Date post: | 11-Mar-2015 |
Category: |
Documents |
Upload: | sparky224666 |
View: | 173 times |
Download: | 17 times |
TELSTRA CORPORATION LIMITED (ABN 33 01 775 556) | ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 |ISSUE NUMBER: 1.0
AUTHOR‟S NAME: MICHAEL WILLIAMS
BUSINESS UNIT: TELSTRA OPERATIONS
SUB BUSINESS UNIT: NETWORKS AND ACCESS TECHNOLOGIES
ISSUE DATE: 9 MAY. 2011| ISSUE NUMBER: 1.0
DOCUMENT NO: 007338 E10-2
INNOTECH DDC APPROVED CONTROL STRATEGY
BUILDING SERVICES
007338 - Power & Engineering Services
DESIGN STANDARD
SUB DOMAIN: BUILDING SERVICES
This Power & Engineering Services document is to be used by network designers and
constructors to design and install infrastructure approved for Network under 007338 Part
D and in accordance with the deployment criteria specified in 007338 Part C in order to
meet Telstra‟s Business Objectives.
SUMMARY: The Purpose of this document is to provide a framework for programmers of
Innotech Direct Digital Controls (DDC) which details the minimum requirements for
functions and concepts to be incorporated and how those functions are to be programmed
in a standard manner.
VERSION LABEL: Final
SECURITY CLASSIFICATION: Telstra Unrestricted
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 2 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
TABLE OF CONTENTS
1. PURPOSE ....................................................................................................................... 3
2. SCOPE........................................................................................................................... 3
3. KEY STAKEHOLDERS....................................................................................................... 3
4. PROGRAMMING FUNCTIONAL REQUIREMENTS .................................................................. 4
4.1. GENERAL ................................................................................................................ 4
4.2. HVAC ENABLE.......................................................................................................... 4
4.3. TEMPERATURE CONTROL .......................................................................................... 5
4.4. ECONOMY CYCLE ..................................................................................................... 6
4.4.1. ECONOMY CYCLE ENABLE – ENTHALPY .......................................................... 6
4.4.2. ECONOMY CYCLE ENABLE – SENSIBLE TEMPERATURE ..................................... 7
4.4.3. ECONOMY CYCLE CONTROL .......................................................................... 8
4.5. SENSOR ALARMS ..................................................................................................... 9
4.6. COMFORT CONTROLLED AREAS............................................................................... 10
4.7. HEATING CONTROL ................................................................................................ 10
4.8. FAULT HANDLING .................................................................................................. 10
4.9. WATCH PAGES ...................................................................................................... 10
4.10. DATA LOGGING ..................................................................................................... 11
4.11. LEAD / LAG AND DUTY / STANDBY CHANGEOVER ..................................................... 12
5. APPROVED SOFTWARE AVAILABILITY ............................................................................. 13
6. APPLICATION RULES ..................................................................................................... 14
7. REFERENCES ............................................................................................................... 14
7.1. 007338 ................................................................................................................. 14
7.2. OTHER INTERNAL .................................................................................................. 14
7.3. EXTERNAL ............................................................................................................. 14
8. DEFINITIONS ............................................................................................................... 14
9. ATTACHMENTS ............................................................................................................. 15
10. DOCUMENT CONTROL SHEET ........................................................................................ 16
PAGE 3 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
1. PURPOSE
The Purpose of this document is to provide a framework for programmers of Innotech Direct
Digital Controls (DDC) which details the minimum requirements for functions and concepts to
be incorporated and how those functions are to be programmed in a standard manner.
2. SCOPE
This document applies to all new Innotech DDC control strategies. Individual site and HVAC
plant specific requirements may necessitate the addition of some functions such as lead / lag
changeovers etc., however, the programming methodology, minimum required functions and
standard “look and feel” should not require significant change. Retro upgrading of existing
DDC programs should be considered at such times when this can be undertaken cost
effectively. Note that in some cases existing older controls and system resources may not
allow for full retro implementation.
The document uses hyperlinks and colour.
3. KEY STAKEHOLDERS
The following stakeholders (listed alphabetically) have reviewed and agreed to the content of
this document before issue:
NAME TITLE
George Bakogianis Senior Capacity Planner, Network Planning Studies, Telstra
Chris Baran-Kamp 007338 Technical Editor - Network & Facilities Mgmt, Telstra
George Bradilovic General Manager – Network and Facilities Management, Telstra
Greg Dendle Senior Technology Specialist, Building Network Design, Telstra
Pat Fitzgerald Strategic Facilities Mgmt, Network Services, Telstra
Allan Gontar National Energy Manager – Telstra Property
Mark Kelly Snr Capacity Planner Network Standards & Compliance, Telstra
Anthony Price Strategic Planning Manager, Network Group, Telstra Property
David Roach Technology Team Manager – Power, Telstra
Ron Roberts National Contract & Service Mgr, Network & IT Ops, Telstra
Aurecon (Represented by Paul Brown)
Silcar (O&M) (Represented by G. McIntyre)
Silcar (D&C) (Represented by G. Mullen)
Table 1: Key Stakeholders
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 4 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
4. PROGRAMMING FUNCTIONAL REQUIREMENTS
4.1. GENERAL
For conceptual illustration, the control system described is based on a networkable Direct
Digital Controller (DDC) serving a 4 stage HVAC system with Economy Cycle Cooling (ECC).
This control strategy concept can be applied to other DDC systems and plant configurations.
Where Economy Cycle Cooling is not employed, the description of mechanical cooling control
is still applicable and can be adapted to systems incorporating fewer or greater than four
cooling stages as described here.
Some functions included for illustration (such as Fire and VESDA status inputs and alarms)
may be applicable to specific projects or required by regulatory code or Telstra Standards on
an individual installation basis. Where these functions are not required by specification they
should be deleted from the final control strategy. Ensure all control strategies are compliant
with Fire & VESDA standards C9-2 & E10-1.
Note that all program blocks are to be discretely named and a printed copy of the „as
installed‟ control program, block details and wiring diagram must be included in O&M
manuals.
Text blocks should be used to label programming functions and provide detail regarding any
variation to standard such as inclusion of time delays etc.
4.2. HVAC ENABLE
Generally, the Air-conditioning Unit will run continuously. A Master On/Off switch accessed
via the front panel of the Controller (Watch page 1) can be used to stop the unit from
running. An airflow switch in the supply air ductwork confirms the supply air fan status. Once
the fan is requested and the status is confirmed as running, the automatic control functions
are enabled (Control Enable). If the fan status is lost, the control functions are disabled. If
the supply air fan is called to run and no fan status has been received by the duct mounted
air-flow switch after a 60 second delay period, a Supply Air Fan fault will be displayed on the
LCD of the Controller. This fault will be displayed as SAF Fault.
PAGE 5 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 1: HVAC Enable Logic Diagram
4.3. TEMPERATURE CONTROL
If the automatic control functions are enabled, the controller responds to its discrete
temperature sensor (or the averaged value or high signal select input as appropriate where
multiple sensors are specified and installed) to maintain a target long term average room
temperature of 250C.
As the space temperature rises above a nominal 24.50C set-point, the four compressors will
be cycled through a single Cooling PID loop with a nominal proportional band of 2.50C. For all
cases Integral and Derivative values will both be 0%
Individual Hysteresis blocks and values as below are provided for each cooling stage. With
nominal set-point and proportional band values as above, the four compressors will be cycled
in the following manner to maintain conditions –
i. Compressor 1 On – 25.1ºC (25% output) Off - 24.6ºC (5% Output)
ii. Compressor 2 On - 25.7ºC (50% Output) Off - 25.1 ºC (25% Output)
iii. Compressor 3 On - 26.3ºC (75% Output) Off - 25.7ºC (50% Output)
iv. Compressor 4 On - 26.8ºC (95% Output) Off - 26.3ºC (75% Output)
Figure 2: Temperature Control Compressor Cycling
Time delay blocks are not incorporated into the temperature controlled cooling sequence
unless these are a necessary replacement for absent electrical / mechanical start delay or
short cycle timers within the HVAC plant.
For systems incorporating fewer or greater than 4 stages, the above staging schedule and
proportional band should be amended as required to maintain an average long term
temperature of 250C while maintaining the main control point values e.g. 2 stage cooling –
Compressor 1 on at 50% output and Off at 5% output, Compressor 2 On at 95% output and
Off at 50% output.
Limits are placed on the User Temperature Set-point so this cannot be adjusted below 24ºC
or above 28ºC.
For maintenance purposes a “Unit Test Mode” soft switch (User Variable) is provided via
Watch Page 1, which operates the plant at a reduced control set-point between 18°C and
22°C (User adjustable) for a set time of 20 minutes.
TEMPERATURE
24.5°C 25°C 25.5°C 26°C 26.5°C 27°C
(C1 on)
(C2 off)
(C2 on)
(C3 off)
(C3 on)
(C4 off)
(C4 on)
(C1 off)
OUTPUT
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 6 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 3: Temperature Control Logic Diagram
Figure 4: Temperature Control Test Logic Diagram
4.4. ECONOMY CYCLE
4.4.1. ECONOMY CYCLE ENABLE – ENTHALPY
(Where specified for inclusion)
The Economy Cycle is enabled by an Enthalpy Comparator mode. If the Ambient Enthalpy is
1 KJ/Kg below the Return Air Enthalpy the economy cycle will be enabled to operate. If the
Ambient Enthalpy rises to equal the Return Air Enthalpy then the Economy Cycle will be
disabled. Where specified, a VESDA or Fire Alert will inhibit operation of the economy cycle.
Further interlocks for the economy cycle to be enabled are as follows:
Ambient Humidity Low Limit > 20% High Limit < 80%
Ambient Temperature Low Limit >5ºC High Limit <25ºC
These operating parameters are established through the use of Hysteresis blocks.
PAGE 7 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 5: Economy Cycle Enable (Enthalpy Comparison) Logic Diagram
4.4.2. ECONOMY CYCLE ENABLE – SENSIBLE TEMPERATURE
(Where specified for inclusion)
The Economy Cycle is enabled by a Temperature comparison mode. When the ambient
temperature is a minimum 1ºC below return air or conditioned space temperature the
economy cycle will be enabled to operate. If the ambient temperature rises to equal the
return air or conditioned space temperature then the Economy Cycle will be disabled. No
Relative Humidity sensing or limits are included in a sensible temperature enabled Economy
Cycle system.
Further interlocks for the economy cycle to be enabled are as follows:
Ambient Temperature Low Limit >5ºC High Limit <18ºC (to a maximum of 23 ºC in some
nominated colder climates)
These operating parameters are established through the use of Hysteresis blocks.
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 8 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 6: Economy Cycle Enable (Sensible Temperature) Logic Diagram
4.4.3. ECONOMY CYCLE CONTROL
(Enthalpy or Sensible temperature models)
When enabled by the above conditions, the economy cycle is ready to be controlled. If the
Return Air Temperature rises above a nominal set-point (named ECC Low Limit), of 20ºC the
economy cycle dampers will modulate through a proportional band of 3ºC. That is, at a room
temperature of 20ºC the ECC fresh air make-up and spill air dampers would have modulated
to the fully closed position with the return air damper fully open. At 23ºC the ECC fresh air
make up and spill air dampers would have modulated to the fully open position and return air
dampers would be fully closed.
Limits are placed on this Set-point (ECC Low Limit) so this cannot be adjusted below 18ºC or
above 20ºC.
The control strategy shall also include a Test Mode Function of 5 minutes duration operated
via a soft switch grouped with other ECC functions. This test mode will operate all ECC
dampers to their fully on position.
An automatic timer function (ECC Damper maintenance) will operate all ECC dampers to
their fully functioning positions each Monday from 2:00 am to 2:05 am. This is to reduce the
incidence of dampers seizing after long periods of inactivity.
PAGE 9 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 7: Economy Cycle Control Logic Diagram
4.5. SENSOR ALARMS
If any outside air sensor output is below 1% or above 85% of normal full scale output and if
this condition is sustained for a continuous period of greater than 168 hours, a latched alarm
within the DDC is to output the warning “Check OA Sensor” to the display panel. This latched
alarm should not lock out the economy cycle as under some conditions e.g. prolonged rain
periods, a “false alarm” might be generated. The purpose of this flag alarm is to alert
maintenance operators that the outside air sensors should be checked for operation /
accuracy. A soft switch alarm reset must be provided within the DDC.
Figure 8: Ambient Conditions Logic Diagram
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 10 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 9: Ambient Sensor Fault Alarm Logic Diagram
4.6. COMFORT CONTROLLED AREAS
(Offices, Lunch rooms etc.)
Where controlled supply air dampers or stand alone HVAC plant are provided to office or
other areas conditioned for human comfort only, then for each independently conditioned
space, an “On/Off” user variable soft switch will be provided and HVAC will be enabled via
individual discrete time control functions activating operation during normal business hours
only (nominally 7:30 am – 5:00 pm Mon–Fri). A physical push button will be provided which
enables cooling for a 1 hour period outside normal business hours. A separate independent
cooling set point and PID block will be provided with a limited user input range of 23ºC to
28ºC. The controlled dampers or mechanical cooling will modulate though a 1 deg
proportional band.
4.7. HEATING CONTROL
In limited cases where heating is provided for human comfort in office spaces etc. for each
independent conditioned space, a “Heating Enable” on/off user variable soft switch will also
be incorporated. Heating will be controlled via a discrete time control block activating the
heating function during normal business hours only (nominally 7:30 am – 5:00 pm Mon –
Fri). A separate independent heating PID block will be enabled after confirmation of Supply
Air Fan Status (Control enable). The user input set-point range will be limited to 18ºC to
22ºC. Note that this provides a minimum 1ºC difference between the maximum heating and
minimum cooling independent set-points to avoid heat/cool conflicts.
4.8. FAULT HANDLING
System faults within the DDC should be logged and display if in alarm but should not latch
(with the exception described under Economy Cycle). DDC configurations should inhibit the
running of any component in fault condition but automatically reset when a fault clears
without requiring a hard reset. This does not apply to hardware faults such as HP/LP and
motor contactor overloads etc. Treatment of these faults should be specified elsewhere.
4.9. WATCH PAGES
The following system data is displayed via the DDC watch pages. Any repetitive display is
deliberate in order to maintain logical grouping of data. Flash page and Watch page 1 are
mandatory but some additions or deletions to subsequent pages may be necessary
dependant on the program configuration. The assignment of all data should follow a logical
grouping. Where a watch page is left totally blank through deletions then all subsequent
watch pages move up 1 designation. Typical Layout –
Flash Page –
Control Enable Status
Supply Fan Status
Return Air or Room Temp (Controlling temperature point)
PAGE 11 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Cooling Demand %
Economy Cycle Demand % (For ECC installed systems only)
Page 1 –
Master (Unit) On / Off switch ( User variable)
Test Mode Set-point ( User variable)
Test Mode On/Off (Cooling Test mode User Variable)
Return Air or Room Temp (Controlling temperature point)
Cooling Set Point (User variable)
Page 2 –
Cooling Demand %
Compressor or Cooling Stage 1 enable Status
Compressor or Cooling Stage 2 enable Status
Compressor or Cooling Stage 3 enable Status
Compressor or Cooling Stage 4 enable Status
Page 3 –
Outside Air Temp (For all ECC installed systems only)
Outside Air Humidity (For Enthalpy ECC installed systems only)
Outside Air Sensor Alarm reset (For all ECC installed systems only)
Return or Room Air Temp (Controlling temperature point)
Return or Room Air Humidity (Controlling RH point) (For Enthalpy ECC installed
systems only)
Page 4 –
Economy Cycle Enabled Status (For all ECC installed systems only)
Outside Air Enthalpy or Temperature (specific to the type of ECC installed)
Return Air Enthalpy or Temperature (specific to the type of ECC installed)
Economy Test On/Off (For all ECC installed systems only)
Economy Cycle Low Limit (User Variable) (For all ECC installed systems only)
Subsequent Watch Pages –
All other data points specific to the installation
4.10. DATA LOGGING
All available points should be logged and grouped together on a common program page. This
necessitates that each logged point be assigned and individual label. If system resources are
limited, the following points are to be logged as a minimum -
Supply Fan Fault.
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 12 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Return Air and or Room Air Temperature/s. (all sensor points and averaged or high
select values as specific to the installation)
Return Air and or Room Air Humidity (For Economy Cycle installations)
Cooling Set-point.
Unit Test Mode function
Heating Set-point if heating is provided
Return Air Enthalpy. (For Enthalpy Economy Cycle installations)
Ambient Air Temperature. (For all Economy Cycle installations)
Ambient Air Relative Humidity. (For Enthalpy Economy Cycle installations)
Ambient Enthalpy. (For Enthalpy Economy Cycle installations)
Economy Damper Actuators. (For all Economy Cycle installations)
All Cooling Stages
Economy Cycle Test Mode function (For all Economy Cycle installations)
Other points specific to a particular configuration such as VESDA Alert, Fire Alarm
shut down, Standby Generator status etc. where these are specified to form an
integral part of a control strategy
Figure 10: Typical Data Logging Layout (for illustration only - not all required points included)
4.11. LEAD / LAG AND DUTY / STANDBY CHANGEOVER
Where lead/lag and duty/standby changeover is required, this should be achieved through a
calendar block and counter function with an automatic reset and user manual advance.
PAGE 13 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
Figure 11: Lead / Lag and Duty / Standby Changeover Logic Diagram
5. APPROVED SOFTWARE AVAILABILITY
Software and HVAC control strategy programming is available from
Innotech Control Systems –
Global Headquarters and Manufacturing
Innotech Control Systems - Brisbane
Office Address:
Brisbane Technology Park, 6 McKechnie Drive
Eight Mile Plains, QLD, 4113, Australia
Postal Address:
PO Box 292
Sunnybank, QLD, 4109, Australia
Phone: +61 7 3841 1388
Fax: +61 7 3841 1644
Office Hours: 7:30 AM - 5:00 PM (EST) Monday - Friday
E-Mail: [email protected]
Web: www.innotech.com.au
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 14 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
6. APPLICATION RULES
The control strategy and functions described are applicable to Innotech Maxim and Genesis
series direct digital controllers.
Individual site and HVAC plant specific requirements may necessitate the addition of some
functions such as Supply Air Fan damper control, Toilet Exhaust Fan control or load shedding
of some mechanical cooling capacity during Emergency Power Plant operation etc. However,
the programming methodology, minimum required functions and standard “look and feel”
should not require significant change.
This document applies to all Telstra sites where any HVAC plant is controlled by an Innotech
DDC. This does not apply to small individual modular HVAC plant such as IVTRES or Emerson
TEX plant which is delivered and installed with an integrated pre programmed Innotech DDC.
7. REFERENCES
7.1. 007338
DOCUMENT NUMBER TITLE
C3-1 Network Building Environmental Standards
C3-3 Air Conditioning Services
C3-4 Environmental Controls
C3-5 Economy Cycle
C9-2 Provision of Fire Detection & Alarm Systems and Portable Fire
Extinguishers
E10-1 Multi-Point Aspirated Smoke Detection Systems for Network Sites
7.2. OTHER INTERNAL
DOCUMENT NUMBER TITLE
Nil
7.3. EXTERNAL
DOCUMENT NUMBER TITLE
Nil
8. DEFINITIONS
TERM DEFINITION
DDC Direct Digital Controller
PAGE 15 OF 16 TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) |ISSUED: 9 MAY. 2011
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
TERM DEFINITION
DUTY / STANDBY Two or more HVAC plant controlled in such a manner that only the
duty plant operates and the standby plant is called into operation if
the duty plant fails. The plant designated as duty can be rotated on
a time based schedule
ECC Economy Cycle Cooling. The introduction of up to 100% fresh air
into the HVAC air distribution system when the outside air condition
is suitable.
HVAC Heating, Ventilation and Air Conditioning plant
LEAD /LAG Two or more HVAC plant controlled in such a manner that if heat
load cannot be satisfied by the primary “Lead” plant, then the
cooling strategy will call the additional “Lagging” plant to operate in
unison. The plant designated as leading can be rotated on a time
schedule or fault condition basis.
WATCH PAGE A group of data or controlled point status values viewed via an LCD
front panel of the DDC
9. ATTACHMENTS
DOCUMENT NUMBER TITLE
Nil
TELSTRA CORPORATION LIMITED (ABN 33 051 775 556) | ISSUED: 9 MAY. 2011 PAGE 16 OF 16
FINAL | TELSTRA UNRESTRICTED | 007338 E10-2 | ISSUE NUMBER: 1.0
10. DOCUMENT CONTROL SHEET
Contact for Enquiries and Proposed Changes
If you have any questions regarding this document contact:
NAME: MICHAEL WILLIAMS
DESIGNATION: TECHNOLOGY SPECIALIST
PHONE: (03) 8647 5425
EMAIL: [email protected]
If you have a suggestion for improving this document, please contact the person listed above or complete the
online Change Proposal Form at http://www.in.telstra.com.au/ism/007338/feedback.asp
ISSUE
NO.
ISSUE DATE APPROVED NATURE OF AMENDMENT
1.0 May 9, 2011 Chris Baran-Kamp
007338 Technical
Editor