HVAC Energy Flow in Buildings Charles H. Culp, P.E., Ph.D., FASHRAE, LEED-AP Professor, Department of Architecture Associate Director, Energy Systems Lab Texas A&M University
Transcript
Page 1: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

HVAC Energy Flow in Buildings

Charles H. Culp, P.E., Ph.D., FASHRAE, LEED-APProfessor, Department of Architecture Associate Director, Energy Systems Lab

Texas A&M University

Page 2: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Goals• View a building’s energy flow • Differences between commercial and residential buildings• Building HVAC equipment• Comfort considerations• Health considerations• Limits of building efficiency • Advances in new buildings• Advances in improving existing buildings

Page 3: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Radiation

Infiltration

Ground Conduction

Exfiltration and Exhaust

Solar

QClimateSensitive = QSolar + QWeather + QOutsideAir+ QGround

The Climate Sensitive load is the sum of:

AC

WeatherTemperatureRH…

Outside AirVentilation

Building Energy Flow

Page 4: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Infiltration

Ground Conduction

Exfiltration and Exhaust

QInternal = QPeople + QLights + QPlug

The Internal load is the sum of:

Solar

AC

WeatherTemperatureRH…

Outside AirVentilation

Building Energy Flow

Page 5: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Infiltration

Ground Conduction

Exfiltration and Exhaust

QTotal = QClimateSensitive + QInternal

The Total load is the sum of:

Solar

AC

WeatherTemperatureRH…

Outside AirVentilation

Building Energy Flow

Page 6: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Infiltration

Ground Conduction

Exfiltration and Exhaust

QTotal = QClimateSensitive + QInternal

The Total load is the sum of:

Solar

WeatherTemperatureRH…

Outside AirVentilation

Building Energy Flow

Page 7: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Radiation

Ground Conduction

Exhale / Inhale

Solar

The Climate Sensitive heat load is the sum of:

QClimateSensitive = QSolar + QWeather + QOutsideAir+ QGround

WeatherTemperatureRH…

Outside AirVentilation

Personal Energy Flow

Page 8: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Radiation

Ground Conduction

Exhale / Inhale

Solar

The Internal heat load is the sum of:

QInternal = QSensible + QLatent

Sensible

Latent

WeatherTemperatureRH…

Personal Energy Flow

Page 9: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Conduction

ConvectionEvaporation

if wet

Radiation

Ground Conduction

Exhale / Inhale

Solar

The Total heat load is the sum of:

Sensible

Latent

QTotal = QClimateSensitive + QInternal

Personal Energy Flow

Page 10: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Heat Flow• HVAC changes heat flows

• Move heat to outside in summer

Outdoor Unitbasc.pnnl.gov

Heat Pump – Summer Cooling

Indoor Unit Suction Line

Liquid Line

Page 11: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Heat Flow• HVAC changes heat flows

• Move cold to outside in winter

Outdoor Unitbasc.pnnl.gov

Heat Pump – Winter Heating

Indoor Unit Suction Line

Liquid Line

Page 12: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

• A Residential Systems Contains• Recycles indoor air (where does fresh air come from?)• Cooling

• Compressor• Evaporator• Condenser• Expansion device• Fan• Ducts and registers• Filter(s)

• Heating• Above + • Burner• Heat exchanger

HVAC - Residential

Page 13: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Psychrometric Chart• Variables of Interest

• Temperature• Impacts comfort• Influences condensation

• Relative Humidity• Can calculate dew point from relative humidity/temperature• Want inside temperature higher than dew point of outside air

• Humidity Ratio• Ratio of lbs of H2O to lbs of dry air

Page 14: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Temperature

40 50 60 70 80 90 100 110 ºF

Page 15: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Relative Humidity

40%

20%

60%80%

100%

50%

Page 16: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Humidity Ratio

0.009

0.006

0.003

0.018

0.015

0.012

0.027

0.024

0.021

Page 17: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

TemperatureHumidity RatioRelative Humidity

0.009

0.006

0.003

0.018

0.015

0.012

0.027

0.024

0.021

40

20

6080

100

50

40 50 60 70 80 90 100 110 ºF

Page 18: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Residential• Asthma

• Incidence1,2

• 2008 – 2.8%• 1996 – 0.6%• 1980 – 0.25%• Other refs indicate growth from 2% of the population to

10.6%.

• Costs2

• About $3,300 per person per year

1Asthma incidence: data from the Nat. Health Interview Survey, http://www.ncbi.nlm.nih.gov/pubmed/17365207

2American Academy of Allergy Asthma and Immunology, http://www.aaaai.org/about-the-aaaai/newsroom/asthma-statistics.aspx

Page 19: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Residential

SA (Supply Air)IA (Inside Air) CC

Filter

Attic ducts leak

Negative pressure

inside

Inside75°F50% RH

Summer95°F59% RH~78°F Dew Point

Page 20: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Residential

Summer95°F59% RH~78°F Dew Point

SA (Supply Air)IA (Inside Air) CC

Filter

Attic ducts leak

Negative pressure

inside

Inside75°F50% RH 95°F

85°F

78°F

Page 21: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Residential• Negative Pressure • Positive Pressure

Inside75°F

Inside75°F

Outside95°F

59% RH

Outside95°F

59% RH

Inside75°F50% RH

85°F

85°FInside75°F50% RH

Page 22: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Bad

Inside75°F

Inside75°F50% RH

85°F

Outside95°F

50% RH

95°F

Page 23: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Good

Inside75°F

Outside95°F

50% RH

85°FInside75°F50% RH

Page 24: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Residential

SA (Supply Air)IA (Inside Air) CC

Filter

Attic ducts leak

Adjustablepressure

inside

Inside75°F50% RH

Summer95°F59% RH~78°F Dew Point

Page 25: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Health Indoors - Commercial• Generally positively pressurized• Maintenance is an issue

AHU – Air Handler Unit

Page 26: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

ASHRAE Standard 90.1-2013

• For commercial buildings• Specifies efficiency

requirements for:• Insulation• HVAC• Lighting• Power

• Title: Thermal Environmental Conditions for Human Occupancy

Page 27: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

ASHRAE Standard 62.1-2013

• For commercial buildings• Specifies minimum outside

air • Ventilation Rate Procedure

• People contamination• Building materials

contamination• OA is the Outside Air

required

• Title: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings

Page 28: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

ASHRAE Standard 62.1-2013

• For commercial buildings• Specifies minimum outside

air

• Title: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings

#

2 2

Page 29: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

ASHRAE Standard 55-2013• Title: Thermal Environmental Conditions for

Human Occupancy• Specifies commercial

building comfort requirements

• Provides an evaluation procedure for existing buildings

Page 30: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Personal Comfort• Balance temperature / moisture

• Keep body core temperature at a comfortable level• Sedentary comfort

• Sensible: ~250 Btu/hr• Latent: ~200 Btu/hr

• Active comfort• Sensible: Ranges from 300 to 800+ Btu/hr• Latent: ~250 to 700+ Btu/hr

Page 31: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Personal Comfort• From “Thermal Comfort under Transient

Metabolic and Dynamic Localized Airflow Conditions”• A. Ugursal, PhD Thesis

• Background• Occupant productivity

Seppanen et al. (2004)

Page 32: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Personal Comfort• Three groups of body parts based on

contribution to overall thermal sensation1:• Highest: back, chest, pelvis• Moderately: face, neck, breathing, head, arms, legs• Least: hands, feet

• Measurements

1Zhang (2003)

1: Forehead 2: Cheek 3: Neck 4: Chest 5: Abdomen 6: Upper Back 7: Lower Back 8: Upper Arm

9: Lower Arm 10: Hand 11: Anterior Thigh 12: Anterio-medial

Thigh 13: Anterior Calf 14: Posterior Calf15: Instep

Page 33: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Personal Comfort• Results

• People demand more air even when they feel cool• Pulsed air increased perception of thermal comfort• Draught rating of our test (5%) was significantly lower than the

Standard 55 prediction (16%)

Experimental Chamber

Page 34: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Limits of Building Efficiency• Study done by Claridge and Tanskyi at the ESL • Assumptions

• Comply with ASHRAE energy efficiency, comfort and ventilation standards

• Calibrated building energy use to actual use

ESL Building – 25 kft2 Bullitt Cascadia Center – 52 kft2

Page 35: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Limits of Building Efficiency• Use – kBtu/ft2-yr

• Normal Building: 82 kBtu/ft2-yr • ESL Building: 50 kBtu/ft2-yr • Bullitt Cascadia Center: 16 kBtu/ft2-yr (planned) • “Carnot Limit” Building: 0.73 kBtu/ft2-yr

ESL Building – 25 kft2 Bullitt Cascadia Center – 52 kft2

Page 36: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Limits of Building Efficiency• Demand – kBtu/ft2-yr

• ESL Building: 138 kW summer178 kW winter

• “Carnot Limit” Building: 2.2 kW summer1.6 kW winter

ESL Building – 25 kft2

Page 37: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Residential• Today’s residential buildings

• Get outside air through envelope leakage • Stick built, poor sealing• Lack control

• Typically control on/off to temperature only

• Tomorrow’s residential buildings • Tighter and better insulated

• Sprayed foam is becoming more common• Still 2-times the cost of fiberglass

• Tightness REQUIRES outside air be provided

• Higher performance HVAC • Enthalpy recovery ventilators (ERVs, HRVs) available• New very-high efficiency AC in the lab today

Page 38: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Residential• Enthalpy recovery ventilators (ERVs, HRVs)

available• Existing commercial HRVs deliver 69% or so

effectiveness• HRV in lab delivers 90% effectiveness, ~85%

efficiency

Straight Airfoils Airfoils AvailableChannel Hgt. 0.25” 0.4” 0.5” -Effectiveness 91% ±5% 95% ±5% 81% ±5% 69% ±5%∆P (in-H2O) 0.16 ±0.01 0.11 ±0.01 0.09 ±.01 0.40 ±.01

Page 39: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Residential - Summer• Application of HRVs – 90% Effective

• At 90% effectiveness

• At 69% effectiveness

Fresh air to space

Stale air to outsideOutside air

Exhaust air

Stale Air Out Outside Air Fresh Air Exhaust AirWinter 72°F 42°F 69°F 45°FSummer 78°F 98°F 80°F 96°F

Stale Air Out Outside Air Fresh Air Exhaust AirWinter 72°F 42°F 63°F 51°FSummer 78°F 98°F 84°F 92°F

78°F

96°F

Page 40: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Residential - Winter• Application of HRVs – 90% Effective

• At 90% effectiveness

• At 69% effectiveness

Fresh air to space

Stale air to outsideOutside air

Exhaust air

Stale Air Out Outside Air Fresh Air Exhaust AirWinter 72°F 42°F 69°F 45°FSummer 78°F 98°F 80°F 96°F

Stale Air Out Outside Air Fresh Air Exhaust AirWinter 72°F 42°F 63°F 51°FSummer 78°F 98°F 84°F 92°F

72°F

45°F

Page 41: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Residential• Higher performance HVAC – ARPA-E, Navy

• New very-high efficiency AC in the lab today

• Benefits• Theoretical 60+ SEER with 40+ practical• No refrigerants• Generates clean H2O• Healthier • Also works with commercial buildings• Lab unit is working

Type System COP

First Cost3 Ton Unit

Comfort Operating Cost

Refrigerant ~ 3 to 5 $5K to $8K Med High

Desiccant ~ 4 to 5 $7K to $14K High Very High

Membrane-Evaporative

~ 5 to 18 Initial: $9K to $16KMature: $4K to 8K

High Low

Tech

nolo

gy

Page 42: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Commercial• Today’s commercial buildings

• Typically built to minimum standards• Energy use ranges 40 to 120 kBtu/ft2-yr• Poorly trained operators

• Tomorrow’s commercial buildings • Codes are increasingly stringent

• Will drive better materials, less “all-glass”

• Higher performance HVAC • Enthalpy recovery ventilators (ERVs, HRVs) will be required• Several HVAC improvements moving to marketplace

• Energy and enthalpy wheels, refrigerant compressors, variable flow refrigerant systems, etc.

Page 43: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Improving Commercial• Major opportunity in new and existing

buildings – Controls and Tuning• Existing building commissioning can achieve

• 10% to 20% reduction in total energy use• Translates to a 20% to 40% reduction in HVAC energy use

• 2 to 3 year payback• Healthier building since the controls will work correctly

-$400,000

-$200,000

$0

$200,000

$400,000

$600,000

$800,000

$1,000,000

Nov

-08

Feb-

09

May

-09

Aug

-09

Nov

-09

Feb-

10

May

-10

Aug

-10

Nov

-10

Feb-

11

May

-11

Aug

-11

Nov

-11

Feb-

12Project Timeline

Net Cumulative Savings Cumulative Savings Cumulative Costs

Page 44: Texas A&M University - ARPA-E · 2015-06-03 · ASHRAE Standard 62.1-2013 • For commercial buildings • Specifies minimum outside air • Title: Ventilation and Acceptable Indoor

Summary• Residential buildings

• Need to bring in outside air• Commercial buildings

• Need to be operated well• Improve implementation of controls

• Understand • Temperature• Moisture• Pressurization