+ All Categories
Home > Documents > Temperature Control Lab Report Muz

Temperature Control Lab Report Muz

Date post: 08-Jan-2016
Category:
Upload: ahmad-muzammil
View: 329 times
Download: 0 times
Share this document with a friend
Description:
Temperature Control Lab reportON OFF Control SystemHeat ExchangerUniKL MICETProcess Dynamics & Control

of 18

Transcript
  • 1""

    PROCESS DYNAMICS & CONTROL

    CPB 30004

    TEMPERATURE CONTROL

    LAB REPORT

    AHMAD MUZAMMIL BIN IDRIS

    55201113653

  • 2""

    1.0 OBJECTIVES

    1. To identify the major components of the heat exchanger process control training

    system.

    2. To systematically start-up the process.

    3. To study ON/OFF temperature control of electric heaters.

    4. To study temperature control in the heat exchanger using PID controller.

    2.0 SUMMARY

    The experiment was conducted to determine the main objective which is to identify

    the major components of the heat exchanger process control training system and learn how to

    start-up the process systematically. Moreover, the experiment were run to study ON/OFF

    temperature control of electric heaters and finally the temperature control in the heat

    exchanger using PID controller. Based on the theory, the main purpose of a heat exchanger

    system is to transfer heat from a hot fluid to a cooler fluid, so temperature control of outlet

    fluid is of prime importance. It also functions to control the temperature of outlet fluid of the

    heat exchanger system by using a conventional PID controller. The designed controller

    regulates the temperature of the outgoing fluid to a desired set point in the shortest possible

    time irrespective of load and process disturbances, equipment saturation and nonlinearity.

    Hence, there are few types of heat exchanger that works on its own design. The experiment

    was begun with the filling up both the tank until it overflows and certain valves were opened

    and shut according to the procedure. Next, the set point, PBI, TII and TDI was set and

    changed accordingly until the experiment end. (tambah pasal discussion main points) The

    result was recorded using the recorder in the PID controller and results were tabulated in

    chart paper. Based on the discussion, the green and red pen played an important role. Finally,

    the objective of doing this experiment was achieved but some recommendation such as

    having good knowledge on control prior of conducting the experiment will be a good value to

    avoid misconduct during the experiments.

  • 3""

    3.0 INTRODUCTION AND THEORY

    Heat exchanger system is widely used in chemical plants because it can sustain wide

    range of temperature and pressure. The main purpose of a heat exchanger system is to

    transfer heat from a hot fluid to a cooler fluid, so temperature control of outlet fluid is of

    prime importance. To control the temperature of outlet fluid of the heat exchanger system a

    conventional PID controller can be used. Due to inherent disadvantages of conventional

    control techniques, model based control technique is employed and an internal model based

    PID controller is developed to control the temperature of outlet fluid of the heat exchanger

    system. The designed controller regulates the temperature of the outgoing fluid to a desired

    set point in the shortest possible time irrespective of load and process disturbances,

    equipment saturation and nonlinearity. The developed internal model based PID controller

    has demonstrated 84% improvement in the overshoot and 44.6% improvement in settling

    time as compared to the classical controller.

    A shell-and-tube exchanger is used for larger flows, which are very common in

    chemical process industries. The design of this exchanger is a shell with a bundle of tubes

    inside. The tubes are in parallel and a fluid flows around them in the shell. Each arrangement

    allows for a different type of flow such as co-current, counter-current and cross flow. The

    tube-side can have one or more passes to increase the energy exchange from the tube-side

    fluid. The shell-side may contain baffles, or walls, that channel the fluid flow and induce

    turbulence, and thus, increase energy exchange.

    Figure 3.1: Shell and Tube Heat Exchanger Controller System in Industry

  • 4""

    Heat exchanger find widespread used in refrigeration, power generation, heating and

    air-conditioning, chemical process, manufacturing, and medical application. A heat is

    installed in an extension of the double pipe configuration. Instead of single pipe within a

    larger pipe, a heat exchanger consists of bundles of pipes or tubes enclosed within a

    cylindrical shell. In the heat exchanger one fluid flows through a tubes and a second fluid

    flows through within the space between the tubes and the shell.

    The outlet temperature of the heat exchanger system has to be kept at a desired set

    point according to a process requirement. Firstly a classical PID controller is implemented in

    a feedback control loop so as to achieve the control objectives. PID controllers exhibits high

    overshoot which is undesirable. To reduce the overshoot and optimize the control

    performance, a feed forward controller is used along with a feedback controller. The

    combined effect of feedback and feed forward control schemes gives a much better result

    than the feedback PID controller.

    Figure 3.2: ON/OFF Controller working scheme to achive Set Point (SV).

  • 5""

    4.0 RESULTS AND DISCUSSIONS

    The purpose of this experiment are to identify the major components of the

    heat exchanger process control training system, to systematically start-up the process, to

    study ON/OFF temperature control of electric heaters and to study temperature control in the

    heat exchanger using PID controller. For the first objective, the process consist of two tanks,

    T61 and T62, one shell and tube heat exchanger, three centrifugal pump, (P61, P62, P611),

    and resistance temperature detector (RTD) as a temperature detector for T61 while

    thermocouple is temperature sensor for T62. The heat exchanger used hot water from tank,

    T62 as a heating medium to heat cold water from tank, T61. In this experiment also, the green

    line indicated the temperature of the flowrate while the red line indicated wall of the heater

    temperature.The results obtained while conducting this experiment can be divided into two

    parts which were ON/OFF temperature control and PID control of temperature.

    4.1 START-UP PROCESS

    During the start up procedures (No 3.2 according to Lab Manual), the manual (M)

    mode of manipulated value (MV) was 100% has been set with the value of proportional band

    (PB1) was 15%, the time integral (TI1) was 35 seconds and the time derivative (TD1) was 8

    seconds. The set value (SV) or simply set point was 40C and the chart speed was ensured at

    500!!!! . By referring to the graph, green line indicated the temperature of TE62 whilst the red line indicated TE61 temperature.

    Basically, the control valve TCV 61 is Air-to-Open and has a current-to-air positioner

    (EP), in which it was tagged as TCY61 in the plant. Air to open valves is normally held

    closed by the spring and require air pressure (a control signal) to open them - they open

    progressively as the air pressure increases. Then, a test on control valve, TCV61 has been

    done by adjusting the MV values. When MV = 25%, 50% and 100% opened, the control

    valve, TCV61 stem position are also opened according to MV adjustments. Figure 4.1 shows

    a pneumatic Actuator, Air to Open and the position of Stem that will drive the position

    indicator to shows the value of MV.

  • 6""

    Figure 4.1 : Pneumatic Actuator with Air-to-Open function.

    4.2 ON/OFF TEMPERATURE CONTROL

    In this experiment, there are two types of controller that we study which is ON/OFF

    controller of heater, and the heat exchanger controller using PID controller. Firstly, the

    ON/OFF temperature controller of heater experiment is performed. The equipment was tested

    by running some trial in order to ensure it runs in a good condition. Besides that, it help a

    better understanding on how an ON/OF controller functions; the function of controller in

    order to maintain the set point.

    For ON/OFF temperature control, the heater will be turned on till it reaches the set

    point of 40C. Then, the heater will be switched off when the temperature went above the set

    point temperature that was 40C. Due to the tank is an open tank, thus the temperature will

    drop. Thus, the heater will then be switched on when the temperature was 0.5C less than the

    set point which also known as Deadband. Figure 4.2 explains the theory of deadband.

  • 7""

    The parameters of the ON/OFF controller were then set up at high temperature limit

    as shown in Table 4.1 in which (PO1) equal to 55C same as the high limit for annunciator

    TAH62 (PO3) and the dead band (PO2) indicated 0.5C same as the dead band for

    annunciator TAH61 (PO4). The I/O data showed that the value of X2 was 44.3 with DO2 was

    off (0) and DO1 (1) was on position. The data and the graph were shown below as in figure

    4.3.

    Figure 4.2: Deadband in a temperature operating control system

    Table 4.1: The PT Register value set up (According to Lab Manual, 3.3 No. 4)

    PT Register Temperature value

    PO1 (high temperature limit) 55 oC

    PO2 (dead band) 0.5 oC

    PO3 (high limit for annunciator) 55 oC

    PO4 (dead band for annunciator) 0.5 oC

    Table 4.2: The I/O Data recorded

    I/O Data

    Status X2

    TIC62 Controller DO1: 0 55 oC

    TAH62, Annunciator DO2: 1 55 oC

  • 8""

    The graph are represented in Figure 4.3. No 1 marked in the graph shows that the

    recorder TR61 has been started. During this process (Refer Lab Manual- 3.3 No. 6), TE62 or

    TIT62 rises and exceeds the High Limit, 55C. When the temperature go above 55C, the

    heaters are noted to be switched off and the Annunciator TAH62 is activated (with alarm

    sounds). This indicates the temperature that already exceeds the highest point that has been

    set in the system, 55C. Then, temperature drops to the High Limit Temperature, 55C. The

    temperature drops further by an amount equal to deadband which is 0.5C (drops 0.5C

    below high limit), this is representated as No. 2 in the graph. In this stage, the heaters are

    switched on again. The temperature will rise till it reaches the High Limit of 55C and

    exceeds further. When it exceeds the high limit, (56C) the annunciator will sounds and

    TAH62 is switched OFF by pressing the acknowledge button on the control panel. The

    status and the I/O Data has been recorded in Table 4.2.

    The process continues in the same mode as shown in graph, a full of 3 cycles with

    decay ratio (the measure of the amount by which the controlled variable exceeds the set-point

    in successive peaks) is achieved and indicated as No. 3 (56C), No. 4 (57C) and No. 5

    (56C) on the graph in Figure 4.3. It produces an oscillatory curve which is the nature of

    ON/OFF controller as shown in Figure 3.2.

    Basically, an On-Off control is like operating a switch. This type of temperature

    controller will turn on the heat when the process variable is below the set point and turn it off

    when the process variable is above the set point. These controllers normally include a delay,

    hysterisis and or a cycle time to reduce the cycling or "hunting" when the process variable is

    close to the set point.

  • 9""

    Figure 4.3: The graph produced for ON/OFF controller.

    4.3 PID CONTROL OF TEMPERATURE

    For this experiment, the temperature of heated product at the exit of the heat

    exchanger measured by TE61/TIT61 is controlled by the controller PID of TIC61.

    On the temperature controller using the PID, the auto mode is being selected. The first

    point is set at 40C and the PID values are recorded in Table 4.3.

    Table 4.3: First Controller Parameters Values

    PID PB1 (%) TI1 (seconds) TD1

    (seconds)

    Product

    Flowrate

    (FI61) (!!!") Setpoint

    (SV1) (C)

    First Trial

    PID

    15 35 8 1.3 40

  • 10""

    By referring to the graph in Figure 4.4, noted as No. 1 was the time during the chart

    start to record. Where as, No. 2 indicates the observation on response of TE61/TIT61 as it

    becomes steady around 40C when the Auto mode has been activated with the PID values

    from Table 4.3. The process response smoothly in short period of time.

    Since this process use all three control algorithms (PID) together, this process can be explained:

    ! Achieve rapid response to major disturbances with derivative control

    ! Hold the process near setpoint without major fluctuations with proportional control

    ! Eliminate offset with integral control

    Then, the process maintain at 40C steadily as indicated No. 3 on the graph in Figure 4.4.

    For the second temperature controller in heat exchanger, initially the cold water

    circulation was started up. Then, the mode will be changed into Auto (A) mode. Two test

    disturbances were being conducted; set point change and load change.

    Set point change has been done according to Lab Manual, 3.4 No. 5. The second Set

    point and PID trial values has been key in on the control panel as shown in Table 4.4. Where

    as, by referring the graph in Figure 4.4, its noted as No. 4. Since this is a temperature

    operating process, thus a small dead time is encountered at No. 4 before it become steady at

    new setpoint, 42C at No.5 on the graph in Figure 4.4.

    Table 4.4: Second Controller Parameters Values

    PID PB1 (%) TI1 (seconds) TD1

    (seconds)

    Product

    Flowrate

    (FI61) (!!!") Setpoint

    (SV2) (C)

    Second Trial

    PID

    10 30 7 2.8 42

    Then, as the system maintained in steady state, the step change of the product flow

    rate by opeing fully the MV61 has been done. The flowrate at FI61 has been noted was at 2.8

    m3/hr. This was noted as No. 6 in the graph in Figure 4.4. The temperature drops to almost

    40C before becomes steady again as indicated as No. 7 in the graph in Figure 4.4.

  • 11""

  • 12##

    One of the temperature sensor elements used in this system was, Platinum thin film

    RTD temperature sensor elements. The surface of thin film RTD temperature sensor element

    is coated with ceramic, so the element can withstand high voltage and show high insulation

    resistance.

    4.4 CONTROL ALGORITHMS FOR DIFFERENT PROCESS VARIABLES

    Figure 4.5: Control Algorithms for a few Controlled Variables.

    The heat transfer process is generally a slow and a low gain process compared to flow

    or level processes. This is also can be explained that, the processes with heat transfer has a

    high chance to produce dead time and decay ratio. Because of the time required to change the

    temperature of a process fluid (time taken for the heat to be transferred from the heating

    medium to the fluid), temperature loops tend to be relatively slow. Feedforward control

    strategies are often used to increase the speed of the temperature loop response. RTDs or

    thermocouples are typical temperature sensors. Temperature transmitters and controllers are

    used, although it is not uncommon to see temperature sensors wired directly to the input

    interface of a controller.

    Where as, flow and level control loops are regarded as fast loops that respond to

    changes quickly, since they are dealing with heat transfer, rather only with mass transfer.

    Therefore, flow control equipment must have fast sampling and response times.

    Furthermore, by referring to Figure 4.5, its stated that the one and only process that

    uses all three algorithm was temperature process/controlled variable. Nevertheless, only

    temperature variable uses derivative algorithm and not the flow or level control. This is due

    temperature variable are very slow response. Thus Derivative algorithm are needed to apply

    an immediate response that is equal to the proportional plus reset action that would have

    occurred in the process.

    Controller Algorithms and Tuning

    Controller Algorithms

    Fundamentals of Control 45 2006 PAControl.com

    ActivitiesProportional, PI, and PID ControlBy using all three control algorithms together, process operators can: Achieve rapid response to major disturbances with derivative

    control Hold the process near setpoint without major fluctuations with

    proportional control Eliminate offset with integral control

    Not every process requires a full PID control strategy. If a small offset has no impact on the process, then proportional control alone may be sufficient.

    PI control is used where no offset can be tolerated, where noise(temporary error readings that do not reflect the true process variable condition) may be present, and where excessive dead time (time after a disturbance before control action takes place) is not a problem.

    In processes where no offset can be tolerated, no noise is present, and where dead time is an issue, customers can use full PID control. Table 7.2 shows common types of control loops and which types of control algorithms are typically used.

    ControlledVariable

    Proportional Control PI Control PID Control

    Flow Yes Yes No

    Level Yes Yes Rare

    Temperature Yes Yes Yes

    Pressure Yes Yes Rare

    Analytical Yes Yes Rare

    Table 7.2: Control Loops and Control Algorithms

    14. What type of control is used in an application where noise is present, but where no offset can be tolerated?

    P onlyPDPIPID

    1

    2

    3

    4

    COMPLETE WORKBOOK EXERCISE - CONTROLLER ALGORITHMS AND TUNING

    www.PAControl.com

  • 13##

    With integral action, the controller output is proportional to the amount of time the

    error is present. Integral action eliminates offset.

    Figure 4.6: P, I and D controllers to show the response against Process Variable.

    It can be noted that the offset (deviation from set-point) in the time response plots is

    has gone. Integral action has eliminated the offset. The response is somewhat oscillatory and

    can be stabilized some by adding derivative action. (Graphic courtesy of ExperTune Loop

    Simulator.)

    Integral action gives the controller a large gain at low frequencies that results in

    eliminating offset and "beating down" load disturbances. The controller phase starts out at

    90 degrees and increases to near 0 degrees at the break frequency. This additional phase lag is

    what you give up by adding integral action. Derivative action adds phase lead and is used to

    compensate for the lag introduced by integral action.

    Where as, with derivative action, the controller output is proportional to the rate of

    change of the measurement or error. The controller output is calculated by the rate of change

    of the measurement with time. Some manufacturers use the term rate or pre-act instead of

    derivative. Derivative, rate, and pre-act are the same thing.

    DERIVATIVE = RATE = PRE ACT

  • 14##

    Derivative action can compensate for a changing measurement. Thus derivative takes

    action to inhibit more rapid changes of the measurement than proportional action. When a

    load or set-point change occurs, the derivative action causes the controller gain to move the

    "wrong" way when the measurement gets near the set-point. Derivative is often used to avoid

    overshoot. Derivative action can stabilize loops since it adds phase lead. Generally, if

    derivative action was used, more controller gain and reset can be used.

    Figure 4.7: Phase degree and Amplitude Ratio for Derivative and Integral

    With a PID controller the amplitude ratio now has a dip near the center of the

    frequency response. Integral action gives the controller high gain at low frequencies, and

    derivative action causes the gain to start rising after the "dip". At higher frequencies the filter

    on derivative action limits the derivative action. At very high frequencies (above 314

    radians/time; the Nyquist frequency) the controller phase and amplitude ratio increase and

    decrease quite a bit because of discrete sampling. If the controller had no filter the controller

    amplitude ratio would steadily increase at high frequencies up to the Nyquist frequency (1/2

    the sampling frequency). The controller phase now has a hump due to the derivative lead

    action and filtering.

  • 15##

    Valve positioners compare a control signal to a valve actuators position and move the

    actuator accordingly. They are used with both linear valves and rotary valves. Valve

    positioners are used when the 0.2 to 1 bar pressure in the diaphragm chamber is not able to

    cope with friction and high differential pressures. The positioner is fitted to the yoke of the

    actuator and is linked to the spindle of the actuator by a feedback arm in order to monitor

    valve position. When a control signal differs from the valve actuators position, the valve

    positioner sends the necessary power to move the actuator until the correct position is

    reached. This uses a high air supply.

    Figure 3: shows the temperature and heat output in a room controlled by an ON/OFF

    controller. In practice the use of ON/OFF control can cause problems. As can be seen in

    Figure 2, the heating system rapidly switches ON an OFF leading to inefficient system

    operation and increased mechanical wear.

    Figure 2: ON/OFF control of air temperature.

    upper set point OFF

    lower set point ON

    oC

    ON

    oC

    ON

    OFF

    ON

    OFF

    OFF

  • 16##

    Figure 3: ON/OFF control with a dead band

    To address this deficiency a 'dead band' may be introduced. Effectively this defines an upper

    and lower set-point. The control mechanism is now as summarised in Figure 3:

    if the sensed temperature is below the lower set-point then the heating system is ON;

    if the sensed temperature rises above the lower set-point but is still below the upper set-

    point then the heating system is ON;

    if the sensed temperature is above the upper set-point then the heating system is OFF; and

    if the sensed temperature falls below the upper set-point but is still above the lower set-

    point then the heating system is ON.

    The addition of the upper and lower set-points acts to reduce the frequency of the plant

    switching at the expense of poorer control of the controlled variable (here temperature).

    ON/OFF control offers a crude means of controlling conditions in a building and is typically

    employed where close control is not required, e.g. temperature control of domestic boilers.

    Qmax

    heat output room air temperature

    set point temp.

    oC

  • 17##

    5.0 CONCLUSION

    The experiment conducted meet the objective as were discussed earlier. The entire

    four objectives were achieved and discussed with the accordance in theory of process control.

    6.0Recommendation

    As a recommendation, using more advance or intelligent machine can help to get

    accurate and better result. Especially the recorder, by using more computational and visualize

    to show the pattern of the response it would be much easier; the response can be record using

    software or cds so that the students do not have to use paper to record because the papers got

    stucked. Besides, students that handle the machine should get the overview how the machine

    running and also should have some basic knowledge to obtain a correct reading. Mainly, the

    chart paper should be placed correctly in order to avoid error during the recording.

    Furthermore, during the changes of set point and other related parameters the student should

    jot down for discussion purpose and their understanding. Ensure all the valves are closed and

    opened as mentioned in the methodology. Set Point change for ON/OFF controller should be

    added in the experiment change as well as the PID Controller system, and both types of

    control system should be discussed to show the major difference of both control systems.

  • 18##

    REFERENCES

    Yuvraj, B.K, and Yaduvir, S. (2010). PID Control of Heat Exchanger System, International

    Journal of Computer Applications, 22-23.

    Mark, J.W. (1999). Some Conventional Pocess Control Schemes, Department of Chemical

    and Process Engineering University of Newcastle, 2-5.

    Process Control, 2012. [pdf].

    Available at: [Accessed 4

    September 2012]


Recommended