+ All Categories
Home > Documents > Technical Perspective - RMEL · 2018. 3. 28. · 3) Based on IEEE 1584 equations. 1 inch gap, 1.641...

Technical Perspective - RMEL · 2018. 3. 28. · 3) Based on IEEE 1584 equations. 1 inch gap, 1.641...

Date post: 12-Feb-2021
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
29
Page 1 www.brainfiller.com .com P.O. Box 12024 | Scottsdale, AZ 85267, USA | 800.874.8883 Arc Flash Technical Perspective Jim Phillips, P.E.
Transcript
  • Page 1 www.brainfiller.com

    .com P.O. Box 12024 | Scottsdale, AZ 85267, USA | 800.874.8883

    Arc FlashTechnical

    Perspective

    Jim Phillips, P.E.

  • Arc Flash and the Technical Perspective

    ● Vice Chair of IEEE 1584 IEEE Guide for Performing Arc Flash Hazard Calculations● International Chair of Geneva Based IEC TC78 Committee – Live Working● Liaison Officer between IEEE 1584 and IEC TC78 Arc Flash Committees● Author of the book: Complete Guide to Arc Flash Hazard Calculation Studies● Member: Steering Committee – IEEE/NFPA Arc Flash Collaborative Research Project● Founder of the Electrical Power and Electrical Safety Training Company: Brainfiller.com● Founder of the internationally known website: ArcFlashForum.com

    Jim Phillips will discuss the relevant OSHA, NESC and IEEE standards used for protecting workers from the arc flash hazard. See how to create an arc flash protection strategy by determining the severity of the thermal hazard and specifying suitable arc rated clothing and related personal protective equipment. Jim is at the forefront of arc flash standards both nationally and internationally and is:

  • Major Standards

    Electrical Safety Pyramid

    OSHAFederal

    Regulations

    Consensus Standards

    NFPA 70E - General Industry

    NESC - Electric Utility

    Guides, Practices, Methods

    IEEE 1584 - IEEE Guide for Performing Arc Flash Hazard Calculations

  • OSHA 1910.269(I)(8)(ii)

    Clothing Restrictions

    • The employer shall ensure that

    each employee who is

    exposed to the hazards of

    flames or electric arcs does not

    wear clothing that, when

    exposed to flames or electric

    arcs, could increase the extent

    of injury that would be

    sustained by the employee.

  • OSHA 1910.269(I)(8)

    • Assess workplace for hazards from flames or

    electric arcs

    • If there is exposure, estimate incident energy

    • Appendix E provides methods for estimating Ei

    • Other methods could be used if reasonable

    • Require Arc Rated clothing under certain

    conditions

    • Select clothing with arc rating grater than

    estimated incident energy

  • Copyrig

    ht ©

    Obero

    n

  • • Intensity

    • Duration

    • Distance

    • Equipment Type

  • Copyrig

    ht ©

    Obero

    n

    • ATPV or Ebt

    • Arc Rating is on

    the Garment Label

    • cal/cm2

    • J/cm2

    • kJ/m2

  • Higher Short Circuit + Longer Clearing Time

    = Greater Incident Energy

    How much short circuit current?

    Arc Flash Duration?

    Protective device

    opening time?

  • Arc Flash Duration and Incident Energy

    Incid

    en

    t E

    ne

    rgy –

    ca

    l/cm

    2

    0

    2

    4

    6

    8

    10

    12

    3 6 9 12

    Clearing Time - cycles

  • Selecting a Reasonable Incident Energy

    Calculation Method

    • IEEE 1584 Calculations - 3 Phase• Good for equipment in enclosures

    • Empirical < 15 kV

    • Theoretical > 15 kV

    • OSHA 1910.269 Appendix E Tables

    • NESC Tables 410-1 and 410-2

    • Arc Pro - 1 Phase

  • IEEE 1584 – IEEE Guide for Performing

    Arc-Flash Hazard Calculations

    • Calculations based on IEEE working group

    • Calculations are still evolving

    • Based on statistical analysis and curve fitting

    • Calculations for incident energy limitations• Voltage 208 Volts to 15 kV three phase

    • 50 to 60 Hz.

    • 700 Amps to 106,000 Amps short circuit

    • 13 mm to 152 mm conductor gap

    • Intended for three phase - Conservative if

    single phase event

  • PPE / Arc Rating Selection from Study

    Results Using IEEE 1584 Calculations

    Arc Flash Calculation Study ResultsBrainfiller Industries

    Bus NameVoltage

    (kV)Equipment

    TypeArc Gap

    (mm)

    Bolted Fault (kA)

    Est. Arc Fault (kA)

    Arcing Time (sec)

    Est. Arc Flash

    Boundary (feet)

    Working Distance (inches)

    Incident Energy

    (cal/cm2)PPE Level

    MAINSWGR

    0.48 Switchgear 32 37.734 19.034 0.167 6.65 24 7.0 #2

    PANEL 1A 0.48 Panel 25 27.285 15.457 0.200 5.67 18 10.6 #3

    PANEL 1B 0.48 Panel 25 27.368 15.497 0.050 2.13 18 2.7 #1

    MCC-1 0.48 MCC 25 21.117 12.418 0.100 2.81 18 4.2 #2

    PANEL 2 0.48 Panel 25 21.164 12.442 0.033 1.44 18 1.4 #1

    Incident Energy in cal/cm2

  • 2017 NESC Rule 410.A.3Paraphrased

    Performed by: Wylie E. Coyote

    Reviewed by: Road Runner

    Employer shall ensure assessment is

    performed to determine arc flash hazard

    Perform a detailed arc hazard analysis or

    use Table 410-1, 410-2 or 410-3

    Analysis includes calculation of estimated

    arc energy

    Employees wear clothing or clothing system

    with effective arc rating not less than

    anticipated level of arc energy.

    Exception: If clothing can create a greater

    hazard then an arc rating less than required

    may be worn

  • NESC Table 410-1 Clothing and clothing

    systems for 50 V to 1000 V (ac)

    Equipment TypeNominal Voltage Range and cal/cm2

    50 V to 250 V 251 V to 600 V (14) 601 V to 1000 V

    Self-contained meters / cabinets 4 (2) 20 (4) 30 (8)

    Pad mounted transformers 4 (9) 4 (9) 6 (8)

    CT meters and control wiring 4 (2) 4 (5) 6 (8)

    Metal-clad switchgear / motor

    control centers8 (3) 40 (6) 60 (8)

    Pedestals / pull boxes / hand

    holes4 (2) 8 (7) 12 (8)

    Open air (includes lines) 4 (2) 4 (7) 6 (8)

    Network protectors 4 (10) (11) (11)

    Panel boards – single phase (all) /

    three phase ( 100A)4 (2) (13) (13)

    2017 National Electrical Safety Code – always consult the latest editionNote: Use the NESC table

  • NESC Table 410-1

    Notes – Partial List

    1) Developed from fault testing based on equipment type and is

    independent of fault current unless otherwise noted.

    2) Industry testing shows arc does not sustain more than 2 cycles

    3) Based on IEEE 1584 equations. 1 inch gap, 1.641 distance

    factor, 208V, 1000 kVA transformer, 500 MVA source, max

    duration 10 cycles

    4) Industry testing did not exceed 20 cal/cm2

    5) Industry testing did not exceed 4 cal/cm2

    6) Based on IEEE 1584 equations. 1 inch gap, 1.641 distance

    factor, 480 V, 12.47 kA, max duration 85 cycles

    7) Incident analysis does not exceed table values

    8) Engineering analysis shows using 150% multiplier is conservative

    9) Industry testing shows values do not exceed 4 cal/cm2

    2017 National Electrical Safety Code – Consult the standard for the complete list. Always consult the latest edition

  • NESC Table 410-1

    Notes – Partial List

    10)Industry testing shows values do not exceed 4 cal/cm2

    11)Industry testing shows arc will not self extinguish and heat flux

    rates will exceed 60 cal/cm2/second at 24 inch working

    distance – perform analysis.

    12)Industry testing shows values do not exceed 8 cal/cm2

    13)Industry testing shows arc will not self extinguish and heat flux

    rates will exceed 60 cal/cm2/second at 18 inch working

    distance – perform analysis.

    14)IEEE 1584 original test data indicates there is no significant

    difference between heat flux rates for 400V class and 600V

    class equipment.

    2017 National Electrical Safety Code – Consult the standard for the complete list. Always consult the latest edition

  • Transformer Secondary Blind Spot

    Forensic Analysis

    Sleeve burned through

    Leather burned through, rubber

    line is intact

    Example of an arc rated FR shirt (5 - 6 cal/cm2) and

    gloves worn by a person who was burned in a

    secondary fault while hooking up some 120/208V.

    leads to a pad mounted transformer. He came out

    of it with just some 2nd degree burns on his arm.

  • Arc Rated Clothing and PPEC

    opyr

    ight

    © O

    bero

    n

  • NFPA 70E 130.7(C)(10) (b)(1)

    Head Protection < 12 cal/cm2

    Arc rated face shield with

    arc rated balaclava for

    head protection when head

    is within arc flash boundary.

    Arc rated hood is permitted

    instead of face shield and

    balaclava

  • NFPA 70E 130.7(C)(10) (b)(2)

    Head Protection > 12 cal/cm2

    When the incident energy

    exposure is greater than 12

    cal/cm2, an rated hood shall

    be used.

  • Head Protection

    OSHA 1910.269(i)(8)(v)(C) thru (E)

    1910.269(l)(8)(v)(C)

    Arc-rated protection is not necessary for the employee's head when the employee is

    wearing head protection meeting § 1910.135 if the estimated incident energy is less

    than 9 cal/cm2 for exposures involving single-phase arcs in open air or 5 cal/cm2 for

    other exposures,

    1910.269(l)(8)(v)(D)

    The protection for the employee's head may consist of head protection meeting §

    1910.135 and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated

    incident-energy exposure is less than 13 cal/cm2 for exposures involving single-

    phase arcs in open air or 9 cal/cm2 for other exposures, and

    1910.269(l)(8)(v)(E)

    For exposures involving single phase arcs in open air, the arc rating for the

    employee's head and face protection may be 4 cal/cm2 less than the estimated

    incident energy.

  • Face Protection

    Face shields must have

    sufficient arc rating and a

    wrap-around guarding to

    protect the face, chin,

    forehead, ears and neck.

  • Hand Protection

    Heavy duty leather gloves or

    arc-rated gloves shall be worn

    Leather protectors shall be worn

    over rubber insulating gloves.

  • Clothing Material Characteristics

    • Non-AR fabrics that ignite

    (start to burn) will continue

    to burn and can increase

    the severity of the burn.

    • AR fabric can ignite but will

    extinguish itself after the

    ignition source is gone.

    • AR materials provide

    thermal protection.

  • NFPA 70E

    130.5(H) Equipment Labeling

    130.5(H)(1) Nominal system voltage

    130.5(H)(2) Arc flash boundary

    130.5(H)(3) At least one of the following:

    Incident Energy and Working Distance Selected

  • Thank You!

    .com

    [email protected]

  • Stay Connected!

    Brainfiller https://twitter.com/brainfiller

    BrainfillerTV https://www.youtube.com/user/BrainfillerTV

    Jim Phillips Brainfiller.com

    Brainfiller https://www.linkedin.com/in/brainfiller

    [email protected]


Recommended