TECHNICAL REPORTTR-BTM-037015
TSR Number:Customer NamePT. SMOE INDONESIA
Customer Group-
Contact PersonMR. SADLIEmail-
Address
KOMPLEK INDUSTRIAL KABILTelephone0813 6395 0010
Fax
End User-
Job No-Job Open Date
Make-DIS/ Delivery date
Equipment TypeSTAMFORDFailure Date
ModelGD23-1331695Engine MadeCUMMINS
Equipment S/NG13K531336Engine ModelQSK23-G3
Customer Unit No.-Engine SN00326081
LocationPT. SMOE (KABIL)Hour meter50.03- HR
Application/UseCUMMINS POWER GENERATORStatusEngine trouble
Last Service-AuthorTANDI SURMARGI
Complaint Engine cant run. Have alarm shutdown in display engine.Inspection Result Check ploblem actual in panel engine. Problem in fuel card (GCS) connection diode burnt.correction Check control GCS in panel generator. Test calibration GCS. (GCS cant respon callibration) Check harness engine and panel PCC. (Good condition) Check fuse in connection harness engine and fuse base card. (Good condition) Measure actual voltage input/output in panel PCC 24 vdc. (Good condition) Check connection wiring diagram. Check connector fuel card, base card and parraling card. (Good condition) Check connection external charging. (Good condition) Check condition diode in magnetic switch starter. (Good condition) Engine photograph for reporting.Suggestions Change fuel card new.
Acknowledged By, Reported By,
( Danang Bayuaji K ) ( TANDI S. )
Photo attachment :
Condition harnes engine.
Condition panel after renove GCS
Condition actual diode burnt
Condition actual diode burnt
Condition battery 24 vdc
Check diode in connection magnetic switch
Relay in cover GCS
Connector GCS
Data plate Engine
Data plate altenator
Component in display board burnt
Charging external battery