+ All Categories
Home > Documents > Tema 07 - High Low Impedance Busbar Protection 092

Tema 07 - High Low Impedance Busbar Protection 092

Date post: 02-Jun-2018
Category:
Upload: yinder-vega-osorio
View: 222 times
Download: 0 times
Share this document with a friend

of 92

Transcript
  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    1/92

    Fundamentals of

    Bus Bar Protection

    GE Multilin

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    2/92

    2

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Outline

    Bus arrangementsBus componentsBus protection techniquesCT SaturationApplication Considerations:

    High impedance bus differential relayingLow impedance bus differential relayingSpecial topics

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    3/92

    3

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Distribution and lower transmission voltage levels

    No operating flexibility Fault on the bus trips all circuit breakers

    Single bus - single breaker

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    4/92

    4

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Distribution and lower transmission voltage levels

    Limited operating flexibility

    Multiple bus sections - single breaker withbus tie

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    5/92

    5

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Transmission and distribution voltage levels Breaker maintenance without circuit removal

    Fault on a bus disconnects only the circuits being connected

    to that bus

    Double bus - single breaker with bus tie

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    6/92

    6

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Increased operating flexibility A bus fault requires tripping all breakers

    Transfer bus for breaker maintenance

    Main and transfer buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    7/92

    7

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Very high operating flexibility Transfer bus for breaker maintenance

    Double bus single breaker w/ transfer bus

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    8/92

    8

    GE Consumer & IndustrialMultilin

    1 Nov 14

    High operating flexibility Line protection covers bus section between two CTs

    Fault on a bus does not disturb the power to circuits

    Double bus - double breaker

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    9/92

    9

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Used on higher voltage levels

    More operating flexibility

    Requires more breakers

    Middle bus sections covered by line or other equipment

    protection

    Breaker-and-a-half bus

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    10/92

    10

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Higher voltage levels

    High operating flexibility with minimum breakers

    Separate bus protection not required at line positions

    Ring bus

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    11/92

    11

    GE Consumer & IndustrialMultilin

    1 Nov 14

    Bus componentsbreakers

    SF6, EHV & HV - Synchropuff

    Low Voltage circuit breakers

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    12/92

    12GE Consumer & Industrial

    Multilin

    1 Nov 14

    Disconnect switches & auxiliary contacts

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    13/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    14/92

    14GE Consumer & Industrial

    Multilin

    1 Nov 14

    Protection Requirements

    High bus fault currents due to large number of circuitsconnected:

    CT saturation often becomes a problem as CTs may not be sufficientlyrated for worst fault condition case

    large dynamic forces associated with bus faults require fast clearingtimes in order to reduce equipment damage

    False trip by bus protection may create serious problems:

    service interruption to a large number of circuits (distribution and sub-transmission voltage levels)

    system-wide stability problems (transmission voltage levels)

    With both dependability and security important, preference isalways given to security

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    15/92

    15GE Consumer & Industrial

    Multilin

    1 Nov 14

    Bus Protection Techniques

    Interlocking schemes Overcurrent (unrestrained or unbiased)

    differential

    Overcurrent percent (restrained or biased)differential

    Linear couplers

    High-impedance bus differential schemes

    Low-impedance bus differential schemes

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    16/92

    16GE Consumer & Industrial

    Multilin

    1 Nov 14

    Interlocking Schemes

    Blocking scheme typically

    used Short coordination time

    required

    Care must be taken with

    possible saturation of feederCTs

    Blocking signal could be sentover communications ports(peer-to-peer)

    This technique is limited tosimple one-incomerdistribution buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    17/92

    17GE Consumer & Industrial

    Multilin

    1 Nov 14

    Overcurrent (unrestrained) Differential

    Differential signal formed bysummation of all currents feedingthe bus

    CT ratio matching may berequired

    On external faults, saturated CTsyield spurious differential current

    Time delay used to cope with CTsaturation

    Instantaneous differential OC

    function useful on integratedmicroprocessor-based relays

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    18/92

    18GE Consumer & Industrial

    Multilin

    1 Nov 14

    59

    Linear Couplers

    ZC= 2 20 - typical coil impedance

    (5V per 1000Amps => 0.005 @ 60Hz )

    If = 8000 A

    40 V 10 V 10 V 0 V 20 V

    2000 A 2000 A 4000 A0 A

    0 V

    ExternalFault

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    19/92

    19GE Consumer & Industrial

    Multilin

    1 Nov 14

    59

    Linear CouplersEsec= Iprim*Xm - secondary voltage on relay terminals

    IR= Iprim*Xm /(ZR+ZC) minimum operating current

    where,Iprim primary current in each circuitXmliner coupler mutual reactance (5V per 1000Amps => 0.005 @ 60Hz )ZR relay tap impedance

    ZC sum of all linear coupler self impedances

    If = 8000 A

    0 A

    0 V 10 V 10 V 0 V 20 V

    40 V

    2000 A 2000 A 4000 A0 A

    Internal BusFault

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    20/92

    20GE Consumer & Industrial

    Multilin

    1 Nov 14

    Fast, secure and proven

    Require dedicated air gap CTs, which may not be used forany other protection

    Cannot be easily applied to reconfigurable buses The scheme uses a simple voltage detector it does notprovide benefits of a microprocessor-based relay (e.g.oscillography, breaker failure protection, other functions)

    Linear Couplers

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    21/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    22/92

    22GE Consumer & Industrial

    Multilin

    1 Nov 14

    Percent Differential

    Percent characteristic usedto cope with CT saturationand other errors

    Restraining signal can be

    formed in a number ofways

    No dedicated CTs needed

    Used for protection of re-

    configurable busespossible

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    23/92

    23GE Consumer & Industrial

    Multilin

    1 Nov 14

    Low Impedance Percent Differential

    Individual currents sampled by protection and summated digitallyo CT ratio matching done internally (no auxiliary CTs)

    o Dedicated CTs not necessary

    Additional algorithms improve security of percent differentialcharacteristic during CT saturation

    Dynamic bus replica allows application to reconfigurable buseso Done digitally with logic to add/remove current inputs from differentialcomputation

    o Switching of CT secondary circuits not required

    Low secondary burdens

    Additional functionality available

    o Digital oscillography and monitoring of each circuit connected to bus zone

    o Time-stamped event recording

    o Breaker failure protection

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    24/92

    24GE Consumer & Industrial

    Multilin

    1 Nov 14

    Digital Differential Algorithm Goals

    Improve the main differential algorithm operation

    o Better filtering

    o Faster response

    o Better restraint techniques

    o Switching transient blocking

    Provide dynamic bus replica for reconfigurable bus bars Dependably detect CT saturation in a fast and reliable manner,

    especially for external faults

    Implement additional security to the main differential algorithm toprevent incorrect operation

    o External faults with CT saturationo CT secondary circuit trouble (e.g. short circuits)

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    25/92

    25GE Consumer & Industrial

    Multilin

    1 Nov 14

    Low Impedance Differential (Distributed)

    Data Acquisition Units (DAUs)

    installed in bays

    Central Processing Unit (CPU)processes all data from DAUs

    Communications between DAUsand CPU over fiber usingproprietary protocol

    Sampling synchronisationbetween DAUs is required

    Perceived less reliable (morehardware needed)

    Difficult to apply in retrofitapplications

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    26/92

    26GE Consumer & Industrial

    Multilin

    1 Nov 14

    Low Impedance Differential (Centralized)

    All currents applied to a singlecentral processor

    No communications, externalsampling synchronisationnecessary

    Perceived more reliable (lesshardware needed)

    Well suited to both new andretrofit applications.

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    27/92

    27GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    28/92

    28GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation Concepts

    CT saturation depends on a number of factorso Physical CT characteristics (size, rating, winding resistance,

    saturation voltage)

    o Connected CT secondary burden (wires + relays)

    o Primary current magnitude, DC offset (system X/R)

    o Residual flux in CT core

    Actual CT secondary currents may not behave in the same manner asthe ratio (scaled primary) current during faults

    End result is spurious differential current appearing in the summationof the secondary currents which may cause differential elements tooperate if additional security is not applied

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    29/92

    29GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation

    No DC Offset

    Waveform remains fairlysymmetrical

    With DC Offset

    Waveform starts off beingasymmetrical, thensymmetrical in steadystate

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    30/92

    30GE Consumer & Industrial

    Multilin

    1 Nov 14

    External Fault & Ideal CTs

    Fault starts at t0 Steady-state fault conditions occur at t1

    t0

    t1

    Ideal CTs have no saturation or mismatch errors thusproduce no differential current

    l l l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    31/92

    31GE Consumer & Industrial

    Multilin

    1 Nov 14

    External Fault & Actual CTs

    Fault starts at t0 Steady-state fault conditions occur at t1

    t0

    t1

    Actual CTs do introduce errors, producing some differentialcurrent (without CT saturation)

    E l F l i h CT S i

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    32/92

    32GE Consumer & Industrial

    Multilin

    1 Nov 14

    External Fault with CT Saturation

    Fault starts at t0, CT begins to saturate at t1 CT fully saturated at t2

    t0

    t1

    t2

    CT saturation causes increasing differential current thatmay enter the differential element operate region.

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    33/92

    33GE Consumer & Industrial

    Multilin

    1 Nov 14

    Some Methods of Securing Bus Differential

    Block the bus differential for a period of time (intentional delay)o Increases security as bus zone will not trip when CT saturation is present

    o Prevents high-speed clearance for internal faults with CT saturation orevolving faults

    Change settings of the percent differential characteristic (usually Slope 2)

    o Improves security of differential element by increasing the amount ofspurious differential current needed to incorrectly trip

    o Difficult to explicitly develop settings (Is 60% slope enough? Should it be75%?)

    Apply directional (phase comparison) supervision

    o Improves security by requiring all currents flow into the bus zone beforeasserting the differential element

    o Easy to implement and test

    o Stable even under severe CT saturation during external faults

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    34/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    35/92

    35GE Consumer & Industrial

    Multilin

    1 Nov 14

    High Impedance Voltage-operated RelayExternal Fault

    59 element set above max possible voltage developed acrossrelay during external fault causing worst case CT saturationFor internal faults, extremely high voltages (well above 59

    element pickup) will develop across relay

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    36/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    37/92

    37GE Consumer & Industrial

    Multilin

    1 Nov 14

    High Impedance Voltage Operated RelayRatio matching with Multi-ratio CTs

    Use of auxiliary CTs to obtain correct ratio matching is alsopossible, but these CTs must be able to deliver enough voltagenecessary to produce relay operation for internal faults.

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    38/92

    38GE Consumer & Industrial

    Multilin

    1 Nov 14

    Electromechanical High Impedance BusDifferential Relays

    Single phase relays

    High-speed

    High impedance voltage sensing

    High seismic IOC unit

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    39/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    40/92

    Hi h I d M d l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    41/92

    41GE Consumer & Industrial

    Multilin

    1 Nov 14

    High-Impedance Module+

    Overcurrent Relay

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    42/92

    42GE Consumer & Industrial

    Multilin

    1 Nov 14

    Fast, secure and proven

    Requires dedicated CTs, preferably with the same CT ratioand using full tap

    Can be applied to small buses

    Depending on bus internal and external fault currents, high

    impedance bus diff may not provide adequate settings forboth sensitivity and security

    Cannot be easily applied to reconfigurable buses

    Require voltage limiting varistor capable of absorbingsignificant energy

    May require auxiliary CTs

    Do not provide full benefits of microprocessor-based relaysystem (e.g. metering, monitoring, oscillography, etc.)

    High Impedance Bus Protection - Summary

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    43/92

    43GE Consumer & Industrial

    Multilin

    1 Nov 14

    Low-Impedance

    Bus Differential

    Considerations

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    44/92

    44GE Consumer & Industrial

    Multilin

    1 Nov 14

    P-based Low-Impedance Relays

    No need for dedicated CTs

    Internal CT ratio mismatch compensation

    Advanced algorithms supplement percent differential

    protectionfunction making the relay very secure

    Dynamic bus replica (bus image) principle is used inprotection of reconfigurable bus bars, eliminating the need

    for switching physically secondary current circuits

    Integrated Breaker Failure (BF) function can provide

    optimal tripping strategy depending on the actual

    configuration of a bus bar

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    45/92

    45GE Consumer & Industrial

    Multilin

    1 Nov 14

    Up to 24 Current Inputs 4 Zones

    Zone 1 = Phase A Zone 2 = Phase B Zone 3 = Phase C Zone 4 = Not used

    Different CT Ratio Capability forEach Circuit

    Largest CT Primary is Base inRelay

    2-8 Circuit Applications

    Small Bus Applications

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    46/92

    46GE Consumer & Industrial

    Multilin

    1 Nov 14

    Relay 1 - 24 Current Inputs

    4 Zones Zone 1 = Phase A (12 currents) Zone 2 = Phase B (12 currents) Zone 3 = Not used Zone 4 = Not used

    CB 12CB 11

    Different CT Ratio Capability for Each Circuit Largest CT Primary is Base in Relay

    Relay 2 - 24 Current Inputs

    4 Zones Zone 1 = Not used Zone 2 = Not used Zone 3 = Phase C (12 currents) Zone 4 = Not used

    9-12 Circuit Applications

    Medium to Large Bus Applications

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    47/92

    47GE Consumer & Industrial

    Multilin

    1 Nov 14

    Large Bus Applications

    87B phase A

    87B phase B

    87B phase C

    Logic relay

    (switch status,

    optional BF)

    L B A li ti

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    48/92

    48GE Consumer & Industrial

    Multilin

    1 Nov 14

    Large Bus ApplicationsFor buses with up to 24 circuits

    S i E t l C t

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    49/92

    49GE Consumer & Industrial

    Multilin

    1 Nov 14

    Summing External CurrentsNot Recommended for Low-Z 87B relays

    Relay becomes combinationof restrained and unrestrainedelements

    In order to parallel CTs:

    CT performance must be closelymatched

    o Any errors will appear asdifferential currents

    Associated feeders must be radial

    o No backfeeds possible Pickup setting must be raised to

    accommodate any errors

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    50/92

    50GE Consumer & Industrial

    Multilin

    1 Nov 14

    Definitions of Restraint Signals

    maximum of

    geometrical average

    scaled sum of

    sum of

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    51/92

    ff l d h

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    52/92

    52GE Consumer & Industrial

    Multilin

    1 Nov 14

    Bus Differential Adaptive Approach

    ff l d

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    53/92

    53GE Consumer & Industrial

    Multilin

    1 Nov 14

    Bus Differential Adaptive Logic Diagram

    DIFL

    DIR

    SAT

    DIFH

    OR

    AND

    O

    R87B BIASED OP

    AND

    h i i i l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    54/92

    54GE Consumer & Industrial

    Multilin

    1 Nov 14

    Phase Comparison Principle Internal Faults:All fault (large) currents are approximately in

    phase.

    External Faults:One fault (large) current will be out of phase

    No Voltages are required or needed

    Secondary Current ofFaulted Circuit

    (Severe CT Saturation)

    h i i i l i d

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    55/92

    55GE Consumer & Industrial

    Multilin

    1 Nov 14

    Phase Comparison Principle Continued

    CT S i

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    56/92

    56GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation

    Fault starts at t0, CT begins to saturate at t1 CT fully saturated at t2

    t0

    t1

    t2

    CT S t ti D t t St t M hi

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    57/92

    57GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation Detector State Machine

    NORMAL

    SAT := 0

    EXTERNAL

    FAULT

    SAT := 1

    EXTERNAL

    FAULT & CT

    SATURATION

    SAT := 1

    The differential

    characteristic

    entered

    The differential-

    restraining trajectory

    out of the differential

    characteristic for

    certain period of time

    saturation

    condition

    The differential

    current below the

    first slope for

    certain period of

    time

    CT S t ti D t t O ti

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    58/92

    58GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation Detector OperatingPrinciples

    The 87B SAT flag WILL NOTbe set during internal faults,regardless of whether or not any of the CTs saturate.

    The 87B SAT flag WILLbe set during external faults,

    regardless of whether or not any of the CTs saturate. By design, the 87B SAT flag WILLforce the relay to use

    the additional 87B DIR phase comparison for Region 2

    The Saturation Detector WILL NOT Block the Operation ofthe Differential Element it will only Force 2-out-of-2Operation

    CT S t ti D t t E l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    59/92

    59GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation Detector - Examples The oscillography records on the next two slides were captured from a

    B30 relay under test on a real-time digital power system simulator

    First slide shows an external fault with deep CT saturation (~1.5 msec ofgood CT performance)

    o SAT saturation detector flag asserts prior to BIASED PKP busdifferential pickup

    o DIR directional flag does not assert (one current flows out of zone),so even though bus differential picks up, no trip results

    Second slide shows an internal fault with mild CT saturation

    o BIASED PKP and BIASED OP both assert before DIR asserts

    o CT saturation does not block bus differential

    More examples available (COMTRADE files) upon request

    CT S t ti E l E t l F lt

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    60/92

    60GE Consumer & Industrial

    Multilin

    1 Nov 14

    Despite heavy CTsaturation theexternal fault currentis seen in theopposite direction

    CT Saturation Example External Fault

    0.06 0.07 0.08 0.09 0.1 0.11 0.12-200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    time, sec

    current,A

    ~1 ms

    CT S t ti I t l F lt E l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    61/92

    61GE Consumer & Industrial

    Multilin

    1 Nov 14

    CT Saturation Internal Fault Example

    A l i L I d Diff ti l

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    62/92

    62GE Consumer & Industrial

    Multilin

    1 Nov 14

    Applying Low-Impedance DifferentialRelays for Busbar Protection

    Basic Topics

    Configure physical CT Inputs

    Configure Bus Zone and Dynamic Bus Replica

    Calculating Bus Differential Element settingsAdvanced Topics

    Isolator switch monitoring for reconfigurable buses

    Differential Zone CT Trouble

    Integrated Breaker Failure protection

    C fi i CT I t

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    63/92

    63GE Consumer & Industrial

    Multilin

    1 Nov 14

    Configuring CT Inputs

    For each connected CT circuit enter Primary rating andselect Secondary rating.

    Each 3-phase bank of CT inputs must be assigned to aSignal Source that is used to define the Bus Zone andDynamic Bus Replica

    Some relays define 1 p.u. as the maximumprimary current of all of the CTs connected in the

    given Bus Zone

    Per Unit Current Definition Example

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    64/92

    64GE Consumer & Industrial

    Multilin

    1 Nov 14

    Per-Unit Current Definition - Example

    CurrentChannel

    Primary Secondary Zone

    CT-1 F1 3200 A 1 A 1

    CT-2 F2 2400 A 5 A 1

    CT-3F3 1200 A 1 A 1

    CT-4 F4 3200 A 1 A 2

    CT-5 F5 1200 A 5 A 2

    CT-6 F6 5000 A 5 A 2

    For Zone 1, 1 p.u. = 3200 AP

    For Zone 2, 1 p.u. = 5000 AP

    Configuration of Bus Zone

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    65/92

    65GE Consumer & Industrial

    Multilin

    1 Nov 14

    Configuration of Bus Zone

    Dynamic Bus Replica associates a status signal with each

    current in the Bus Differential Zone Status signal can be any logic operand

    o Status signals can be developed in programmable logicto provide additional checks or security as required

    o Status signal can be set to ON if current is always in thebus zone or OFF if current is never in the bus zone

    CT connections/polarities for a particular bus zone must beproperly configured in the relay, via either hardwire or

    software

    Configuring the Bus Differential Zone

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    66/92

    66GE Consumer & Industrial

    Multilin

    1 Nov 14

    Configuring the Bus Differential Zone

    1. Configure the physical CT Inputs

    o CT Primary and Secondary values

    o Both 5 A and 1 A inputs are supported by the UR hardware

    o Ratio compensation done automatically for CT ratio differences up to 32:1

    2. Configure AC Signal Sources3. Configure Bus Zone with Dynamic Bus Replica

    Bus Zone settings defines the boundaries of the Differential

    Protection and CT Trouble Monitoring.

    Dual Percent Differential Characteristic

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    67/92

    67GE Consumer & Industrial

    Multilin

    1 Nov 14

    Dual Percent Differential Characteristic

    HighBreakpoint

    Low

    Breakpoint

    Low Slope

    High Slope

    High Set

    (Unrestrained)

    Min Pickup

    Calculating Bus Differential Settings

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    68/92

    68GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Bus Differential Settings The following Bus Zone Differential element parameters need to be set:

    o Differential Pickup

    o Restraint Low Slope

    o Restraint Low Break Point

    o Restraint High Breakpoint

    o Restraint High Slope

    o Differential High Set (if needed)

    All settings entered in per unit (maximum CT primary in the zone)

    Slope settings entered in percent

    Low Slope, High Slope and High Breakpoint settings are used by the CTSaturation Detector and define the Region 1 Area (2-out-of-2 operation

    with Directional)

    Calculating Bus Differential Settings

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    69/92

    69GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Bus Differential Settings Minimum Pickup

    Defines the minimum differential current required foroperation of the Bus Zone Differential element

    Must be set above maximum leakage current not zoned offin the bus differential zone

    May also be set above maximum load conditions for addedsecurity in case of CT trouble, but better alternatives exist

    Calculating Bus Differential Settings

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    70/92

    70GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Bus Differential Settings Low Slope

    Defines the percent bias for the restraint currents fromIREST=0 to IREST=Low Breakpoint

    Setting determines the sensitivity of the differential element

    for low-current internal faults Must be set above maximum error introduced by the CTs in

    their normal linear operating mode

    Range: 15% to 100% in 1%. increments

    Calculating Bus Differential Settings

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    71/92

    71GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Bus Differential Settings Low Breakpoint

    Defines the upper limit to restraint currents that will bebiased according to the Low Slope setting

    Should be set to be above the maximum load but not morethan the maximum current where the CTs still operatelinearly (including residual flux)

    Assumption is that the CTs will be operating linearly (nosignificant saturation effects up to 80% residual flux) up tothe Low Breakpoint setting

    Calculating Bus Differential Settings

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    72/92

    72GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Bus Differential Settings High Breakpoint

    Defines the minimum restraint currents that will be biasedaccording to the High Slope setting

    Should be set to be below the minimum current where the

    weakest CT will saturate with no residual flux Assumption is that the CTs will be operating linearly (no

    significant saturation effects up to 80% residual flux) up tothe Low Breakpoint setting

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    73/92

    Calculating Unrestrained Bus Differential

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    74/92

    74GE Consumer & Industrial

    Multilin

    1 Nov 14

    Calculating Unrestrained Bus DifferentialSettings

    Defines the minimum differential current for unrestrainedoperation

    Should be set to be above the maximum differential currentunder worst case CT saturation

    Range: 2.00 to 99.99 p.u. in 0.01 p.u. increments

    Can be effectively disabled by setting to 99.99 p.u.

    Dual Percent Differential Characteristic

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    75/92

    75GE Consumer & Industrial

    Multilin

    1 Nov 14

    Dual Percent Differential Characteristic

    HighBreakpoint

    Low

    Breakpoint

    Low Slope

    High Slope

    High Set

    (Unrestrained)

    Min Pickup

    Reconfigurable Buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    76/92

    76GE Consumer & Industrial

    Multilin

    1 Nov 14

    Protecting re-configurable buses

    Reconfigurable Buses

    Reconfigurable Buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    77/92

    77GE Consumer & Industrial

    Multilin

    1 Nov 14

    Protecting re-configurable buses

    Reconfigurable Buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    78/92

    Reconfigurable Buses

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    79/92

    79GE Consumer & Industrial

    Multilin

    1 Nov 14

    Protecting re-configurable buses

    Reconfigurable Buses

    Isolators

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    80/92

    80GE Consumer & Industrial

    Multilin

    1 Nov 14

    Isolators Reliable Isolator Closed signals are needed for the Dynamic

    Bus Replica

    In simple applications, a single normally closed contact maybe sufficient

    For maximum safety:o Both N.O. and N.C. contacts should be used

    o Isolator Alarm should be established and non-valid combinations(open-open, closed-closed) should be sorted out

    o Switching operations should be inhibited until bus image is recognizedwith 100% accuracy

    o Optionally block 87B operation from Isolator Alarm

    Each isolator position signal decides:o Whether or not the associated current is to be included in the

    differential calculations

    o Whether or not the associated breaker is to be tripped

    Isolator Typical Open/Closed

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    81/92

    81GE Consumer & Industrial

    Multilin

    1 Nov 14

    Isolator Typical Open/ClosedConnections

    Switch Status Logic and Dyanamic Bus

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    82/92

    82GE Consumer & Industrial

    Multilin

    1 Nov 14

    Isolator OpenAuxiliaryContact

    Isolator ClosedAuxiliaryContact

    Isolator Position Alarm Block Switching

    Off On CLOSED No No

    Off Off LAST VALID After time delayuntilacknowledged

    Until IsolatorPosition is valid

    On On CLOSED

    On Off OPEN No No

    NOTE: Isolator monitoring function may be a built-in feature or user-programmable in low impedance bus differential digital relays

    Replica

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    83/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    84/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    85/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    86/92

    Example Architecture Dynamic Bus

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    87/92

    87GE Consumer & Industrial

    Multilin

    1 Nov 14

    Phase AAC signals wiredhere, bus replica configuredhere

    Phase BAC signals wiredhere, bus replica configuredhere

    Phase CAC signals wiredhere, bus replica configured

    here

    Auxuliary switches wired here;

    Isolator Monitoring function

    configured here

    p yReplica and Isolator Position

    Example Architecture BF Initiation &

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    88/92

    88GE Consumer & Industrial

    Multilin

    1 Nov 14

    Phase AAC signals wiredhere, current statusmonitored here

    Phase BAC signals wiredhere, current statusmonitored here

    Phase CAC signals wiredhere, current status

    monitored here

    Breaker Failureelements configuredhere

    Example Architecture BF Initiation &Current Supervision

    Example Architecture Breaker Failure

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    89/92

    89GE Consumer & Industrial

    Multilin

    1 Nov 14

    Phase AAC signals wiredhere, current statusmonitored here

    Phase BAC signals wiredhere, current statusmonitored here

    Phase CAC signals wiredhere, current status

    monitored here

    Breaker Fail Op commandgenerated here and send to tripappropriate breakers

    Trip

    TripTrip

    Example Architecture Breaker FailureTripping Trip

    IEEE 37.234

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    90/92

    90GE Consumer & Industrial

    Multilin

    1 Nov 14

    IEEE 37.234

    Guide for Protective Relay Applications to PowerSystem Buses is currently being revised by the K14Working Group of the IEEE Power System RelayingCommittee.

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    91/92

  • 8/10/2019 Tema 07 - High Low Impedance Busbar Protection 092

    92/92


Recommended