84
Technical Directory 2006 NATURAL SMOKE AND HEAT EXHAUST VENTILATION AND ROOF LIGHTING SYSTEMS Ever since its formation in 1988, Mercor has been an established leader in the passive fire-safety systems market. Our product lines of: fire partitions, natural smoke and heat exhaust ventilation and roof lighting systems, fire ventilation systems, fireproofing of building structures set the standard for building projects all over the country. With our qualified staff we offer customised products for our clients providing comprehensive services – from design advice, through pricing, manufacturing, mounting and servicing. Our products have the required technical approvals and certificates of ITB and CNBOP laboratories acknowledged by the fire brigade. They also fulfil the requirements of EN 12101-2 therefore can be distributed in all EU countries. In 2005 we became a co-owner of Hasil, the biggest manufacturer of fire partitions in the Czech Republic. Using the modern technologies and the potential of both companies, we can effectively improve the strong market position in our region of Europe. The catalogue we place in your hands has been produced to enable all interested parties access to the technical details of our products. The current version of the technical guide is available in electronic form on our website: www.mercor.com.pl We look forward to doing business with you. Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk
Transcript
Page 1: Teknisk dokumentation ovenlys og brandventilation

Technical Directory 2006

NAT

URAL

SMO

KE A

ND H

EAT

EXHA

UST

VENT

ILAT

ION

AND

RO

OF

LIGHT

ING

SYST

EMS

Ever since its formation in 1988, Mercor has been an established leader in the passive �re-safety systems market.Our product lines of:• �re partitions,• natural smoke and heat exhaust ventilation and roof lighting systems,• �re ventilation systems,• �reproo�ng of building structures

set the standard for building projects all over the country.With our quali�ed sta� we o�er customised products for our clients providing comprehensive services – from design advice, through pricing, manufacturing, mounting and servicing.Our products have the required technical approvals and certi�cates of ITB and CNBOP laboratories acknowledged by the �re brigade. They also ful�l the requirements of EN 12101-2 therefore can be distributed in all EU countries. In 2005 we became a co-owner of Hasil, the biggest manufacturer of �re partitions in the Czech Republic. Using the modern technologies and the potential of both companies, we can e�ectively improve the strong market position in our region of Europe.The catalogue we place in your hands has been produced to enable all interested parties access to the technical details of our products.The current version of the technical guide is available in electronic form on our website: www.mercor.com.pl

We look forward to doing business with you.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 2: Teknisk dokumentation ovenlys og brandventilation

Natural smoke and heat exhaust ventilation and roof lighting systemstechnical directory 2006

editing: Mercor – Team of the Smoke and Heat Ventilation Division

cover design : Jerzy Wojciech Wołodźko

graphic design and dtp:gato studio gra�czne grzegorz petrycki

©2006 MERCOR Gdańsk (20.05.2006)

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 3: Teknisk dokumentation ovenlys og brandventilation

1. mcr prolight – smoke vents 5

1.1. smoke vents MCR-Prolight, C and E type, square and rectangular with upright curb 6

1.2. smoke vents MCR-Prolight, DVP type, double-leaf rectangular with upright curb 8

1.3. smoke vents MCR-Prolight, NG type, square and rectangular with skew curb 10

1.4. smoke vents MCR-Prolight, R type, round with upright curb 12

1.5. smoke vents MCR-Prolight, overlay type, for profiled roofs, PR variety 14

1.6. smoke vents MCR-Prolight, overlay type, for plinth, N variety 15

2. mcr prolight – skylights C, E, NG, and R type, on upright and skew curbs 16

3. mcr prolight – roof hatchways C, E, and NG type 18

4. mcr prolight – smoke vents and skylights – additional equipment 20

5. mcr prolight – methods of mounting and roof work for smoke vents, skylights and roof hatchways 22

6. mcr prolight – continuous rooflights with integrated smoke vents and/or ventilation hatches 27

6.1. arch-shaped continuous rooflights 28

6.2. triangular continuous rooflights 29

6.3. pyramid skylights 30

6.4. igloo-shaped skylights 31

6.5. smoke vents and ventilation hatches integrated in continuous rooflights 32

7. mcr prolight – methods of mounting for curbs of continuous rooflights and finishing 35

8. fillings 39

8.1. fillings of spot smoke vents, spot skylights, and spot hatchways 39

8.2. fillings of spot smoke vents, spot skylights, spot hatchways, and continuous rooflights 40

9. control systems for smoke vents 41

9.1. pneumatic control system for smoke and heat ventilation and/or daily ventilation 42

9.2. electrical control system for smoke and heat ventilation and/or daily ventilation 56

9.3. mechanical control system for smoke and heat ventilation and/or daily ventilation 73

10. oso mcr – window-based smoke and heat ventilation system 75

11. mcr kurtyna prosmoke – smoke curtains 83

table of contents

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 4: Teknisk dokumentation ovenlys og brandventilation

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 5: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 5

mcr prolight

introduction

Smoke vents MCR-Prolight Plus are automatic smoke exhaust devices. The basic function of smoke vents MCR-Prolight is to exhaust smoke, combustion gases and heat energy from enclosed spaces (production floors, storage spaces, public facilities, etc.) to the outside of buildings, in order to protect human lives and property by:

• maintaining escape routes with low smoke levels permitting effective evacuation,• facilitating fire-fighting action by easier location of the place of fire,• reducing the risk of destruction of the building structure by lowering the temperature,• limiting fire damage caused by smoke, hot combustion gases and thermal decomposition products.

They may also serve the function of ventilation hatches, combined smoke and heat ventilators with daily ventilation, roof hatchways, as well as roof lighting. By using smoke vents, the investor gains the opportunity to:

• reduce the fire resistance class of the building,• enlarge the acceptable fire zones,• lengthen the escape routes.

Depending on the requirements of individual customers, MERCOR offers single-leaf and double-leaf smoke vents, on upright and skew curbs, in a wide range of opening dimensions and curbs heights. With prior inquiry, it is also possible to make curbs of dimensions not included in this technical guide. All steel elements of vents are protected with a zinc coating applied by hot-galvanising or electro-galvanising and chemically passivated.As standard, the bases are delivered with 20 mm thick thermal insulation. Individual selection of the thickness and type of thermal insulation is possible.The following filling types of openable leaf are used:

• cellular polycarbonate, 10 to 25 mm thick, different degrees of transparency, different heat transfer coefficients,• single, double, and triple acrylic domes,• solid polycarbonate sheets,• laminar boards (e.g. aluminium – foamed polystyrene – aluminium) – so called “blind” filling.

Detailed information about filling is given in the table (pages 37-38).Smoke vents MCR-Prolight are offered with the following control systems:

• electrical control,• pneumatic control,• pneumatic-electrical control,• mechanical control.

All these control systems may serve the function of smoke exhaust or smoke exhaust and daily ventilation. Opening of smoke vents may be realised both from the user level and automatically by thermal fuses, smoke exhaust control panels, or fire alarm signalling.Smoke vents of type MCR-Prolight offered by MERCOR satisfy the requirements of the technical approval ITB no. AT-15-6495/2005 confirmed by the certificate of conformity no. ITB-0920/W as well as the certificate of conformity in accordance with EN 12101-2: 2004

smoke vents

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 6: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

6

standard description1.1.1.

smoke vent MCR-PROLIGHT with an example control system, C or E type – cross-section1.1.2.

vent execution options1.1.3.

smoke vents C and E type, square and rectangular with upright base

C and E type vents are accommodated for flat and sloped roofs, covered with e.g. roofing paper or PVC membrane.

• upright base of galvanised steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• lower part of the base is equipped with a flange used for mounting to the roof structure,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking of the thermal insulation that permits

finishing of the base,• filling in form of cellular or solid polycarbonate sheet, acrylic

dome, or laminar board,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

K A x B

H

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. actuator holder6. smoke exhaust actuator7. venting actuator

8. hook console9. upright base10. thermal insulation of the base11. leaf gasket12. base flange13. hinge14. external planking – galvanized steel sheet

• leaf position sensor (open – closed),• anti-burglary grate painted in a colour of RAL palette,• painting of the base in any colour of RAL palette,• wind deflectors, painted in any colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,• non-standard opening dimensions and base height,• accommodation of the lower mounting flange dimensions to

the roof structure,

• external casing of the base made of e.g. galvanised steel sheet (can be painted in any colour of RAL palette),

• polyester base,• external planking of the thermal insulation made of PVC-

coated sheet metal,• directing nozzle, painted in any colour of RAL palette.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 7: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 7

mcr prolight

technical data1.1.4.

type

nominal dimensions

(inlet opening dimensions)

aerodynamical free areaapproximate

weight

rated current of electric actuator for snow load

class

standard with wind deflectors

with directing nozzle

with deflectors and directing

nozzleSL250 SL550

[cm] [m2] [m2] [m2] [m2] [kg] [A] [A]C 100 100 x 100 0,60 0,75 0,88 0,96 70 max 2 2,6C 110 110 x 110 0,73 0,91 1,08 1,20 75 2,0 4,0C 120 120 x 120 0,86 1,08 1,25 1,39 80 2,6 4,0C 130 130 x 130 1,01 1,27 1,44 1,60 85 2,6 4,0C 140 140 x 140 1,18 1,47 1,64 1,82 90 6,0C 150 150 x 150 1,35 1,69 1,85 2,05 95 6,0C 160 160 x 160 1,54 1,92 2,11 2,33 100 6,0C 180 180 x 180 1,94 2,43 2,60 2,88 110 6,0C 200 200 x 200 2,40 3,00 3,19 3,53 120

E 100/120 100 x 120 0,72 0,90 1,04 1,14 75 2,0 4,0E 100/130 100 x 130 0,78 0,98 1,15 1,28 78 2,0 4,0E 100/140 100 x 140 0,84 1,05 1,23 1,36 80 2,6 4,0E 100/150 100 x 150 0,90 1,13 1,31 1,45 82 2,6 4,0E 100/160 100 x 160 0,96 1,20 1,38 1,53 85 2,6 4,0E 100/180 100 x 180 1,08 1,35 1,53 1,69 90 2,6E 100/200 100 x 200 1,20 1,50 1,69 1,87 95 4,0E 100/220 100 x 220 1,32 1,65 1,83 2,03 100 4,0E 100/240 100 x 240 1,44 1,80 2,00 2,22 105 4,0E 100/250 100 x 250 1,50 1,88 2,08 2,30 110 4,0E 120/140 120 x 140 1,01 1,26 1,43 1,59 82 4,0 4,0E 120/150 120 x 150 1,08 1,35 1,53 1,69 87 4,0E 120/170 120 x 170 1,22 1,53 1,70 1,89 90 4,0E 120/180 120 x 180 1,30 1,62 1,79 1,99 95 4,0E 120/200 120 x 200 1,44 1,80 2,00 2,22 100 4,0E 120/220 120 x 220 1,58 1,98 2,18 2,42 105 4,0E 120/240 120 x 240 1,73 2,16 2,34 2,59 110 4,0E 120/250 120 x 250 1,80 2,25 2,46 2,72 120E 130/150 130 x 150 1,17 1,46 1,63 1,81 90 4,0E 130/160 130 x 160 1,25 1,56 1,73 1,92 95 4,0E 130/180 130 x 180 1,40 1,76 1,92 2,13 100 4,0E 130/200 130 x 200 1,56 1,95 2,15 2,38 105 4,0E 130/220 130 x 220 1,72 2,15 2,34 2,59 110 4,0E 130/230 130 x 230 1,79 2,24 2,44 2,70 112E 130/250 130 x 250 1,95 2,44 2,63 2,92 115E 140/150 140 x 150 1,26 1,58 1,77 1,96 95 4,0E 140/180 140 x 180 1,51 1,89 2,08 2,30 100 6,0E 140/200 140 x 200 1,68 2,10 2,29 2,53 105E 140/250 140 x 250 2,10 2,63 2,81 3,11 120E 150/160 150 x 160 1,44 1,80 2,00 2,22 100 6,0E 150/180 150 x 180 1,62 2,03 2,21 2,45 105 6,0E 150/200 150 x 200 1,80 2,25 2,46 2,72 110E 150/240 150 x 240 2,16 2,70 2,87 3,17 120E 150/250 150 x 250 2,25 2,81 2,98 3,30 125E 160/180 160 x 180 1,73 2,16 2,34 2,59 110 6,0E 160/200 160 x 200 1,92 2,40 2,57 2,85 115E 160/220 160 x 220 2,11 2,64 2,81 3,11 120E 160/240 160 x 240 2,30 2,88 3,04 3,37 125E 180/200 180 x 200 2,16 2,70 2,87 3,17 120E 180/220 180 x 220 2,38 2,97 3,12 3,46 125E 180/240 180 x 240 2,59 3,24 3,41 3,80 130E 180/250 180 x 250 2,70 3,38 3,56 3,94 135E 190/200 190 x 200 2,28 2,85 3,00 3,33 120E 200/250 200 x 250 3,00 3,75 3,94 4,35 140It is possible to make intermediate dimensions of vents between the values given in the table.The aerodynamical free area for these dimensions is determined using linear interpolation.

smoke vents C and E type, square and rectangular with upright base

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 8: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

8

standard description1.2.1.

smoke vent MCR-PROLIGHT, DVP type, with an example control system – cross-section1.2.2.

vent execution options1.2.3.

smoke vents DVP type, double-leaf rectangular with upright base

DVP type vents are accommodated for flat and sloped roofs, covered with e.g. roofing paper or PVC membrane.

• upright base of galvanized steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• lower part of the base is equipped with a flange used for mounting to the roof structure,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking of the thermal insulation that permits

finishing of the base,• filling in form of cellular or solid polycarbonate sheet or

laminar board,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. base cross-bars set6. smoke exhaust actuator7. venting actuator8. hook console

9. upright base10. thermal insulation of the base11. leaf gasket12. base flange13. hinge14. gutter15. thermal insulation of the gutter16. external planking – galvanized steel sheet

• leaf position sensor (open – closed),• anti-burglary grate painted in a colour of RAL palette,• painting of the base in a colour of RAL palette (powder

painting up to dimensions 180 x 300),• wind deflectors, painted in any colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,• non-standard opening dimensions and base height,

• accommodation of the lower mounting flange dimensions to the roof structure,

• external casing of the base made of e.g. galvanised steel sheet (can be painted in any colour of RAL palette),

• external planking made of PVC-coated sheet metal,• directing nozzle, painted in any colour of RAL palette.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 9: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 9

mcr prolight

technical data1.2.4.

type of double-leaf vent with upright

base

nominal dimensions

(inlet opening dimensions)

aerodynamic free area

approximate weight

rated current of electric

actuator for snow load

class*

standard with wind deflectors

with directing

nozzle

with deflectors

and directing nozzle

SL550

[cm] [m2] [m2] [m2] [m2] [kg] [A]DVP 120/250 120 x 250 1,80 2,19 2,34 2,57 150 2* 1,3DVP 120/300 120 x 300 2,16 2,63 2,78 3,05 170 2* 1,6DVP 150/250 150 x 250 2,25 2,74 2,85 3,12 160 2* 2,0DVP 150/300 150 x 300 2,70 3,29 3,37 3,67 180 2* 2,6DVP 160/160 160 x 160 1,54 1,87 2,01 2,20 130 2* 1,6DVP 160/250 160 x 250 2,40 2,92 3,01 3,30 170 2* 2,0DVP 160/280 160 x 280 2,69 3,27 3,35 3,67 180 2* 2,6DVP 160/300 160 x 300 2,88 3,50 3,57 3,89 190 2* 2,6DVP 170/300 170 x 300 3,06 3,72 3,74 4,09 195 2* 4,0DVP 180/160 180 x 160 1,73 2,10 2,23 2,45 140 2* 2,0DVP 180/180 180 x 180 1,94 2,37 2,48 2,72 150 2* 2,0DVP 180/250 180 x 250 2,70 3,29 3,35 3,67 170 2* 2,6DVP 180/280 180 x 280 3,02 3,68 3,72 4,08 190 2* 2,6DVP 180/300 180 x 300 3,24 3,94 3,97 4,35 195 2* 4,0DVP 200/200 200 x 200 2,40 2,92 3,00 3,30 160 2* 2,6DVP 200/240 200 x 240 2,88 3,50 3,55 3,89 180 2* 4,0DVP 200/250 200 x 250 3,00 3,65 3,68 4,04 185 2* 4,0DVP 200/280 200 x 280 3,36 4,09 4,09 4,49 190 2* 4,0DVP 200/300 200 x 300 3,60 4,38 4,36 4,77 200 2* 4,0DVP 220/220 220 x 220 2,90 3,53 3,57 3,92 180 2* 4,0DVP 220/240 220 x 240 3,17 3,85 3,87 4,24 185 2* 6,0DVP 220/250 220 x 250 3,30 4,02 4,02 4,41 190 2* 6,0DVP 240/240 240 x 240 3,46 4,20 4,19 4,60 190 2* 6,0DVP 240/250 240 x 250 3,60 4,38 4,35 4,77 200 2* 6,0DVP 250/250 250 x 250 3,75 4,56 4,52 4,96 205 2* 6,0DVP 250/300 250 x 300 4,50 5,48 5,36 5,88 220 2* 6,0DVP 300/300 300 x 300 5,40 6,57 6,35 6,96 240* for smoke vents with H=50 cm

It is possible to make intermediate dimensions of vents between the values given in the table.The aerodynamic free area for these dimensions is determined using linear interpolation.

smoke vents DVP type, double-leaf rectangular with upright base

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 10: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

10

standard description1.3.1.

smoke vent MCR-PROLIGHT, NG type, with an example control system – cross-section1.3.2.

vent execution options1.3.3.

smoke vents NG type, square and rectangular with skew base

NG type vents are accommodated for flat and sloped roofs, covered with e.g. roofing paper or PVC membrane.

• skew base of galvanised steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• lower part of the base is equipped with a flange used for mounting to the roof structure,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking of the thermal insulation that permits

finishing of the base,• filling in form of cellular or solid polycarbonate sheet, acrylic

dome, or laminar board,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. actuator holder6. smoke exhaust actuator7. venting actuator

8. hook console9. skew base10. thermal insulation of the base11. leaf gasket12. base flange13. hinge14. external planking – galvanised steel sheet

• individual accommodation of the opening dimensions to the trimmer beams structure and the filling dimensions,

• leaf position sensor (open – closed),• anti-burglary grate painted in a colour of RAL palette,• painting of the base in a colour of RAL palette,• wind deflectors, painted in a colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,

• non-standard opening dimensions and base height,• accommodation of the lower mounting flange dimensions to

the roof structure,• external casing of the base made of e.g. galvanised steel

sheet (can be painted in any colour of RAL palette),• external planking of the thermal insulation made of PVC-

coated sheet metal.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 11: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 11

mcr prolight

technical data1.3.4.

type of single-leaf vent with

skew base

nominal dimensions

(roof opening

dimensions)

vent opening

dimensions

aerodynamic free area

approximate weight

rated current of electric actuator for snow load

class

standardwith wind deflectors

with directing

nozzle

with deflectors

and directing nozzle

SL250 SL550

[cm] [cm] [m2] [m2] [m2] [m2] [kg] [A] [A]NG 100/100 100 x 100 80 x 80 0,55 0,63 0,63 0,63 60 1,3 1,6NG 100/150 100 x 150 80 x 130 0,83 1,03 1,00 1,03 70 1,6 2,6NG 100/200 100 x 200 80 x 180 1,10 1,40 1,32 1,43 90 2,0 4,0NG 100/220 100 x 220 80 x 200 1,21 1,54 1,48 1,58 95 2,6 4,0NG 100/240 100 x 240 80 x 220 1,32 1,68 1,61 1,72 100 2,6NG 100/250 100 x 250 80 x 230 1,38 1,75 1,67 1,78 105 2,6NG 120/120 120 x 120 100 x 100 0,79 0,96 0,94 0,96 70 max 2,0 2,6NG 120/150 120 x 150 100 x 130 0,99 1,26 1,19 1,29 80 2,0 4,0NG 120/180 120 x 180 100 x 170 1,19 1,51 1,44 1,54 90 2,6 4,0NG 120/240 120 x 240 100 x 220 1,58 2,02 1,93 2,07 100 4,0 4,0NG 120/250 120 x 250 100 x 230 1,65 2,10 2,00 2,15 110 4,0NG 150/150 150 x 150 130 x 130 1,24 1,58 1,49 1,59 90 4,0 4,0NG 150/160 150 x 160 130 x 140 1,32 1,68 1,58 1,68 95 4,0NG 150/180 150 x 180 130 x 160 1,49 1,89 1,81 1,94 100 4,0NG 150/220 150 x 220 130 x 200 1,82 2,31 2,24 2,41 110 6,0NG 150/240 150 x 240 130 x 220 1,98 2,52 2,43 2,61 115 6,0NG 150/250 150 x 250 130 x 230 2,06 2,63 2,53 2,71 120 6,0NG 160/160 160 x 160 140 x 140 1,41 1,79 1,72 1,85 100 4,0NG 160/180 160 x 180 140 x 180 1,58 2,02 1,91 2,05 105 6,0NG 160/200 160 x 200 140 x 180 1,76 2,24 2,13 2,26 110 6,0NG 160/220 160 x 220 140 x 200 1,94 2,46 2,38 2,55 115NG 160/250 160 x 250 140 x 230 2,20 2,80 2,67 2,86 120NG 180/180 180 x 180 160 x 160 1,78 2,27 2,20 2,36 110 6,0NG 180/200 180 x 200 160 x 200 1,98 2,52 2,42 2,60 115 8,0NG 180/220 180 x 220 160 x 200 2,18 2,77 2,64 2,83 120 8,0NG 180/240 180 x 240 160 x 220 2,38 3,02 2,86 3,07 125 8,0NG 180/250 180 x 250 160 x 230 2,48 3,15 2,97 3,22 130 8,0NG 200/200 200 x 200 180 x 180 2,20 2,80 2,66 2,86 120 6,0NG 200/250 200 x 250 180 x 230 2,75 3,50 3,33 3,54 130NG 200/300 200 x 300 180 x 280 3,30 4,32 4,00 4,25 140NG 220/220 220 x 220 200 x 200 2,66 3,39 3,23 3,43 130It is possible to make intermediate dimensions of vents between the values given in the table.

The active surface area for these dimensions is determined using linear interpolation.

smoke vents NG type, square and rectangular with skew base

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 12: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

12

standard description1.4.1.

smoke vent MCR-PROLIGHT, R type, with an example control system – cross-section1.4.2.

vent execution options1.4.3.

smoke vents R type, round with upright base

R type vents are accommodated for flat and sloped roofs, covered with e.g. roofing paper or PVC membrane.

• upright base of galvanised steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• painting of the base in a colour of RAL palette,• lower part of the base is equipped with a flange used for

mounting to the roof structure,• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking on the entire height of the base,• filling in form of acrylic dome,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. actuator holder6. smoke exhaust actuator7. venting actuator

8. hook console9. upright base10. thermal insulation of the base11. leaf gasket12. base flange13. hinge14. external planking – galvanized steel sheet

• leaf position sensor (open – closed),• anti-burglary grate painted in a colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,

• non-standard opening dimensions and base height,• accommodation of the lower mounting flange dimensions to

the roof structure.

średnica

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 13: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 13

mcr prolight

technical data1.4.4.

type of single-leaf round vent

with upright base

nominal dimension

(inlet opening diameter)

aerodynamic free areaapproximate

weight

ratedcurrent of electric actuator for snow

load classstandard with directing

nozzle SL250 SL550[cm] [m2] [m2] [kg] [A] [A]

R 100 100 0,43 0,46 65 1,6 2,0R 110 110 0,52 0,55 70 1,6 2,6R 115 115 0,57 0,60 72 1,6 4,0R 120 120 0,62 0,66 75 2,0 4,0R 125 125 0,67 0,71 77 2,0 4,0R 130 130 0,73 0,77 80 2,6 4,0R 135 135 0,79 0,83 83 4,0 6,0R 140 140 0,85 0,89 86 4,0 6,0R 150 150 0,97 1,02 90 4,0R 155 155 1,04 1,09 93 4,0R 160 160 1,11 1,17 97 6,0

It is possible to make intermediate dimensions of vents between the values given in the table.The active surface area for these dimensions is determined using linear interpolation.

smoke vents R type, round with upright base

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 14: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

14

standard description1.5.1.

smoke vent MCR-PROLIGHT, PR type, example structure varieties1.5.2.

vent execution options1.5.3.

smoke vents for profiled roofs, PR variety

PR type vents are accommodated for flat and sloped roofs, covered with profiled (e.g. trapezoid) sheet metal or sandwich-type of selected profiles.

• vent bases as the bases of C, E, DVP, and NG types,• thermal insulation of thickness 20 mm,• external aluminium finishing accommodated to the metal

sheet of the roof covering (prior arrangements are necessary, concerning the roof covering type),

• accommodation of the lower mounting flange dimensions to the roof structure (prior arrangements are necessary, concerning the structure type),

• filling as for C, E, DVP, and NG type vents,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. system gasket6. upper part of the external casing

7. lower part of the external casing8. upright base9. thermal insulation of the base10. gasket11. profiled flange

• leaf position sensor (open – closed),• anti-burglary grate painted in any colour of RAL palette,• painting of the base in a colour of RAL palette,• wind deflectors, painted in any colour of RAL palette,• change of the thermal insulation thickness and type,

• change of the base thickness and material,• non-standard opening dimensions and base height,• directing nozzle.

PR smoke vent, section of the side along the roof slope

PR smoke vent, section of the side perpendicular to the roof slope – bottom

PR smoke vent, section of the side perpendicular to the roof slope – top

notes1.5.4.

It is recommended to use PR vents for SANDWICH type covering at distances up to 2 m from the roof ridge or in the roof ridge.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 15: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 15

mcr prolight

standard description1.6.1.

smoke vent MCR-PROLIGHT, N type, with an example control system – cross-section1.6.2.

hatch execution options1.6.3.

smoke vents overlay type, for plinth, N variety

Overlay vents are accommodated for mounting on existing concrete or steel plinths and they are manufactured in dimensions of C, E, DVP, and NG vents.

• vent bases as the bases of C, E, DVP, and NG types,• lower part of the base is equipped with a flange used

for mounting on a plinth or on an existing base, e.g. of a skylight, executed in accordance with the client’s specification,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external finishing of galvanised steel sheet with a flange

accommodated to the plinth dimensions and equipped with a drip cap of height 50 mm,

• filling as for C, E, DVP, and NG type vents,• optional control: pneumatic, electrical, mechanical, or

pneumatic-electrical.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. actuator holder6. smoke exhaust actuator7. venting actuator

8. hook console9. upright base10. thermal insulation of the base11. leaf gasket12. base flange13. hinge14. external planking – galvanised steel sheet

• leaf position sensor (open – closed),• anti-burglary grate painted in a colour of RAL palette,• painting of the base in a colour of RAL palette,• wind deflectors, painted in a colour of RAL palette,• change of the thermal insulation thickness and type,

• change of the base thickness and material,• non-standard opening dimensions and base height,• directing nozzle painted in a colour of RAL palette.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 16: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

16

standard description2.1.

skylight MCR-PROLIGHT, C or E type – cross-section2.2.

skylights C, E, NG, and R type, on upright and skew bases

Skylights are accommodated for flat and sloped roofs, covered with roofing paper, PVC membrane, roofing tile (C, E, NG, R types), profiled sheet metal (PR type), or for plinths (N type). They are manufactured in structural varieties as vents: C, E, N, NG, PR, and R.

• upright or skew (NG) base of galvanised steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• lower part of the base is equipped with a flange used for mounting to the roof structure,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking of the thermal insulation that permits

finishing of the base or planking on the entire height of the base in R and N types,

• filling in form of cellular or solid polycarbonate sheet, acrylic dome, or laminar board.

1. filling2. pressing frame3. upright or skew (NG) base4. thermal insulation of the base

5. gasket6. base flange7. external planking (C, E, NG, PR)

NG type skylight

A x Ba x b

H

E-N type skylight

A x B

H

R type skylight

H

E-PR type skylight

A x B

H

diameter

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 17: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 17

mcr prolight

technical data2.3.

skylight execution options2.4.

• anti-burglary grate painted in any colour of RAL palette,• painting of the base in any colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,• non-standard opening dimensions and base height,• accommodation of the lower mounting flange dimensions to

the roof structure,• external finishing made of e.g. galvanised steel sheet,• upper planking made of PVC-coated sheet metal,• skylight accommodation for mounting on roofs covered with

profiled sheet metal – PR type.

typ opening dimensions A x B [cm]

squareC 50 50 x 50C 70 70 x 70C 80 80 x80C 85 85 x 85C 100 100 x 100C 120 120 x 120C 140 140 x 140C 150 150 x 150C 160 160 x 160C 180 180 x 180C 200 200 x 200

rectangularE 50/100 50 x 100E 70/100 70 x 100E 100/140 100 x 140E 100/150 100 x 150E 100/200 100 x 200E 100/220 100 x 220E 120/150 120 x 150E 120/170 120 x 170E 120/180 120 x 180E 120/250 120 x 250E 120/300 120 x 300E 140/200 140 x 200E 150/250 150 x 250E 150/300 150 x 300E 160/180 160 x 180E 160/250 160 x 250E 180/250 180 x 250E 180/300 180 x 300E 200/250 200 x 250E 200/300 200 x 300E 200/400 200 x 400

roundR 70 Ø 70R 85 Ø 85R 100 Ø 100R 120 Ø 120R 140 Ø 140R 160 Ø 160R 180 Ø 180R 200 Ø 200R 250 Ø 250R 300 Ø 300

typdome opening

dimensions [cm]

roof opening dimensions

[cm]with skew base

NG 60/90 40 x 70 60 x 90NG 90/90 70 x 70 90 x 90

NG 100/100 80 x 80 100 x 100NG 100/140 80 x 130 100 x 150NG 100/150 80 x 120 100 x 140NG 100/200 80 x 180 100 x 200NG 100/240 80 x 120 100 x 240NG 100/250 80 x 230 100 x 250NG 120/120 100 x 100 120 x 120NG 120/150 100 x 130 120 x 150NG 120/180 100 x 160 120 x 180NG 120/240 100 x 220 120 x 240NG 120/250 100 x 230 120 x 250NG 150/150 130 x 130 150 x 150NG 150/180 130 x 160 150 x 180NG 150/210 130 x 190 150 x 210NG 150/240 130 x 220 150 x 240NG 150/250 130 x 230 150 x 250NG 180/180 160 x 160 180 x 180NG 180/240 160 x 220 180 x 240NG 180/250 260 x230 180 x 250NG 200/200 180 x 180 200 x 200NG 220/220 200 x 200 220 x 220

domes for skylights2.5.

We offer single, double, and triple acrylic domes in most dimensions of the manufactured vents and skylights. Please contact our sales department for detailed information. Domes of solid polycarbonate are only available on special request.

note2.6.

Not all skylight dimensions are available with all filling types – please consult our sales department.

skylights C, E, NG, and R type, on upright and skew bases

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 18: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

18

standard description3.1.

roof hatchway, C type, with gas springs – cross-section3.2.

roof hatchways C, E, and NG type

Hatchways are accommodated for flat and sloped roofs, covered with roofing paper, PVC membrane, roofing tile (C, E, NG types), or profiled sheet metal (PR type). They are manufactured in structural varieties as vents: C, E, NG, PR.

• upright or skew (NG) base of galvanised steel sheet of thickness 1.25 mm, height H = 300 or 500 mm,

• lower part of the base is equipped with a flange used for mounting to the roof structure,

• upper part of the base is profiled for a water removal system,• thermal insulation of thickness 20 mm,• external planking of the thermal insulation that permits

finishing of the base,• filling in form of cellular or solid polycarbonate board, acrylic

dome, or laminar board,• gas springs used in order to facilitate opening the hatchway

and keeping it open.

1. filling2. pressing frame3. supporting frame4. leaf cross-bar5. hatchway lock6. gas spring7. upright or skew (NG) base8. thermal insulation of the base

9. leaf gasket10. base flange11. hinge12. opening limit cord13. actuator mounting console14. handle15. external planking – galvanised steel sheet

• leaf position sensor (open),• anti-burglary grate painted in a colour of RAL palette,• painting of the base in a colour of RAL palette,• change of the thermal insulation thickness and type,• change of the base thickness and material,• non-standard opening dimensions and base height,• accommodation of the lower mounting flange dimensions to

the roof structure,

• external casing of the base made of e.g. galvanised steel sheet (can be painted in any colour of RAL palette),

• upper planking made of PVC-coated sheet metal,• hatchway accommodation for mounting on roofs covered

with profiled sheet metal.

hatchway execution options3.3.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 19: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 19

mcr prolight

technical data3.4.

typ vent opening dimensions A x B [cm]

squareC 80 80 x 80C 100 100 x 100C 120 120 x 120C 140 140 x 140C 150 150 x 150

rectangularE 100/140 100 x 140E 100/150 100 x 150E 100/200 100 x 200E 100/220 100 x 220E 120/150 120 x 150E 120/170 120 x 170

typvent opening dimensions

[cm]

base openingdimensions

[cm]with skew base

NG 100/100 80 x 80 100 x 100NG 100/150 80 x 130 100 x 150NG 120/120 100 x 100 120 x 120NG 150/150 130 x 130 150 x 150

roof hatchways C, E, and NG type

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 20: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

20

anti-burglary grates4.3.

elements of the leaf position signalling system4.4.

smoke vents and skylights – additional equipment

• accommodated to the entire range of smoke vents and skylights offered by MERCOR,

• protect from unauthorized entry and safeguard against the accidental fall of a person,

• mounted inside smoke vents and skylights,• made of steel sections,• rotational mounting of grate bars protects against sawing,• powder painted in any colour of RAL palette,• mounted in the base opening or directly below the base,• execution options: – galvanised grate, – hinged grate with lock, – accommodated for mounting on the structure below the

skylight or smoke vent.

wind deflectors4.1.

• used for signalling the position of a smoke vent or ventilation hatch leaf in order to present this information on the control switchboard in building automation systems,

• the following elements may be included in the system: – limit switches mounted in a vent / hatch (NO and NC

volt-free contacts), – control switchboard located according to the customer’s

needs,• selection of elements and exact configuration of the system

are done on the basis of the customer’s order,• depending on the customer’s needs, the following states

may be signalled: – leaf closed, – leaf open.

• used for: – increasing the aerodynamic free area of smoke exhaust, – protecting the vent against whipping rain or snow when

using the ventilation function,• made of galvanised steel sheet, aluminium sheet, or

polyester,• option: painted in any colour of RAL palette.

additional directing nozzle4.2.

• used for increasing the aerodynamic free area of smoke exhaust,

• mounted under the vent,• made of galvanised steel sheet, aluminium sheet, or

fibreglass-reinforced polyester,• option: painted in any colour of RAL palette

b +200

a + 200

100

b

a

300

a, b – vent base dimensions

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 21: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 21

mcr prolight

• example application: masking from inside the roof structure below mounting of the vent or skylight (drawing on page 22, ref. 7)

• made according to the customer’s order, of galvanised steel sheet or aluminium sheet,

• option: painted in any colour of RAL palette.

additional roof work4.5.

sunblinds4.6.

• sunblind are used for controlling the amount of light coming through a skylight,

• sunblind are made on special request of the customer for C, E, NG, N, and PR type skylights,

• may be mounted in the base opening or directly below the base,

• sunblind are available for the following dimensions of blanked opening [cm]:

– 40 x 40 – 90 x 120– 40 x 70 – 100 x 100– 50 x 50 – 100 x 130– 60 x 60 – 100 x 160– 60 x 90 – 100 x 200– 70 x 70 – 110 x 110– 70 x 100 – 120 x 120– 75 x 75 – 130 x 130– 75 x 125 – 130 x 160– 75 x 175 – 130 x 200– 80 x 80 – 130 x 230– 80 x 130 – 150 x 150– 90 x 90 – 160 x 200

• additionally, a handle may be ordered for manual shifting of sunblind of the following lengths: 1.50 m; 2.0 m or 3.0 m.

smoke vents and skylights – additional equipment

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 22: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

22

steel base on reinforced concrete slab5.1.

methods of mounting and roof work for smoke vents, skylights and hatchways

finishing with PVC membrane finishing with roofing paper

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with PVC membrane5. thermal insulation of the roof6. reinforced concrete slab

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with roofing paper5. thermal insulation of the roof6. reinforced concrete slab

steel base on steel structure5.2.

finishing with PVC membrane finishing with roofing paper

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with PVC membrane5. thermal insulation of the roof6. trapezoid sheet metal7. additional roof work8. steel supporting structure

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with roofing paper5. thermal insulation of the roof6. trapezoid sheet metal7. additional roof work8. steel supporting structure

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 23: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 23

mcr prolight

steel base on steel structure5.3.

steel base on steel structure5.4.

methods of mounting and roof work for smoke vents, skylights and hatchways

finishing with PVC membrane finishing with roofing paper

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with PVC membrane5. thermal insulation of the roof6. trapezoid sheet metal7. steel supporting structure

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing board or membrane3. thermal insulation of the base4. finishing with roofing paper5. thermal insulation of the roof6. trapezoid sheet metal7. steel supporting structure

finishing with PVC membrane finishing with roofing paper

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with PVC membrane5. thermal insulation of the roof6. trapezoid sheet metal7. steel supporting structure

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with roofing paper5. thermal insulation of the roof6. trapezoid sheet metal7. steel supporting structure

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 24: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

24

steel or polyester skew base on steel structure5.5.

steel base on steel, wooden, or reinforced concrete plinth5.6.

methods of mounting and roof work for smoke vents, skylights and hatchways

steel base polyester base

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with roofing paper or PVC membrane5. thermal insulation of the roof6. trapezoid sheet metal7. steel supporting structure

1. polyester base of the smoke vent2. thermal insulation of the base3. finishing with roofing paper or PVC membrane4. thermal insulation of the roof5. trapezoid sheet metal6. steel supporting structure

1. steel base of the smoke vent or skylight2. thermal insulation of the base3. thermal insulation of the overlay4. drip cap5. finishing with roofing paper or PVC membrane6. thermal insulation of the roof7. reinforced concrete slab

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 25: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 25

mcr prolight

steel base on steel structure5.7.

steel base on steel structuresystem roof of SANDWICH type5.8.

methods of mounting and roof work for smoke vents, skylights and hatchways

gasket

external flashing

insulation

system fastener

system gasketcovering sheet metal

vent base of galvanised steel sheet

supporting structure

supporting structure

insulation

covering sheet metal

system gasketsystem fastener

roof slope

system fastener

supporting structure

insulation

covering sheet metal

system gasket

roof slope

cross-section through the vent base perpendicular to the roofing corrugations

cross-section through the vent base parallel to the roofing corrugations, on the eaves side

cross-section through the vent base parallel to the roofing corrugations , on the roof ridge side

system roof – aluminium finishing on a profiled sheet metal roofro

of s

lope

roof

slo

pe

max

2 m

max

2 m

It is possible to mount smoke vents, skylights and roof hatchways in the zone at the roof ridge, at a max. distance of 2 m.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 26: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

26

suspending a directing nozzle under a vent MCR-Prolight 5.9.

vent execution options5.10.

methods of mounting and roof work for smoke vents, skylights and hatchways

97

∼220 ∼220roof opening dimension

300

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with PVC membrane5. thermal insulation of the roof6. trapezoid sheet metal7. additional masking element 8. steel supporting structure9. directing nozzle

1. steel base of the smoke vent or skylight2. sheet metal strip for mounting of the roofing paper or PVC membrane3. thermal insulation of the base4. finishing with roofing paper5. thermal insulation of the roof6. reinforced concrete slab7. directing nozzle

on steel structurefinishing with PVC membrane

on concrete ceilingfinishing with roofing paper

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 27: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 27

mcr prolight

functions6.0.1.

continuous roo�ights with smoke exhaust and/or ventilation vents

Continuous roo�ights with integrated smoke hatches serve a triple function:• provide smoke and heat exhaust ventilation during �re,• provide lighting of rooms,• permit natural ventilation of the building.

A continuous roo�ight consist of a base and a dome.

The base of continuous roo�ights is made of galvanised steel sheet of thickness 1.25 ÷ 5 mm and standard modular length 1000, 1250, 2500, 3000 mm. Standard base height is 300 mm or 500 mm.The base is equipped with a lower �ange used for mounting the base on a trimmer beam or on the roof structure. Modular bases are connected with each other using bolted joints. The base is mounted to the foundation using self-tapping screws, plain screws,

or expansion bolts, depending on the materials of the supporting structure.In the case of larger clear spans of continuous roo�ights, the bases are sti�ened using braces at every 2500 ÷ 3000 mm, made of cold-formed sections.Mounting and �nishing of the bases of continuous roo�ights is presented on pages 33 – 38.

base of continuous roo�ights6.0.2.

• base height from 100 mm to 700 mm,• skew base,• self-supporting base of modular length up to 6000 mm,• mounting of the continuous roo�ight on an existing

concrete, wooden, or steel plinth, using a steel overlay (page 40),

• painting of bases and bracings in a colour of RAL palette,• anti-burglary grates.

options for the bases of continuous roo�ights 6.0.3.

options6.0.5.

dome of continuous roo�ights6.0. 4.

The dome (vault) of a continuous roo�ight is either mounted on a previously insulated base with waterproof sealing or on an existing plinth using a steel overlay base.The dome of a continuous roo�ight is made of a framework of aluminium sections of special shape that permits water removal.The dome �lling usually consists of milky or transparent cellular polycarbonate. The dome �lling of a continuous roo�ight may be

selected from the table – �lling options (on page 38), selecting proper material suitable for you depending on the requirements in respect of transparency and the value of the heat transfer coe�cient for a given material.

• selection of �lling according to the table on page 40,• painting of aluminium sections in colours of RAL palette.

Continuous roo�ights are designed to be equipped with smoke vents and ventilation hatches. Continuous roo�ights of type MCR-Prolight o�ered by MERCOR satisfy the requirements of the technical approval ITB no. AT-15-5661/2005 con�rmed by the certi�cate of conformity ITB-539/W. Smoke vents for continuous roo�ights are certi�ed according to EN 12101-2.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 28: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

28

arch-shaped continuous rooflights6.1.

shapes6.1.1.

continuous rooflights with smoke exhaust and/or ventilation vents

cross-section

longitudinal section

* Module is selected by the manufacturer depending on the rooflight clear span and the filling used.** Filling page 40.

R – radius of the continuous rooflight (depending on the filling material)S – clear span of the continuous rooflight (min. 0.5 m – max 7 m)L – length of the continuous rooflight (no limitations)f – rise of arch (depending on the radius and clear span)h – height of the base (standard 300 mm and 500 mm)

double-leaf smoke vent

90°

ventilation hatch arch-shaped section filling**

tympanum base edge section

standard module*

2110,1060,710

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 29: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 29

mcr prolight

triangular continuous rooflights 6.2.

continuous rooflights with smoke exhaust and/or ventilation vents

≥90°

≥90°

ventilation hatch filling**aluminium section

standard module*

1060,710

smoke ventbasetympanum

cross-section

longitudinal section

shapes6.2.1.

a – inclination angle of the continuous rooflight walls (standard 30° or 45°)S – clear span of the continuous rooflight (min. 0.5 m – max 7 m)L – length of the continuous rooflight (no limitations)H – height of the continuous rooflight (depending on the inclination angle and clear span)h – height of the base (standard 300 mm and 500 mm)

* Module is selected by the manufacturer depending on the rooflight clear span and the filling used.** Filling page 40.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 30: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

30

pyramid skylights 6.3.

shapes6.3.1.

continuous rooflights with smoke exhaust and/or ventilation vents

* Filling page 40.

≥90°

ventilation hatch base smoke vent

filling*aluminium section

a – inclination angle of the pyramid walls (standard 30° or 45°)S – clear span of the skylight (min. 0.5 m; max 7 m)H – height of the pyramid (depending on the inclination angle and clear span)h – height of the base (standard 300 mm and 500 mm)

top view

cross-section

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 31: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 31

mcr prolight

igloo skylights 6.4.

shapes6.4.1.

continuous rooflights with smoke exhaust and/or ventilation vents

drawing description

top view

* Filling page 40.

filling*arch-shaped section

base

R – radius of the dome (depending on the filling material)D – diameter of the skylight (min. 0.5 m; max 7 m)H – height of the dome (depending on the diameter and radius)h – height of the base (standard 300 mm and 500 mm)

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 32: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

32

smoke vents in continuous rooflights6.5.1.

ventilation hatches in continuous rooflights6.5.2.

smoke vents and ventilation hatches in continuous rooflights

double-leaf overlay type

single-leaf type, full clear span of the continuous rooflight

double-leaf type, full clear span of the continuous rooflight

single-leaf overlay type

single-leaf type, half clear span of the continuous rooflight

single-leaf overlay type

single-leaf type, full clear span of the continuous rooflight

single-leaf type, half clear span of the continuous rooflight

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 33: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 33

mcr prolight

standard dimensions of smoke vents in continuous rooflights6.5.3.

smoke vents and ventilation hatches in continuous rooflights

dimensions of double-leaf vent

aerodynamic free area of smoke vent rated current of electric actuator for snow load class *

without deflectors with deflectors SL250 SL550 SL650[cm] [m2] [m2] [A] [A] [A]

100 x 150 0,90 1,05 2* 0,8 2* 0,8 2* max 1,3100 x 250 1,50 1,75 2* 0,8 2* 0,8 2* max 1,3120 x 120 0,86 1,01 2* 0,8 2* 0,8 2* 0,8120 x 210 1,51 1,76 2* 0,8 2* 1,0 2* max 1,6150 x 150 1,35 1,57 2* max 1,3 2* 1,6 2* 1,6150 x 210 1,89 2,21 2* max 1,6 2* 2,0 2* 2,0150 x 250 2,25 2,63 2* 1,6 2* 2,0 2* 2,6180 x 210 2,27 2,65 2* max 1,3 2* 1,6 2* 2,0200 x 210 2,52 2,94 2* 1,3 2* 1,6 2* 2,6200 x 250 3,00 3,25 2* 1,6 2* 2,0 2* max 4,0220 x 250 3,30 3,58 2* 2,0 2* 2,6 2* max 6,0240 x 250 3,60 3,90 2* max 2,6 2* 4,0 2* 6,0250 x 250 3,75 4,06 2* max 2,6 2* max 6,0 2* 6,0

* rated current depending on rooflight width and height

It is possible to make intermediate dimensions of vents between the values given in the table.The aerodynamic free area for these dimensions is determined using linear interpolati.

dimensions of single-leaf

vent

aerodynamic free area of smoke vent in continuous rooflight of width S: rated current of electric actuator for snow

load class *1,0 m ≤ S ≤ 2,8 m 2,8 m ≤ S ≤ 7,0 m

without deflectors

with deflectors

without deflectors

with deflectors SL250 SL550 SL650

[cm] [m2] [m2] [m2] [m2] [A] [A] [A]100 x 100 0,60 0,73 0,60 0,68 2,0 2,6 4,0100 x 120 0,72 0,88 0,72 0,82 2,0 4,0 4,0100 x 140 0,84 1,02 0,84 0,95 2,6/4,0 4,0/6,0 4,0100 x 160 0,96 1,17 0,96 1,09 2,6/4,0 4,0/6,0100 x 180 1,08 1,31 1,08 1,22 2,6/6,0 8,0100 x 200 1,20 1,46 1,20 1,36 2,6/6,0100 x 220 1,32 1,61 1,32 1,50 4,0/8,0100 x 250 1,50 1,83 1,50 1,70 4,0120 x 120 0,86 1,05 0,86 0,98 2,6 4,0120 x 160 1,15 1,40 1,15 1,31 4,0120 x 180 1,30 1,58 1,30 1,47 4,0120 x 210 1,51 1,84 1,51 1,71120 x 250 1,80 2,19 1,80 2,04150 x 150 1,35 1,64 1,35 1,53 6,0150 x 180 1,62 1,97 1,62 1,84 6,0150 x 210 1,89 2,30 1,89 2,14150 x 250 2,25 2,74 2,25 2,55180 x 180 1,94 2,37 1,94 2,20180 x 210 2,27 2,76 2,27 2,57180 x 250 2,70 3,29 2,70 3,06200 x 200 2,40 2,92 2,40 2,72200 x 210 2,52 3,07 2,52 2,86200 x 250 3,00 3,65 3,00 3,40

* depending on positioning of the vent

It is possible to make intermediate dimensions of vents between the values given in the table.The aerodynamic free area for these dimensions is determined using linear interpolati.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 34: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

34

smoke vents and ventilation hatches in continuous rooflights

control system – pneumatic actuator for smoke exhaust6.5.5.

control system – 24 V= electric actuator for smoke exhaust6.5.6.

control system – 230 V~ electric actuator for ventilation6.5.8.

control system – pneumatic actuator for smoke exhaust + 230 V~ electric actuator for daily ventilation6.5.7.

1. filling of the continuous rooflight2. vent leaf3. base of the continuous rooflight4. supporting structure of the actuator5. smoke exhaust actuator

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 35: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 35

mcr prolight

steel base on reinforced concrete structure7.1.

Presented below are the most frequently used installation methods for bases of continuous rooflights for roofs covered with roofing paper, PVC membrane, corrugated sheet metal, and roofs made of sandwich panels. For the bases where the thermal insulation thickness exceeds 60 mm we recommend bases equipped with an additional steel overlay.

base

hei

ght

base

hei

ght

upright base overlay base

1. steel base of the continuous rooflight2. thermal insulation of the base

3. finishing with roofing paper or membrane4. thermal insulation of the roof

5. reinforced concrete slab6. overlay

1. steel base of the continuous rooflight2. thermal insulation of the base

3. finishing with roofing paper or membrane4. thermal insulation of the roof

5. trapezoid sheet metal 6. steel supporting structure7. overlay

steel base on steel structure7.2.

base

hei

ght

base

hei

ght

methods of mounting for bases of continuous rooflights and roof works

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 36: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

36

1. steel base of the continuous rooflight2. thermal insulation of the base3. finishing with roofing paper or membrane4. thermal insulation of the roof

5. additional masking element6. trapezoid sheet metal 7. steel supporting structure8. overlay

base

hei

ght

base

hei

ght

steel base on steel structure7.3.

1. steel base of the continuous rooflight2. thermal insulation of the base3. finishing with roofing paper or membrane4. thermal insulation of the roof

5. trapezoid sheet metal 6. steel supporting structure7. overlay

base

hei

ght

base

hei

ght

steel base on steel structure7.4.

methods of mounting for bases of continuous rooflights and roof works

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 37: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 37

mcr prolight

steel base on steel structure, system roof – aluminium flashings on a profiled sheet metal roof7.5.

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. steel base of the continuous rooflight2. thermal insulation of the base3. external aluminium flashing4. thermal insulation of the roof

5. system bolt6. system gasket7. covering sheet metal 8. supporting structure

methods of mounting for bases of continuous rooflights and roof works

possible finishing variants of continuous rooflights on roofs covered with sheet metal

possible finishing variants of continuous rooflights on roofs covered with sheet metal

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 38: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

38

1

2

3

4

5

6

7

8

9

steel base on steel structure, system roof – aluminium flashings on a profiled sheet metal roof7.6.

1. steel base of the continuous rooflight2. thermal insulation of the base3. external aluminium flashing4. thermal insulation of the roof5. system bolt6. system gasket7. covering sheet metal 8. supporting structure9. additional masking element

It is possible to mount continuous rooflights in the roof ridge, and also perpendicular to the roof ridge at a max. distance of 2 m from the roof ridge.

roof

slo

pero

of s

lope

max

. 2 m

max

. 2 m

steel base on steel structure – sandwich-type system roof7.7.

1. plinth2. thermal insulation of the plinth3. covering with roofing paper or membrane4. roof insulation5. reinforced concrete slab6. overlay-type base

min

. 300

steel base on concrete, steel, or wooden plinth7.8.

possible finishing variants of continuous rooflights on roofs covered with sheet metal

methods of mounting for bases of continuous rooflights and roof works

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 39: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 39

mcr prolight

�llings of individual standing smoke vents, skylights, and hatchways8.1.

�lling materialsnienia

execution domes and pyramidscolour• milky (opal)• transparent• smoky (brown)• black• others on request

approx. light transmittance [%]7685

• single dome• double dome• triple dome

approx. thermal insulating power [W/m 2K]5,42,9 1,9

approx. acoustic insulating power [dB]202530

other properties of the material • hail resistance • resistance to temperatures between –30°C to +120°C• self-cleaning• impact resistance : impact-proof acrylic glass 4 mm: 12 kJ/m 2 (acc. to ISO 179)

execution domes and pyramidscolour• milky (opal)• transparent

approx. light transmittance [%]4085

• single dome• double dome• triple dome

approx. thermal insulating power [W/m 2K]5,32,9 1,9

approx. acoustic insulating power [dB]202530

other properties of the material • hail resistance• self-cleaning• unbreakable (acc. to ISO 179)

acrylic domes8.1.1

solid polycarbonate domes8.1.2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 40: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr prolight

40

fillings of smoke vents, skylights, and hatchways8.2.

filling materialsnienia

thickness (mm) number of cells colour light transmittance

[%]thermal insulating power

[W/m2K]

10 1 transparentmilky (opal)

77 – 8830 – 66 3,0 – 3,35

10 2 transparentmilky (opal)

73 – 7948 – 59 2,7 – 3,0

10 3 transparentmilky (opal)

68 – 8847 – 66 2,5 – 2,7

16 2 transparentmilky (opal)

70 – 8215 – 64 2,3 – 2,5

16 4 transparentmilky (opal)

55 – 7924 – 61 1,8 – 2,4

16 Z* transparentmilky (opal)

55 – 7924 – 61 1,8 – 2,1

20 4 transparentmilky (opal)

51 – 6928 – 49 1,7 – 2,1

25 5 transparentmilky (opal)

47 – 6918 – 66 1,5 – 1,9

32 Z* transparentmilky (opal)

55 – 7018 – 35 1,4

* – boards of complex cross-sectionsParameters of cellular polycarbonate sheets are specified on the basis of technical information from the sheet manufacturers.

cellular polycarbonate8.2.1

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 41: Teknisk dokumentation ovenlys og brandventilation

pneumatic

introduction9.

control systems

Operation of smoke vents, as well as smoke vents with additional venting function, in spot execution or located in continuous rooflights, requires some activation devices for their opening and closing. These devices, or rather sets of devices, form a control system for smoke and heat exhaust or smoke and heat exhaust combined with daily ventilation. Depending on the type of devices used, a smoke exhaust control system may be executed as:

• pneumatic system,• electrical system,• mechanical system,• pneumatic-electrical system (pneumatic part for smoke exhaust and electrical part controlling the ventilation).

A control system for smoke exhaust and/or ventilation may be used in:• spot vents,• vents in arch-shaped continuous rooflights,• vents in triangular continuous rooflights,• vents in pyramid skylights,• vents in igloo skylights,• smoke exhaust windows.

Smoke exhaust control systems are activated automatically by smoke detectors or by an increase of air temperature, and with a smoke vent they constitute an automatic smoke exhaust device. In accordance with the customer’s needs, apart from automatic activation, a control system may be equipped with devices permitting remote manual activation, as well as releasing from a fire alarm signalling system. In addition, integration with a fire alarm signalling system permits synchronised operation of the smoke exhaust system with the operation of sprinklers, smoke and fire curtains, fire partitions, operation of inlet ventilation, or with a system controlling the operation of aeration openings. A control system for smoke vents and ventilation hatches may be optionally equipped with adequate sensors and a weather monitoring unit, permitting the closing of vents opened beforehand for ventilation, in the case of rain or strong wind.The purpose of using automatic smoke exhaust devices is to remove smoke and fire gases from enclosed spaces (production floors, storage spaces, public facilities, etc.) to the outside of buildings, and to lower the temperature. These devices contribute to the protection of human lives and property by:

• maintaining escape routes with low smoke levels, permitting evacuation,• facilitating the fire-fighting action by easier location of the place of fire,• reducing the risk of destruction of the building structure by lowering the temperature,• reducing the rate at which any fire spreads,• reducing the risk to human lives and limiting the fire damage caused by smoke, hot combustion gases and thermal decomposition

products.

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 41

mcr

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 42: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

42

elements of a pneumatic control system – flow controllers9.1.1.

control system for smoke exhaust and/or daily ventilation – equipment

flow controllers with thermal fuseFlow controller with thermal fuse, called also thermal release valve or thermal tripper, is used for feeding a pneumatic smoke exhaust actuator from its own CO2 cartridge or from a CO2 installation. The release of gas from the CO2 cartridge installed in the thermal valve occurs automatically after exceeding the nominal temperature of the thermal fuse – an alcohol ampoule – its breaking causes the release of the needle and punching the CO2 cartridge protection.

The released gas is directed to the pneumatic smoke exhaust actuator, forcing the vent to lift:

• variations: TAVE, TAVZ – pneumatic diagrams below,• disposable CO2 cartridge with threaded connection 1/2”

UNF,• alcohol ampoules: for nominal temperatures of 68°C, 93°C,

110°C, 141°C,• maximum operating pressure: 8 MPa,• no tools are necessary to strain the needle and exchange the

ampoule.

TAVE• function: local and remote opening of a vent in order to

exhaust smoke (opening only),• thermal release valve accommodated for operation with an

alarm box equipped only with manual emergency opening function,

• may be used for single and triple pipe installations (see: Example executions of pneumatic control system),

• 2 x 1/8” connectors,• integrated initial valve for deaeration of the system or

for connecting other control devices (e.g. alarm box or ventilation box),

• optionally, the possibility of remote releasing by electrical signal (CA-TEA-VVE) or pneumatic signal (CA-TPA-VVE), which permits cooperation with other control systems, e.g. a fire alarm signalling system.

pneumatic diagram of TAVE thermal release valve

INfrom alarm box – open

OUTto vents – open

TAVZ• function: local and remote opening of a vent in order to

exhaust smoke and closing of the vent (opening and the possibility of remote closing),

• thermal release valve accommodated for operation with an alarm box equipped with both manual emergency opening and closing function,

• may be used for double and four-pipe installations (see: Example executions of pneumatic control system),

• 4 x 1/8” connectors,• integrated initial valve for deaeration of the system or

for connecting other control devices (e.g. alarm box or ventilation box),

• optionally, the possibility of remote releasing by electrical signal (CA-TEA-VVZ) or pneumatic signal (CA-TPA-VVZ), which permits cooperation with other control systems, e.g. a fire alarm signalling system.

pneumatic diagram of TAVZ thermal release valve

INfrom alarm box – open

INfrom alarmbox – close.

OUTto vents – open

OUTto vents – close.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 43: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 43

pneumatic control system for smoke exhaust and/or daily ventilation – equipment

Pneumatic actuator is used for opening of vent leafs for ventilation and/or smoke exhaust function:

• double action pneumatic cylinder (opening/closing),• body of anodised aluminium,• piston rod of stainless steel with anti-dust protection,• recommended operating pressure: 0.6…1 MPa,• maximum static operating pressure: 6 MPa,• locking in fully extended position – other executions

optional,• maximum locking force: 6500 N,• manual release of the lock.

elements of a pneumatic control system – alarm boxes9.1.3.

Emergency boxes are devices used for remote emergency opening of vents using the energy of compressed CO2 contained in the cartridge installed in the box. The release of gas occurs after manual operation of the valve using the marked lever – it causes the release of the needle, the punching of the CO2 cartridge, and then the outflow of gas to the system.

• sheet steel box in red colour RAL 3000,• lockable door, with replaceable glass panel,• lever controlling the emergency opening, visible through the

glass panel,• connector terminals on the upper side of the box,• equipped with valves in a configuration depending on the

customer’s needs,• sizes and number of cartridges in the box selected for the

customer’s application, box size depending on the size of installed cartridges,

• connectors for 6 mm pipe, option: for 8 mm pipe,• CO2 cartridge connectors: 1/2” UNF,· maximum operating

pressure in CO2 circuits: 8 MPa,• note: connecting of boxes in series or in parallel is not

possible without additional elements,• designed for one smoke exhaust section, for more sections

on special request.

interior of an example emergency box

box size

box dimensions W x H x D

[mm]

window dimensions

[mm]

glass panel dimensions

[mm]

AK 2 230 x 270 x 125 120 x 110 130 x 120 x 1AK 3 230 x 400 x 125 120 x 110 130 x 120 x 1AK 4 300 x 500 x 125 135 x 120 155 x 140 x 1AK 5 255 x 345 x 115 135 x 120 155 x 140 x 1AK 6 110 x 530 x 100 100 x 190 105 x 195 x 1

dimensions of boxes and spare glasses

elements of a pneumatic control system – pneumatic actuator9.1.2.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 44: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

44

example configurations of alarm boxes9.1.4.

control system for smoke exhaust and/or daily ventilation – equipment

manual and remote emergency opening (HxA)

• release of CO2 for emergency opening of smoke vents is effected by manual operation of the valve lever or remotely by electrical (HEA) or pneumatic (HPA) signal, which permits cooperation with other control systems, e.g. a fire alarm signalling system.

pneumatic diagram of a box with manual and electrical emergency opening

manual emergency opening (HA)

• release of CO2 for emergency opening of smoke vents is effected by manual operation of the valve lever.

pneumatic diagram of a box with manual emergency opening

OUT

OUT

manual emergency opening and closing (HA-HZ)

• release of CO2 for emergency opening of smoke vents, and then their closing, is effected by manual operation of valve levers,

• box equipped with separate cartridges for opening and closing,

• protection against faulty operation: the closing lever is not visible through the glass window,

• after switching from opening to closing function, there is automatic deaeration of the part of installation responsible for opening – it is not necessary to remove the cartridge. Deaeration also occurs after switching from closing to opening.

pneumatic diagram of a box with manual emergency opening and closing

manual and remote emergency opening and closing (HxA-HZ)

• release of CO2 for emergency opening of smoke vents is effected by manual operation of the valve lever or remotely by electrical (HEA) or pneumatic (HPA) signal, which permits cooperation with other control systems, e.g. a fire alarm signalling system,

• release of CO2 for emergency closing of smoke vents is effected by manual operation of valve levers,

• box equipped with separate cartridges for opening and closing,

• protection against faulty operation: the closing lever is not visible through the glass window,

• after switching from opening to closing function, there is automatic deaeration of the part of installation responsible for opening – it is not necessary to remove the cartridge. Deaeration also occurs after switching from closing to opening.

pneumatic diagram of a box with manual and electrical emergency opening and manual emergency closing

OUT closing

OUT opening

OUT closing

OUT opening

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 45: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 45

pneumatic

ventilation boxes9.1.5.

control system for smoke exhaust and/or daily ventilation – equipment

Ventilation boxes are used for remote control of pneumatic actuators opening and closing the vents for ventilation. The boxes contain valves, controlling the opening and closing of vents, and an air preparation system.

• sheet steel box in colour RAL 5012,• lockable door,• controlling of valves using levers inside the box, option:

additional pushbuttons on doors after prior arrangement of technical feasibility,

• optionally possible to cooperate with an alarm box for emergency opening and closing, with a weather monitoring unit for automatic closing of vents in the case of rain or strong wind; optional remote opening and closing controlled electrically or pneumatically,

• contains filter, water separator, pressure reducer (outlet pressure 0…0.1 MPa).

dimensions of ventilation boxes

interior of an example ventilation box

box sizebox dimensions

W x H x D [mm]

notes

LUK 2 230 x 270 x 125 for one ventilation group

LUK 3 230 x 400 x 125 for two ventilation groups

LUK 4 300 x 500 x 125 for three ventilation groups

example configurations9.1.6.

• ventilation (diagram 1) HH 5/2,• ventilation + additional pushbuttons (diagram 2) HH 5/2-TT,• ventilation + electrical closing (diagram 3) HH 5/2-EZ,• ventilation + electrical closing and opening (diagram 4)

HH 5/2-EA-EZ,• ventilation + pneumatic remote closing and opening

HH 5/2-PA-PZ,• ventilation + cooperation with alarm box for emergency

opening HH 5/2-VVZ,• ventilation + electrical closing + cooperation with alarm box

for emergency opening HH 5/2-VVZ-EZ,• ventilation + electrical closing and opening + cooperation

with alarm box for emergency opening HH 5/2-VVZ-EA-EZ,• ventilation + pneumatic remote closing and opening +

cooperation with alarm box for emergency opening (diagram 5) HH 5/2-VVZ-PA-PZ,

• ventilation + electrical closing + cooperation with alarm box for emergency opening and closing HH 5/2-VVAZ-6-EZ,

• ventilation + electrical closing and opening + cooperation with alarm box for emergency opening and closing (diagram 6) HH 5/2-VVAZ-6-EA-EZ,

• ventilation + pneumatic remote closing and opening + cooperation with alarm box for emergency opening and closing (diagram 6) HH 5/2-VVAZ-6-PA-PZ,

• other configurations available on special request.

diagram 1

optionpossibility of selecting the mode of operation during simultaneous application of electrical signal to both electromagnets:

– EAV – opening function is operating,– EZV – closing function is operating.

diagram 4

OUT closing

OUT opening

OUT closing

OUT opening

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 46: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

46

elements of the air preparation system9.1.7.

control system for smoke exhaust and/or daily ventilation – equipment

diagram 2

optionpossibility of selecting the mode of operation during simultaneous pressing of pushbuttons or simultaneous application of control pressure to the valve 5/2:

– PAV – opening function is operating,– PZV – closing function is operating.

diagram 3

diagram 6

diagram 5

notes– switching pressure in the pneumatic opening/closing system

min. 0.3 MPa,– switching pressure in the CO2 emergency opening system

min. 0.4 MPa.

notes– switching pressure in the pneumatic opening/closing system

min. 0.3 MPa,– switching pressure in the CO2 emergency opening system

min. 0.4 MPa,– max. CO2 supply pressure: 6 MPa.

OUT closing

OUTopening

OUT closing

OUTopening

opening closing

INpneumatic opening.

IN pneumatic closing

INCO2

emergencyopening

OUT closing

OUT opening

OUT closing

OUT opening

INCO2

emergency opening

INCO2 emergency closing

The purpose of the air preparation system is to clean and to remove moisture from the air, and to set the pressure supplying further systems at a constant level.

• pressure reducer,• filter,• water separator,• condensation drain screw,• outlet pressure adjusted continuously in the range 0…1 MPa,• max. inlet pressure 1.6 MPa,• 2 x 1/4”connectors,• option: console for mounting.

pneumatic diagram of the air preparation system

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 47: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 47

pneumatic control system for smoke exhaust and/or daily ventilation – equipment

pressure sensor and valves9.1.8.

pressure sensor DS-S-42 with normally open contact• galvanised steel casing,• the contact switches after exceeding the factory setting of

0.5 MPa; option: other switching pressures may be factory-adjusted in the range 0.1…1 MPa,

• switching pressure tolerance: ± 0.05 MPa,• overload capacity up to 30 MPa,• one normally open contact, load capacity 42 V/100 VA,• protection class IP65 – sensor,• cable connector – screw terminals 0.5…1.5 mm2,• thread 1/4”,• casing: hexagon 24,• option: shield for cable terminals with central opening for

a cable of diameter 1.5…5 mm (see the picture).

pressure sensor DS-W-230 with change-over contactPressure sensors are used for monitoring of the pressure level in the pneumatic system.

• galvanised steel casing,• the contact switches after exceeding the factory setting of

0.5 MPa; option: other switching pressures may be factory-adjusted in the range 0.1…1 MPa,

• switching pressure tolerance: ± 0.05 MPa,• overload capacity up to 30 MPa,• one change-over contact, load capacity 230 V~/4 A or

50 V=/2 A,• protection class IP65 – sensor,• cable connector – insert terminals 6.3 x 0.8 mm,• thread 1/4”,• casing: hexagon 27,• option: angle plug – shield for cable connection with gland for

a cable of diameter 1.5…5 mm and screw terminals 0.5…1.5 mm2 (see the picture).

sequence valve with pressurising valve ZSV-BVEControls the division of air or CO2 depending on the pressure of the supplying medium:

• in normal position (supply pressure < 0.6 MPa) the outlet to the smoke exhaust actuator is connected to the atmosphere; when the valve inlet is charged with CO2 of pressure > 1 MPa, the valve switches over, permitting the flow of CO2 to the smoke exhaust actuator; when the pressure is removed, the valve will automatically reset,

• nominal switching pressure: 0.7 MPa,• maximum operating pressure: 6 MPa,• connectors 2 x 1/8”.

pneumatic diagram of the valve ZSV-BVE

OUTINCO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 48: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

48

smoke exhaust function – emergency automatic opening, with flow controller with thermal fuse9.1.9.

control system for smoke exhaust and/or daily ventilation – example configurations

pneumatic diagram pictorial diagram

opening, to smoke exhaust

actuator

list of devices

• thermal release valve TAVE,• pneumatic smoke exhaust actuator.

note

Depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list.

smoke exhaust function – emergency automatic opening and remote closing, with flow controller with thermal fuse and alarm box – and ventilation function with electric actuator

9.1.10.

pneumatic diagram pictorial diagram

list of devices

• thermal release valve TAVZ,• alarm box, e.g. AKx-CA-HA-HZ-SA,• pneumatic smoke exhaust actuator,• E type electric actuator for daily ventilation,• LT ventilation pushbutton.

note

1 depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list,

2 in systems with ventilation function use of an automatic weather control system is recommended.

230 V

opening, to smoke exhaust

actuator

closing, to smoke exhaust actuator

other vents

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 49: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 49

pneumatic

smoke exhaust function – emergency automatic and manual opening, with flow controller with thermal fuse and alarm box

9.1.11.

control system for smoke exhaust and/or daily ventilation – example configurations

list of devices

• thermal release valve TAVE,• alarm box, e.g. AK6-HA-BVE,• pneumatic smoke exhaust actuator.

note

Depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list.

pneumatic diagram pictorial diagram

opening, to smoke exhaust

actuator

other smoke vents

CO2

CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 50: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

50

smoke exhaust function – emergency automatic opening, with flow controller with thermal fuse and alarm box – and ventilation function with pneumatic actuator – 3-pipe system

9.1.12.

pneumatic diagram pictorial diagram

list of devices

• thermal release valve TAVE,• ventilation box,• alarm box, e.g. AK6-HA-BVE,• pneumatic smoke exhaust actuator,• pneumatic actuator for daily ventilation.

note

1. depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list,

2. in systems with ventilation function use of an automatic weather control system is recommended.

other smoke vents

opening to smoke exhaust

actuator

openingto ventilation

actuator

closingto ventilation actuator

control system for smoke exhaust and/or daily ventilation – example configurations

CO2

CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 51: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 51

pneumatic

smoke exhaust function – emergency automatic opening, with flow controller with thermal fuse and alarm box – and ventilation function with pneumatic actuator – 2-pipe system

9.1.13.

control system for smoke exhaust and/or daily ventilation – example configurations

pneumatic diagram pictorial diagram

note

1. depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from these specified on the list,

2. in systems with ventilation function use of an automatic weather control system is recommended.

list of devices

• valve ZSV-BVE,• thermal release valve TAVZ,• ventilation box with option VVZ,• alarm box, e.g. AKx-CA-HA-SA,• pneumatic smoke exhaust actuator,• pneumatic actuator for daily ventilation.

other smoke vents

openingto smoke exhaust

actuator

openingto ventilation

actuator

closingto ventilation actuator

CO2

CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 52: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

52

smoke exhaust function – emergency automatic opening, with flow controller with thermal fuse and alarm box – and ventilation function with electric actuator

9.1.14.

control system for smoke exhaust and/or daily ventilation – example configurations

pneumatic diagram pictorial diagram

note

1. depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list,

2. in systems with ventilation function use of an automatic weather control system is recommended.

list of devices• thermal release valve TAVE,• ventilation box with option VVZ,• alarm box, e.g. AKx-CA-HA-SA,• pneumatic smoke exhaust actuator,• E type electric actuator for daily ventilation,• LT ventilation pushbutton.

230 V

other smoke vents

openingto smoke exhaust

actuator

smoke exhaust function – emergency automatic opening and remote closing, with flow controller with thermal fuse and alarm box

9.1.15.

pneumatic diagram pictorial diagram

list of devices• thermal release valve TAVZ,• alarm box with option HA-HZ, e.g. AKx-CA-HA-HZ-SA,• pneumatic smoke exhaust actuator.

noteDepending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list.

openingto smoke exhaust

actuator

closingto smoke exhaust actuator

other smoke vents

CO2

CO2

CO2

CO2CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 53: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 53

pneumatic

smoke exhaust function – emergency automatic opening and remote closing, with flow controller with thermal fuse and alarm box – and ventilation function with pneumatic actuator – 4-pipe system

9.1.16.

control system for smoke exhaust and/or daily ventilation – example configurations

pneumatic diagram pictorial diagram

list of devices

• thermal release valve TAVZ,• ventilation box,• alarm box, e.g. AKx-CA-HA-SA,• pneumatic smoke exhaust actuator,• pneumatic actuator for daily ventilation.

note

1. depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list,

2. in systems with ventilation function use of an automatic weather control system is recommended.

openingto ventilation

actuator

openingto smoke exhaust

actuator

closingto smoke exhaust actuator

other smoke vents

closingto ventilation actuator

CO2 CO2

CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 54: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

pneumatic

54

smoke exhaust function – emergency automatic opening and remote closing, with flow controler with thermal fuse and alarm box – and ventilation function with pneumatic actuator – 2-pipe system

9.1.17.

control system for smoke exhaust and/or daily ventilation – example configurations

pneumatic diagram pictorial diagram

list of devices

• 2 x valve ZSV-BVE,• thermal release valve TAVZ,• ventilation box with option VVAZ-6,• alarm box, e.g. AKx-CA-HA-SA,• pneumatic smoke exhaust actuator,• pneumatic actuator for daily ventilation.

note

1. depending on the customer’s needs, devices of a smoke and heat exhaust ventilation system may differ from those specified in the list,

2. in systems with ventilation function use of an automatic weather control system is recommended.

openingto ventilation

actuator

openingto smoke exhaust actuator

closingto smoke exhaust actuator

other smoke vents

closingto ventilation

actuator

CO2

CO2 CO2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 55: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 55

pneumatic

description9.1.18.

control system for smoke exhaust with gas springs

A variant of the pneumatic control system for smoke and heat exhaust is a system with smoke vents equipped with gas springs (oleopneumatic actuators). Actuation of smoke vents is effected by the energy of compressed gas in the gas springs. The vent is kept closed by a mechanical catch lock with thermal fuse. When the temperature rises above a certain level, the lock opens and the actuators expand, causing the opening of the vent. With adequate lock design (use of pneumatic micro-actuator), the system may be opened remotely by a pneumatic signal from an alarm box. Such a solution permits integration with central control panel for smoke exhaust and fire alarm signalling systems, when used with adequately configured alarm box. Key features of the system with gas springs:

• lower price compared to other configurations,• this system cannot be used for ventilation,• after operation of the system, the vents are closed from the

roof level.

component elements

• smoke vents MCR PROLIGHT equipped with gas springs and locks with pneumatic micro-actuators,

• alarm box with CO2 cartridge.

method of operation

The system has the following methods of emergency activation:• automatic, controlled by the thermal fuse located inside the

vent,• manual, from the alarm box,• automatic, by a signal from a fire control centre or fire alarm

signalling system (alarm box with option HEA and control centre MCR9705 or MCR0204 is required).

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 56: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

56

description9.2.1.

componentsof electrical control system for smoke exhaust

The smoke exhaust system consists of:• smoke vent MCR PROLIGHT accommodated for mounting of

electric actuator (or actuators),• spindle actuators of type MCR W,• electric control centre of type MCR 9705 or MCR 0204 with

batteries,• optical or thermal smoke detectors,• ROP alarm pushbuttons (manual call points),and additional

equipment: – ventilation pushbutton LT, – wind/rain sensor with weather monitoring unit.

method of operation of electrical control system for smoke exhaust

The system has the following methods of emergency releasing:• automatic, controlled by a smoke or thermal detector,• automatic, by a signal from a fire control centre ,• manual, using smoke exhaust pushbuttons.

The system permits the lifting of smoke vents for ventilation using a ventilation pushbutton.

diagram of typical electrical system for smoke and heat exhaust ventilation system in staircase9.2.2.

OCDoptical smoke detector

smoke vent MCR PROLIGHT with electric actuator

wind and rain sensor

WRSweather monitoring unit

LTventilation pushbutton

GROUNDFLOOR

ROP (RPO-1)alarm smoke

exhaust pushbutton

EMERGENCY EXIT

YnTKSY 1x2x0,8

(YnTKSY 4x2x0,5) YDY 3x1,5

HLGs 2x1,5

230 V~

YnTKSY 1x2x0,8

YDY 3x1,5

YnTKSY 1x2x0,8

LAST STOREY

230 V~

ROP (RPO-1)alarm smoke

exhaust pushbutton

MCR 0204 orMCR 9705 v 2control centre of smoke and heat exhaust system

noteWire symbols are examples – select for the actual system configuration.

control system for smoke exhaust and/or daily ventilation

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 57: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 57

electrical

The control centre for smoke and heat exhaust MCR 9705 is used for actuation of devices of electrical smoke exhaust system of MERCOR on the basis of alarm signals from thermal or optical smoke detectors, manual smoke exhaust pushbuttons (RPO), or from another control centre (e.g. from a fire alarm signalling system, from a building automation system).The control centre is supplied with AC voltage 230 V~ and it supplies voltage 24 V= to the devices of the electrical smoke exhaust system. The controller is equipped with rechargeable batteries, therefore it is insensitive to supply voltage decay and it can operate for 72 hours after voltage failure. After that time a single actuation of the devices (e.g. opening of smoke vents) is possible.The control centre has the following features:

• remote actuation of the smoke exhaust system devices by a signal from a fire signalling control unit (NC volt-free contact or 24 V= signal),

• manual release by alarm pushbuttons,• automatic release by conventional (thermal or optical) smoke

sensors,• indication of the control centre status by LEDs on the front

panel and buzzer,• integration with manual smoke exhaust pushbutton RPO-1

and alarm pushbutton ROP,• transmitting information about emergency relese of the control

centre (NC/NO contact and LED on pushbutton RPO-1),• transmitting information about voltage failure and defects

(NC/NO contact and LED on pushbutton RPO-1),• transmitting information about opening of smoke vents

(NC/NO contact),• monitoring of the stand-by status of all connected devices

of the smoke exhaust system and presentation of possible defects on a panel inside the control centre,

• manual opening of smoke vents for ventilation of the building during normal use (without activating the alarm status, separately for each group),

• automatic closing of vents lifted for ventilation in the case of rain or strong wind, by a signal from a weather monitoring unit (has no effect on the emergency operation).

Maximum number of electric actuators powered from the control centre depends on the actuator type (current consumption) and the size of central unit used – load capacity of current outputs, depending on the type, is from 1*5 A to 8*5 A. Maximum number of smoke detectors on 1 monitoring line, depending on the detector type, is from 8 to 10. Maximum number of alarm pushbuttons on 1 monitoring line is 10 for pushbuttons ROP without LEDs and 4 for pushbuttons RPO-1.The control centre MCR 9705 v 2 differs from the previous model in that it can be integrated with the pushbutton RPO-1 (it permits remote presentation of the control centre status and remote reset of the alarm), and the reduced number of lines (2) in the actuators circuit.Detailed information about the control centre for smoke exhaust MCR 9705 v 2 is contained in the technical and operational documentation delivered with the unit.

9.2.3. control centre for smoke and heat exhaust MCR 9705 v 2

type MCR 9705-5A MCR 9705-10A MCR 9705-15A MCR 9705-20A

supply voltage 230 V~, 50 Hz 230 V~, 50 Hz 230 V~, 50 Hz 230 V~, 50 Hzmax. power consumption from power network 150 VA 300 VA 450 VA 600 VAbackup power supply voltage 24 V=, 3 Ah 24 V=, 6 Ah 24 V=, 9 Ah 24 V=, 12 Ahbattery charging voltage 27,6 V+/-0,2 V 27,6 V+/-0,2 V 27,6 V+/-0,2 V 27,6 V+/-0,2 Vnumber of lines and groups max. 1 max. 2 max. 3 max. 4load capacity of current output 5 A, 24 V= 10 A, 24 V= 15 A, 24 V= 20 A, 24 V=protection class IP 54 IP 54 IP 54 IP 54casing dimensions [cm] 30 x 30 x 15 40 x 40 x 20 60 x 60 x 20 60 x 60 x 20

type MCR 9705-25A MCR 9705-30A MCR 9705-35A MCR 9705-40A

supply voltage 230 V~, 50 Hz 230 V~, 50 Hz 230 V~, 50 Hz 230 V~, 50 Hzmax. power consumption from power network 750 VA 900 VA 1050 VA 1200 VAbackup power supply voltage 24 V=, 15 Ah 24 V=, 18 Ah 24 V=, 21 Ah 24 V=, 24 Ahbattery charging voltage 27,6 V+/-0,2 V 27,6 V+/-0,2 V 27,6 V+/-0,2 V 27,6 V+/-0,2 Vnumber of lines and groups max. 5 max. 6 max. 7 max. 8load capacity of current output 25 A, 24 V= 30 A, 24 V= 35 A, 24 V= 40 A, 24 V=protection class IP 54 IP 54 IP 54 IP 54casing dimensions [cm] 80 x 60 x 30 80 x 60 x 30 100 x 60 x 40 100 x 60 x 40

9.2.4. technical data

control system for smoke exhaust and/or daily ventilation – control centre MCR 9705 v 2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 58: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

58

typical configuration of smoke and heat exhaust ventilation system with control centre MCR 9705-5A and weather monitoring unit9.2.5.

LT – ventilation pushbuttonRPO – manual smoke exhaust pushbuttonM – electric actuatorOCD – optical smoke detector

FS 1 – protection of batteryFS 2 – protection of 230 V~ power networkFS 3 – protection of actuators

SW 1-1 – off: normal operation on: disconnection of actuator lineSW 1-2 – off: normal operation

on: disconnection of detector lineSW 1-3 – off: normal operation on: disconnection of ROP lineSW 1-4 – off: normal operation on: disconnection of input/output lineSW 1-5 – off: actuator operates only while the “up” ventilation pushbutton is pressed on: actuator will open fully after the “up” ventilation pushbutton is pressed onceSW 1-6 – off: smoke and heat exhaust mode operation on: door automation mode operation

windsensor

rainsensor ra

in s

enso

r te

rmin

al s

trip

123456

wea

ther

mon

itorin

g un

it te

rmin

al s

triproof WRS 1b

230~LN2019

987

FIRE SIGNALLING CONTROL CENTRE

NC

10k 10k

RPO

-1

OCD

L1 close

L1 openL2

4 14 12 6 2 8 10

3 13 11 5 1 7 9

10k

RPO

-1

OCD

L1 close

L1 openL2

4 14 12 6 2 8 10

3 13 11 5 1 7 9

ME

ME

PMPM

LT

P 17 P 16 P 15 P 14 P 13 P 12 P 11 P 10 P 9 FS 3 P 8 P 7 P 6

P 3

P 2

FS1

SW 4SW 3SW 2

1 2 3

SW 1

control centrestatus

signalling on RPO-1

vent open

defect alarm alarm - +power supply

+ -detectors

R URPO

+ -RPO

6,3 A - + wind/rain

G D push-button

T

OUTPUTS INPUTIE LINES ACTUATORS VENTILATION

SYSTEM CHECK

RESET VENT CLOSING

P 5 P 4

1 +-

BATTERY 24 V/3 AhBATTERY 26.3 A

BATTERY ubat

FS 2

6

123456

control system for smoke exhaust and/or daily ventilation – control centre MCR 9705 v 2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 59: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 59

electrical

The control centre for smoke and heat exhaust MCR 0204 is a control device in electrical smoke exhaust systems. The control centre MCR 0204 is used for actuation of devices of electrical smoke exhaust system of MERCOR on the basis of alarm signals from thermal or optical smoke detectors, or from manual smoke exhaust pushbuttons (RPO). The central unit is supplied with AC voltage 230 V~, and the operating voltage on outputs is 24 V=. The control centre is equipped with rechargeable batteries permitting the system to operate for 72 hours after a mains voltage failure – after that time a single emergency opening of smoke vents or smoke exhaust windows is possible.The control centre has the following features:

• manual alarm release by alarm pushbuttons,• automatic alarm release by smoke sensors,• transmitting information about alarm (signal on NO/NC

contact),• transmitting information about defects of the control centre

(signal on NO/NC contact),• connectable with manual call point RPO-1 and ROP,• remote alarm reset and vent closing,• monitoring of the stand-by status of all connected devices

of the smoke exhaust system and presentation of possible defects on a panel inside the control centre,

• manual opening of smoke exhaust windows or smoke vents for ventilation of the building during normal use without activating the alarm status,

• automatic closing of smoke exhaust windows or smoke vents opened for ventilation, in the case of rain or strong wind (when a weather monitoring unit with a wind-rain sensor is installed).

The control center MCR 0204 features visual signalling of its operational status on the front panel, repeated on emergency pushbuttons RPO-1, which permits easy identification of the alarm or system defect.

control centre for smoke and heat exhaust MCR 02049.2.6.

parameter value

supply voltage – basic 230 V~ , 50 Hzmax. power consumption from mains 10 VAoutput voltage (power supply for actuators) 24 V=, max. 4 A

backup power supply 2 batteries HP2-12 (12 V, 2 Ah),connected in series

battery charging voltage 27,5 V ±0,2 V @20°Coperating temperature range(climatic class II acc. to WBO/19.1/BA/2001) –25° C do +50° C

maximum number of detectors of types:– POLON-ALFA – TUP-37, DOR-35 and TNP-37 in sockets G31 and G37– ARITECH – DP 862 and DT 864 in socket DB 860

10 items8 items

maximum number of pushbuttons of type:– MERCOR – RPO-1– ROP

4 items10 items

maximum number of actuators of type:– MCR L– MCR W 105– MCR W 205– MCR W 101– MCR W 081

2 items4 items2 items4 items5 items

maximum diameter of wires entering the unit 1,5 mm2

time of operation in STAND-BY state without network voltage min. 72 hload capacity of relay outputs max. 100 mA, 24 Vcasing protection class IP 54insulation class IIdimensions (H x W x D) 255 x 180 x 100 mm

technical data9.2.7.

control system for smoke exhaust and/or daily ventilation – control centre MCR 0204

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 60: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

60

typical configuration of smoke and heat exhaust ventilation system with control centre MCR 0204 and pushbutton ROP9.2.8.

typical configuration of smoke and heat exhaust system with central controller MCR 0204 and pushbutton RPO-19.2.9.

FIRE SIGNALLING

CONTROL CENTRE

NO

10k

P9 P8 P7 P6 P5 P4 P3 P2

P1

10k 10k 10k

1a 2a

1 2

2a1a

1 2

ROP

ROP

OCD

OCD

L1 close

L1 openL2

L1 close

L1 openL2

CPWRS 1b

ME

MEPE

PE

LT

230 V50 Hz

ALARM DEFECTS

+24

V

GND

RESE

T ROP LINE +

DETEC-TOR LINE- +

WIND/RAIND -

VENTILA-TION

D G -

ACTUATOR - +

7 9

ALARM DEFECTS

+24

V

GND ROP

LINE- +

DETEC-TORLINE- +

WIND/RAIND -

VENTILA-TION

D G -

ACTUATOR - +

RESE

T

P9 P8 P7 P6 P5 P4 P3 P2

P1P14

230 V50 Hz

10kCP

WRS 1bME

MEPE

PE

LT

7 9

10k 10k

RPO-1

RPO-1

OCD

OCD

L1 close

L1 openL2

L1 close

L1 openL2

FIRE SIGNALLING

CONTROL CENTRE 4 6 14 12 2 8 10

4 6 14 12 2 8 10

3 5 13 11 1 7 9

3 5 13 11 1 7 9

RPO/LED

OCD – optical smoke detectorRPO – alarm smoke exhaust pushbuttonPM – junction boxME – electric actuatorCP – weather monitoring unitLT – ventilation pushbutton

control system for smoke exhaust and/or daily ventilation – control centre MCR 0204

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 61: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 61

electrical

technical data 9.2.10.

typical configuration of extension module MCR R0424-1 (1 x 24 A)9.2.11.

The extension module MCR-R 04xx is used for supplying power to 1 group of actuators 24 V= of total current consumption up to 48 A or 24 A, depending on execution. The module is controlled by a voltage signal 24 V= that may come from the control centre MCR 9705 or MCR 0204 (actuator line output). The device, in combination with a MCR central unit, ensures detection of defects of all connected actuator lines. The module is supplied with mains voltage 230 V~. The energy required for operation of actuators comes from a battery (24 V, 9 Ah), therefore the maximum time of continuous operation at the nominal load depends on module size e.g. for a consumption of 24 A it is 20 minutes.The battery charging time after complete discharge is approx. 10 hours.

The module MCR-R 04xx is equipped with signalling of the following states:

• power supply 230 V~ correct green LED on• power supply 24 V= correct yellow LED on,• operation of actuators yellow LED on,• defect signal transmitted to the

control centre in the case of defect of the actuator line or decay of power supply 24 V=.

types• MCR-R 0424-2 2 output lines 12 A each,• MCR-R 0424-1 or MCR-R 0424K 1 output line 24 A,• MCR-R 0448-4 4 output lines 12 A each,• MCR-R 0448-2 2 output lines 24 A each,• MCR-R 0448-1 or MCR-R 0448K 1 output line 48 A.Typical variations are presented, “K” suffix = execution for curtains.

parameter value

type: MCR-R 0424 MCR-R 0448supply voltage – basic 230 V~, 50 Hzmax. power consumption from power network 48 V A 96 V Aoutput voltage 24 V=max. current consumption by actuators 24 A 48 Aoperating temperature range -25°C .. 50°Cdimensions (H x W x D) 300 x 400 x 150 mmprotection class IP 54entry of wires at the top or at the rear

TERMINAL P2MCR 0204

TERMINAL P8MCR 9705

M

M

M

M MO

TORS

UP

TO 2

4 A

LPEN

SUPPLY NETWORK 230 V~

F1F2

+ - + -

B1

US

ZSK1 K2

B2

INPUT FROM MCR CONTROL CENTRE

MCR

230 V~ SUPPLY INPUT

MODULE OUTPUT

control system for smoke exhaust and/or daily ventilation – extension module MCR-R 04xx

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 62: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

62

control system for smoke exhaust and/or daily ventilation – actuators

actuators MCR9.2.12.

Actuators MCR are used for opening of smoke vents and smoke exhaust windows, as well as for daily ventilation. They are powered with 24 VDC voltage. Actuator casing is made of anodised aluminium. As standard, they are equipped with interference suppression capacitor, overload breaker, and limit switches. Optionally they may be equipped with a volt-free contact informing about the state of the actuator (option E). Protection class IP 54 for actuators MCR W…, IP 33 for MCR L, IP 20 for MCR L K…, operating mode (acc. to DIN EN 0530) S2. MCR W 081 - 550 - E

type stroke (mm) option

ordering example

actuator type rated current max. load nominal load speedat nominal load standard strokes

[A] [N] [N] [mm/s] [mm]MCR W 081 (08A) 0,8 900 900 3,4 350,550,750MCR W 101 (10A) 1,0 1200 900 3,4 350,550,750MCR W 105 (10B) 1,0 850 650 6,1 350,550,750

MCR W 13B 1,3 1150 650 6,1 350,550,750MCR W 13C 1,3 830 450 8,4 350,550,750MCR W 13G 1,3 870 490 8,1 350,550,750MCR W 16B 1,6 1240 860 7 350,550,750MCR W 16G 1,6 940 650 9,3 350,550,750MCR W 20B 1,6 1630 860 7 350,550,750MCR W 20G 2,0 1240 650 9,3 350,550,750

MCR W 201 (20H) 2,0 870 460 13,3 350,550,750MCR W 26G 2,6 1670 650 9,3 350,550,750MCR W 26H 2,6 1180 460 13,3 350,550,750MCR W 40G 4,0 2500 2110 9,7 350,550,750MCR W 40H 4,0 1600 1350 13,9 350,550,750MCR W 40N 4,0 1890 1590 10,4 350,550,750MCR W 60J 6,0 2160 1120 17,9 350,550,750MCR W 60P 6,0 2560 1320 13,4 350,550,750MCR W 80V 8,0 2400 900 19,1 350,550,750

spindle actuators

actuator type rated current pulling/pushingforce speed at nominal load standard strokes

[A] [N] [mm/s] [mm]MCR L 1,7 150/300 40 250, 370

MCR L K05C 0,5 150/150 6,7 250MCR L KT10C 1,0 2x(150/150) 6,7 250MCR L KR10B 1,0 300/300 7,6 400,500

MCR L KRT20B 2,0 2x(300/300) 7,6 400,500

chain actuators

ventilation actuators 9.2.13.

Ventilation actuators are used for smoke vents with pneumatic control and for ventilation hatches of spot type and in continuous skylights. They may be controlled by a ventilation pushbutton LT and/or a weather monitoring unit MCRP 054 or WRS-1b. They

are powered with 230 VAC voltage. The actuators are equipped with an electronic or mechanical overload breaker and a volt-free contact signalling the open state (NO). Protection class of actuators is IP 54.

actuator type pushing force pulling force powerconsumption stroke casing

materialoperating mode

(acc. to DIN VDE 0530)[N] [N] [W] [mm]

E-300-230 500 500 23 300 plastic S3 25%E-500-230 500 500 23 500 plastic S3 25%E-750-230 500 500 23 750 plastic S3 25%

JMBB-500-300-LA 500 150 140 300 plastic S2JMB-500-300-LS 500 350 200 300 aluminium S2JMB-500-500-LS 500 350 200 500 aluminium S2JMB-500-300-L 500 350 200 500 aluminium S2JMB-500-500-L 500 350 200 500 aluminium S2

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 63: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 63

electrical control system for smoke exhaust and/or daily ventilation – actuators

spindle actuator MCR W 081, 101, 105 ventilation actuator E 300, 500, 750

60+

stro

ke

55

25

74

23,5

8

73

47 58

134

70+

stro

ke

17

8054

8518

0

L

brow

n

whi

te

whi

tebl

ue

blac

k

N

M~

spindle actuator MCR 205

chain actuator MCR L

60+

stro

ke

55

14

70

23,5

8

73

47 58

160

86

5026

9

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 64: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

64

actuator JMBB-500-300-LS i L connection diagram for actuator JMBB-500-300-LS

control system for smoke exhaust and/or daily ventilation – actuators

Ø 6,1

Ø 8,1

Ø 8,1

Ø 54

Ø 54

Ø 70

Ø 28

SW 8

22437

mm

(str

oke

300

mm

)

196

52+

22

(max.250 V/4 A)M1~

L NPE

brow

ngr

een

/yel

low

blac

kbl

ue

whi

te

oran

ge

connection diagram for actuator JMBB-500-300-L

M1~

brow

n

gree

n/y

ello

w

blac

k

blue

whi

te

oran

ge

L N PE

actuator JMBB-500-300-LA

Ø 54Ø 6,1

Ø 8

,1Ø

7,1

Ø 54

SW 17

8

49+

1518

3

359

70

15

connection diagram for actuator JMBB-500-300-LA

M1~

(max.250 V/4 A)

brow

n

blac

k 1

blac

k 2

blac

k 3

blue

L N

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 65: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 65

electrical control system for smoke exhaust and/or daily ventilation – actuators

chain actuator MCR L K0 5C chain actuator MCR L KR 10B

chain actuator MCR L KRT 20B chain actuator MCR L KT 10C

35 73,513 47

312,

511

00

1725

2727

20

7,5

35 73,5

13

3880

0

871

2727

20

7,5

47

35 73,513

319

3820

7,5

47

Ø 5,1

35 74

194+

stro

ke

2720

7,5

47

63,5

+st

roke

/2

Ø 5,1

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 66: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

66

control system for smoke exhaust and/or daily ventilation – detectors

optical detectors9.2.14.

technical data

Optical smoke detectors are used for detection of visible smoke that accompanies the outbreak of most fires. They permit the detection of fire in its early stages, while the material is still smouldering, which usually occurs long before the outbreak of open flame and noticeable increase of temperature. Detectors are characterised by resistance to wind, pressure variations, and steam condensation. They are highly sensitive to visible smoke.An optical detector consists of a set of two diodes. The first diode – an infrared LED – transmits a light beam. The second one, a receiver, is located in a labyrinth tunnel. In normal conditions, visible light from the outside or from the transmitter diode never reaches the receiver diode. When smoke penetrates the detector, the receiver diode starts to receive the light emitted by the transmitter diode and dispersed by the particles of smoke. This activates the detector and starts the alarm state.Detectors are equipped with visual indicators of operation (alarm) in the form of a LED, which facilitates finding an activated detector. In addition, if detectors are located in invisible places, they may be equipped with external operation indicators.Detectors are mounted in adequate sockets.Detectors are approved for use in fire protection systems.

detector DOR-40

detector DP 652

type DP 652 DOR - 40

operating voltage [V=] 9 ... 33 12 ... 28max. monitoring current [mA] 45 60alarm current [mA] 52 mA at 24 V 20operating temperature range [°C] -20 ... +60 -25 ... +55max. relative humidity [%] 93 95dimensions of detector with socket [mm] Ø100 x 50 Ø115 x 54weight with socket [kg] 0,15 0,2socket type DB 860 G - 40colour white white

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 67: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 67

electrical control system for smoke exhaust and/or daily ventilation – detectors

heat detectors9.2.15.

Heat detectors are used for the detection of fire hazards in rooms where a quick increase of temperature may be expected in the first stage of fire development, or in places where optical smoke detectors cannot be used.There are 2 basic types of heat detectors: fixed temperature type and differential type.Fixed temperature detectors react to the exceeding of a fixed threshold temperature. Temperature measurement is performed by an electronic thermo-sensitive element.Differential detectors are equipped with 2 thermo-sensitive elements (thermistors) – one of them is a reference thermistor and the other is located in a protruding part of the detector. In normal conditions the temperature of both thermistors is similar, and in the case of a quick increase of temperature the second thermistor heats up much faster than the reference one. This disturbs the system balance and activates the alarm state of the detector.Detectors are equipped with visual indicators of operation (alarm) in the form of a LED, which facilitates finding an activated detector. In addition, if detectors are located in invisible places, they may be equipped with external operation indicators.Detectors are mounted in adequate sockets.Detectors are approved for use in fire protection systems.

detector DT 654

detector TUP-40

technical data

DT 654 TUP - 40operating voltage [V=] 9 ... 33 15 ... 28max. monitoring current [mA] 45 38alarm current [mA] 52 20operating temperature range [°C] 60 54 ... 65temperature range [°C] -20 ... +90 -25 ... +50max. relative humidity [%] 95 95dimensions of detector with socket [mm] Ø100 x 50 Ø115 x 54weight with socket [kg] 0,15 <0,3detector type static and differential static and differentialtriggering class acc. to PN-EN-5 A1R A1Rsocket type DB 860 G - 40colour white white

Detector sockets are executed so as to permit quick and easy mounting of a detector without using excessive force. A detector may be mounted in the base in only one position. Bases do not contain any electronic parts that could be damaged during mounting.

DB 860 G - 40

dimensions [mm] Ø100 x 16 Ø107 x 28,5weight [kg] 0,05 <0,1colour white white

G-40 DB 860

sockets9.2.16.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 68: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

68

control system for smoke exhaust and/or daily ventilation – pushbuttons RPO-1, ROP, LT

manual smoke exhaust pushbutton RPO-19.2.17.

Manual smoke exhaust pushbutton (call point) MCR RPO-1 is used in smoke and heat exhaust systems for manual releasing of alarm and for signalling of the operational status of the smoke exhaust control centre. In addition, the pushbutton permits the remote reset of alarm.The pushbutton has three signalling LEDs:

• red – ALARM,• yellow – DEFECT,• green – OK.

LED leads are directly and independently connected to the terminal strip, which permits universal application of the pushbutton MCR RPO-1.The pushbutton can be integrated with smoke exhaust control centres MCR 0204 and MCR 9705 v 2 – connection diagrams – see descriptions of the control units. The pushbutton is designed for use in interiors.

parameter valuepushbutton type RPO-1emergency pushbutton parameters 24 V DC, max 100 mAoperating temperature range -10°C.. +55°Ccable type for connection to control centre YnTKSY 4x2x0,5casing protection class IP 30dimensions (H x W x D) 135 x 135 x 33 mmcasing colour orange

description of terminal strip RPO-1

1, 2 – RESET line wire 13, 4 – RESET line wire 25 – ALARM LED cathode6 – ALARM LED anode7, 8 – RPO line wire 1

9, 10 – RPO line wire 211 – DEFECT LED cathode12 – DEFECT LED anode13 – OK LED cathode14 – OK LED anode

1 2 3 4 5 6 7 8 9 10 11 12 13 14

manual fire alarm pushbutton ROP9.2.18.

Alarm pushbutton (call point) ROP has a microswitch with a contact that closes after the glass is broken. Signal from the pushbutton ROP is transmitted to the central smoke exhaust control centre MCR 9705 or MCR 0204.Standard equipment includes a key that permits very easy simulation of the alarm state.Casing colour: blue.Dimensions: 87 x 87 x 50 mm.

ventilation pushbutton LT9.2.19.

It is used for actuation (opening and closing) of vents or windows for ventilation during normal use.Casing colour: white.Dimensions: 80 x 80 x 55 mm.

electrical diagram

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 69: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 69

electrical control system for smoke exhaust and/or daily ventilation – weather monitoring units

The weather monitoring unit MCRP 054 is used for controlling the operation of actuators at ventilation windows or vents which should be closed in the case of rain or wind. The device may be connected to smoke exhaust control centres, ventilation control devices, or drives powered with 230 V~ voltage. The closing signal is transmitted on the basis of measurements from the wind sensor WM1 and the rain sensor RS1

• the device contains 4 change-over contacts which are activated in the case of rain/wind or during a mains voltage decay. The contact remains active for a configured time from the end of rain/wind.

• the value of rain intensity that triggers the alarm is adjustable by the user (weak rain – strong rain).· the value of wind power that releases the alarm is adjustable by the user in the range from weak breeze (approx. 5 m/s) to gusty wind (approx. 15 m/s).

• additional input for signalling of vent leaf position (contact closed while a vent is opened) permits the visual indication of the vent state.

• the device is equipped with signalling of the following states: – supply 230 V~ – green LED, – “wind” alarm – red LED, – “rain” alarm – red LED, – “vent open” signalling – yellow LED. – wind speed indicator – LED board: 7 yellow LEDs and

one red LED (for wind speed above 15 m/s).• surface-mount plastic casing, dimensions H x W x D:

180 x 180 x 75 mm; IP 54, light grey colour (~RAL 7035), entry of wires at the top or at the rear of the casing.

weather monitoring unit MCRP 0549.2.20.

weather monitoring unit WRS 1b9.2.21.

optionsOption ZK-1: one additional relay contact for connection in total of two smoke exhaust control centres or two ventilation groups 230 V~.Option ZK-2: two additional relay contacts.Option ZK-3: three additional relay contacts.Option SG: casing as above but with transparent door opening to the left, protection class IP 54.

The weather monitoring unit can be connecter with a smoke exhaust control centre (e.g. MCR 9705 or MCR 0204) or actuators 230 V~. The weather monitoring unit operates with the wind sensor WM 1 and/or the rain sensor RS 1:

• during a mains failure the weather monitoring station automatically activates the “CLOSING” function or prevents ventilation,

• output: relay contact that activates in the case of sensor response or mains failure. The contact remains active for at least 2 minutes, or as long as the sensor operates.

• response threshold of the rain sensor is adjustable (from drizzle to strong rain/rainstorm).

• response threshold of the wind sensor is adjustable – from weak breeze to strong wind (approx. 5 m/s - 15 m/s or approx. 20 km/h – 60 km/h).

• visual displays/indicators: – stand-by (green), – wind (yellow), – rain (yellow),• possibility of programming the following options: – contact responds both to active wind sensor and rain

sensor, – contact responds only to active wind sensor, – contact responds only to active rain sensor,• contactor (relay) of standard contact load capacity 24 V=/8

A, 230 V~/5 A,• surface-mount plastic casing, protection class IP 44

according to DIN EN 60 529, light grey colour RAL 7035,• dimensions: 165 x 155 x 95 [mm] (W x H x D).

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 70: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

70

control system for smoke exhaust and/or daily ventilation – weather monitoring units

combination of sensors WM1-RS19.2.22.

Rain sensor RS1:• heated rain sensor (heating is activated when the sensor

responds and deactivated after drying),• gold-coated sensor surface, approx. 80 cm2, • sold together with the wind sensor on a mounting console,• option: available separately.

Wind sensor WM1:• sensor for wind speed measurement,• sold together with the rain sensor on a mounting console,• option: heating for the wind sensor, with a temperature

sensor with operating temperature < 5°C (the option must be specified at ordering the sensor and the weather monitoring unit WRS1b, requires additional 2 lines from the station WRS1b, e.g. cable YTKSY 3x2x0.8),

• option: available separately.Example connection cable for the sensor set WM1-RS1 to WRS1b: YTKSY2x2x0.8.

extension module KEControl contactor for extension of the weather monitoring unit MCRP 054 and WRS 1 to more than 4 independent control groups that are closed simultaneously during rain and wind.

• control voltage 230 V~, volt-free contact 5 A/30 V or 5 A/230 V~,

• plastic casing, grey RAL 7032,• dimensions: 254 x 180 x 111 [mm] (W x H x D).

additional equipmentOption KE-4: control contactor with four contacts used for expansion of the weather monitoring unit WRS 1 by three independent groups.Option KE-8: control contactor with eight contacts used for expansion of the weather monitoring unit WRS 1 by seven independent groups.Option KE-12: control contactor with twelve contacts used for expansion of the weather monitoring unit WRS 1 by eleven independent groups.Option SU: programmable timer embedded in the extended KE contact for programming the automatic switching of the contact (e.g. automatic closing).

connection diagram for weather monitoring unit WRS1 and sensors WM1-RS1

connection diagram for weather monitoring unit MCRP 054 and sensors WM1-RS1

outp

u W

RS1b

addi

tiona

l out

put f

rom

op

tion

ZK1

addi

tiona

l out

put f

rom

op

tion

ZK2

addi

tiona

l out

put f

rom

op

tion

ZK3

outp

ut 2

30 V

~, m

ax 5

A

supp

ly23

0 V~

, 50/

60 H

Z

sensorWM1–RS1

YTKS

Y2x2

x0,8

(YTK

SY3x

2x0,

8)

WM

1 he

ating

(opt

ion)

WM

1 he

atin

g (o

ptio

n)

WRS1b

1 2 3 4 5 6 7 8 9 10 11 12 13 15 16 17 18 19

21 3 4 5 6

NO NC C NO NC C NO C NO NNC C

N20 L1

NL1 L1

13

NC

RS1

heat

ing

grou

nd

WM

1

RS1

supp

ly 2

30V

50Hz

outp

ut 2

30V

5A m

ax.

vent

ope

ning

sen

sor

WM1

RS1

MCR

970

5/02

04

win

d/ra

in

rem

ote

oper

atio

n m

odul

e (o

ptio

n)

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 71: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 71

electrical control system for smoke exhaust and/or daily ventilation – weather monitoring units

Smoke vents with pneumatic control and hinged spot skylights, as well as vents in continuous rooflights, may be equipped with electric actuators 230 V~ for ventilation. Using these actuators, daily ventilation of the building is possible without the necessity of activating the emergency opening of smoke vents.

components of electrical ventilation systemThe ventilation system consists of:

• ventilation actuators,• ventilation pushbutton LT, and additional equipment:• weather monitoring unit with wind/rain sensor (described on

page 67).

method of operation of electrical ventilation systemThe ventilation pushbutton is used for opening and closing of vents/windows during daily use. In addition, it is recommended that the system be equipped with a weather monitoring unit with wind/rain sensor, causing automatic closing of vents opened for ventilation during unfavourable weather conditions (rain or wind).

notein ventilation hatches and windows operated with actuators use of weather monitoring system is recommended.

ventilation control – system without weather monitoring unit9.2.23.

ventilation control – system with weather monitoring station9.2.24.

WIND SENSOR

RAIN SENSOR

TERMINAL STRIP IN RAIN SENSOR

TERMINAL STRIP IN WRS 1b

220 V AC5 A

L1NP

connection diagram for connecting the wind-rain sensor to the weather monitoring unit and for connecting the weather monitoring unit to power supply

connection diagram for connecting the ventilation actuators to the weather monitoring unit

M M M M

M M M M

L1NPE

LT-I LT-II LT-III LT-III

NA SECTION I i II SECTION III SECTION IV SECTION V, VI and VII

vent

ilatio

n ac

tuat

or

vent

ilatio

n ac

tuat

or

vent

ilatio

n ac

tuat

or

vent

ilatio

n ac

tuat

or

cont

acts

in

WRS

1b

cont

acts

in

WRS

1b

cont

acts

in

WRS

1b

cont

acts

in

WRS

1b

supply 230 V~

ventilation actuator

ventilation actuator

YDY 2 x 1,5

YDY 3 x 1,5

YDY 3 x 1,5

YDY 3 x 1,5

LT pushbutton

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 72: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

electrical

72

control system for smoke exhaust with gas springs

A variant of the electrical control system for smoke exhaust is a system with smoke vents equipped with gas springs (oleopneumatic actuators). Actuation of smoke vents is effected by the energy of compressed gas in the gas spring. The vent is kept closed by a mechanical catch lock with thermal fuse. When the temperature rises above a certain level, the lock opens and the actuators expands, causing the opening of the hatch. With adequate lock design (use of electromagnet), the system may be opened remotely by an electrical signal (24 V–), which permits e.g. integration with central control panel for smoke exhaust and fire alarm signalling systems. Key features of the system with gas springs:

• lower price compared to other configurations,• this system cannot be used for ventilation,• after operation of the system, the vents are closed from the

roof level.

component elementsThe above smoke exhaust system consists of:

• smoke vents MCR PROLIGHT equipped with gas springs,• electrical control centre of type MCR 9705 or MCR 0204

with battery,• optical smoke detectors (optionally),· ROP pushbuttons.

method of operationThe system has the following methods of emergency activation:

• automatic, controlled by the thermal fuse located inside the vent,

• automatic, by a signal from a fire control centre (after connecting),

• manual, using smoke exhaust pushbuttons.

description9.2.25.

alarm pushbutton ROP (RPO-1)

control centreMCR 9705 v 2

optical detector

YnTKSY 1x2x0,8(YnTKSY 4x2x0,5)HLGs 2x1,5

YDY 3x1,5

230 V

YnTK

SY 1

x2x0

,8

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 73: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 73

mechanical control system for smoke exhaust – release lever

release lever – individual opening and closing9.3.1.

system description• smoke vent equipped with an oleopneumatic (gas-spring)

actuator,• lever permits the release of locks and the opening of the

smoke vent without damaging the thermal fuse,• only opening,

• closing of the vent together with setting of the lock is effected from the roof level,

• in the case of destruction of the thermal fuse – it should be replaced before closing the vent,

• maximum cable length = 10 m,• closing of the vent from the roof level.

5550

140

250

1500

250

r=min 100mountingAssign the cable route and the right place for installing the lever casing. It should be located in a clearly visible place, near doors, and beyond the reach of children.1 – firmly mount the lever casing (1),2 – mount the cable protecting tube (4) using the rings (5) and screws; make as few bends as possible; the bend radius should be at least 100 mm; the rings for mounting the protecting tube should be inserted at intervals of bends,3 – mount the final ring holding the protecting tube (8) at a distance of approximately 10 cm from the casing of the tripping mechanism, mount and cut off the tube above the final ring,4 – insert the cable (3) into the tube, beginning from the final ring holding the protecting tube, and greasing it simultaneously during this operation, lead the cable to the lever casing,5 – lead the cable under the pin inside the tripping holder, and then insert it into the opening; clamp the cable using the hexagonal clamp and cut off the remainder; move the holder up,6 – open the dome, tighten the cable in the upper part, wrap it with adhesive tape, cut off the remainder, insert the end into the tripping holder (9) and attach the cable clamp,7 – close the dome, accurately pressing the latch (11) into the tripping catch; check the stability of closure; if the dome opens easily, the cable should be slightly loosened,8 – make an attempt to open, fully lowering the lever handle (2), let loose, check the opening of the dome,9 – repeat operation no. 7 and then fix glass with an adhesive label (6), inserting it upwards into the top side grooves, then shift it upwards and lower it into the bottom groove; insert the sealing line (7) in front of the glass and apply a lead seal.

1 – casing2 – handle3 – cable4 – protecting tube5 – rings6 – glass with adhesive label7 – lead seal8 –end of protecting tube9 – tripping holder10 – cable clamp11 – manual closing holder latch12 – catch13 – fuse

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 74: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mechanical

74

system properties• safe opening and reliable operation: locking is effected using

the windlass with the self-locking system, located at the operator level,

• closing again:a/ without any intervention on the roof,b/ provided by the windlass with automatic resetting,

• ventilation: possible thanks to partial opening controlled from below using the crank,

• smoke exhaust: constantly possible, even in the initial position of the vent opened for ventilation,

• checking: correct operation of the outlet may be checked at any time,

• maximum cord length – 15 m,• maximum number of pulleys – 4.

Mechanical control is a commonly used actuation system for smoke vents. When the release lever is pulled, a steel cord wound on a drum in a windlass is automatically released. The smoke vent will open fully, regardless of its initial position. Closing the vent again is effected using a crank, which is standard equipment for the mechanism. When necessary, the vent may be opened and

closed in order to ventilate the building. This is provided for by a crank mechanism with a high gear ratio with a self-locking system, permitting the opening of dome to desired position

windlass resetting– after “manual” actuation – insert the crank into the

hexagonal opening and pull it down in order to reengage the winding device (control pushbutton is set automatically).

releasing gear catch with fuse to windlass

fuse

initial cable pulley

cable pulleys on bends

string

protective tube

string

protective tube

fire alarmsystem lever

tip

mechanism blockmounted by 3 screws

cable locking screw

hexagonal key

casing

crank

windlass – construction of crank mechanism

side screw for string mounting

nylonroller

cable

drum

lead sealemergencyactuation lever

control system for smoke exhaust – windlass

windlass – individual opening and closing with possibility of ventilation9.3.2.

principle of operation9.3.4.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 75: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 75

oso mcr

components of window-based smoke exhaust system OSO-MCR10.1.

window-based smoke exhaust system – smoke and heat exhaust

• windows of adequate construction and louvered vents (under preparation);

• control devices: electrical control centre for smoke exhaust MCR 9705 or MCR 0204, pneumatic alarm boxes, pneumatic ventilation boxes.

• releasing elements: smoke detectors, thermal detectors in electrical systems, thermal release valves in pneumatic systems, thermal fuses in catch locks (system with gas springs), manual smoke exhaust control pushbuttons RPO-1 or ROP.

• window actuators: electrical spindle actuators of type MCR W or chain actuators MCR L, pneumatic actuators of type Pxxx, gas springs;

• actuator consoles;• catch locks for windows with gas springs.and additional

equipment:• ventilation pushbuttons LT,• weather monitoring units (MCRP054 or WRS1b) with wind/

rain sensors.

applicationThe window-based smoke exhaust system OSO-MCR is designed for:• smoke and heat removal in the event of �re inside the

building, using the windows mainly in staircases of public facilities, in passages and atria of shopping centres,

• ventilation of rooms in normal use conditions, without tripping the alarm state,

• aeration (providing su�cient in�ow of fresh air) in buildings where an automatic aeration system is used apart from windows, see page 77.

determination of smoke exhaust and aeration surface areaObtaining a particular surface area of smoke exhaust in the system OSO-MCR is dependent on the window size and the actuator stroke. For windows with aerodynamic active area tests results available, these results should be used. If no tests results are available, the active area should be determined in accordance with the speci�ed principles and the drawing (in accordance with EN12 101-2):

1. Determine the geometrical surface area of the opening P: P = H * B

2. A A = C V * P As the aeration surface area, use the geometrical surface area of the opening P (in accordance with PN-B-02877-4:2001).

window constructionIt is possible to use in the system the windows embedded in the building. The key feature of windows in the smoke exhaust system OSO-MCR is the e�ciency of operation – opening and closing. Special attention should be given to accurate �tting of the casement to the window frame, not causing the jamming of these elements.Window types for use in the window-based smoke exhaust system OSO-MCR:• bottom or top hinged windows (to the outside or to the

inside of the building),• hinged windows with vertical opening axis (to the outside or

to the inside of the building),• hinged windows with horizontal opening axis located in half

of the window height.Windows may be made of:• impregnated wood,• PVC of increased resistance to impacts and with internal steel

sections,• aluminium protected against corrosion by anodising or

painting.

αcoe�cient of discharge Cv

window openingto the outside

window openingto the inside

30° 0,25 0,2045° 0,30 0,2560° 0,40 0,3090° 0,50 0,40

min. 0,5 m

α α

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 76: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

oso mcr

76

window-based smoke exhaust system – air inlets

OSO-MCR with electrical controlThe electrical system consists of: windows equipped with electric actuators, and the control centre MCR 9705 or MCR 0204 with detectors and manual smoke exhaust pushbuttonsThe system can be released as follows:

• automatically, controlled by a smoke or thermal detector,• automatically, by a signal from a fire alarm signalling system

through the control centre MCR 9705,• manually, using smoke exhaust pushbuttons.

Closing of windows after their emergency opening (cancelling the alarm state) occurs after prior removal of the cause of alarm and after resetting the alarm with the “reset” pushbutton, and then by using the ventilation pushbutton or the “vent closing” pushbutton.Electrical control panels may be installed near a smoke exhaust window or in a building monitoring room. They are supplied with voltage 230 V~. The operating voltage (supply to actuators) is 24 V=. The control panels are equipped with batteries permitting system operation for 72 hours after a mains voltage outage, and after that time a single emergency opening of windows is possible. The controllers feature visual and audible (MCR 9705) signalling of the operational status, which permits easy identification of the source of alarm or location of a system defect. The system status signals are repeated on the pushbuttons RPO-1.The system may be equipped with additional devices, i.e. the ventilation pushbutton LT and the weather monitoring station with wind sensor WM 1 and rain sensor RS 1. The ventilation pushbutton LT is used for opening and closing of windows for ventilation during normal use of the system, without tripping the alarm state. The purpose of the wind/rain sensors WM 1/RS 1 is to automatically close the windows opened for ventilation in the case of unfavourable weather conditions.

OSO-MCR with pneumatic controlThe pneumatic system consists of the following elements: windows equipped with pneumatic actuators with thermal valves, optionally with CO2 alarm box and pneumatic ventilation box.

The system can be released as follows:– automatic from the thermal trippers on the basis of

temperature increase,– manual from the CO2 emergency box.

Optionally, the system may be integrated with control centres for smoke exhaust MCR 9705 and MCR 0204 and accept signals from RPO-1/ROP, from a fire alarm signalling system, and from smoke detectors, after equipping the alarm boxes or thermal valves with electromagnets.The thermal release valves contain a thermal fuse and a CO2 cartridge, and they should be mounted in the space near the actuated window/windows. Alarm boxes contain a CO2 cartridge and a manually controlled valve.Closing of windows may be effected manually or from alarm boxes – depending on the configuration of the box and the pneumatic system.Equipping the system with a ventilation box permits the opening and closing of windows for ventilation. The ventilation box may be additionally equipped with electromagnet(s) in order to accommodate integration with an automatic weather system (see electrical system) and ventilation pushbuttons.

OSO-MCR with gas springsThe system with gas springs consists of the following elements: windows with catch locks and gas springs.The window is held closed by the catch lock. Release of the lock may occur after exceeding the operational temperature of the thermal fuse (fusible or alcohol type) built into the lock. After release of the lock, the window is opened as a result of the action of springs and it remains in this position. Closing of the window is effected manually.Catch locks, after equipping with pneumatic or electric micro-actuators, may be controlled from the CO2 emergency box or from the control centre for smoke exhaust MCR 9705/MCR 0204, respectively.

principle of operation10.2.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 77: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 77

oso mcr

providing sufficient supply of air10.3.

window-based smoke exhaust system – electrical control system for smoke exhaust

Window-based aerat ion system. In accordance with PN-B-02877-4, adequate inflow of air should be provided for rooms with smoke vents installed above (e.g. production floors, storage spaces, shopping floors, passages, etc.). In order to ensure full utilization of the aerodynamical free area of smoke vents, adequate number of openings should be provided for passing the supplementary air, located in lower parts of the room.

Windows located in the lower part of the room (equipped with actuator and the remaining control devices included in the system OSO-MCR), as well as inflow fans and door openings (in accordance with the standard PN-8-02877-4), may be used for automatic aeration in the case of emergency actuation of smoke vents.

1. smoke layer2. smoke vents MCR Prolight3. smoke curtain4. aerating window controlled by the system OSO-MCR5. space free of smoke

Thanks to the use of air inlets (aerating openings), exhausting smoke from the building becomes more effective. The effects connected with smoke and hot fire gases are thus minimized.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 78: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

oso mcr

78

diagram of typical electrical system for smoke and heat exhaust system in staircase OSO-MCR10.4.

window-based smoke exhaust system – electrical control system for smoke exhaust

noteWire sections are examples – select for the actual system configuration.Elements of the system OSO-MCR:

• control centre for smoke exhaust MCR 9705 or MCR 0204,• emergency smoke exhaust pushbutton (described on page 68),• optical smoke detector OCD (described on page 66),• ventilation pushbutton LT (described on page 68),• weather monitoring unit WRS (described on page 69),• wind/rain sensor (described on page 70), *AA – aerodynamic free area of smoke exhaust.

aerodynamic free area AA

H

B

YnTKSY 1x2x0,8

(YnTKSY 4x2x0,5)

YnTKSY 1x2x0,8

YnTKSY 1x2x0,8

YDY 3x1,5

YDY 3x1,5

HLGs 2x1,5

230 V~

230 V~

ROP (RPO-1)emergency

smoke exhaust pushbutton

ROP (RPO-1)emergency

smoke exhaust pushbutton

GROUND FLOOR

EMERGENCY EXIT

wind and rain sensor

WRSweather monitoring unit

LTventilation pushbutton

MCR 0204 orMCR 9705 v 2control centre of smoke and heat ventilation system

LAST STOREYOCDopticalsmoke

detector

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 79: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 79

oso mcr

window opening to the inside10.5.1.

window-based smoke exhaust system – actuators

mounting method for actuator MCR Lat window opening to the inside

mounting method for actuator MCR Lat window opening to the outside

1. chain actuator MCR L2. window casement3. window frame4. “internal” console

1. chain actuator MCR L2. window casement3. window frame4. “external” console

window opening to the outside10.5.2.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 80: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

oso mcr

80

mounting consoles for spindle actuators

MK 47-2mounting console, internal width 47 mm, type 2

MK 47-4mounting console, internal width 47 mm, type 4

110

42

53

6047

30

5,2

25

13

9

8799

1130

6030

13

2,547

1410

7

5567

429

115

50

USO 1window console for actuators MCR W, width 47 mm

USO 2window console for actuators MCR W, width 52 mm

20

13,5

40

5

3

30

52

132 11

7

53

5

13,5

3

30

20

47

40 30

101,

586

,5

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 81: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 81

oso mcr

console of type KB 6

console of type KB 10

console of type KB 86

23 30

28

12

10

6,5 10

20

46

60

23 30

8

28

12

10

6,5 10

20

46

60

23

30

10

28

12

10

6,5

10

20

46

60

mounting consoles and pins for spindle actuators

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 82: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

oso mcr

82

mounting consoles for ventilation actuators 230 V

console of type KB 2/70

54

112

80

97

30

55

38

Ø 6,5

70

55

42,5

17Ø 13

console of type MK 56-3

1580

70

30

56 3

12,5

42 60

6,5

9

4x

for actuators of type JMB

for actuators of type E 300, E 500, E 750

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 83: Teknisk dokumentation ovenlys og brandventilation

Mercor SA, ul. Grzegorza z Sanoka 2, 80-408 Gdańsk, Poland, phone: +48 58 341 42 45, fax: +48 058 341 39 85 83

mcr kurtyna prosmoke smoke curtain

smoke curtain - description11.1.

construction of MCR Kurtyna ProsmokeMCR KURTYNA PROSMOKE may seal off openings of height max. 8 m, of width dependent on the number of used curtain modules.Smoke curtains consist of the following basic elements:

• special non-combustible fabric MCR TK G1 or MCR TK G2 (silver-grey colour),

• winding shaft with actuator enclosed in a casing of galvanised steel sheet,

• lower ballast of the curtain made of galvanised steel sheet,• power supply module,• optional side guides,• control centre MCR 9705 or MCR 0204.

The curtain dimensions, and in consequence the device size and the used actuators and control devices, are determined in each case on the basis of the customer’s requirements.The curtain is made of a special non-combustible fabric of dimensions adequately adjusted to the opening sealed off by the curtain. The fabric is wound on the shaft by an actuator enclosed in the casing. The casing is mounted to a lintel, roof, ceiling, or wall, using adequately selected fasteners. Correct unrolling of the fabric and correct positioning of the curtain in the alarm state are ensured by the linear ballast (bottom bar). In addition, the curtain position in the alarm state may be fixed by optional side guides mounted to walls or pillars. The curtain is rolled and unrolled using an electric actuator powered with safe voltage 24 V=.In the case of curtains of considerable length, the device is combination of several modules as described above.The curtain control system is supplied from mains 230 V~, and in the case of a mains supply failure it may operate in stand-by state for 72 hours, and then be actuated once. In addition, the control system provides monitoring of the supply lines of the curtain actuator.

A curtain wall is a vertical partition mounted on the inside to the roof or ceiling, preventing the spread of smoke and fire gases in a horizontal direction.One of the possible executions of a curtain wall is the automatic rolled smoke curtain MCR KURTYNA PROSMOKE. The use of an automatic rolled smoke curtain allows architects, apart from ensuring safety and satisfying the regulatory requirements, to shape the space as desired – this solution does not prevent the lighting of the building interior. Due to small overall dimensions and low weight, it requires no special structural solutions, and may be fitted easily into any room.

applicationA smoke curtain, as one of the elements of a smoke and heat ventilation system, is used to separate a smoke container in the building, within smoke exhaust zones, by division of the space under the roof or ceiling into smaller parts. In combination with smoke vents MCR-Prolight and inlet openings, MCR KURTYNA PROSMOKE permits:

• increasing the operating efficiency of vents by accumulation of smoke in smoke reservoirs within a zone,

• maintaining escape routes free of smoke,• reducing the damage caused by smoke and hot gases,

optimising smoke control.

principle of operation of rolled smoke curtainMCR Kurtyna ProsmokeIn the stand-by state, the curtain is fully rolled. When the alarm state is identified, the curtain controlled by the control panel MCR 9705 or MCR 0204 is fully unrolled until it reaches the designed curtain height. The unrolled curtain fabric prevents smoke and hot gases from penetrating to other smoke containers. The lowered fabric may be rolled using an electric motor.Operation of the curtain is controlled by the control panels MCR 9705 and MCR 0204 used for controlling smoke exhaust devices. Depending on the system configuration and the used devices, curtains may be actuated on the basis of a signal from smoke or heat detectors, from manual pushbuttons (ROP or RPO-1), or a signal received from a fire alarm signalling system.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk

Page 84: Teknisk dokumentation ovenlys og brandventilation

natural smoke and heat exhaust ventilation and roof lighting systems – technical directory 2006

mcr kurtyna prosmoke

84

smoke curtain

schematic diagram11.2.

1. casing with shaft2. side guides3. special fabric4. bottom bar

room

hei

ght

curt

ain

heig

ht

opening width

optical detector

pushbuttonRPO-1

MCR 0204or

MCR9705

230 V~

MCR Kurtyna Prosmoke is made of modules of length max. 6 m. The number of used modules depends on the required total length of the curtain. Maximum height of the curtain is 8 m.

total curtain length [m] minimum number of modules number of motors x nominal motor current

> 6,00 1 1 6,3A6,01 .. 11,50 2 2 x 6,3A11,51 .. 17,00 3 3 x 6,3A17,01 .. 22,50 4 4 x 6,3A22,51 .. 28,00 5 5 x 6,3A28,01 .. 33,50 6 6 x 6,3A33,51 .. 39,00 7 7 x 6,3A

Larger total curtain lengths are also possible.

The smoke curtain satis�es the requirements of the technical approval ITB no. AT-15-6351/2004 con�rmed by the certi�cate of conformity no. ITB-0921/W.

Gelco Nordic ApS . Hylkedamvej 70 . DK-5591 Gelsted Tel.: +45 63 46 54 08 . www.gelco-nordic.dk


Recommended