    Technical Data

     INDUSTRIAL STEAM 

     BOILERS

    THD-U E 

    THSD-I E 

    Conservation of energy, protection of 

    the environment.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    2/28

    HovalContents

    1-10 500 -

     4000kg/hTHD-U E  Industrial Steam Boiler for Gas and Oil Firing

     Section 1

     2-12 2000 -

     20000kg/hTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

     Section 2

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    3/28

    THD-U E  Industrial Steam Boiler for Oil and Gas Firing

     Description

    Hoval

     Design, Quality & Construction

    The Hoval high output steam boilers

    are constructed from high quality steel

    and are distinguished by their solid,

    robust and flexible design. The Hoval

    boiler combines ease of operation and

    maintenance with optimal efficiency.

    The boiler is designed with all

    necessary inspection doors and is

    constructed for gas or oil firing.

    Construction and production is

    according to EN12953, the Pressure

    Equipment Directive 97/23/EG and CE

    marked. An independent authorised

    institution carries out quality approval

    at our factory. The ISO 9001

    certification and internal quality control

    ensures excellent performance and

    longevity of service. The client receives

    an economical, environmentally friendly

    compact unit, supplied ready for

    installation.

    THD-UE Steam Boiler 

    The THD-UE is a three-pass flame

    tube/flue gas tube boiler with

    reverse flame tube and an inner fully

    water-cooled reversal chamber with

    finned tube wall. The boiler consists of

    a cylindrical shell, two endplates,

    gusset stay supports, the reverse flame

    tube with finned tube wall and single

    pass dimpled flue gas tubes - which

    increase the heat transfer (Hoval

    patent), with low gas side resistance.

    The boiler is completely electrically

    welded and provided with all required

    inspection openings.

    The spacious flame tube with low

    thermal heat release results in excellent

    combustion and low emissions.

    Large water content and steam space

    provides steady state operation.

    • Efficiency of up to 89% and up to

    94.5% with economiser can be

    achieved.

    • Standard design

    pressures of

    11 and 14 barg are

    available. Higher

    pressures can be

    manufactured on

    request.

    Thermal Insulation

    The boiler is fully

    insulated with

    100 mm mineral wool

    insulation. The casing is made of 1mm

    thick stucco aluminum plate with

    neatly trimmed connections and cut-

    outs. The flue gas collector is also

    thermally insulated.

    Valves, Fittings & Sockets

    • Water level regulation and water

    level control

    • Water level indicator (reflex type)

    • Pressure switch for pressure

    regulation and supervision

    • Pressure gauge

    • Main steam valve

    • Safety valve(s)

    • Feed pump, strainer and valves

    • Manual tds

    • Manual double valved

    blowdown/drain

     Boiler assembly 

    2 Heavy construction boiler

    base supports

    1 Instrument tube placed either on

    the right (standard) or on the left

    1 Flue gas collector with integrated

    horizontal flue gas connection,

    cleaning door and integrated

    relief flap

    1 Boiler door for burner mounting,

    thermal insulated and designed

    gas proof, placed on left and

    right hinges for the flue

    gas side cleaning of boiler

    1 Internal feed water distribution pipe

    1 Data plate

    1 Low water mark

    1 Internal steam dryer

    1 Flue gas tube cleaning kit

    Control Panel 

    The control panel is equipped with the

    required controls and indicators for

    control and supervision of the boiler

    and burner. Control switches, indicator

    lights and alarm signals are provided.

    The control panel is supplied to match

    the burner to be used.

     Feed Water Quality 

    Boiler water quality has to be

    respected. Detailed information can be

    found in the appendix.

     Also available

    - Access ladder and platform

    - Second feed water pump

    - Second safety valve

    - Modulating feedwater control

    - Automatic tds blowdown

    - Water sample cooler

    - Automatic timed bottom blowdown

    - Removable cladding sections

    - Economiser

    - Customised control panel

    - Remote system monitoring and

    controls

    - Variable speed motor controls

    - Hotwell and blowdown vessels

    - Termed maintenance contracts

    1-1

    Hoval

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    4/28

    HovalTHD-U E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THD-U E without and with economiser 500-1500

    Technical data boiler without economiser (based on 10 barg working pressure)

    Model 500 650 800 1000 1200 1500

    Steam rating kg/h 500 650 800 1000 1200 1500

    Operating output kW 326 423 521 651 781 977

    Working pressure barg 10 10 10 10 10 10

    Heating surface load (nominal capacity) kg/m2 66,3 61,4 64,0 64,7 61,5 61,5

    Heating surface flue gas side (complete)* m2 7,54 10,58 12,50 15,45 19,50 24,40

    *For heating surface water side approximately +15%

    Boiler efficiency minimum % 88,0 88,0 88,0 88,0 88,0 88,0

    Pressure drop flue gas side mbar 3,5 3,6 3,9 4,0 4,4 4,5

    Water content operating litres 600 910 960 970 1178 1386

    Water content full litres 790 1076 1240 1332 1470 1965

    Model 500 650 800 1000 1200 1500

     Additional output with economiser kW 24 29 32 42 47 52

    Boiler efficiency with economiser % 94,0 94,0 94,0 94,0 94,0 94,0

    Pressure drop flue side including economiser mbar 6,5 6,6 6,9 7,0 7,4 7,5

    Flue gas temperature after economiser °C 140 140 140 140 140 140

    1-2

    Technical data boiler with economiser (based on 10 barg working pressure)

    Model 500 650 800 1000 1200 1500

    Oil calorific value kJ/kg 42,700 42,700 42,700 42,700 42,700 42,700

    Fuel consumption at full capacity kg/h 31 40 50 62 75 93

    Wet flue gas volume at 2,7% O2 Nm3 /h 433 550 677 846 1016 1269

    Dry flue gas volume at 3% O2 Nm3 /h 390 495 610 762 914 1143

    Fuel heat input without economiser kW 377 479 591 736 882 1102

    Fuel heat input with economiser kW 347 451 555 694 833 1041

    Flue gas temperature °C 140 140 140 140 140 140

    Technical data Diesel Oil (35 secs)

    Model 500 650 800 1000 1200 1500

    Natural gas calorific value kJ/Nm3 36,000 36,000 36,000 36,000 36,000 36,000

    Fuel consumption at full capacity Nm3 /h 35 45 56 69 83 104

    Wet flue gas volume at 2,4% O2 Nm3 /h 431 547 673 842 1010 1262

    Dry flue gas volume at 3% O2 Nm3 /h 368 467 575 719 863 1079

    Fuel heat input without economiser kW 377 479 590 737 888 1110

    Fuel heat input with economiser kW 347 451 555 694 833 1041

    Flue gas temperature °C 140 140 140 140 140 140

    Technical data Natural gas

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    5/28

    HovalTHD-U E  Industrial Steam Boiler for Oil and Gas Firing

    Technical data

    THD-U E without and with economiser 2000-4000

    Technical data boiler without economiser (based on 10 barg working pressure)

    Model 2000 2500 3000 3500 4000

    Steam rating kg/h 2000 2500 3000 3500 4000

    Output kW 1303 1628 1953 2279 2605

    Working pressure barg 10 10 10 10 10

    Heating surface load (nominal capacity) kg/m2 63,0 58,2 57,6 58,8 58,9

    Heating surface flue gas side (complete)* m2 31,74 42,93 52,10 59,50 67,90

    *For heating surface water side approximately +15%

    Boiler efficiency minimum % 88,0 88,0 88,0 88,0 88,0

    Pressure drop flue gas side mbar 5,2 5,3 5,8 6,1 6,8

    Water content operating litres 2000 2575 2894 3240 3540

    Water content full litres 2550 3500 3840 4270 4525

    Model 2000 2500 3000 3500 4000

     Additional output with economiser kW 69 82 105 134 165

    Boiler efficiency with economiser % 94,0 94,0 94,0 94,0 94,0

    Pressure drop flue side mbar 8,2 8,3 8,8 9,1 9,8

    Flue gas temperature after economiser °C 140 140 140 140 140

    Technical data boiler with economiser (based on 10 barg working pressure)

    Model 2000 2500 3000 3500 4000

    Oil EL calorific value kJ/kg 42,700 42,700 42,700 42,700 42,700

    Fuel consumption at full capacity kg/h 124 155 186 217 249

    Wet flue gas volume at 2,7% O2 Nm3 /h 1693 2116 2539 2962 3385

    Dry flue gas volume at 3% O2 Nm3 /h 1524 1905 2286 2667 3048

    Fuel heat input without economiser kW 1473 1846 2211 2580 2948

    Fuel heat input with economiser kW 1388 1735 2082 2428 2776Flue gas temperature °C 140 140 140 140 140

    Technical data Diesel Oil (35 secs)

    Model 2000 2500 3000 3500 4000

    Natural gas calorific value kJ/Nm3 36,000 36,000 36,000 36,000 36,000

    Fuel consumption at full capacity Nm3 /h 138 184 208 243 278

    Wet flue gas volume at 2,4% O2 Nm3 /h 1683 2104 2552 2946 3366

    Dry flue gas volume at 3% O2 Nm3 /h 1483 1798 2157 2517 2876

    Fuel heat input without economiser kW 1476 1843 2211 2580 2948

    Fuel heat input with economiser kW 1388 1735 2082 2429 2776

    Flue gas temperature °C 140 140 140 140 140

    Technical data fuel Natural gas

    1-3

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    6/28

    HovalTHD-U E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THD-U E 500-4000

    Dimensions and weights

    1-4

    Model 500 650 800 1000 1200 1500

    Boiler length with insulation, without burner mm 2260 2460 2560 2760 2760 3340

    Boiler length with Eco and insulation, mm 3300 3500 3550 3700 3700 4280

    without burner

    Boiler width with insulation, with pump mm 1760 1850 1950 1950 2030 2050

    Boiler height with insulation, with fittings mm 1870 1960 2060 2060 2140 2160

    Insulation thickness mm 100 100 100 100 100 100

    Flue gas outlet diameter1 mm 200 200 250 300 300 300

    Minimum draft tube length mm 350 350 350 350 350 350

    Transport weight at 10 bar kg 2100 2300 2600 2900 3200 3400

    Operating weight flooded at 10 bar kg 3100 3500 4200 4600 5000 5800

    Manhole size mm 420x320 420x320 420x320 420x320 420x320 420x320

    quantity no. 1 1 1 1 1 1

    Inspection port size mm 80 80 80 80 80 80

    quantity no. 2 2 2 2 2 2

    Model 2000 2500 3000 3500 4000

    Boiler length with insulation, with burner mm 3810 3910 3910 4210 4410

    Boiler length with Eco and insulation, mm 4900 4900 4900 5200 5400without burner

    Boiler width with insulation, with pump mm 2100 2350 2500 2550 2550

    Boiler height with insulation, with fittings mm 2210 2460 2560 2640 2640

    Insulation thickness mm 100 100 100 100 100

    Flue gas outlet diameter1 mm 350 450 450 450 450

    Minimum draft tube length mm 350 350 350 350 350

    Transport weight at 10 bar kg 4000 5000 6000 7000 8000

    Operating weight flooded at 10 bar kg 6500 8900 10400 12000 13400

    Manhole size mm 420x320 420x320 420x320 420x320 420x320

    quantity no. 1 1 1 1 1

    Inspection port size mm 80 80 80 80 80

    quantity no. 2 2 2 2 2

    1 Ducting and chimney diameters to be sized for site application.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    7/28

    Hoval

    1-5

     Flame Tube View 

     Fin

    Tube

    Reverse Flame Tube

    THD-U E  Industrial Steam Boiler for Gas and Oil Firing

     Design features

    Three Pass Reverse Design

     Fin Tube Wall 

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    8/28

    HovalTHD-U E  Industrial Steam Boiler for Gas and Oil Firing

     Dimensions

    THD-U E without economiser 

    1 Boiler

    2 Boiler base

    3 Hinged front door

    4 Flue gas outlet

    5 Explosion/cleaning door (flue side)

    6 Inspection opening (waterside)

    7 Instrument assembly

    8 tds shut off valve

    9 Steam shut off valve

    10 Safety valve(s)

    11 Water level gauges

    12 Water level control

    13 Water level alarms

    14 Feed water inlet pipework

    15 Feed water valve(s)1

    16 Bottom blow down ball valve

    17 Pressure stats

    18 Feed water pump(s)1

    19 Electrical control panel

    20 Burner2

    21 Flame viewing point

    L

    2260

    2460

    2560

    2760

    2760

    3340

    3810

    3910

    3910

    4210

    4410

    B

    1760

    1850

    1950

    1950

    2030

    2050

    2100

    2350

    2500

    2550

    2550

    B2

    1625

    1675

    1775

    1775

    1875

    1875

    1975

    2075

    2225

    2225

    2225

    B3

    1460

    1550

    1650

    1650

    1730

    1750

    1800

    2050

    2150

    2200

    2200

    H

    1870

    1960

    2060

    2060

    2140

    2160

    2210

    2460

    2560

    2640

    2640

    H2

    805

    850

    900

    900

    940

    950

    975

    1100

    1150

    1175

    1175

    H4

    673

    700

    735

    735

    760

    770

    771

    877

    882

    945

    945

    D

    1210

    1300

    1400

    1400

    1480

    1500

    1550

    1800

    1900

    1950

    1950

    L1

    1300

    1500

    1500

    1500

    1500

    2200

    2500

    2500

    2500

    2800

    3000

    B1

    850

    900

    1000

    1000

    1100

    1100

    1200

    1300

    1450

    1450

    1450

    H1

    1470

    1560

    1660

    1660

    1740

    1760

    1810

    2060

    2160

    2210

    2210

    D1

    200

    200

    250

    300

    300

    300

    350

    450

    450

    450

    450

    THD-U EModel

    500

    650

    800

    1000

    1200

    1500

    2000

    2500

    3000

    3500

    4000

    Main dimensions Boiler base   Flue gasconnection3

    1 Optional 2nd feed water pump.2 Burner shown is monoblock type.3 Ducting and chimney diameters to be sized for site application.

    Dimensions incl. 100 mm insulation thickness.

    Transport dimensions for pressure level 11 bar.

    Design pressure 11 and 14 bar (overpressure).

    Higher pressures available on request.

    1-6

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    9/28

    Hoval

    1-7

    THD-U E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THD-U E with economiser 

    1 Boiler

    2 Boiler base

    3 Hinged front door

    4 Flue gas outlet

    5 Explosion/cleaning door (flue side)

    6 Inspection opening (waterside)

    7 Instrument assembly8 tds shut off valve

    9 Steam shut off valve

    10 Safety valve(s)

    11 Water level gauges

    12 Water level control

    13 Water level alarms

    14 Feed water inlet pipework

    15 Feed water valve(s)1

    16 Bottom blow down ball valve

    17 Pressure stats

    18 Feed water pump(s)1

    19 Electrical control panel

    20 Burner2

    21 Flame viewing point

    22 Economiser4

    L

    3300

    3500

    3550

    3700

    3700

    4280

    4900

    4900

    4900

    5200

    5400

    B

    1760

    1850

    1950

    1950

    2030

    2050

    2100

    2350

    2500

    2550

    2550

    B2

    1625

    1675

    1775

    1775

    1875

    1875

    1975

    2075

    2225

    2225

    2225

    B3

    1460

    1550

    1650

    1650

    1730

    1750

    1800

    2050

    2150

    2200

    2200

    H

    1870

    1960

    2060

    2060

    2140

    2160

    2210

    2460

    2560

    2640

    2640

    H1

    1470

    1560

    1660

    1660

    1740

    1760

    1810

    2060

    2160

    2210

    2210

    H2

    805

    850

    900

    900

    940

    950

    975

    1100

    1150

    1175

    1175

    H4

    673

    700

    735

    735

    760

    770

    771

    877

    882

    945

    945

    D

    1210

    1300

    1400

    1400

    1480

    1500

    1550

    1800

    1900

    1950

    1950

    L1

    1300

    1500

    1500

    1500

    1500

    2200

    2500

    2500

    2500

    2800

    3000

    B1

    850

    900

    1000

    1000

    1100

    1100

    1200

    1300

    1450

    1450

    1450

    H3

    805

    850

    900

    900

    940

    950

    975

    1100

    1150

    1175

    1175

    D1

    200

    200

    250

    300

    300

    300

    350

    450

    450

    450

    450

    THD-U EModel

    500

    650

    800

    1000

    1200

    1500

    2000

    2500

    3000

    3500

    4000

    Main dimensions Boiler base   Flue gasconnection3

    1 Optional 2nd feed water pump.2 Burner shown is monoblock type.3 Ducting and chimney diameters to be sized for site application.4 Economiser can be positioned vertically.

    Dimensions incl. 100 mm insulation thickness.

    Transport dimensions for pressure level 10 bar.

    *Add 100mm to H1 for crane hooks.

    Design pressure 11 and 14 bar (overpressure).

    Higher pressures available on request.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    10/28

    Hoval

    1-8

    To facilitate installation and

    maintenance the stated clearances

    should be met. Drawing indicates right

    hand (standard) hinged door.

    Minimal space refers to boiler.

    Depending on equipment (accessories)

    the minimal space needs to be

    reviewed according to local codes.

     Positioning

    - No air pollution through

    halogenated hydrocarbon

    (contained e.g. sprays, paints,

    solvents and cleaners)- No large amounts of dust

    - No high atmospheric humidity

    - Frost-resistant and well ventilated

    - Boiler to be installed and

    positioned in a weatherproof, non-

    hazardous and safe classified area.

    Otherwise damage to the installation

    may occur.

    The boiler may only be installed in

    rooms where air pollution throughhalogenated hydrocarbon can occur if

    sufficient measures are taken ensuring

    the supply of unpolluted combustion

    air.

    Boiler room dimensions can be

    reduced by the fitting of a shutter door

    or knockout panel.

    Model

    THD-U E a (mm)

    500

    1850

    650

    2050

    800

    2050

    1000

    2050

    1200

    2050

    1500

    2750

    2000

    3050

    2500

    3050

    Model

    THD-U E a (mm)

    3000

    3050

    3500

    3350

    4000

    3550

    *300mm+ burner overall length (consider pivoting range/pivoting side)

    **Consider control panel, pump(s) assembly

    ***Flame tube length for tube witdrawal and cleaning

    THD-U E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    Installation

    a ***

    * 1200

    Minimum

    ** 1200

    Minimum

    500 Minimum

    500 Minimum

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    11/28

    Hoval

    1-9

    THD-U E  Industrial Steam Boiler for Gas and Oil Firing

     Engineering

     Rules and regulations

    The following rules and regulations

     have to be respected:

    - Hoval technical information and

    installation guide

    - Fire protection regulations

    - National regulations concerning

    permission, installation and operation of

    boiler appliances. Boiler appliances

    have to be installed according to

    national laws and regulations and

    accessory requirements.

    - Besides the national and local

    regulations the project specificcircumstances of the boiler supplier

    have to be considered for every

    application.

    Water treatment/water quality 

    - The quality of the boiler water has to be

    guaranteed according to Hoval technical

    information and national guidelines.

    - Hoval boilers may only be operated with

    treated water. The national regulations

    for the treatment of water apply for the

    values to be maintained.

    - Required water quality: see page 1-10.

    - The water quality has to be checked

    daily.

     Planning, operation and 

     maintenance

    - The heating of the feed water and the

    degassing takes place in the feed water

    tank (hot well).

    - To increase the efficiency, especially for

    natural gas operation, an economisercan be added to pre-heat the feed

    water.

    - Pumps (especially horizontal rotary

    pumps and warm water/condensate

    pumps, NPSH pumps) need to be

    installed with the necessary flow and

    return pipework according to

    requirements. The installation has to be

    completely free of tension (anti-

    vibration proof).

    - Feedwater tank height must satisfy the

    feed pump NPSH requirement.

    - National and local rules and regulations

    have to be considered for the fuel

    supply. Fuel filters are highly

    recommended

    - The operation and water analysis data

    is to be recorded daily in the operation

    booklet.

    - Safety valve, condensate and blowdown

    connections must discharge to a safe

    place.

    - Filters and strainers have to be cleaned

    periodically, especially if installed in

    front of control devices.

    - The drain of the tds, blow down,

    drainage, etc has to be safely

    discharged into a blowdown vessel.

    - All heating components and pipework

    are to be insulated in order to reduce

    radiation losses.

    Combustion air 

    - The supply of combustion air must be

    guaranteed for a safe and economic

    operation. There must be no possibility

    of the air supply being shut off.

    - Ventilation of the boiler house has to

    also be provided.

    - In the installation room no negative

    pressure larger than 3 N/m2 is allowed.

    To adhere to this demand, plan a free

    area for the air supply opening of at

    least 200 cm2, plus 2 cm2 per KW

    output. The aspect ratio for rectangular

    openings should not be more than 1.5 :1.

    If the opening is louvered ensure

    the free area is sufficient. National laws

    have to be respected.

    - Boiler houses have to be fitted with

    relevant fresh air supply openings or

    ducted system.

    - Gas boilers are not to be installed in

    rooms where halogen compounds occur

    which can enter the combustion air.

     Noise level reduction

    The following measures for noise level

    reduction are possible:

    - Solid construction of boiler room

    walls, ceiling and floor, installation

    of silencer in fresh air supply, noise

    insulation for support and bracket

    of pipes.

    - Installation of acoustic shroud for

    the burner.

    - A substantial part of the sound caused

    in the combustion chamber and in the

    top heating surfaces is radiated from

    the flue outlet as sound transmitted by

    air. In addition to this, resonance

    features, depending on chimney

    dimensioning and inlet, may occur

    which are triggered by the oscillation of

    the combustion process. These sounds

    can be reduced by burner-lateral

    measures, e.g. changes of flame

    geometry, atomisation characteristics or

    fuel throughput.

    - Flue gas attenuators cause a substantial

    sound level reduction. These should

    usually be tuned at low frequencies of

    60 - 250 Hz. Flue gas attenuators

    function according to the principle of

    sound absorption. The kinetic energy of

    the exhaust gases is reduced by friction

    requiring an increase in chimney draft in

    the flue system. This has to be

    considered for burner sizing. The

    connection piece from the boiler to the

    flue gas sound absorber has to be

    gastight.

    - The necessary space requirement of

    approximately 1 m for the later

    installation of a flue gas attenuator

    should already be included when

    planning.

    Chimney/flue gas system

    - A properly designed chimney/flue

    arrangement must be provided to

    match each particular application.

    - To achieve a smooth discharge of the

    exhaust gases from the boiler into thechimney, the flue connection is

    recommended to enter the chimney at

    approximately 30-45°.

    - From a length of greater than 1 m

    thermal insulation is necessary.

    - Adequate provision should be made to

    drain off condensate from the base of

    the chimney ensuring condensate does

    not run back into the boiler smokebox.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    12/28

    Hoval

    1-10

    THD-U E  Industrial Steam Boiler for Gas and Oil Firing

     Boiler and feed water specifications for steam boiler plants

    Feed water specifications for natural circulating boilers

    Boiler water specifications for natural circulating boilers

    Working pressure bar 1 < 22 >22 < 68

    Properties colourless, clear, free from suspended matter and foam

    pH-value at 25°C > 9 > 9 >9

    Sum of alkaline earth elements (Ca + Mg)1 mmol/l < 0,02 < 0,02 < 0,01

    °dH < 0,112 < 0,112 < 0,056

    Conductivity at 25°C µS/cm see guidelines for boiler water specifications only

    Oxygen (O2 ) mg/l < 0,1 < 0,02 < 0,02

    Carbon dioxide (CO2 ) dissolved mg/l < 25 < 25 < 25

    Iron (Fe), total mg/l - < 0,05 < 0,03

    Copper (Cu), total mg/l - < 0,01 0,005

    Silicate acid (SiO2 ) mg/l see guidelines for boiler water only

    Consumption of Potassium permanganate mg/l < 10 < 10 < 10

    Oil, fat mg/l < 3 < 1 < 1

    1 Noted in the past at °dH, changing factor: 1 mmol/l = 5,6 °dH (German hardness).

    It is not necessary to make continuous control of the following parameters: Conductivity, Oxygen (O2 ), Carbon dioxide (CO2 )

    dissolved, Iron (Fe), total, Copper (Cu), total, Silicate (SiO2 ), Consumption of Potassium permanganate, Oil, fat.

    Working pressure bar 1 < 22 >22 < 44

    Properties colourless, clear, free from suspended matter and foam

    pH-value at 25°C 10,5-12 10,5-12 10-11,8

    Sum of alkaline earth elements (Ca + Mg)2 mmol/l < 0,02 < 0,02 < 0,01

    °dH < 0,112 < 0,112 < 0,056

    Conductivity at 25°C µS/cm < 5000* < 5000* < 2000*

     Acid capacity KS 8,23 (p-value) mmol/l 1-12 1-12 0,5-6

    Carbon dioxide (CO2 ) dissolved mg/l < 25 < 25 < 25

    Iron (Fe), total mg/l - < 0,05 < 0,03

    Silicate acid (SiO2 ) mg/l < 150 < 100 < 50

    Phosphate (P2O4 )4 mg/l 10-20 5-10 5-10

    Sodium sulphate (Na2SO3 )4 mg/l 5-10 5-10 3-5

    (Polyamide)5 mg/l (3-5) (3-5) --

    1 Take care to maintain the allowed value of acid capacity - at this point the allowed conductivity has to be lower on many

    plants; for water level electrodes minimum conductivity > 5 µS/cm2 Noted in the past at °dH, changing factor: 1 mmol/l = 5,6 °dH (German hardness)3 Noted in the past as p-value, changing factor: KS 8,2 = 1 according p-value = 14 Measurements only necessary if dosing chemicals are used which contains these values5 It is recommended to use Amine (film producing) only instead of other dosing chemicals for boilers which have a small

    heating load and up to maximum 16 bar working pressure. Because of the danger of foam production overdosing is not

    permitted!

    Boiler water quality to comply with BS2486.It is not necessary to make continuous control of the following parameters: Silicate (SiO2 )

    Important note: Hoval recommend that a water treatment specialist is employed to advise on each application and to carry

    out routine monitoring of the feed and boiler water to ensure it remains within specification.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    13/28

    Hoval

    1-11

     Industrial steam and hot water boilers

     Boiler plant total supply package

     Hoval can design and supply all components for the boiler plant room including in-house manufacture of the

     Steam or Hot Water Boiler, Hotwells (Feedwater Tanks), Blowdown Vessels, Deaerators and Economisers

    where appropriate.

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    14/28

    Hoval Industrial steam and hot water boilers

     Design of steam boiler plant 

    1-12

       S   T   E   A   M

       B   O   I   L   E   R

       E   C   O   N   O   M   I   S

       E   R

       H   O   T   W   E   L   L

       W   A   T   E   R   T   R   E   A   T   M   E   N   T

       C   O   N   D   E   N   S   A   T   E   S   T   A   T   I   O   N

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    15/28

    THSD-I E  Industrial Steam Boiler for Gas and Oil Firing

     Description

    Hoval

     Design, Quality & Construction

    The Hoval high output steam boilers

    are constructed from high quality steel

    and are distinguished by their solid,

    robust and flexible design. The Hoval

    boiler combines ease of operation and

    maintenance with optimal efficiency.

    The boiler is designed with all

    necessary inspection doors and is

    constructed for gas or oil firing.

    Construction and production is

    according to EN12593, the Pressure

    Equipment Directive 97/23/EG and CE

    marked. An independent authorised

    institution carries out quality approval

    at our factory. The ISO 9001

    certification and internal quality control

    ensures excellent performance and

    longevity of service. The client receives

    an economical, environmentally friendly

    compact unit, supplied ready for

    installation

    THSD-IE Steam Boiler 

    The THSD-IE is a three-pass flame

    tube/flue gas tube boiler with

    an inner fully water-cooled reversal

    chamber with finned tube wall. The

    boiler consists of a cylindrical shell, two

    endplates, gusset stay supports, flame

    tube, gas reversal chamber with

    water cooled finned tube wall and two

    tube bank gas passes with low gas

    side resistance. The boiler is

    completely electrically welded and

    provided with all required inspection

    openings.

    The spacious flame tube with low

    thermal heat release results in excellent

    combustion and low emissions.

    Large water content and steam space

    provides steady state operation.

    • Efficiency of up to 91% and up to

    95% with economiser can be

    achieved.

    • Standard design

    pressures of

    10,13,16 and 20 barg

    are available. Higher

    pressures can be

    manufactured on

    request.

    Thermal Insulation

    The boiler is fully

    insulated with

    120 mm mineral wool

    insulation. The casing is made of 1mm

    thick stucco aluminum plate with neatly

    trimmed connections and cut-outs. The

    flue gas collector is also thermally

    insulated.

    Valves, Fittings & Sockets

    • Water level regulation and water

    level control

    • Water level indicator (reflex type)

    • Pressure switch for pressure

    regulation and supervision

    • Pressure gauge

    • Main steam valve

    • Safety valve(s)

    • Feed pump, strainer and valves

    • Manual tds

    • Manual-double valve

    blowdown/drain

     Boiler assembly 

    2 Heavy construction boiler

    base supports

    1 Instrument tube placed either on

    the right (standard) or on the left

    1 Flue gas collector with integrated

    horizontal flue gas connection,

    cleaning door and integrated

    relief flap

    1 Boiler door for burner mounting,

    thermal insulated and designed

    gas proof, placed on left and

    right hinges for the flue

    gas side cleaning of boiler

    1 Internal feed water distribution pipe

    1 Data plate

    1 Low water mark

    1 Internal steam dryer

    1 Flue gas tube cleaning kit

    Control Panel 

    The control panel is equipped with the

    required controls and indicators for

    control and supervision of the boiler

    and burner. Control switches, indicator

    lights and alarm signals are provided.

    The control panel is supplied to match

    the burner to be used.

     Feed Water Quality 

    Boiler water quality has to be

    respected. Detailed information can be

    found in the appendix.

     Also available

    - Access ladder and platform

    - Second feed water pump

    - Second safety valve

    - Modulating feedwater control

    - Automatic tds blowdown

    - Water sample cooler

    - Automatic timed bottom blowdown

    - Removable cladding sections

    - Economiser

    - Customised control panel

    - Remote system monitoring and

    controls

    - Variable speed motor controls

    - Hotwell and blowdown vessels

    - Termed maintenance contracts

    2-1

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    16/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 2000-8000

    Technical data without economiser 

    Model 2000 2500 3000 4000 5000 6000 8000

    Steam output kg/h 2000 2500 3000 4000 5000 6000 8000

    Operating output at 10 barg kW 1304 1630 1956 2608 3260 3912 5216

    at 13 barg kW 1308 1635 1963 2617 3271 3925 5234

    at 16 barg kW 1311 1639 1967 2623 3278 3934 5246

    Boiler efficiency Natural gas at 10 barg % 89,8 90,0 89,7 89,9 90,2 90,4 89,7

    at 13 barg % 89,3 89,5 89,2 89,4 89,7 90,0 89,2

    at 16 barg % 89,0 89,1 89,9 89,0 89,3 89,5 89,0

    Boiler efficiency at 10 barg % 90,2 90,1 89,8 89,9 90,2 90,4 89,7

    Diesel Oil (35 secs) at 13 barg % 89,7 89,6 89,3 89,4 89,7 90,0 89,2

    at 16 barg % 89,3 89,2 89,0 89,0 89,3 89,5 89,0

    Flue gas resistance mbar 9,0 9,0 10,0 10,0 10,0 10,0 10,0

    Model 2000 2500 3000 4000 5000 6000 8000

     Additional operating output at 10 barg kW 62 79 102 131 154 175 272

    with economiser at 13 barg kW 68 88 116 144 171 194 299

    at 16 barg kW 74 95 120 156 186 213 315

    Boiler efficiency with economiser % 94,4 94,4 94,4 94,4 94,4 94,4 94,4

    Flue gas resistance of economiser mbar 2.5 2.5 2.5 2.5 2.5 2.5 2.5

    Flue gas temperature after economiser °C 140 140 140 140 140 140 140

    Technical data with integral economiser, fuel natural gas and low sulphur fuel oil

    2-2

    Model 2000 2500 3000 4000 5000 6000 8000

    Natural gas calorific value kJ/Nm3 36000 36000 36000 36000 36000 36000 36000

    Fuel consumption at at 10 barg Nm3 /h 145,3 181,1 220,7 290,3 361,7 432,9 581,9

    full capacity at 13 barg Nm3 /h 146,7 182,7 222,7 292,9 364,9 436,5 587,1

    at 16 barg Nm3 /h 147,7 184,0 224,2 294,9 367,5 439,8 583,6

    Flue gas volume, at 10 barg Nm3 /h 1688 2018 2458 3234 4030 4822 6482

    excess air @10% at 13 barg Nm3 /h 1701 2036 2481 3263 4066 4863 6540

    at 16 barg Nm3 /h 1414 2050 2498 3285 4094 4899 6501

    Fuel heat input at 10 barg kW 1453 1811 2181 2902 3614 4327 5815at 13 barg kW 1465 1826 2201 2928 3647 4361 5868

    at 16 barg kW 1476 1839 2215 2948 3671 4396 5901

    Technical data Natural Gas

    Model 2000 2500 3000 4000 5000 6000 8000

    Diesel Oil calorific value kJ/kg 42700 42700 42700 42700 42700 42700 42700

    Fuel consumption at at 10 barg kg/h 121,9 152,6 183,8 244,6 304,9 364,9 490,3

    full capacity at 13 barg kg/h 123,0 154,0 185,4 246,8 307,6 368,0 494,7

    at 16 barg kg/h 123,9 155,1 186,7 284,5 309,8 370,8 491,8

    Flue gas volume, at 10 barg Nm3 /h 1647 2061 2482 3304 4117 4928 6621

    excess air @12% at 13 barg Nm3 /h 1661 2080 2504 3333 4154 4970 6680

    at 16 barg Nm3 /h 1673 2094 2522 3365 4183 5007 6641

    Fuel heat input at 10 barg kW 1446 1810 2179 2900 3614 4327 5815

    at 13 barg kW 1458 1825 2199 2926 3647 4361 5868

    at 16 barg kW 1468 1838 2213 2947 3671 4396 5894

    Technical data Diesel Oil (35 secs)

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    17/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 10000-20000

    Technical data without economiser 

    Model 10000 12000 14000 16000 18000 20000

    Steam rating kg/h 10000 12000 14000 16000 18000 20000

    Operating output at 10 barg kW 6520 7824 9128 10432 11736 13040

    at 13 barg kW 6542 7850 9159 10467 11776 13084

    at 16 barg kW 6557 7868 9180 10491 11802 13114

    Boiler efficiency Natural gas at 10 barg % 89,9 89,8 89,8 89,9 89,6 89,9

    at 13 barg % 89,4 89,5 89,4 89,4 89,2 89,4

    at 16 barg % 89,2 89,1 89,0 89,0 89,0 89,0

    Boiler efficiency at 10 barg % 89,9 89,89 89,9 89,8 89,7 89,9

    Diesel Oil (35 secs) at 13 barg % 89,4 89,5 89,5 89,5 89,2 89,4

    at 16 barg % 89,1 89,0 89,0 89,0 89,0 89,0

    Flue gas resistance mbar 11,0 10,0 10,0 10,0 11,0 11,0

    Model 10000 12000 14000 16000 18000 20000

     Additional operating output at 10 barg kW 326 399 465 522 622 652

    with economiser at 13 barg kW 366 432 513 586 686 732

    at 16 barg kW 382 464 557 637 716 796

    Boiler efficiency with economiser % 94,4 94,4 94,4 94,4 94,4 94,4

    Flue gas resistance of economiser mbar 2,5 2,5 2,5 3,0 3,0 3,0

    Flue gas temperature after economiser °C 140 140 140 140 140 140

    Technical data with integral economiser, fuel natural gas and low sulphur fuel oil

    2-3

    Model 10000 12000 14000 16000 18000 20000

    Natural gas calorific value kJ/Nm3 36000 36000 36000 36000 36000 36000

    Fuel consumption related at 10 barg Nm3 /h 725,7 871,4 1016,7 1162,1 1310,0 1451,5

    at 13 barg Nm3 /h 732,2 877,4 1024,6 1171,1 1320,1 1464,5

    at 16 barg Nm3 /h 728,0 883,6 1031,7 1179,3 1329,4 1474,7

    Flue gas volume, at 10 barg Nm3 /h 8084 9707 11327 12946 14594 16170

    excess air @10% at 13 barg Nm3 /h 8156 9774 11414 13046 14706 16315

    at 16 barg Nm3 /h 8110 9843 11494 13137 14809 16429

    Fuel heat input at 10 barg kW 7253 8713 10165 11604 13098 14505at 13 barg kW 7318 8771 10245 11708 13020 14635

    at 16 barg kW 7351 8831 10315 11788 13291 14735

    Technical data Natural Gas

    Model 10000 12000 14000 16000 18000 20000

    Diesel Oil calorific value kJ/kg 42700 42700 42700 42700 42700 42700

    Fuel consumption related at 10 barg kg/h 611,5 734,3 856,8 979,3 1103,8 1223,2

    at 13 barg kg/h 617,0 739,5 863,5 987,0 1112,4 1234,2

    at 16 barg kg/h 613,6 744,7 869,7 994,0 1120,3 1245,9

    Flue gas volume, at 10 barg Nm3 /h 8259 9916 11571 13226 14907 16520

    excess air @12% at 13 barg Nm3 /h 8333 9987 11662 13329 15023 16667

    at 16 barg Nm3 /h 8287 10057 11745 13424 15129 16756

    Fuel heat input at 10 barg kW 7253 8703 10154 11617 13084 14505

    at 13 barg kW 7318 8771 10234 11695 13202 14635

    at 16 barg kW 7359 8860 10338 11788 13291 14735

    Technical data Diesel Oil (35 secs)

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    18/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 2000-8000

    Dimensions and weights

    2-4

    Model 2000 2500 3000 4000 5000 6000 8000

    Boiler length with insulation, without burner,

    without economiser mm 3750 3950 4150 4500 4950 5150 5650

    Boiler length with economiser,

    without insulation, without burner mm 4700 4900 5100 5450 5900 6100 6600

    Boiler width with insulation, with pump mm 2450 2550 2600 2700 2800 2900 3100

    Boiler height with insulation, with fittings mm 2700 2800 2850 3075 3250 3400 3650

    Insulation thickness mm 120 120 120 120 120 120 120

    Flue gas outlet diameter (ducting, and mm 350 450 450 550 550 650 650

    chimney diameters to be sized for site application

    Heating surface flue gas side (complete)* m2 47,4 57,3 65,9 88,4 108,3 129,2 169,7

    *For heating surface water side approximately +15%

    Water content operating litres 2750 4350 4850 5850 7200 8200 10000

    flooded litres 4600 5450 6000 7250 9000 10300 12500

    Transport weight without at 10 barg kg 5000 6000 7000 8000 9500 11000 14500

    burner and without Economiser at 13 barg kg 5500 6500 7500 8500 10500 12000 15500

    including accessories at 16 barg kg 6000 7000 8000 9500 11500 13500 16500

    Manhole (size) mm 420 x 420 x 420 x 420 x 420 x 420 x 420 x

    320 320 320 320 320 320 320

    (quantity) 1 1 1 1 1 1 1

    Inspection opening (size) mm 220 x 220 x 220 x 220 x 220 x 220 x 220 x

    150 150 150 150 150 150 150

    (quantity) 2 2 2 2 2 2 2

     Design features

    Three Pass Conventional Design

    Flame Tube

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    19/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 10000-20000

    Dimensions and weights

    Model 10000 12000 14000 16000 18000 20000

    Boiler length with insulation, without burner,

    without economiser mm 6150 6550 6850 7150 7350 7850

    Boiler length with economiser,

    without insulation, without burner mm 7050 7450 7750 8050 8250 8750

    Boiler width with insulation, with pump mm 3300 3400 3600 3700 3800 3900

    Boiler height with insulation, with fittings mm 3925 4125 4350 4425 4625 4725

    Insulation thickness mm 120 120 120 120 120 120

    Flue gas outlet diameter mm 800 850 950 1000 1000 1000

    chimney diameters to be sized for site application

    Heating surface flue gas side (complete)* m2

    211,8 284,5 324,9 381,3 410,7 467,6*For heating surface water side approximately +15%

    Water content operating litres 14200 15900 17600 20000 23000 24250

    flooded litres 18000 20350 22700 25000 29200 31400

    Transport weight without at 10 barg kg 17500 21500 25000 28000 30000 33000

    burner and without Economiser at 13 barg kg 18500 21500 26000 29000 31000 35000

    including accessories at 16 barg kg 19500 24000 28000 31000 35000 39000

    Manhole (size) mm 420 x 420 x 420 x 420 x 420 x 420 x

    320 320 320 320 320 320

    (quantity) 1 1 1 1 1 1

    Inspection opening (size) mm 220 x 220 x 220 x 220 x 220 x 220 x

    150 150 150 150 150 150(quantity) 2 2 2 2 2 2

    2-5

    Construction View 

     Mounting of the Fin

    tube wall 

     Second pass

    Third pass

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    20/28

    Hoval

    Model 2000 2500 3000 4000 5000 6000 8000

    1 Flue gas tube cleaning equipment YES YES YES YES YES YES YES

    1 Main steam valve 10 barg DN80 DN80 DN100 DN100 DN100 DN125 DN150

    13 barg DN65 DN80 DN80 DN100 DN100 DN100 DN125

    16 barg DN65 DN65 DN80 DN80 DN100 DN100 DN125

    1 Vent valve DN25 DN25 DN25 DN25 DN25 DN25 DN25

    2 Safety valves* 10 barg DN25/40 DN25/40 DN32/50 DN32/50 DN32/50 DN40/65 DN40/65

    13 barg DN25/40 DN25/40 DN25/40 DN32/50 DN32/50 DN32/50 DN40/65

    16 barg DN25/40 DN25/40 DN25/40 DN25/40 DN32/50 DN32/50 DN32/50

    2 Isolation valves DN20 DN20 DN20 DN20 DN20 DN20 DN20

    2 Reflection indicators fixing centre (mm) 420 420 420 420 420 420 420

    1 Blow down sight glass drain (screwed) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

    1 Desalting shut off valve DN15 DN15 DN15 DN15 DN15 DN15 DN15

    1 Blow down shut off valve DN40 DN40 DN40 DN40 DN40 DN40 DN40

    1 Blow down ball valve DN40 DN40 DN40 DN40 DN40 DN40 DN40

    1 Pressure gauge with three-way valve (screwed) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

    Water level control type

    1 Feed water valve DN25 DN32 DN32 DN32 DN40 DN40 DN50

    1 Feed water non-return valve/anti syphon valve DN25 DN32 DN32 DN32 DN40 DN40 DN50

    1 Strainer pump (suction side) DN40 DN50 DN50 DN50 DN65 DN65 DN80

    1 Ball valve pump (suction side) DN40 DN50 DN50 DN50 DN65 DN65 DN80

    1 Pressure gauge (pump) with

    shut off valve (screwed) 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"

    1 Feed water pump 10 barg CR CR CR CR CR CR CR

    Motor rating kW 2.2 2.2 3.0 4.0 4.0 5.5 5.5

    1 Feed water pump 13 barg CR CR CR CR CR CR CR

    Motor rating kW 2.2 3.0 4.0 4.0 4.0 7.5 7.5

    1 Feed water pump 16 barg CR CR CR CR CR CR CRMotor rating kW 3.0 4.0 4.0 5.5 7.5 7.5 11.0

    *Safety valve number and size to be advised at contract stage subject to set pressure requirement.

    THSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 2000-8000

    Fittings

    2-6

    ON/OFF

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    21/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E 10000-20000

    Fittings

    Model 10000 12000 14000 16000 18000 20000

    1 Flue gas tube cleaning equipment YES YES YES YES YES YES

    1 Main steam valve 10 barg DN150 DN200 DN200 DN200 DN200 DN250

    13 barg DN150 DN150 DN200 DN200 DN200 DN200

    16 barg DN125 DN150 DN150 DN150 DN200 DN200

    1 Vent valve DN25 DN25 DN25 DN25 DN25 DN25

    2 Safety valve* 10 barg DN50/80 DN50/80 DN65/100 DN65/100 DN65/100 DN65/100

    13 barg DN40/65 DN50/80 DN50/80 DN65/100 DN65/100 DN65/100

    16 barg DN40/65 DN40/65 DN50/80 DN50/80 DN50/80 DN65/100

    2 Isolation valve DN20 DN20 DN20 DN20 DN20 DN20

    2 Reflection indicators fixing centre (mm) M=420 M=420 M=420 M=420 M=420 M=420

    1 Blow down sight glass drain (screwed) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

    1 tds shut off valve DN15 DN15 DN15 DN15 DN15 DN15

    1 Blow down shut off valve DN40 DN40 DN40 DN40 DN40 DN40

    1 Blow down ball valve DN40 DN40 DN40 DN40 DN40 DN40

    1 Pressure gauge with three-way valve 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"

    Water level control type

    1 Feed water valve DN50 DN50 DN65 DN80 DN80 DN80

    1 Feed water non-return valve/anti syphon valve DN50 DN50 DN65 DN80 DN80 DN80

    1 Strainer pump (suction side) DN80 DN80 DN100 DN125 DN125 DN125

    1 Ball valve pump (suction side) DN 80 DN 80 DN100 DN125 DN125 DN125

    1 Pressure gauge (pump) with shut off valve 1/4" 1/4" 1/4" 1/4" 1/4" 1/4"

    1 Feed water pump 10 barg CR CR CR CR CR CR

    Motor rating kW 11.0 11.0 11.0 11.0 15.0 15.0

    1 Feed water pump 13 barg CR CR CR CR CR CR

    Motor rating kW 11.0 11.0 15.0 15.0 18.5 18.5

    1 Feed water pump 16 barg CR CR CR CR CR CR

    Motor rating kW 15.0 15.0 18.5 18.5 18.5 22.0

    *Safety valve number and size to be advised at contract stage subject to set pressure requirement.

    2-7

    MODULATING

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    22/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E without economiser 

    1 Boiler

    2 Boiler base

    3 Front reversal chamber

    Hinged front door

    4 Flue gas outlet

    5 Explosion/cleaning door (flue side)

    6 Inspection openings (water side)

    7 Instrument assembly

    8 tds shut off valve

    9 Steam shut off valve

    10 Safety valve(s)

    11 Water level gauges

    12 Water level control

    13 Water level alarms

    14 Feed water inlet

    15 Feed water valve(s)

    16 Bottom blow down ball valve

    17 Pressure stats

    18 Feed water pump(s)

    19 Electrical control panel

    20 Burner5

    21 Vent valve

    22 Condensate drainage

    23 Flame viewing port

    L

    3750

    3950

    4150

    4500

    4950

    51505650

    6150

    6550

    6850

    7150

    7350

    7850

    B

    2450

    2550

    2600

    2700

    2800

    29003100

    3300

    3400

    3600

    3700

    3800

    3900

    H

    2700

    2800

    2850

    3075

    3250

    34003650

    3925

    4125

    4350

    4425

    4625

    4725

    H1

    2250

    2350

    2400

    2550

    2650

    28002925

    3200

    3300

    3500

    3600

    3700

    3800

    H2

    1175

    1225

    1250

    1350

    1400

    14501550

    1700

    1750

    1850

    1900

    1950

    2000

    D

    1990

    2090

    2140

    2240

    2340

    24402640

    2840

    2940

    3140

    3240

    3340

    3440

    L3

    300

    300

    300

    300

    300

    300300

    350

    350

    350

    350

    350

    350

    L4

    700

    700

    700

    700

    700

    700700

    850

    850

    850

    850

    850

    850

    L1

    2300

    2500

    2700

    3000

    3400

    36004100

    4500

    5000

    5000

    5500

    5500

    6000

    L2

    400

    400

    400

    400

    400

    400400

    475

    475

    475

    475

    475

    475

    B1

    1175

    1225

    1250

    1350

    1400

    14501550

    1700

    1750

    1850

    1900

    1950

    2000

    B2

    160

    160

    160

    160

    160

    160160

    200

    200

    200

    200

    200

    200

    H3

    1750

    1825

    1850

    1950

    2000

    21002200

    2350

    2400

    2500

    2550

    2650

    2700

    D1

    350

    450

    450

    550

    550

    650650

    800

    850

    950

    1000

    1000

    1000

    THSD-I EModel

    2000

    2500

    3000

    4000

    5000

    60008000

    10000

    12000

    14000

    16000

    18000

    20000

    Main dimensions   Boiler base   Flue gasconnection6

    1 up to THSD-I E (4000) 100mm less2 up to THSD-I E (4000) 200mm less3 up to THSD-I E (4000) 100mm less, from THSD-I E (12000) 100mm more4

    up to THSD-I E (4000) 200mm less, from THSD-I E (12000) 100mm more5 Burner shown is monobloc type. Width/height may alter with fabricated

    wind box type burner.6 Ducting and chimney diameters to be sized for site application

    Pos. 14 up to THSD-I E (4000) 400mm less

    Dimensions incl. 120 mm insulation thickness

    Design pressure 10, 13 and 16 bar

    (overpressure)

    Other models available for different working

    pressures.Transport dimensions for pressure level 10 bar.

     Add 100mm to H1 for crane hooks.

    2-8

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    23/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    THSD-I E with economiser - subject to local site alterations

    1 Boiler

    2 Boiler base

    3 Front reversal chamber

    Hinged front door

    4 Flue gas outlet

    5 Explosion/cleaning door (flue side)

    6 Inspection openings (water side)

    7 Tube assembly

    8 tds shut off valve

    9 Steam shut off valve

    10 Safety valve(s)

    11 Water level gauges

    12 Water level control

    13 Water level alarms

    14 Feed water inlet pipework

    15 Feed water valve(s)

    16 Bottom blow down ball valve

    17 Pressure stats

    18 Feed water pump(s)

    19 Electrical control panel

    20 Burner

    21 Vent valve

    22 Condensate drainage

    24 Economiser7

    L

    4700

    4900

    5100

    5450

    5900

    61006600

    7050

    7450

    7750

    8050

    8250

    8750

    B

    2450

    2550

    2600

    2700

    2800

    29003100

    3300

    3400

    3600

    3700

    3800

    3900

    H

    2700

    2800

    2850

    3075

    3250

    34003650

    3925

    4125

    4350

    4425

    4625

    4725

    H1

    2250

    2350

    2400

    2550

    2650

    28002925

    3200

    3300

    3500

    3600

    3700

    3800

    H2

    1175

    1225

    1250

    1350

    1400

    14501550

    1700

    1750

    1850

    1900

    1950

    2000

    D

    1990

    2090

    2140

    2240

    2340

    24402640

    2840

    2940

    3140

    3240

    3340

    3440

    L3

    300

    300

    300

    300

    300

    300300

    350

    350

    350

    350

    350

    350

    L4

    700

    700

    700

    700

    700

    700700

    850

    850

    850

    850

    850

    850

    L1

    2300

    2500

    2700

    3000

    3400

    36004100

    4500

    5000

    5000

    5500

    5500

    6000

    L2

    400

    400

    400

    400

    400

    400400

    475

    475

    475

    475

    475

    475

    B1

    1175

    1225

    1250

    1350

    1400

    14501550

    1700

    1750

    1850

    1900

    1950

    2000

    B2

    160

    160

    160

    160

    160

    160160

    200

    200

    200

    200

    200

    200

    H3

    1750

    1825

    1850

    1950

    2000

    21002200

    2350

    2400

    2500

    2550

    2650

    2700

    D1

    350

    450

    450

    550

    550

    650650

    800

    850

    950

    1000

    1000

    1000

    THSD-I EModel

    2000

    2500

    3000

    4000

    5000

    60008000

    10000

    12000

    14000

    16000

    18000

    20000

    Main dimensions   Boiler base   Flue gasconnection6

    1 up to THSD-I E (4000) 100mm less2 up to THSD-I E (4000) 200mm less3 up to THSD-I E (4000) 100mm less, from THSD-I E (12000) 100mm more4

    up to THSD-I E (4000) 200mm less, from THSD-I E (12000) 100mm morePos. 14 up to THSD-I E (4000) 400mm less5 Burner shown is monobloc type. Width/height may alter with fabricated

    wind box type burner6 Ducting and chimney diameters to be sized for site application7 Economiser can be positioned vertically.

    Dimensions incl. 120 mm insulation thickness

    Design pressure 10, 13 and 16 bar

    (overpressure)

    Other models available for different workingpressures.

    Transport dimensions for pressure level 10 bar.

     Add 100mm to H1 for crane hooks.

    2-9

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    24/28

    Hoval

    To facilitate installation and

    maintenance the stated clearances

    should be met. Drawing indicates right

    hand (standard) hinged door

    Minimal space refers to boiler.

    Depending on equipment (accessories)

    the minimal space needs to be

    reviewed according to local codes.

     Positioning

    - No air pollution through

    halogenated hydrocarbon

    (contained e.g. sprays, paints,

    solvents and cleaners)- No large amounts of dust

    - No high atmospheric humidity

    - Frost-resistant, dust free and well

    ventilated

    - Boiler to be installed and

    positioned in a weatherproof, non-

    hazardous and safe classified area.

    Otherwise damage to the installation

    may occur.

    The boiler may only be installed inrooms where air pollution through

    halogenated hydrocarbon can occur if

    sufficient measures are taken ensuring

    the supply of unpolluted combustion

    air.

    Boiler room dimensions can be

    reduced by the fitting of a shutter door

    or knockout panel.

    Model

    THSD-I E a (mm)

    2000

    2800

    2500

    3000

    3000

    3200

    4000

    3550

    5000

    4000

    6000

    4200

    8000

    4700

    10000

    5100

    Model

    THSD-I E a (mm)

    12000

    5500

    14000

    5800

    16000

    6100

    18000

    6300

    20000

    6800

    *300mm+ burner overall length (consider pivoting range/pivoting side)

    **Consider control panel, pump(s) assembly

    ***Flame tube length for tube withdrawal/cleaning

    THSD-I E  Industrial Steam Boiler for Gas and Oil Firing

    Technical data

    Typical Installation

    2-10

    a ***

    * 1200

    Minimum

    ** 1200

    Minimum

    500 Minimum

    500 Minimum

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    25/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

     Engineering

     Rules and regulations

    The following rules and regulations

     have to be respected:

    - Hoval technical information and

    installation guide

    - Fire protection regulations

    - National regulations concerning

    permission, installation and operation of

    boiler appliances. Boiler appliances

    have to be installed according to

    national laws and regulations and

    accessory requirements.

    - Besides the national and local

    regulations the project specificcircumstances of the boiler supplier

    have to be considered for every

    application.

    Water treatment/water quality 

    - The quality of the boiler water has to be

    guaranteed according to Hoval technical

    information and national guidelines.

    - Hoval boilers may only be operated with

    treated water. The national regulations

    for the treatment of water apply for the

    values to be maintained.

    - Required water quality: see page 2-12.

    - The water quality has to be checked

    daily.

     Planning, operation and 

     maintenance

    - The heating of the feed water and the

    degassing takes place in the feed water

    tank (hot well).

    - To increase the efficiency, especially for

    natural gas operation, an economisercan be added to pre-heat the feed

    water.

    - Pumps (especially horizontal rotary

    pumps and warm water/condensate

    pumps, NPSH pumps) need to be

    installed with the necessary flow and

    return pipework according to

    requirements. The installation has to be

    completely free of tension (anti-

    vibration proof).

    - Feedwater tank height must satisfy the

    feed pump NPSH requirement.

    - National and local rules and regulations

    have to be considered for the fuel

    supply. Fuel filters are highly

    recommended

    - The operation and water analysis data

    is to be recorded daily in the operation

    booklet.

    - Safety valve, condensate and blowdown

    connections must discharge to a safe

    place.

    - Filters and strainers have to be cleaned

    periodically, especially if installed in

    front of control devices.

    - The drain of the tds, blow down,

    drainage, etc has to be safely

    discharged into a blowdown vessel.

    - All heating components and pipework

    are to be insulated in order to reduce

    radiation losses.

    Combustion air 

    - The supply of combustion air must be

    guaranteed for a safe and economic

    operation. There must be no possibility

    of the air supply being shut off.

    - Ventilation of the boiler house has to

    also be provided.

    - In the installation room no negative

    pressure larger than 3 N/m2 is allowed.

    To adhere to this demand, plan a free

    area for the air supply opening of at

    least 200 cm2, plus 2 cm2 per KW

    output. The aspect ratio for rectangular

    openings should not be more than 1.5 :1.

    If the opening is louvered ensure

    the free area is sufficient. National laws

    have to be respected.

    - Boiler houses have to be fitted with

    relevant fresh air supply openings or

    ducted system.

    - Gas boilers are not to be installed in

    rooms where halogen compounds occur

    which can enter the combustion air.

     Noise level reduction

    The following measures for noise level

    reduction are possible:

    - Solid construction of boiler room

    walls, ceiling and floor, installation

    of silencer in fresh air supply, noise

    insulation for support and bracket

    of pipes.

    - Installation of acoustic shroud for

    the burner.

    - A substantial part of the sound caused

    in the combustion chamber and in the

    top heating surfaces is radiated from

    the flue outlet as sound transmitted by

    air. In addition to this, resonance

    features, depending on chimney

    dimensioning and inlet, may occur

    which are triggered by the oscillation of

    the combustion process. These sounds

    can be reduced by burner-lateral

    measures, e.g. changes of flame

    geometry, atomisation characteristics or

    fuel throughput.

    - Flue gas attenuators cause a substantial

    sound level reduction. These should

    usually be tuned at low frequencies of

    60 - 250 Hz. Flue gas attenuators

    function according to the principle of

    sound absorption. The kinetic energy of

    the exhaust gases is reduced by friction

    requiring an increase in chimney draft in

    the flue system. This has to be

    considered for burner sizing. The

    connection piece from the boiler to the

    flue gas sound absorber has to be

    gastight.

    - The necessary space requirement of

    approximately 1 m for the later

    installation of a flue gas attenuator

    should already be included when

    planning.

    Chimney/flue gas system

    - A properly designed chimney/flue

    arrangement must be provided to

    match each particular application.

    - To achieve a smooth discharge of the

    exhaust gases from the boiler into thechimney, the flue connection is

    recommended to enter the chimney at

    approximately 30-45°.

    - From a length of greater than 1 m

    thermal insulation is necessary.

    - Adequate provision should be made to

    drain off condensate from the base of

    the chimney ensuring condensate does

    not run back into the boiler smokebox.

    2-11

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    26/28

    HovalTHSD-I E  Industrial Steam Boiler for Gas and Oil Firing

     Boiler and feed water specifications for steam boiler plants

    Feed water specifications for natural circulating boilers

    Boiler water specifications for natural circulating boilers

    Working pressure bar 1 < 22 >22 < 68

    Properties colourless, clear, free from suspended matter and foam

    pH-value at 25°C > 9 > 9 >9

    Sum of alkaline earth elements (Ca + Mg)1 mmol/l < 0,02 < 0,02 < 0,01

    °dH < 0,112 < 0,112 < 0,056

    Conductivity at 25°C µS/cm see guidelines for boiler water specifications only

    Oxygen (O2 ) mg/l < 0,1 < 0,02 < 0,02

    Carbon dioxide (CO2 ) dissolved mg/l < 25 < 25 < 25

    Iron (Fe), total mg/l - < 0,05 < 0,03

    Copper (Cu), total mg/l - < 0,01 0,005

    Silicate acid (SiO2 ) mg/l see guidelines for boiler water only

    Consumption of Potassium permanganate mg/l < 10 < 10 < 10

    Oil, fat mg/l < 3 < 1 < 1

    1 Noted in the past at °dH, changing factor: 1 mmol/l = 5,6 °dH (German hardness).

    It is not necessary to make continuous control of the following parameters: Conductivity, Oxygen (O2 ), Carbon dioxide (CO2 )

    dissolved, Iron (Fe), total, Copper (Cu), total, Silicate (SiO2 ), Consumption of Potassium permanganate, Oil, fat.

    Working pressure bar 1 < 22 >22 < 44

    Properties colourless, clear, free from suspended matter and foam

    pH-value at 25°C 10,5-12 10,5-12 10-11,8

    Sum of alkaline earth elements (Ca + Mg)2 mmol/l < 0,02 < 0,02 < 0,01

    °dH < 0,112 < 0,112 < 0,056

    Conductivity at 25°C µS/cm < 5000* < 5000* < 2000*

     Acid capacity KS 8,23 (p-value) mmol/l 1-12 1-12 0,5-6

    Carbon dioxide (CO2 ) dissolved mg/l < 25 < 25 < 25

    Iron (Fe), total mg/l - < 0,05 < 0,03

    Silicate acid (SiO2 ) mg/l < 150 < 100 < 50

    Phosphate (P2O4 )4 mg/l 10-20 5-10 5-10

    Sodium sulphate (Na2SO3 )4 mg/l 5-10 5-10 3-5

    (Polyamide)5 mg/l (3-5) (3-5) --

    1 Take care to maintain the allowed value of acid capacity - at this point the allowed conductivity has to be lower on many

    plants; for water level electrodes minimum conductivity > 5 µS/cm2 Noted in the past at °dH, changing factor: 1 mmol/l = 5,6 °dH (German hardness)3 Noted in the past as p-value, changing factor: KS 8,2 = 1 according p-value = 14 Measurements only necessary if dosing chemicals are used which contains these values5 It is recommended to use Amine (film producing) only instead of other dosing chemicals for boilers which have a small

    heating load and up to maximum 16 bar working pressure. Because of the danger of foam production overdosing is not

    permitted!

    Boiler water quality to comply with BS2486.It is not necessary to make continuous control of the following parameters: Silicate (SiO2 )

    Important note: Hoval recommend that a water treatment specialist is employed to advise on each application and to carry

    out routine monitoring of the feed and boiler water to ensure it remains within specification.

    2-12

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    27/28

  • 8/17/2019 THDUE+THSDIE+Technical+Sales+Brochure

    28/28

    Hoval Limited

    Northgate

    Newark 

    Nottinghamshire

    NG24 1JN

    Tel: 01636 672711

    Fax: 01636 673532

    [email protected] 

    www.hoval.co.uk 

    Hoval Export

     Austrasse 70, 9490 Vaduz

    Principality of Liechtenstein

    Tel: +423 399 2400

    Fax: +423 399 2618

    [email protected] 

    www.hoval.com

    Hoval follows a policy of continued improvement and reserves the right to change specifications without notice