    Qatar Civil Defence Particular RequirementQCDFSS-6.3

    Approved Products

    Mimic Panels

    Plan Submission Details

  • 8/4/2019 Techno Q Feb 09

    3/12

    With the increasing numbers of fire alarm systems

    installations and the myriad of types of systems

    available on the market, in Sept 2007 the QCD perceived

    the need for uniform application of the requirements

    for the provision of fire alarm systems and issued QCD

    FSS 6.3

    This Particular Requirement addresses the need for

    providing fire alarm systems and clearly defines what

    types of systems are required for each type of

    occupancy.

  • 8/4/2019 Techno Q Feb 09

    4/12

    It establishes the code against which compliance will be

    checked and defines parameters and limits for the installation

    of devices.

    It also addresses the needs of fire fighter and first responders.

    Where Fire Alarms Systems are prescribed either by Table 1 or by

    the NFPA101, it is a requirement that these systems also provide

    information for Fire Fighters.

  • 8/4/2019 Techno Q Feb 09

    5/12

    Table 1

    Table 1 lists in the left hand column the various types of

    occupancies and their height.

    The 2nd column lists the limiting floor area where each

    type of system is required.

  • 8/4/2019 Techno Q Feb 09

    6/12

    Examples

    Single Storey Residential buildings regardless of their size do

    not require a fire alarm system.

    If the building has up to 4 storeys and a foot print of 400 m2 or

    greater, then as a minimum a manual fire alarm system is

    required.

    Residential buildings up to the high rise limit require a manual

    alarm system regardless of the size of its foot print.

  • 8/4/2019 Techno Q Feb 09

    7/12

    High Rise Residential buildings require an automatic

    and manual fire alarm systems system.

    Other Occupancies are dealt with in a similar fashion

    considering the proposed occupants, the height of the

    building and the floor area all of which affect the

    number of occupants and their ability to flee a possiblefire.

  • 8/4/2019 Techno Q Feb 09

    8/12

    Fire Alarm Systems Designs and their configurations

    are required to conform to the NFPA 72. These codes in

    turn require components to be listed for the service

    they are intended.

    The QCD implements a Product Approval system that

    ensure fire alarm products sold and marketed in Qatardo meet minimum performance standards.

  • 8/4/2019 Techno Q Feb 09

    9/12

    The testing standards mentioned in the NFPA codes are

    American standards such as ASTM and ANSI however the QCD

    does accept other internationally recognized performance

    standards such as BS, EN and German VDS.

    All products relied upon for fire life safety must not only have

    been tested for performance but shall also carry Product

    Certification from a recognized certification agency acceptable

    to the QCD to ensure that what was tested is what is actually

    delivered and installed in Qatar.

  • 8/4/2019 Techno Q Feb 09

    10/12

    QCD requires Mimic Panels to provide simplified

    information for fire fighters responding to call outs.

    Every fire alarm system shall have a mimic panel that

    shows graphically the layout of the protected property

    and it shall indicate using illuminated red LED's the

    source and location of the alarm.

    The types of alarm required to be indicated on the

    Mimic Panels shall are Sprinkler Flow Switches,

    Automatic Detectors and Manual Call Points.

  • 8/4/2019 Techno Q Feb 09

    11/12

    The intention of these mimic panels is to simplify the

    transmission of basic information to the fire fighters to get them

    quickly to the location of the alarm.

    Subject to the size and or complexity of each floor, Mimic Panels

    may be required on each floor.

    Where the floor area is less than 1,000m2 a zone chart without

    the indicating LED's is permitted. The location of devices shall be

    shown on this chart.

  • 8/4/2019 Techno Q Feb 09

    12/12

    Fire Alarm Systems Plans submitted to theQCD for approval As part of the Building Permit

    Process must be submitted in accordance withFire Safety Handbook No. 1

    Pages 16 and 17 clearly specify the details

    that are required to be shown on the plans.