposure Grade (EXP) are suitable for use in all walls including external walls exposed to
severe marine environments, i.e. up to 1 km from a surf coast or up to 100 m from a non surf coast or walls in
contact with aggressive soils and environments. The distances are specified from mean high water mark.
Walls below damp proof course often require greater durability, even if they are well away from the coast, as
they may be subjected to saline, acidic or alkaline soils. If unsure of the corrosive nature of the site, an
inexpensive total soluble salt content test for soil is available in most areas. Remember it is the designers
responsibility to specify the appropriate durability grade of bricks, mortar and built-in components and it is the
builders responsibility to order bricks, etc. of appropriate durability grade specified by the designer. Brick
manufacturers cannot take any responsibility in this decision as they are not aware of the design requirements
of each site. t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.206
ADV03754
7/22/2019 Technical Manual Whole
14/93
Durability of Masonry (continued)
Refer to Section 1.4 Property Tables for tabulated properties of individual brick types for their salt attack
resistance category.
Mortar mix requirements for durability are referred in Table 11, page 1.301 of this manual and are detailed in
AS3700 Table 10.1.
M4 mortars are required and mortar joints must be tooled in all situations requiring exposure grade materials.
Concrete floors, paths and steps are a source of sulfate salts that if dissolved in water may enter the brickwork and
cause salt attack. Exposed slabs supported on external brickwork should clear the brickwork by 50 mm and
incorporate a drip groove to prevent the run-off from the slab running down the brickwork. A damp proof course
(usually a double layer) is also used under the slab on top of the bricks to prevent water passing through the slab
into the bricks and as a slip joint to prevent a build up of forces as the concrete shrinks and the bricks expand
over time.
Landscaping and gardening practices are also possible sources of salt attack. Care must be taken to not bridge
the damp proof course when landscaping at the base of walls. Watering gardens and lawns, against walls, may
cause salts (fertilisers) to splash up on to the wall where they are absorbed and may cause salt attack.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.207
ADV03755
7/22/2019 Technical Manual Whole
15/93
Brick Ties
In brick veneer construction, ties are used to pass all the lateral out-of-plane loads and forces (such as from wind)
to the structural backing. In cavity brick construction ties either pass the lateral out-of-plane loads and forces to
the stronger leaf or share them between the leaves.
The design of ties in masonry for structural purposes must comply with AS3700 Clause 7.7 for veneer or Clause
7.8 for cavity construction. For small buildings the tie requirements are covered in AS3700 Clause 12.3.4 for brick
veneer construction and Clause 12.3.3.2 for cavity brick construction.
Type A ties are those that have no specific seismic design characteristics. It is difficult to find brick ties other
than Type A in Australia. Ties are available in heavy, medium and light duty in galvanised steel, stainless steel
and plastic. Plastic ties are usually reserved for acoustic applications. Stainless steel ties are used in situations
requiring exposure grade materials or very long life. Galvanised steel ties are those most commonly used.
The Newcastle (NSW) earthquake which occurred in 1989 showed masonry survived well except where the ties
were deficient. Problems found included:
galvanised ties rusted through;
ties only built into one leaf during construction;
loose ties;
absent ties; and,
incorrect duty ties used.
Ties are required to meet the durability requirement of the site for the design life of the building. Should the
design life of the building be exceeded and the ties begin to fail, they can be replaced with remedial ties but this
is a very expensive process and as ties are hidden it is unlikely they will be seen until a catastrophic failure
occurs. As sustainability considerations become more important, the life of buildings is likely to be extended.
Properly maintained, brick buildings may last for centuries. It should be remembered that stainless steel brick
ties offer a longer service life and, although more expensive as a proportion of the overall building cost, the
difference is trivial.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.208
ADV03756
7/22/2019 Technical Manual Whole
16/93
Movement in Masonry Walls
To allow for movements in masonry (expansion and contraction and footing movement) control joints are
required. These can usually be constructed so that the expansion joint and the articulation joint are one and
the same.
Expansion Joints
Expansion and contraction must be allowed for in masonry design by inserting control joints at spacings designed
to suit the magnitude of the movement.
Clay products expand permanently over time. This is the opposite of cement-based products, which permanently
shrink. For this reason it is unwise to use clay and concrete units in the same band in a wall. If clay bricks are
used in concrete framed buildings, control joint spacing and workmanship are critical, as the bricks will expand
as the concrete frame shrinks.
The magnitude of thermal changes varies from brick to brick depending on the many factors, however, allowing
0.008 mm/m/C is usually recommended. Expansion and contraction from wetting and drying of clay bricks is less
than for concrete and calcium silicate products and usually can be ignored in brick masonry design.
AS3700, Clause 4.8 requires expansion joints to be spaced to limit panel movement so that movement from both
sides closes joints by less than 15 mm and joints are at least 5 mm wide when closed. This means the gap, when
constructed, should be 20-25 mm. However, in most buildings articulation joints are used and these are closer
than required for expansion making separate expansion joints unnecessary.
Articulation Joints
Articulation joints are vertical gaps that allow for minor footing movements, to prevent distress or significant
wall cracking. Articulation joints provide the flexibility needed when building on reactive clay soils and usually
are not required for masonry on stable sites (classified according to AS2870). Spacing of articulation joints
depends on the site classification and the slab or footing design, but where used must be placed no closer than
0.5 metres and no further than 3 metres from all corners. The width of articulation joints depends on the height
of the masonry: 10 mm for masonry up to 3 metres and 15 mm for masonry up to 6 metres high. t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.209
ADV03757
7/22/2019 Technical Manual Whole
17/93
Movement in Masonry Walls (continued)
Control Joints (General)
Control joints should be used beside large openings, where wall thickness changes (except where this is for
support eg. engaged piers), where wall height changes by more than 20%, at changes of level in footings and at
other points of potential cracking. Control joints must not continue through bond beams.
Ideally, control joints are located near a corner and concealed behind a down pipe. The bricklayer and renderer
must keep the control joint clean, otherwise, bridging mortar or render will induce cracks as the masonry moves.
External control joints should be finished with a soft flexible sealant to prevent moisture penetration.
The design and construction of control gaps in the external leaf of a full brick wall is identical to that in brick
veneer. In internal masonry, control gaps are not usually required, except at re-entrant angles in long walls.
However, where an internal control joint is required the design is as for external leaves but the thermal
component may be ignored in calculations. Internal control joints can usually be located at a full-height opening
such as a door or window.
Ties are required on both sides of a control joint, but where it is not possible to use them masonry flexible
anchors (MFAs) must be used across the joint. Where MFAs are used in walls over 3 metres or in walls exposed
to high winds, MFAs must be built in at half height and every seventh course (600 mm) above. MFAs are ties that
are of a type that only allows movement in one plane. Unless ties are used, control joints create a free end in
terms of Robustness and Fire Resistance Level calculations for structural adequacy, so their positioning is critical
to the overall design of the structure.
In portal frame construction, the control
joint is positioned at a column so that
both ends can be tied to the columns
flanges.
The principles of control joint
construction are illustrated in the
adjacent figure.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.210
ADV03758
Articulation joints withcompressible backingand mastic sealant
Dividing wall witharticulation joint andMFA's at intersectionwith cavity wall
Brick ties on each sideof articulation joint
Articulationjoint
7/22/2019 Technical Manual Whole
18/93
Thermal Properties
As at 2004, the Building Code of Australia (BCA) requires energy efficiency performance for housing (BCA Vol 2).
Australia is divided into 8 climatic zones. (Sydney and Perth are in Zone 5, Adelaide and Melbourne are in Zone
6, Brisbane is in Zone 2 and Canberra is in Zone 7). The zones and Local Government boundaries are detailed on
a map, which is available from the Australian Building Codes Board (www.abcb.gov.au) but the Local Council
should be able to provide the information where there is any doubt.
The BCA set the minimum energy efficiency requirement of 3.5 stars for Zones 1-3 and 4 stars for Zones 4-8. While
the BCA sets these minimum requirements, State governments may adopt these minimums or may opt for different
requirements. Local authorities may adopt higher star ratings but may not opt for lower ratings than the State adopts.
The ABCB has indicated they are considering requiring 5 stars in line with Victoria and ACT.
Victoria requires a 5 star rating on the building fabric from July 2005 using FirstRate or NatHERS software.
Pre-July 2004, the requirement was 4 stars on the building fabric. Post July 2004, the requirement is either 5 stars
on the building fabric; or 4 stars on the building fabric plus water saving measures and a solar hot water system;
or 4 stars on the building fabric plus water saving measures and a rain water tank.
ACT requires 5 stars from ACTHERS software.
South Australia requires 4 stars from NatHERS or FirstRate software.
The NSW situation is complex. From 1 July 2004 in the Sydney Metropolitan area and 1 July 2005 eleswhere in the
State all new housing, dual occupancies and small (under 300 m2) hostel type accommodation will be required to
have a BASIX rating. From 1 February 2005 in the Sydney Metropolitan area and 1 October 2005 elsewhere in the
state this will apply to all new residential developments. From 1 July 2005 these measures apply to alterations to
residences in Sydney and from 1 October 2005 elsewhere in the State. BASIX is a comprehensive sustainability
rating software, incorporating energy and water efficiency initially with the intention of including stormwater,
transport, site ecology, waste and recycling and materials at a later date. It is a web-based system in which you
enter data about the development in boxes and the whole has to meet targets to get Development Application
approval. BASIX is aimed at achieving energy reductions of 25% (going up to 40% in July 2006) and potable water
savings of 40%.
Different star rating software can produce different ratings. To overcome this, the Australian Building Codes Board
has developed a protocol to ensure all star rating software, as nearly as practical, produces the same rating for the
same design.t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.211
ADV03759
7/22/2019 Technical Manual Whole
19/93
Thermal Properties (continued)
The requirements to meet a star rating are complex because the rating is based on the total building design for a
given site. It is important to remember that roof insulation, shading, orientation and window size and placement
have a much greater impact on energy efficiency than the walls. Heat enters and leaves buildings more readily
through the windows and roof and greater insulation in the roof space is usually the most cost-effective measure
to increase star ratings. Although there is not an exact relationship, to meet the star ratings walls generally have
to meet the following requirements:
Table 4. Wall Insulation Requirements
The BCA states that brick veneer construction made with a single leaf of 110 mm wide bricks has an R value of
0.54 and must incorporate insulation to produce the values above.
Cavity clay masonry is treated differently and is deemed to satisfy wall insulation requirements if it achieves a
mass of 220 kg per square metre of wall in Zones 5 and 6 and in the ACT. In Zone 6 the masonry must be
constructed on a concrete slab in contact with the ground. In the ACT the masonry must be constructed on a
concrete slab in contact with the ground or having an insulated timber floor.
Cavity clay masonry is deemed to satisfy because heavy mass walling has a high thermal inertia (thermal lag).
Heat is slowly absorbed during the day and slowly lost during the cool night. Most thermal requirements focus
on thermal insulation, denoted as R value. When dealing with heavy mass walling and typical non-tropical
diurnal temperature cycles, R value is misleading as it assumes a steady state (constant temperature difference
across the wall) which is not the case because of the day-night temperature cycle. Cavity brick houses are well
known to have a lower temperature fluctuation than lighter weight construction and the deemed-to-satisfy
provision is in recognition of this fact.
In February 2004 the ABCB released a proposal to impose energy efficiency requirements in the BCA Volume 1
for Class 2, 3 & 4 buildings, (residential buildings other than houses). ACT currently has requirements on these
classes of building and Victoria has requirements on these classes and on Class 9c buildings. The requirements
are essentially the same as for Class 1 buildings.
Zones Wall insulation value1, 2, 3 & 5 R1.4
Qld Zones 1, 2 & 3 R1.0
4 & 6 R1.7
7 R1.9
8 R2.8
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.212
ADV03760
7/22/2019 Technical Manual Whole
20/93
Masonry Design for Fire Resistance
Fire Resistance Levels (FRL)
FRLs come from the Building Code of Australias (BCA) Volume 1 tables for Type A, B or C construction. The Type of
construction depends on the Class of building and the number of stories or floors. FRLs for housing come from BCA
Volume 2.
There are three figures in the Fire Resistance Level.
Eg: FRL 120/60/90 means that the wall must achieve Structural Adequacy for 120 minutes / Integrity for 60 minutes /
Insulation for 90 minutes.
Structural Adequacy
This governs the walls height, length, thickness and restraints. Brick suppliers do not control the wall height,
length or restraints so therefore do not control Structural Adequacy.
Integrity
This is the resistance to the passage of flame or gas. To provide integrity, walls must be structurally adequate
and they must maintain insulation. Extensive fire testing of masonry has shown integrity to be closely related to
structural adequacy or insulation. AS 3700 therefore allows Integrity to be equal to the lesser of the Structural
Adequacy or the Insulation periods.
Insulation
This is resistance to the passage of heat through the wall. Insulation is a function of the thickness of the brick
as shown in Table 5, page 1.222 of this manual.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.213
ADV03761
7/22/2019 Technical Manual Whole
21/93
Masonry Design for Structural Adequacy FRL
Structural Adequacy is a minimum provision and may be overridden by design for robustness, wind, live or
earthquake loads.
A fire on one side of a wall will heat that side, making it expand and lean towards the fire. When the lean or bow
reaches half the thickness of the original wall, the wall becomes structurally inadequate. The formulae in
AS3700, Clause 6.3.2.2 limits the panel size, depending on its restraints and thickness.
The Slenderness ratio (Srf) of a proposed wall is calculated according to AS 3700 Clause 6.3.2.2. If this value is
less than the maximum Srf
in Table 6.1 of the Standard [or the Srf
calculated from Fire Tests and AS 3700 Clause
6.3.3(b)(ii)], then the wall complies. If the S rf of the wall is greater than the maximum permissible, it must be
recalculated for an increased thickness and/or extra restraints.
There are 3 formulae for calculating Srf.
AS 3700 Formula 6.3.2.2 (1) and (2) are the formulae for vertically spanning walls (with no support along either
vertical edge).
Formula (1) and (2) always govern where there is no end restraint, and often govern where walls are long, relative
to their height. Projects with multiple wall lengths (eg: home units) can use this formula as a one size fits all
method of calculating the wall thickness.
AS 3700 Formula 6.3.2.2 (3) allows a wall to exceed the height given by formula (1) and (2) provided the top and
at least one end is supported.
AS 3700 Formula 6.3.2.2 (4) allows a wall to exceed the height given in formula (3) where walls are short, relative
to their height (eg: a lift well or vent shaft). Short walls with no top restraint often occur in situations like portal
frame factories.
For cavity walls where both leaves are equally loaded (within 10 per cent of each other, including where there is
no load on either leaf) the thickness is equal to two-thirds of the sum of the thicknesses of both leaves and the
edge restraint condition is that for the leaf not exposed to the fire. Where one leaf is more heavily loaded than
the other, the thickness and edge restraint condition is that of the more heavily loaded leaf. Where cavity walls
are constructed with leaves of different masonry unit types, the structural adequacy is based on the less fire
resistant material.t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.214
ADV03762
7/22/2019 Technical Manual Whole
22/93
Masonry Design for Structural Adequacy FRL (continued)
Refer to the Structural Adequacy Graphs on the following pages for maximum height and length values for walls
of different thicknesses and restraint conditions.
An appropriately qualified engineer should check all calculations. Other loads may supersede Structural
Adequacy requirements.
How to Use the Boral Structural Adequacy FRL Graphs
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.215
ADV03763
1. Select the graph with Structural Adequacy for
the required minutes. (240 minutes for this
example).
2. Select the graph for the chosen wall restraint
(support) criteria. (Support on both vertical
edges, top and bottom for this example).
3. Plot the intersection of the design Wall Height
and the Wall Length on the graph. (For this
example 3 m height x 5 m length).
4. The line ABOVE the intersection indicates the
minimum brick thickness required for the wall.
In this example, 150 mm bricks would be
suitable and the most economical.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
S
S
Laterally supportedon all sides
7/22/2019 Technical Manual Whole
23/93
ADV03764
1.216
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Structural Adequacy for 60 Minutes FRL
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm
90mm
150mm
230mm
SS
S
S
Laterally supported
on all sides
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm
90mm
150mm
230mm
FS
S
S
Laterally supported
on three sides,
one end unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm
90mm
150mm
230mm
SS
F
S
Laterally supported
on three sides,
top unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm
90mm
150mm
230mm
FS
F
S
Laterally supported
one end and bottom,
one end and top unsupported
7/22/2019 Technical Manual Whole
24/93
ADV03765
1.217
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Structural Adequacy for 90 Minutes FRL
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
S
S
Laterally supported
on all sides
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIGHT
BETWE
EN
SUPPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110m m90mm
150m m
230mm
FS
S
S
Laterally supported
on three sides,
one end unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
F
S
Laterally supported
on three sides,
top unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
FS
F
S
Laterally supportedone end and bottom,
one end and top unsupported
7/22/2019 Technical Manual Whole
25/93
ADV03766
1.218
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Structural Adequacy for 120 Minutes FRL
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
S
S
Laterally supported
on all sides
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
FS
S
S
Laterally supported
on three sides,
one end unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm230mm
SS
F
S
Laterally supported
on three sides,
top unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
FS
F
S
Laterally supportedone end and bottom,
one end and top unsupported
7/22/2019 Technical Manual Whole
26/93
ADV03767
1.219
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Structural Adequacy for 180 Minutes FRL
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
S
S
Laterally supported
on all sides
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
FS
S
S
Laterally supported
on three sides,
one end unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm230mm
SS
F
S
Laterally supported
on three sides,
top unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm230mm
FS
F
S
Laterally supportedone end and bottom,
one end and top unsupported
7/22/2019 Technical Manual Whole
27/93
ADV03768
1.220
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Structural Adequacy for 240 Minutes FRL
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
SS
S
S
Laterally supported
on all sides
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETW
EE
N
SU
PPORTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm
230mm
FS
S
S
Laterally supported
on three sides,
one end unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm230mm
SS
F
S
Laterally supported
on three sides,
top unsupported
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
01 2 3 4 5 6 7 12111098
HEIG
HT
BETWE
EN
SU
PPO
RTS
(m
)
L E N G T H B E T W E E N S U P P O R T S ( m )
110mm90mm
150mm230mm
FS
F
S
Laterally supportedone end and bottom,
one end and top unsupported
7/22/2019 Technical Manual Whole
28/93
Structural Adequacy for Panels with Unsupported Ends
This figure shows the situation where there is support top and bottom but none on the sides. This applies
where there are control joints, large openings, long walls, etc. To use this graph select the desired FRL in
minutes and the height of the wall. The line above the intersection shows the brick thickness required.
Maximum Wall Heights for Structural Adequacy for any Wall Length
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.221
ADV03769
7
6
5
4
3
2
1
060 90 120 240180
M
A
XIM
UM
W
ALL
HEIGHT
(m
)
F R L F O R S T R U C T U R A L A D E Q U A C Y
( m i n u t e s )
110mm
90mm
150mm
230mm
FF
S
S
Top and bottom supported,
ends not supported.
7/22/2019 Technical Manual Whole
29/93
Masonry Design for Integrity FRL
It is impractical to provide test results for all possible wall designs, and therefore Integrity must be proved in
some other way. The most practical way to prove Integrity is to prove Structural Adequacy and Insulation
equal to or better than the Integrity requirement. Logically, if the wall is designed to minimise bowing it will
not crack and therefore resist the passage of flame and gas for the specified time.
This method is also the best way to prove Integrity even when a wall may not be required to comply with a
Structural Adequacy FRL value, such as is the case with non-load bearing walls. Eg. If the BCA requires an FRL
of -/90/90, the wall has no actual Structural Adequacy requirement, but to prove Integrity of 90 minutes, the
wall must be structurally adequate for at least 90 minutes.
Masonry Design for Insulation FRL
Insulation is the one FRL component that a brick manufacturer does control. It is governed by the type of
material and material thickness.
Material thickness (t) is defined in AS3700, Clause 6.5.2 as the overall thickness for bricks with cores not more
than 30% of the bricks overall volume.
For cavity walls, t = the sum of material thicknesses in both leaves.
Effect of Recesses for Services on FRLs
Recesses that are less than half of the masonry thickness and are less than 10,000 mm2 (0.01 m2) for both sides
within any 5 m2 of the wall area do not have an effect on fire ratings.
If these limits are exceeded, the masonry design thickness must be reduced by the depth of the recess.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.222
ADV03770
Wall thickness (mm) 90 110 140 or 150160 (150 plus 10 mm
230180 220
render on both sides) (90/90 cavity) (110/110 cavity)
Insulation period (minutes) 60 90 120 180 240 240 240
Table 5. Insulation periods for standard bricks (minutes)
Note: Wall thickness excludes render on side of wall exposed to fire.
7/22/2019 Technical Manual Whole
30/93
Effect of Chases on Fire Rated Masonry
Structural Adequacy FRL
To assess the effect of chases on Structural Adequacy FRLs, the direction in which the wall spans must be taken
into account.
Walls spanning vertically may be chased vertically to full height but horizontal chases are limited in length
to 4 times the walls thickness.
Walls spanning vertically and horizontally may be chased either horizontally up to half the walls length or
vertically up to half the walls height.
If these limits are exceeded, the masonry design thickness must be reduced by the depth of the chase or, in the
case of vertical chases, designed as 2 walls with unsupported ends at the chase. Horizontal chases in all walls
should be kept to a bare minimum.
Note: Chases affect the sound reduction capacity of walls. See Acoustic Design page 1.225 of this manual.
Integrity and Insulation FRLs
AS3700 limits the maximum depth of chase to 30 mm and the maximum area of chase to 1,000 mm2. The
maximum total area of chases on both sides of any 5 m2 of wall is limited to 100,000 mm2 (0.1 m2). If these limits
are exceeded, the masonry design thickness must be reduced by the depth of the chase.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.223
ADV03771
7/22/2019 Technical Manual Whole
31/93
Options for Increasing FRLs
Structural Adequacy FRLs can be increased by adding wall stiffeners, by increasing the overall thickness, by
adding reinforcement or by protecting the wall, e.g. with Boral Plasterboards FireStop board, fixed to furring
channels (on both sides of the wall if a fire rating is required from both sides). Note: Be careful of the effect of
plasterboard on sound reduction in party walls. See Acoustic Design page 1.225 of this manual.
Integrity FRLs are increased by increasing the other two FRL values to the required Integrity FRL.
Insulation FRLs can be increased by adding another leaf of masonry, by rendering both sides of the wall if the fire
can come from either side. Note: Only ONE thickness of render is added to the material thickness and that must
be on the cold side because the render on the exposed face will drop off early in a fire.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.224
ADV03772
7/22/2019 Technical Manual Whole
32/93
ACOUSTIC DESIGN
Acoustic Performance Rating
The BCA requirements for Class 1, 2, 3 and 9c buildings changed in May 2004 with the issue of Amendment 14.
Amendment 14 has been adopted by all jurisdictions other than Queensland, Northern Territory and Western
Australia where Amendment 13 continues in force. It must be remembered that the BCA requirements are the
minimum requirements and some Local Authorities may require better performance. Check with Local Councils
for specific requirements above the BCA minimums. Note: Incremental improvements in sound insulation come
at an ever-increasing cost.
The BCA Amendment 14 requirements are met by:
1. Testing a sample of constructed walls to verify that they meet the Weighted Standardised Level Difference
(Dnt,w explained further in Acoustic Performance On-Site on page 1.231 of this manual) requirements; or
2. Constructing walls using the same materials and techniques as walls that have been constructed and tested in a
laboratory and shown to meet the Weighted Sound Reduction Index (Rw) requirements; or,
3. Constructing walls using the materials and techniques in the Acceptable Construction Practice section of
the BCA; and,
4. Where impact sound reduction is required, it is to be achieved by discontinuous construction; and,
5. Except where the requirements are verified by on-site testing, chasing of services into masonry walls is not
allowed and electrical outlets on either side of the wall must be offset by no less than 100 mm. t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.225
ADV03773
7/22/2019 Technical Manual Whole
33/93
ADV03774
1.226
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Building service Adjacent room Barrier rating
A duct, soil, waste, water supplySole occupancy unit habitable room
Rw40
or stormwater pipe passingother than a kitchen
through a separating wall Sole occupancy unit kitchen or Rw25non habitable room
Table 9. BCA Amendment 14 Service separation* in Class 1, 2, 3 & 9c buildings.
* In Class 1 buildings the requirements apply to those services that pass through more than one building. In Class 2, 3 & 9c requirements apply
to all stormwater pipes and other services that pass through more than one sole occupancy unit.
Wall Separating Wall Rating
Sole occupancy unit all areas Sole occupancy unitRw45 all areas except those below
Sole occupancy unit all areas Laundry, kitchen Rw45
and
discontinuous construction
or
No less resistant to impact
noise than a deemed-to-
satisfy wall
Sole occupancy unit al l areas Bathroom, sanitary compartment (but not anRw45
associated ensuite), plant room, utilities room
Table 8. BCA Volume 1 Amendment 14 Requirements for walls separating sole occupancy units from otherparts of the building in Class 9c Buildings (aged care facilities).
Table 6. BCA Volume 2 Amendment 14 Requirements for walls separating two or more Class 1 Buildings
Wall Separating Wall Rating
Sole occupancy unit Sole occupancy unit
all areas all areas except those belowRw+Ctr50
Sole occupancy unit bathroom, sanitary Sole occupancy unit Rw+Ctr50
compartment, laundry or kitchen habitable room except a kitchen and
discontinuous construction
Wall Separating Wall RatingSole occupancy unit Sole occupancy unit
Rw+Ctr50 all areas except those below all areas except those below
Sole occupancy unit bathroom, Sole occupancy unit Rw+Ctr50
sanitary compartment, laundry or kitchen habitable room except a kitchen and
discontinuous construction
Sole occupancy unit all areas Plant room or lift shaft Rw+Ctr50
and
discontinuous construction
Sole occupancy unit al l areas Stairway, public corridor, publ ic lobbyRw50or areas of different classification
Table 7. BCA Volume 1 Amendment 14 Requirements for walls separating sole occupancy units from otherparts of the building in Class 2&3 Buildings.
Acoustic Performance Rating (continued)
7/22/2019 Technical Manual Whole
34/93
Weighted Sound Reduction Index (Rw)
Rw is a single-number rating of the sound reduction through a wall or other building element. Since the sound
reduction may be different at different frequencies, test measurements are subjected to a standard procedure
that yields a single number that is about equal to the average sound reduction in the middle of the human hearing
range. Two spectral corrections can be applied to Rw: C and Ctr. C compensates for medium to high
frequency noise and Ctr compensates for low frequency noise. C and Ctr are both negative numbers.
Impact Sound Resistance
The BCA Amendment 14 says there is no appropriate test for impact sound reduction in walls. However, in the
case of Class 9c buildings the BCA allows impact sound reduction to be demonstrated by showing a wall
performs no worse than a deemed-to-satisfy wall. To achieve impact sound resistance, the BCA requires walls
consist of two leaves with at least a 20 mm cavity between them and if ties are needed in masonry walls they
must be of the resilient type. Except for the resilient ties in masonry walls there are to be no mechanical linkages
between the walls, except at the periphery (i.e. through walls, floors and ceilings).
BCA Deemed-to-Satisfy Walls
BCA Volume 1 Amendment 14 Specification F5.2 Table 2 gives deemed-to-satisfy walls for sound insulation for
walls separating sole occupancy units.
BCA Volume 2 Amendment 14 Table 3.8.6.2 gives deemed-to-satisfy walls for sound insulation for walls
separating two or more Class 1 Buildings. These walls are the same as those in Volume 1 except only walls
achieving Rw+Ctr50 are allowed.
Deemed-to-satisfy clay brick walls are detailed on the following pages. t
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.227
ADV03775
7/22/2019 Technical Manual Whole
35/93
ADV03776
1.228
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Two leaves of 110 mm clay brick masonry with:
(a) A cavity not less than 50 mm between leaves; and
(b) 50 mm thick glass wool insulation with a density of 11
kg/m3 or 50 mm thick polyester insulation with a density
of 20 kg/m3 in the cavity.
Construction Rating
Table 10. BCA Volume 1 Amendment 14 Deemed-to-Satisfy Brick Walls
BCA Deemed-to-Satisfy Walls (continued)
Rw+Ctr50
Two leaves of 110 mm clay brick masonry with:
(a) A cavity not less than 50 mm between leaves;
and
(b) 13 mm cement render on each outside face.
Rw+Ctr50
Single leaf of 110 mm clay brick masonry with:
(a) A row of 70 mm x 35 mm timber studs or 64 mm steel studs
at 600 mm centres, spaced 20 mm from the masonry wall;
and
(b) 50 mm thick mineral insulation or glass wool insulation with
a density of 11 kg/m3 positioned between studs; and,
(c) one layer of 13 mm plasterboard fixed to outside face of
studs and outside face of masonry.
Rw+Ctr50
Single leaf of 90 mm clay brick masonry with:
(a) A row of 70 mm x 35 mm timber studs or 64 mm steels studs
at 600 mm centres, spaced 20 mm from each face of the
masonry wall; and
(b) 50 mm thick mineral insulation or glass wool insulation with
a density of 11 kg/m3 positioned between studs in each row;
and
(c) one layer of 13 mm plasterboard fixed to studs on each
outside face.
Rw+Ctr50
7/22/2019 Technical Manual Whole
36/93
ADV03777
1.229
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design
Single leaf of 150 mm brick masonry with
13 mm cement render on each face.
Construction Rating
Table 10. BCA Volume 1 Amendment 14 Deemed-to-Satisfy Brick Walls (continued)
BCA Deemed-to-Satisfy Walls (continued)
Rw50
Single leaf of 220 mm brick masonry with
13 mm cement render on each face.Rw50
Single leaf of 110 mm brick masonry with
13 mm cement render on each face.Rw45
7/22/2019 Technical Manual Whole
37/93
Solid v. Cavity Walls
Acoustic performance with single leaf masonry follows the Mass Law. The acoustic performance of these walls
depends on their mass. More mass gives better performance, however, the relationship is logarithmic: If a 110
mm wall gives Rw = 45, a 230 mm wall of the same brick may give Rw = 57.
Cavity walls behave differently because sound waves can resonate in cavities. The narrower the cavity becomes,
the more resonance occurs. Insulation in the cavity helps absorb resonating sound and narrow cavities should
have bond breaker board, to prevent mortar from providing a bridge for sound to travel between the leaves.
Brick Walls with Render
Render on one side of a brick wall adds 2 or 3 to the walls R w but adding render to the second side only adds
1 to the walls Rw. The render appears to fill defects in the wall surface reducing the sound transmission, but this
is a one-off benefit.
Brick Walls with Plasterboard
Cornice cement daubs, used to fix plasterboard directly to brick walls, create a small cavity in which resonance
occurs. Brick walls with daub fixed plasterboard on both sides stop less noise than the same walls, bare. Adding
extra daubs (halving spacing) gives lower performances, presumably due to extra bridges through the daubs.
Plasterboard on furring channel is marginally better than daub fixed. A bigger cavity between the wall and the
plasterboard makes it harder for resonating energy to build up pressure on the board. When standard furring
channel clips are used, this system transfers vibrations to the plasterboard via the channels and clips. Boral
Impact Clips (BICs) have a rubber shank on their masonry anchor that isolates the vibrations from the masonry.
The use of BIC mounts can add 3 or 4 dB to the walls Rw. Polyester and glass wool in the cavity helps prevent
resonance and further decreases the sound transmission. Denser grades of plasterboard and additional layers of
plasterboard (fixed with grab screws and leaving no cavities) also decrease sound transmission.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.230
ADV03778
7/22/2019 Technical Manual Whole
38/93
Points to Consider When Designing Wallsfor Acoustic Performance
The BCA specifies minimum levels for sound isolation but experience shows that achieving the minimum
standards is not always sufficient to satisfy occupants. In view of this it is recommended that architects,
developers, builders, etc., consider a higher level of sound insulation, commensurate with the expectations of
the end user. End user expectations are frequently related to the cost of occupying the unit.
Wall design is a balance between acoustical performance, thickness, weight and cost. Frequently it is not
possible to optimise one factor without seriously compromising the others.
Acoustic Performance On-Site
The Rw ratings on walling systems are obtained from tests carried out in accredited laboratories, under
controlled conditions. When identical partitions in buildings are tested in-situ, it is often found that the actual
result obtained, called the Weighted Standardised Level Difference (Dnt,w), is lower than the laboratory Rw. This
reduction in performance can be due to rooms being too small, varying size of the element being tested, flanking
paths (noise passing through other parts of the building) or background noise. The allowance in the BCA for a
difference of 5 between the laboratory test and the field test is not to allow for poor construction practice. To
repeat the performance in the field, attention to detail in the design and construction of the partition and its
adjoining floor/ceiling and associated structure is of prime importance. Even the most basic elements, if ignored,
can seriously downgrade the sound insulation performance.
The most common field faults include bricklayers not completely filling all mortar joints, poor sealing between
walls and other building elements, electrical power outlets being placed back to back, chasing masonry and
concrete walls, leaving gaps in insulation, screwing into insulation and winding it around the screw when
attaching sheet materials, not staggering joints in sheet materials and poor sealing of penetrations.
Boral Bricks cannot guarantee that field performance ratings will match laboratory performance. However, with
careful attention during construction of the wall, correct installation to specification and proper caulking/sealing,
the assembly should produce a field performance close to and comparable with tested values. The following
items can also affect the acoustic performance on site.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.231
ADV03779
7/22/2019 Technical Manual Whole
39/93
Perimeter Acoustical Sealing
As the Rw of a wall increases, the control of flanking paths becomes more critical. Consequently, the perimeter
sealing requirements for a low sound rating wall, such as Rw = 45, are much less than for a high sound rating
wall, such as Rw = 60. Note: it is neither necessary, nor is it cost effective, to provide very high perimeter
acoustic sealing for a low Rw wall.
Effective sealants have the following properties:
Good flexibility, (elastic set);
Low hardness;
Excellent adhesion, usually to concrete, timber, plaster and galvanised steel;
Minimal shrinkage (less than 5%);
Moderate density (greater than 800 kg/m3); and are,
Fire rated where required (All walls required by the BCA to be sound rated also have fire ratings).
All of the above properties must be maintained over the useful life of the building, that is, greater than 20 years.
Note: Use of expanding foam sealants is not acceptable.
Refer to the manufacturer to ensure the particular type or grade of sealant is suitable for the purpose.
Doors
Hollow, cored and even solid doors generally provide unsatisfactory sound insulation. Doors can provide direct
air leaks between rooms lowering the overall Rw of the wall in which they are inserted. Where sound insulation
is important, specialised heavyweight doors or, preferably, two doors separated by an absorbent lined airspace
or lobby should be used.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.232
ADV03780
7/22/2019 Technical Manual Whole
40/93
Lightweight Panels Above Doors
Panels are often incorporated for aesthetic reasons, however, they should not be used unless they have an R w
equal to or better than the walls requirement.
Air Paths Through Gaps, Cracks or Holes
Seal all gaps, cracks or openings, however small, with an acoustic sealant. Holes readily conduct airborne
sounds and can considerably reduce the Rw of a wall.
Appliances
Noise producing fixtures or appliances such as water closets, cisterns, water storage tanks, sluices,
dishwashers, washing machines and pumps should be isolated from the structure with resilient mountings and
flexible service leads and connections.
Electrical Outlets & Service Pipes
Penetrations of all sorts should be avoided but if unavoidable, seal around them effectively. If possible introduce
a discontinuity in pipe work between fittings, such as a flexible connection within or on the line of a partition.
Use acoustically rated boxes for all general power outlets, light switches, telephone connections, television
outlets, etc. Seal the sides of electrical boxes and the perimeter of all penetrations with acoustic sealant. Offset
all power outlets on either side of a wall by at least 100 mm.
Bricks & Pavers Technical Manual
Section 1.2. Brick Masonry Design 1.233
ADV03781
7/22/2019 Technical Manual Whole
41/93
Brick Masonry Construction1.3
7/22/2019 Technical Manual Whole
42/93
The following information relates to the construction of brick walls to meet AS3700, the design and aesthetic
requirements.
Mortar
AS3700: 2001, Table 10.1 gives the options for mortar mixes classified as M1 to M4. M1 mortars are for
restoration applications. M2 mortars are for use in interior walls above dampcourse or in exterior walls above
dampcourse if more than one km from a body of salt water and 10 km from a surf coast and the wall has
protection from water ingress above. M3 and M4 mortars are those most commonly used in construction. Table
11 gives the proportions of the most commonly used mortars. Other deemed-to-satisfy compositions are given in
AS3700. Special mortars that are tested and shown to meet requirements are allowed with verification on site.
Note: Proportions are by volume and should be measured with a bucket or gauge box, NOT A SHOVEL.
Table 11. Typical Mortar Mixes
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.301
ADV03783
Refer to page 1.104 for description of Durability Class. *Methylcellulose type, not air entrainers such as detergent.
Where masonry strength is crucial, trial walls should be constructed with the bricks and mortar to be used on
the job, then tested before construction commences. Masonry bond strength is related to the suction of the
bricks, the particle size distribution of the sand, cement content, additive contents, etc. For many jobs these
panels can also be used as physical samples of the required quality of the bricklaying and cleaning.
Note: AS 3700 allows the use of:
Cements complying with AS 3972 or AS 1316
Lime complying with AS 1672.1
Sand that is free of any deleterious materials
Water that is free from deleterious materials and
Admixtures including plasticisers, air entraining agents and set retarders complying with AS1478.1,
cellulose-type water thickeners, colouring pigments complying with BS EN 12878 and bonding polymers.t
Mortar DurabilityMix proportions by volume
Type Class Portland or Hydrated WaterBlended Cement Lime Sand Thickener*
M1 PRO 0 1 3 No
M2 PRO 1 2 9 No
M3 GP 1 1 6 No
M3 GP 1 0 5 Yes
M4 EXP 1 12 412 No
M4 EXP 1 0 4 Yes
7/22/2019 Technical Manual Whole
43/93
Mortar (continued)
No other material may be used until tests on masonry constructed with the mortar, made with the material or
admixture shows the masonry complies with the standards requirements for compressive strength, flexural
strength and durability.
Deleterious materials are those reducing the strength or durability of the masonry and including anything that
attacks the built-in components. This means the use of fire clay, detergent, sugar, soft drink, etc., are banned.
Most of these materials severely reduce mortar strength and durability. Water thickener must be used only
according to the manufacturers directions because overuse severely reduces mortar strength.
Mortar Estimator
Table 12. Estimated Material Requirements to Lay 1,000 Standard Bricks
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.302
ADV03784
Mix Composition 40 kg bags 25 kg bags Cubic metres Tonnes of
(C:L:S) of cement of lime of sand damp sand
M3 1 : 1 : 6 4 2.4 0.64 1.2
M3 1 : 0 : 5 4 0 0.64 1.2
M4 1 : 0 : 4 6.5 0 0.64 1.2
M4 1 : 12 : 412 5.3 1.6 0.64 1.2
This table assumes partial filling of cores and typical site wastage.
Only make sufficient mortar for immediate use. If mortar starts to set, it may be re-tempered once only.
Where bricklaying is interrupted, the mortar should be covered to prevent evaporation and mixed with the trowel
before continuing. t
7/22/2019 Technical Manual Whole
44/93
Mortar (continued)
Mortar Colour
The mortar colour can dramatically affect the overall look. The colour of mortar is influenced by the colour of the
cement and the aggregates (sand). Many pigments are also available ranging in colour through red, yellow,
brown, green, blue and black (mainly oxides but carbon black can be used to give black mortar). The cheapest
way of colouring mortar is to use coloured sand. White and yellow sands are commonly available but red and
brown sands are also available. Sands are normally natural materials which vary considerably even in the one
deposit. To ensure colour consistency, sufficient sand from the one batch should be set aside for the whole job.
Where colour is crucial to the look of the masonry, before accepting the sand, a trial wall should be built (4 bricks
x 10 courses). After the mortar dries assess the colour. Where oxides or carbon black are used as colours never
use more than 10% by weight of the cement content.
Colours are additive in their effect and it is possible to get different shades and tones of mortar using different
combinations of cement, sands and oxides.
Table 13: Typical Coloured Mortar Components
Note: The colour of mortar can be severely degraded by incorrect or poor brick cleaning.
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.303
ADV03785
Mortar Colour Cement Sand Oxide
Red Grey White or Yellow or Red Red
Yellow Off-white or Grey Yellow Yellow & Brown
Cream Off-white Yellow None
Tan Grey White or Yellow Brown
Black Grey Yellow Black
7/22/2019 Technical Manual Whole
45/93
Joint Types
The type of joint can dramatically affect the overall look of brick masonry. Joints can be used to create a casual,
rustic or formal look to brickwork. There are many different joints; the most common ones used in Australia are
shown below.
Terminology and joint preference differs in different countries and within Australia. Where there is any
confusion, always use a drawing or physical sample to avoid misunderstandings.
Shallow ironed joints are recommended in areas requiring exposure grade bricks and mortar. Tooling the joint to
produce ironed and struck joints is equivalent to steel trowelling concrete and produces a dense smooth surface
which sheds water and dirt better than other types of joint. Ironed and struck joints should always be used for
bricks with straight sharp edges such as Smooth Face and Velour bricks.
Raked joints may be used with any type of brick but they tend to retain dirt and may lead to streaks down the
masonry in dirty environments. Raking must not come closer than 5 mm to any core. This usually limits raking to
less than 10 mm, however it is best to check the bricks that are being used before raking. AS3700 specifies that
joints in walls in marine, severe marine or aggressive environments or on aggressive soils must be tooled to a
dense smooth surface. This precludes raking and in practice ironed joints are the only ones that consistently
meet the requirement.
Flush joints may be used with any type of brick. However, flush joints are particularly effective with rumbled
bricks as flush joints make the joints look to be of variable thickness that gives a pleasing rustic look.
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.304
ADV03786
Flush Joint Raked Joint Ironed Joint Weathered JointStruck Joint
7/22/2019 Technical Manual Whole
46/93
Joint Sizes
Mortar bed joints are required to be less than 10 mm unless the design specifies another thickness. A different
thickness may only be specified after the designer considers the effect on compressive and flexural strength of
the masonry. During construction mortar bed joints are allowed to deviate by 3mm. Because of poor practice
or lack of proper direction some slabs and footings are finished at the wrong height. Mortar joints up to 50 mm
thick have been used to get the correct coursing, however, this is not allowed under AS3700.
Perpends are to have a minimum design thickness of 5 mm. In structural brickwork perpends may be up to 10 mm
thicker than the specified thickness but no thinner. In face brickwork perpends may deviate by 5 mm from the
average width but in any one wall the maximum difference allowable between any two perpends is 8 mm.
The preceding tolerances do not apply in the case of thin bed mortars and perpend tolerances do not apply where
perpends are not filled with mortar.
Weepholes
Weepholes are to allow moisture that collects in the cavity to escape. Weepholes should be spaced at less than
1200 mm centres wherever flashing is built into the masonry to shed water from the cavity. Weepholes are
usually empty perpends (10 mm wide) but proprietary products are available to prevent the entry of insects. In
high wind areas it has been known for water to be blown up the cavity onto the inner wall and as this is very
undesirable, more, narrower weepholes are usually built into the wall. It is essential that weepholes remain open
and render and other applied coatings, where used, must be raked out of the joint.
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.305
ADV03787
7/22/2019 Technical Manual Whole
47/93
Brick Estimator
Brickwork is based on the 600 mm unit, (seven courses high and two and a half bricks long). This unit fits in with
doors, windows and other building materials. The number of bricks required for a wall can be determined from
the Brick Coursing Height and Brick Gauge tables on pages 1.310-1.312 of this manual. Select the height of the
wall and from the following page for the brick height chosen determine the number of courses. From the next
page for 230 mm long bricks or the one after for 290 mm bricks, determine the number of bricks for the length of
your wall. A half brick should be calculated as 1 whole brick, due to site wastage. Multiply the number of bricks
by the number of courses to give the number of bricks for the wall. Saw cutting bricks may mean getting two
halves from a brick but this is not usual practice because of the cost of cutting.
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.306
ADV03788
7/22/2019 Technical Manual Whole
48/93
Brick bonds and other decorative effects
A bond is the pattern in which bricks are laid. The most common bond is Stretcher Bond which consists of courses
of full bricks where every course is offset half a brick from the course below. When following the mortar joint,
stretcher bond has the longest vertical pathway and therefore the best bend strength.
Stretcher bond is used in walls one brick wide. Where walls are two or more bricks wide then stretcher bond
needs ties to hold the leaves together to give it a monolithic action. To avoid the use of ties traditional practice
has been to lay some of the bricks sideways. This has usually been either full courses of headers with full
courses of stretcher (English) or courses of alternating header and stretcher (Flemish). A variation of Flemish
Bond is Garden Wall Bond where courses are made of a header and three stretchers alternating.
Corner treatment can be different in these bonds. English corners end in full stretchers or full headers, and any
part brick required to make up the course is set inside the corner. Dutch corners end in the part bricks.
Variations on these bonds are common in particular a header course every three or six courses with stretcher
courses between.
Although these bonds have traditionally been developed for thick walls, they can be used in single leaf walls as
a decorative effect using cut bricks for the headers. Such walls are usually non-load bearing. Cutting costs are
high but not excessive as the headers have the cut side turned in and the bricks can be bolstered.
Other decorative bonds may be used in non-load bearing applications, particularly in the form of panels. The
limitations are strengths lower than Stretcher Bond and the cost of cutting and slower brick laying. The
decorative effect of bonds is highlighted by using a mortar in a contrasting colour to the brick.
Other bonds include:
Stack Bond Bricks laid horizontally in vertical columns so all vertical joints align.
Soldier Stack Bond Bricks laid vertically in vertical columns so all vertical joints align.
1/3 Bond Every course is offset by 1/3 of a brick.
Zigzag Bond, Vertical Zigzag Bond, 45 Stretcher Bond, Chevron Bond, Basket Weave Bond, 45 Basket
Weave Bond and virtually any pattern that tessellates.t
Bricks & Pavers Technical Manual
Section 1.3. Brick Masonry Construction 1.307
ADV03789
7/22/2019 Technical Manual Whole
49/93
Brick bonds and other decorative effects (continued)
Other decorative effects are available such as:
Laying bands of bricks of the same colour with different textures eg smooth faced and rock faced;
Laying bands of bricks with different (contrasting or complimentary) colours;
Corbelling (bricks set out from the wall);
Racking (bricks set back into the wall);
Quoining (corner bricks in different colours or set out from the wall);
Soldiers above openings or as a single course;
Copings on piers and parapet walls;
Sills in different colours or textures, using sill bricks, etc.; or,
In the late 1800s bricks of contrasting colours were laid in patterns such as diamonds or crosses