Date post: | 21-Feb-2017 |
Category: |
Engineering |
Upload: | pankaj-chakraborty |
View: | 253 times |
Download: | 1 times |
ON MODERN CONCEPTS AND ADVANCED TECHNIQUES OF EARTHING
1
Technical Presentation to PROJECT PRICIPALS
BY PANKAJ CHAKRABORTY
OF
PBC INDUSTRIAL SERVICESBLOCK – 19 , F LAY – 1 1 7 ,
PARNASREE GOVT . HOUS ING ,
KOLKATA – 700 060 , (WEST -BENGAL )
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Objectives
Return path during continuous operation should not be thru earth path unless designed.
Instantaneous fault current should not flow thru the neutral circuit creating live and dangerous neutral.
Dissipate the stray currents, lightning, surges
2
Dissipate the stray currents, lightning, surges keeping system hazard free.
Maintain the whole facility at equipotential.
Provide reference to run the system at specified voltage
7/2/2013PBC Training Document PBC/ER/005 Rev 0
TN System
Transformer neutral is earthed
Frames of electrical load are connected to neutral
Fault is cleared by SCPD
3
Fault is cleared by SCPD
TN-C, TN-S, TN-CS
SCPD/ loop impedance matching
Not recommended for premises having electronic and communication system
Not used when cross-section of live cond. < 10 sqmm
PE may get damaged by loads generating 3rd harmonics.
7/2/2013PBC Training Document PBC/ER/005 Rev 0
TT system
Transformer neutral is earthed
Frame of electrical load is connected to earth connection
Fault cleared by RCD.
4
7/2/2013PBC Training Document PBC/ER/005 Rev 0
IT System
Transformer neutral is not earthed.
Frame of electrical load is earthed.
First fault does not present risk, indication is sufficient
Second fault cleared by SCPD
5
Second fault cleared by SCPD
Ensure continuity of service where human life is at stake or with furnaces
7/2/2013PBC Training Document MEPL/ER/005 Rev 0
7/2/2013PBC Training Document PBC/ER/005 Rev 0 6
Problem for electronic and communication system
7/2/2013PBC Training Document PBC/ER/005 Rev 0 7
Comparing Earthing system8
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Parallel association of Earthing system9
7/2/2013PBC Training Document PBC/ER/005 Rev 0
BREAK 110
THINKING T IME
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Soil Resistivity of different Soil Types11
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Resistivity Plot
Use Wenner 4 point method. Take at least 4 readings in one direction from 7mt spacing to spacing equal to diagonal of the electrical installation.
Repeat these readings in all 8 directions separated by 450
angle.
12
7/2/2013PBC Training Document PBC/ER/005 Rev 0
angle. Calculate the resistivity. Make a polar plot. Calculate the area under the polar plot
Draw a circle of equal area Radius of the circle is the resistivity of the point.
Variation in Resistivity
13
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
7/2/2013PBC Training Document PBC/ER/005 Rev 0 14
Resistivity Plot
15
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Wenner’s method16
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Schulemberger method17
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Essential Practices
Use meter having stray current filter.
where the injected current frequencies can be changed
Injected current can be made high or low depending on current probe resistance.
Apply water and compact the current and potential
18
Apply water and compact the current and potential probes to avoid undue high probe resistance.
Lose potential probe can give high value of R and high resistivity.
Avoid measuring along buried or superficial metal conductors
Take readings in multiple directions
7/2/2013
Abstract of IEEE 81 199319
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Polar curve method for Uniform Soil Resistivity
• Resistivity taken in min 8 directions
• Angular distance between readings 450
• Cautiously Interpolate the readings to 7.50
• Join the Points to form a polar curve
20
PBC Training Document PBC/ER/005 Rev 0
curve• Calculate the area of the polar curve
• Draw equivalent Circular area• Radius of the circle is the average soil resistivity
• This method is particularly beneficial when the resistivity varies significantly in different directions
7/2/2013
Inverse Slope method for 2 layer soil Resistivity
1
1.2
1.4
1.6
1.8
Spacing s / apparent resistivity ρa
Approximate method
21
PBC Training Document PBC/ER/005 Rev 0
0
0.2
0.4
0.6
0.8
1
0 5 10 15 20 25 30 35
0.5/5=.11/.1=ρ2=10Ωm
Spacing s / apparent resistivity
Spacing s in m
0.2/5=.041/.04=ρ1=25Ωm
H=13
7/2/2013
Sunde’s Method22
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
BREAK 223
THINKING T IME
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Essentials of Earthing Design
Crossection Area
Current Density
Dangerous Potentials
Resistance
The Crossection of the conductor to be sufficient for carrying
Continuous surface current density
Step potential Horizontal Plane
Touch potential Vertical Plane
24
PBC Training Document PBC/ER/005 Rev 0
for carrying GRID fault current Instantaneous
Surface current density
Mesh Potential Mutualresistance
GPR
Transfer Potential
PASS PASS PASSPASS OK7/2/2013
(Clause 11.3 of IEEE 80:2000)
TERMS:I – rms current in KATCAP – Thermal capacity per unit volume in J/(cm3. 0C)
Calculation of required minimum cross sectional area of grid conductor:
25
TCAP – Thermal capacity per unit volume in J/(cm . C)tc – Duration of fault current in secαr – Thermal coefficient of resistivity at reference temperature in 1/
0Cρr – Resistivity of the ground conductor at reference temperature in µΩ-cmKo – 1/ α0 in
0CTm – Maximum allowable temperature in
0CTa – Ambient temperature in
0C
Cross Sectional Area of selected grid conductor must be greater than minimum required Cross Sectional Area as required by Asymmetric fault current.
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Crossection area
Equation 37 of IEEE 80 2000 The current is Symmetrical fault current
Enthalpy of vaporization decreases with increase in temperature.
For a large grid the fault current gets
See also
26
PBC Training Document PBC/ER/005 Rev 0
For a large grid the fault current gets multiple parallel paths hence Tm doesn’t pose a problem.
If the Tm is allowed to rise beyond a limit in smaller grids or pits the water molecules beyond a temperature will instantaneously vaporizes and escape from the soil surrounding the conductor.
Tm also applies to surface layer coating or cover
CompoundAt 1000C
Heat of vaporizatio
n(kJ mol-1)
Heat of vaporizatio
n(kJ kg−1)
Water 40.65 2257
7/2/2013
Calculate Grid Current
(Clause 5.2.8.1 of IEEE 665:1995)
TERMS:
27
TERMS:I – rms current in KASf – Split factor (Annex C of IEEE 80:2000)Df – Decremtent factor (Clause 5.2.5.4 of IEEE 665:1995)Cp – Corrective Projection factor
The Remaining design depends on the Current that takes the ground path to return to the source. It is only a portion of 3I0.
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Long term surface CurrentsLong term surface Currents Short Term surface currentsShort Term surface currents
Surface current density as per BS7340 clause 15
If surface current densities are not maintained, junction between electrode and soil, will heat up reducing moisture, failing the electrode or grid.
28
PBC Training Document PBC/ER/005 Rev 0
Long term Surface current density is 40A/m2
Independent of soil resistivity
Given by the formula 1000*Sqrt (57.7/(ρ*t))
Dependent on soil resistivity and time of clearance of fault
EFFECT OF COROSSION
7/2/2013
Symbol unit Value
Relay setting at 6KA 0.32Sec IG A 6000 Input
Diameter of electrode d m 0.04 Input
Length of Electrode
Soil ls m 37 Input
Water lw m 1 Input
Resistivity
Soil ρs Ωm 360 Input
Water ρw Ωm 2 Input
Resistance
Soil Rs Ω 12.25394 Equation 55 IEEE 80 2000
Water Rw Ω 1.368891 Equation 55 IEEE 80 2000
Combined R Ω 1.231338
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Combined Rc Ω 1.231338
Permissible Current Density
Soil σs A/m2 730.9304 Clause 15.2 BS7340
Water σw A/m2 9806.46 Clause 15.2 BS7341
Area
Soil As m2 4.6472 πdls
Water Aw m2 0.1256 πdlw
Current Division Resistance Capacity Design
Soil 3396.779785
Water 1231.691433
TOTAL 4627 A
29
Abstract of IEEE 80 200030
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201331
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201332
Dangerous Potentials
33
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Voltage Variation with proximity
∆V
• The charges are distributed to the surrounding soil.
• The Voltage is thus high near the ∆V
∆V
• The Voltage is thus high near the pit and low away from it
7/2/2013PBC Training Document PBC/ER/005 Rev 0 34
Step Potential
Calculation of permissible Step Potential:
(Clause 7.4 and 12.5 of IEEE 80:2000)
(Clause 8.3 of IEEE
35
TERMS:ρ – Soil Resistivity in Ω-mρs – Soil Resistivity of additional surface layer in Ω-mhs – Thickness of additional surface layer in mts – Shock current duration in secCs – Surface layer de-rating factor
(Clause 8.3 of IEEE 80:2000)
(Clause 8.3 of IEEE 80:2000)
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Calculation of actual Step Potential:
(Clause 16.5 of IEEE 80:2000)
TERMS:ρ – Soil Resistivity in Ω-m
36
ρ – Soil Resistivity in Ω-mKs – Spacing factor for step voltageKi – Correction factor for grid geometryIG – Grid current in KALs – Effective length of (Lc + LR) for step voltage in m
where Lc = Total length of grid conductorLR = Total length of ground rods
Calculated Step Potential must be less than permissible Step Potential.
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Touch Potential
Calculation of permissible Touch Potential:
(Clause 7.4 and 12.5 of IEEE 80:2000)
(Clause 8.3 of IEEE
37
TERMS:ρ – Soil Resistivity in Ω-mρs – Soil Resistivity of additional surface layer in Ω-mhs – Thickness of additional surface layer in mts – Shock current duration in secCs – Surface layer de-rating factor
(Clause 8.3 of IEEE 80:2000)
(Clause 8.3 of IEEE 80:2000)
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Calculation of actual Mesh Potential:
(Clause 16.5 of IEEE 80:2000)
TERMS:ρ – Soil Resistivity in Ω-mKm – Spacing factor for mesh voltage
38
Km – Spacing factor for mesh voltageKi – Correction factor for grid geometryIG – Grid current in KALM – Effective length of (Lc + LR) for mesh voltage in m
where Lc = Total length of grid conductorLR = Total length of ground rods
Calculated Mesh Potential must be less than permissible Touch Potential.
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Tolerable currents by Humans
Frequency based (lethal values)
DC 25Hz 50/60Hz 3-10 KHz
0.5A 0.15A 0.1A high current
39
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Threshold current,
tingling feeling
Let – go current.
Can release
Cannot release
energized object
Ventricular fibrillation
1 mA 1-6 mA 9-25 mA 60 - higher
0.5A 0.15A 0.1A high current
Amplitude based
Tolerable currents by Humans (Con.)
Weight Based Time based
40
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Step potential (Permissible Value)It is the concentration of charge that creates Tension or Voltage
Voltage drives the Current
Permissible Estep = (1000+6Csρs)0.116/sqrt(t)
Actual E < Permissible E
∆V∆V
Actual Estep < Permissible Estep
7/2/2013PBC Training Document PBC/ER/005 Rev 0 41
Mesh Potential (Permissible Value)
E touch is the Voltage difference between where the person is standing in the grid and GPR.
E mesh is the Max E touch in a grid
Permissible E touch is the voltage limit that can produce dangerous currents
42
dangerous currents
E mesh < Permissible E touch Permissible E touch =(1000+1.5Csρs)0.116/sqrt(t)
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Potential Distribution
Permissible Step PotentialActual Step Potential
43
PBC Training Document PBC/ER/005 Rev 0
Permissible Step Potential
Dangerous Step Potential
Actual Step Potential
Corrected Step Potential
7/2/2013
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201344
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201345
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201346
Ring Earth
•The concentric conductors reduce the resistance
significantly
•The reactance is reduced by tying the rings to
each other at the corners
•A ramp arrangement is followed burying the out
conductors deeper than the inner conductors to
47
7/2/2013PBC Training Document PBC/ER/005 Rev 0
conductors deeper than the inner conductors to
obtain a gradual potential curve
Formulae to Calculate Resistance
for plate earthingR = (ρ/4)* sqrt (π/2A) for pipe earthingR = (ρ/2πL)* [ln (8L/d)-1] for strip earthingR=(ρ/PπL)* [ln (2L2 /(wh))+ Q]
48
PBC Training Document PBC/ER/005 Rev 0
R=(ρ/PπL)* [ln (2L2 /(wh))+ Q] for grid earthingR=ρ[(1/LT)+ (1/sqrt (20A) (1+ (1/1+h) sqrt (20A)
Is Material of the grid important for achieving resistance?No. If corrosion factor is taken care of
7/2/2013
Variation of resistance to earth with length at different Soil resistivity
49
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Abstract of IEEE 14250
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Effect of Resistance due to Artificial Treatment
50
60
70
80
Radius of Artificial
treatment inmm
Remaining percentage of resistance to remote earth
51
PBC Training Document PBC/ER/005 Rev 0
0
10
20
30
40
1 10 100 1000 10000
Series1
30 75
60 62
90 54
150 48
300 32
1500 14
7/2/2013
Abstract of IEEE 80 2000
PBC Training Document PBC/ER/005 Rev 0 7/2/201352
Influence of MV on LV
If Rp>1, the voltage Rp*Ihmtshould be less than
100V in under 500 ms
500V in under 100 ms
53
If this is not so Rp and Rn must be separate
Exp. of PDS world wide
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Internationally accepted MV/LV earthing systems
7/2/2013PBC Training Document PBC/ER/005 Rev 0 54
7/2/2013PBC Training Document PBC/ER/005 Rev 0 55
Measurement of Resistance of the grounding system
Fall of point method
61.8% distance rule
Tagg slope method
Tagg intersection curve
Covered in the paper
56
PBC Training Document PBC/ER/005 Rev 0
Covered in the paper already with you
7/2/2013
Positioning of the potential probe57
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Essential Practices
Must use insulation gear
Must keep a gap of at least 6 meters between potential and current lead
Must insulate any joint appearing in the lead
Use meter having stray current filter.
58
PBC Training Document PBC/ER/005 Rev 0
having stray current filter.
where the injected current frequencies can be changed
Injected current can be made high or low depending on current probe resistance.
Apply water and compact the current and potential probes to avoid undue high probe resistance.
Lose potential probe can give high value of R .
Avoid measuring along buried or superficial metal conductors
7/2/2013
Fall of point method59
PBC Training Document PBC/ER/005 Rev 0
The average of the flat part of the graph gives the give the ground impedance
7/2/2013
61.8% Distance Rule
The reading levels of at P2 61.8% of the current probe C2
At distances lower than 61.8%, the impedance reading is lower and dips on approaching the resistance zone of the grid
60
PBC Training Document PBC/ER/005 Rev 0
resistance zone of the grid
Similarly the impedance reading increases as the P2 enters the resistance zone of C2
7/2/2013
TAGG SLOPE Method
µ=(R3-R2)/(R2-R1)0.4 < µ < 1.6
61
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
BREAK 362
THINKING T IME
PBC Training Document PBC/ER/005 Rev 0 7/2/2013
Earth fault Protection
Earth Fault protection in installations
Selection of device for automatic disconnection
Earth fault protection Devices
Duration 15 min
63
Duration 15 min
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Earth Fault Protection in Installation
Trip 65V in 10 Sec, and 230 V instantaneously Earth fault protection involves automatic disconnection to prevent dangerous duration and magnitude of touch voltage.
The earth fault loop impedance has to be low enough to trip overcurrent protective devices.
64
trip overcurrent protective devices. Where low earth fault loop impedance cannot be achieved, disconnection may be facilitated by RCCB or Voltage operated ELCB
RCD having minimum operating current greater than 30mA indirect shock risk protection
RCD having minimum operating current less than 30mA direct shock risk protection
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Voltage Operated ELCBVoltage Operated ELCBRCD Current Operated ELCBRCD Current Operated ELCB
Earth Fault Detection65
Not suitable for protection of humanTrip coil set to operate at 50 V
7/2/2013PBC Training Document PBC/ER/005 Rev 0
RCD Connections66
7/2/2013PBC Training Document PBC/ER/005 Rev 0
IS 304367
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Earthing of Captive Power Plant
Low voltage generators
High voltage generators
Duration 30 min
68
7/2/2013PBC Training Document PBC/ER/005 Rev 0
• It should be connected to installation main earth• The main earth terminal should be connected to earth electrode• Installation should be protected by RCD• RCD cannot protect generator side of the circuit.• For mobile loads the RCD should be 30mA with tripping time of 40mS
7/2/2013PBC Training Document PBC/ER/005 Rev 0 69
Generators above 10kW Working in parallel
• To avoid flow of circulating currents, the neutral point of generator is disconnected in presence of supply
70
7/2/2013PBC Training Document PBC/ER/005 Rev 0
presence of supply neutral
• Generators working in parallel, have only 1 common earth point.
• 30mA RCD to be provided for protection of load side of RCD
RCD
Low voltage standby generators with neutral earthing transformers
71
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Cable Core Sheath Bonding System72
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Statutory Provisions for Earthing
Should follow Indian Electricity Rule 1956
All MV and HV equipments to be earthed by 2 separate earths
Earth electrode should be devised such that testing is possible.
73
possible.
The value of earth resistance should be based on degree of shock protection.
No additional source to be added with out verifying the capacity of earthing system
7/2/2013PBC Training Document PBC/ER/005 Rev 0
Bibliography IEEE 80 2000 for substation
IEEE 665 1995 for Generating Station
IEEE 142 1991 for Industrial establishment
IEEE 81 1993 for Earthing Measurements
IEEE 1100 for powering and grounding electronic equipments.
IEEE 575 for sheath bonding and induced voltages IEEE 575 for sheath bonding and induced voltages
BS 7430 1998 Code of practice for Earthing
IS 3043-1987 Code of practice for Earthing
IEC 62305 Part 1 to Part 4
NFPA 70 and NFPA 780
API RP 2003 for statics and lightning protection
And many more ref. texts
7/2/2013PBC Training Document PBC/ER/005 Rev 0 74
SAFETY THRU DESIGN
Saving life and Assets75
THANKYOU
7/2/2013PBC Training Document PBC/ER/005 Rev 0