The Impact of Short-Circuit Electromagnetic Forces in a 12- pulse Converter Transformer Kamran Dawood 1 , Bora Alboyaci 2 , and Mehmet Aytac Cinar 3 1 Electrical Engineering, Istanbul Technical University, 34469 Maslak, İstanbul, Turkey [email protected] 2 Department of Electrical Engineering, Kocaeli University, Kocaeli, Turkey [email protected] 3 Izmit Vocational School Kocaeli University, Kocaeli, Turkey. [email protected] Abstract Transformers are one of the most costly, critical and major electrical components of the electric power system. Operation and stability of the electric power system mainly depend on the working of the transformer. Short-circuit forces can damage the transformer and accurate calculation of such forces is crucial for the transformer designers. Miscalculation can result in the non-optimal design. There are many different analytical methods for the calculation of the electromagnetic forces. However, these analytical methods do not consider the main factors of the transformer such as material properties of the winding and core, and complexity of the geometry. The numerical method like finite element method takes these factors into account. In this study, the 2- dimensional model is developed to calculate the short-circuit forces acting on the different parts of a 12-pulse converter transformer. 1. Introduction In power system, transformer is one of the important and expensive components. Power quality of the power system mainly depends on the operation of the transformer. Transformers are excited 24 hours a day and variety of the mechanical stresses and faults occur during the operation. External short-circuits is one of the most common and suddenly occurred faults. Transient duration of a transformer is very short but it still damages the transformer. Resulting electromagnetic forces and thermal accumulations are main reasons for the mechanical faults in the transformers; the performance of the transformer can also be predicted from these two parameters. This research focused on the investigation of electromagnetic forces during short-circuit and normal conditions. A short-circuit condition is a system disturbance and it produces higher current as compared to the normal conditions, the currents show nearly a tenfold increase [1]. For the safe operation, electromagnetic force due to short-circuit current must be predicted and analyzed correctly before installing a transformer at electric power system [2]. Electromagnetic forces accumulation can cause displacement in transformer windings and damage level can be increased with time, if the mechanical fault is not cleared in the earliest stage. Electromagnetic forces at over current initiate vibration and these vibrations are one of the major reasons for internal faults [3]. 2. Electromagnetic Forces The electromagnetic forces in the transformer windings are due to the interaction between magnetic field density (B) and current density (J). Force (f) can be calculated by using Eq. (1): f =J×B (1) These forces are exerted on the both inner and outer parts of the windings. During the normal conditions electromagnetic forces and leakage magnetic fluxes in the transformer’s winding are relatively small but when external fault occurs it increases the current, which cause higher electromagnetic forces in the winding. During faulty conditions, the radial and axial components of the leakage field and electromagnetic forces must be fully considered [4]. Forces can be divided into radial and axial forces. During the normal conditions axial component of the leakage flux density is much higher as compared to the radial components of the leakage flux density. At the top and bottom of the transformer windings radial flux is high and it is lowest in the mid of the windings. Radial force is generated by the interaction between axial flux density and current passing the windings. Radial force can be calculated as follow; F r =B z ×J φ (2) F r = π 2 ×(NI) 2 ×D m ×10 -7 h (3) where, Jφ is the current density in φ -axis direction and Bz is the magnetic flux density in the z-direction. NI is the ampere-turn of the winding, Dm is the mean diameter of the winding and h is the height of the winding. The nature of the radial force is such that the free distance between the two windings increases. Therefore, these forces act outward on the outer winding and inward on the inner winding [4,5,6]. Fig. 1. Buckling of the inner winding due to the radial force [7]
Transcript

The Impact of Short-Circuit Electromagnetic Forces in a 12-pulse Converter Transformer

Kamran Dawood1, Bora Alboyaci2, and Mehmet Aytac Cinar3

1Electrical Engineering, Istanbul Technical University, 34469 Maslak, İstanbul, Turkey

[email protected] 2 Department of Electrical Engineering, Kocaeli University, Kocaeli, Turkey

[email protected] 3 Izmit Vocational School Kocaeli University, Kocaeli, Turkey.

[email protected]

Abstract

Transformers are one of the most costly, critical and major electrical components of the electric power system. Operation and stability of the electric power system mainly depend on the working of the transformer. Short-circuit forces can damage the transformer and accurate calculation of such forces is crucial for the transformer designers. Miscalculation can result in the non-optimal design. There are many different analytical methods for the calculation of the electromagnetic forces. However, these analytical methods do not consider the main factors of the transformer such as material properties of the winding and core, and complexity of the geometry. The numerical method like finite element method takes these factors into account. In this study, the 2-dimensional model is developed to calculate the short-circuit forces acting on the different parts of a 12-pulse converter transformer.

1. Introduction

In power system, transformer is one of the important and

expensive components. Power quality of the power system mainly depends on the operation of the transformer. Transformers are excited 24 hours a day and variety of the mechanical stresses and faults occur during the operation. External short-circuits is one of the most common and suddenly occurred faults. Transient duration of a transformer is very short but it still damages the transformer. Resulting electromagnetic forces and thermal accumulations are main reasons for the mechanical faults in the transformers; the performance of the transformer can also be predicted from these two parameters.

This research focused on the investigation of electromagnetic forces during short-circuit and normal conditions. A short-circuit condition is a system disturbance and it produces higher current as compared to the normal conditions, the currents show nearly a tenfold increase [1]. For the safe operation, electromagnetic force due to short-circuit current must be predicted and analyzed correctly before installing a transformer at electric power system [2]. Electromagnetic forces accumulation can cause displacement in transformer windings and damage level can be increased with time, if the mechanical fault is not cleared in the earliest stage. Electromagnetic forces at over current initiate vibration and these vibrations are one of the major reasons for internal faults [3].

2. Electromagnetic Forces

The electromagnetic forces in the transformer windings are due to the interaction between magnetic field density (B) and current density (J). Force (f) can be calculated by using Eq. (1):

f=J×B (1) These forces are exerted on the both inner and outer parts of

the windings. During the normal conditions electromagnetic forces and leakage magnetic fluxes in the transformer’s winding are relatively small but when external fault occurs it increases the current, which cause higher electromagnetic forces in the winding. During faulty conditions, the radial and axial components of the leakage field and electromagnetic forces must be fully considered [4]. Forces can be divided into radial and axial forces.

During the normal conditions axial component of the leakage flux density is much higher as compared to the radial components of the leakage flux density. At the top and bottom of the transformer windings radial flux is high and it is lowest in the mid of the windings. Radial force is generated by the interaction between axial flux density and current passing the windings. Radial force can be calculated as follow;

Fr=Bz×Jφ (2)

Fr=2×π2×(NI)2×Dm×10-7

h (3)

where, Jφ is the current density in φ -axis direction and Bz is the magnetic flux density in the z-direction. NI is the ampere-turn of the winding, Dm is the mean diameter of the winding and h is the height of the winding. The nature of the radial force is such that the free distance between the two windings increases. Therefore, these forces act outward on the outer winding and inward on the inner winding [4,5,6].

Fig. 1. Buckling of the inner winding due to the radial force [7]

Axial force is generated due to the interaction between radial component of the leakage flux and current passing through the winding. Axial force tends to compress windings conductors along the vertical axis in the middle [4, 5]. Large axial forces are mainly due to the asymmetry of LV and HV windings and these forces can cause serious risk for the transformer integrity [8]. Axial force can be calculated as follow:

Fa=Br×Jφ (4)

Fr=2×π2×A×(NI)2×Dm×10-7

heff (5)

where A is the length of the tap section and it is expressed as a fraction of the total length of the winding, heff is the effective length of path of radial flux and value of the heff varies for each arrangement of tapping. Reference [9] can be used for the calculation of the force for different kind of tap arrangements.

Fig. 2. Effects of the axial force [7]

Calculation of the axial force and radial leakage field density is not easy and accurate as compared to radial force and axial leakage field intensity. However residual ampere-turn method is well known approach for the calculation of the axial force and radial leakage field density. In this method winding is split into two groups having same ampere-turns. The radial field is produced by one part and another part produces axial field [9]. Compression and expansion of the windings are mainly due to the axial force [10].

3. Finite Element Method

Finite element method is a numerical method for solving

integral and differential equations such as electromagnetic, magnetostatic and thermal conductivity [11]. FEM divide the geometry in small sub domain elements which is known as finite element. In FEM complex problems are represented as differential equation form, the solution of the FEM is limitless for the engineering design problems in physical science.

In this study 25 kVA, Dd0y11 connected three-phase multi-winding 12-pulse transformer is used. Main parameters, figure and dimensions of the transformer is given in Table 1, Fig. 3 and Fig. 4 respectively.

Fig. 3. 500/55 V, 25 kVA prototype transformer

Fig. 4. Dimensions of the multi-winding transformer

Magnetic flux density distributions, obtained from 3-D and 2-D analyses, are shown in Fig. 5 and Fig. 6 respectively.

Fig. 5. Magnetic flux density distribution in 3-D model

Fig. 6. Magnetic flux density distribution in 2-D model

Table 1. Transformer data

Rating Power (kVA)

High voltage (V)

Low voltage (V)

25 500 55

Core Core

Material Flux

Density(T) No-load

losses (W) M5 1.71 157

Winding

Number of turns of HV

winding

Number of turns of upper LV winding

Number of turns of lower LV winding

173 19 11

3.1. Electromagnetic Forces Calculation using FEM

Table 2 shows the radial forces acting on the LV and HV windings during the normal operating condition. By using ANSYS Maxwell electromagnetic analysis software, we get the distributed radial force (Fr-d) along the winding, which can be calculated using equation (6) [12],

Fr-d=2×π×(NI)2×10-7

h (6)

Table 2. Radial forces acting on the multi-winding transformer

Winding Analytical (N) FEM (N)

Error%Fr-d

Total Force

Fr-d Total Force

Upper HV 58.03 32.53 51.50 28.87 11.25

Lower HV 58.03 32.53 51.30 28.75 11.60

Upper LV 57.45 24.26 50.50 21.33 12.10

Lower LV 57.98 24.48 50.70 21.41 12.55

Axial forces are small and negligible in the magnetostatic analysis during the normal operating condition. Axial forces acting on the LV and HV windings are between 0 to 2 N.

3.2. Short-Circuit Test

During short-circuit test, multi-winding transformer has been analyzed under three different conditions. In condition I all the phases of the LV wye windings (lower LV winding) are short circuited and delta connections of LV (upper LV winding) remain open circuited during the short-circuit test. During the condition I lower windings have higher current. Fig. 7 and Fig. 8 show current in the lower windings.

Fig. 7. Current in HV lower windings (Condition I)

Fig. 8. Current in LV lower windings (Condition I)

During the short circuit test of the multi-winding transformer, in first few cycles, the forces along the windings are different due to the inrush current. However, after few cycles, inrush current becomes zero which resulted in the same ampere-turn in the lower LV and HV windings, which resulted in approximately same distributed radial forces along the windings. Forces of the phase A lower windings are shown in Fig.9, to fig. 12.

Fig. 9 Forces in HVA lower inner winding (Condition I)

Fig. 10 Forces in HVA lower outer winding (Condition I)

Fig. 11 Forces in LVA lower inner winding (Condition I)

Fig. 12 Forces in LVA lower outer winding (Condition I) During the Condition I lower windings of phase B and C also have higher current and forces. Upper windings of the transformer have less current as compared to the lower windings which resulted in the fewer forces. In Condition II all the phases of LV delta windings are short-circuited and wye connections of LV remain open circuited. During the Condition II upper windings have higher current. Current of the upper windings are shown in Fig. 13 and Fig. 14.

Fig. 13. Current in HV upper windings (Condition II)

Fig. 14 Current in LV upper windings (Condition II) Due to the higher current in upper windings, forces of the upper windings are also high. For the first few cycles, forces are even higher than the normal short-circuit conditions due to the inrush current. However, after few cycles, minimization in the inrush

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-600.00

-400.00

-200.00

0.00

200.00

400.00

600.00

Y1 [A

]

Maxwell2DDesign1CURRENTHVLOWER ANSOFT

Curve Info rms

Current(HVALOWER)Setup1 : Transient

355.2422

Current(HVBLOWER)Setup1 : Transient 359.0023

Current(HVCLOWER)Setup1 : Transient

333.3016

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-12500.00

-10000.00

-7500.00

-5000.00

-2500.00

0.00

2500.00

5000.00

7500.00

10000.00

Y1 [A

]

Maxwell2DDesign1CURRENTLVLOWER ANSOFT

Curve Info rms

Current(LVALOWER)Setup1 : Transient

6088.4054

Current(LVBLOWER)Setup1 : Transient

6109.7450

Current(LVCLOWER)Setup1 : Transient

5928.7800

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-12.50

-6.25

0.00

6.25

12.50

Y1

[kN

ew

ton

]

Maxwell2DDesign1HVALOWER_IN ANSOFT

Curve Info pk2pk

HVALOWER_IN.Force_magSetup1 : Transient

11.2186

HVALOWER_IN.Force_xSetup1 : Transient 11.2897

HVALOWER_IN.Force_ySetup1 : Transient 0.8378

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

Y1 [k

New

ton]

Maxwell2DDesign1HVALOWER_OUT ANSOFT

Curve Info pk2pk

HVALOWER_OUT.Force_magSetup1 : Transient 12.5448

HVALOWER_OUT.Force_xSetup1 : Transient

12.1462

HVALOWER_OUT.Force_ySetup1 : Transient

4.0472

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

Y1 [k

New

ton]

Maxwell2DDesign1LVALOWER_IN ANSOFT

Curve Info pk2pk

LVALOWER_IN.Force_magSetup1 : Transient

13.5960

LVALOWER_IN.Force_xSetup1 : Transient 13.5924

LVALOWER_IN.Force_ySetup1 : Transient 0.9132

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-15.00

-10.00

-5.00

0.00

5.00

10.00

15.00

Y1

[kN

ew

ton]

Maxwell2DDesign1LVALOWER_OUT ANSOFT

Curve Info pk2pk

LVALOWER_OUT.Force_magSetup1 : Transient

14.9098

LVALOWER_OUT.Force_xSetup1 : Transient

14.2576

LVALOWER_OUT.Force_ySetup1 : Transient 5.1196

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-600.00

-400.00

-200.00

0.00

200.00

400.00

600.00

Y1 [A

]

Maxwell2DDesign1CURRENTHVUPPER ANSOFT

Curve Info rms

Current(HVAUPPER)Setup1 : Transient 362.0637

Current(HVBUPPER)Setup1 : Transient

360.1739

Current(HVCUPPER)Setup1 : Transient

340.7264

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-8000.00

-6000.00

-4000.00

-2000.00

0.00

2000.00

4000.00

6000.00

Y1 [A

]

Maxwell2DDesign1CURRENTLVUPPER ANSOFT

Curve Info rms

Current(LVAUPPER)Setup1 : Transient

3611.4867

Current(LVBUPPER)Setup1 : Transient 3556.4961

Current(LVCUPPER)Setup1 : Transient 3500.4158

current resulted in the approximately same distributed radial force along the windings. Forces of the phase A upper windings are shown in Fig. 15 to Fig. 18.

Fig. 15. Forces in HVA UPPER inner winding (Condition II)

Fig. 16. Forces in HVA upper outer winding (Condition II)

Fig. 17. Forces in LVA upper inner winding (Condition II)

Fig. 18. Forces in LVA upper outer winding (Condition II) During the Condition II upper windings of phase B and C also have higher current and forces. Lower windings of the transformer carry less current as compared to the upper windings which resulted in the fewer forces. During the Condition III, all of the low voltage windings are short-circuited which resulted in the higher current in all of the windings. Current of the high and low voltage windings are shown in Fig. 19 to Fig. 22.

Fig. 19. Current in HV upper windings (Condition III)

Fig. 20. Current in LV upper windings (Condition III)

Fig. 21. Current in HV lower windings (Condition III)

Fig. 22. Current in LV lower windings (Condition III) During Condition III after first few cycles, distributed radial forces become approximately same for all of the windings. The forces of the phase A windings are shown in Fig.23 to Fig. 30.

Fig. 23. Forces in HVA lower inner winding (Condition III)

Fig.24. Forces in HVA lower outer winding (Condition III)

Fig. 25. Forces in HVA upper inner winding (Condition III)

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-12.50

-6.25

0.00

6.25

12.50

Y1 [k

New

ton]

Maxwell2DDesign1HVAUPPER_IN ANSOFT

Curve Info pk2pk

HVAUPPER_IN.Force_magSetup1 : Transient 12.0521

HVAUPPER_IN.Force_xSetup1 : Transient 12.1387

HVAUPPER_IN.Force_ySetup1 : Transient 0.7619

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-4.00

-2.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

Y1 [k

New

ton]

Maxwell2DDesign1HVAUPPER_OUT ANSOFT

Curve Info pk2pk

HVAUPPER_OUT.Force_magSetup1 : Transient 13.5040

HVAUPPER_OUT.Force_xSetup1 : Transient

13.0795

HVAUPPER_OUT.Force_ySetup1 : Transient

4.3557

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.50

0.00

2.50

5.00

7.50

10.00

12.50

15.00

Y1

[kN

ewto

n]

Maxwell2DDesign1LVAUPPER_IN ANSOFT

Curve Info pk2pk

LVAUPPER_IN.Force_magSetup1 : Transient 14.6009

LVAUPPER_IN.Force_xSetup1 : Transient 14.6063

LVAUPPER_IN.Force_ySetup1 : Transient 0.9403

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-20.00

-15.00

-10.00

-5.00

0.00

5.00

10.00

15.00

20.00

Y1

[kN

ewto

n]

Maxwell2DDesign1LVAUPPER_OUT ANSOFT

Curve Info pk2pk

LVAUPPER_OUT.Force_magSetup1 : Transient 16.0082

LVAUPPER_OUT.Force_xSetup1 : Transient 15.2998

LVAUPPER_OUT.Force_ySetup1 : Transient 5.5409

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-600.00

-400.00

-200.00

0.00

200.00

400.00

600.00

Y1

[A]

Maxwell2DDesign1CURRENTHVUPPER ANSOFT

Curve Info rms

Current(HVAUPPER)Setup1 : Transient 364.8492

Current(HVBUPPER)Setup1 : Transient 366.9679

Current(HVCUPPER)Setup1 : Transient 365.0987

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-6000.00

-4000.00

-2000.00

0.00

2000.00

4000.00

6000.00

Y1 [A

]

Maxwell2DDesign1CURRENTLVUPPER ANSOFT

Curve Info rms

Current(LVAUPPER)Setup1 : Transient

3382.9927

Current(LVBUPPER)Setup1 : Transient 3320.9726

Current(LVCUPPER)Setup1 : Transient

3262.0440

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-600.00

-400.00

-200.00

0.00

200.00

400.00

600.00

Y1 [A

]

Maxwell2DDesign1CURRENTHVLOWER ANSOFT

Curve Info rms

Current(HVALOWER)Setup1 : Transient 357.4716

Current(HVBLOWER)Setup1 : Transient

362.8005

Current(HVCLOWER)Setup1 : Transient 357.3941

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-10000.00

-7500.00

-5000.00

-2500.00

0.00

2500.00

5000.00

7500.00

10000.00

Y1 [A

]

Maxwell2DDesign1CURRENTLVLOWER ANSOFT

Curve Info rms

Current(LVALOWER)Setup1 : Transient 5712.2869

Current(LVBLOWER)Setup1 : Transient 5683.7262

Current(LVCLOWER)Setup1 : Transient

5533.3762

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-12.50

-6.25

0.00

6.25

12.50

Y1

[kN

ewto

n]

Maxwell2DDesign1HVALOWER_IN ANSOFT

Curve Info pk2pk

HVALOWER_IN.Force_magSetup1 : Transient 11.8169

HVALOWER_IN.Force_xSetup1 : Transient 11.8083

HVALOWER_IN.Force_ySetup1 : Transient 0.5576

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.00

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

Y1

[kN

ew

ton]

Maxwell2DDesign1HVALOWER_OUT ANSOFT

Curve Info pk2pk

HVALOWER_OUT.Force_magSetup1 : Transient 13.7430

HVALOWER_OUT.Force_xSetup1 : Transient

13.7595

HVALOWER_OUT.Force_ySetup1 : Transient 0.3343

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-15.00

-10.00

-5.00

0.00

5.00

10.00

15.00

Y1

[kN

ewto

n]

Maxwell2DDesign1HVAUPPER_IN ANSOFT

Curve Info pk2pk

HVAUPPER_IN.Force_magSetup1 : Transient 12.6278

HVAUPPER_IN.Force_xSetup1 : Transient 12.6103

HVAUPPER_IN.Force_ySetup1 : Transient 0.7095

Fig. 26. Forces in HVA upper outer winding (Condition III)

Fig. 27. Forces in LVA lower inner winding (Condition III)

Fig. 28. Forces in LVA lower outer winding (Condition III)

Fig. 29. Forces in LVA upper inner winding (Condition III)

Fig. 30. Forces in LVA upper outer winding (Condition III) It can be observed from the results that axial force is higher during the inrush current. Results also show that axial forces are higher during the condition I and II as compared to Condition III i.e. when one LV winding is short-circuited; axial forces are higher as compared to the both LV windings short-circuited. In normal conditions, the distributed radial force in LV and HV windings was less than 60 N. However, during short-circuit transient test, these forces can be increased up to 16 kN. From the results of the simulation, it can be concluded that during the short-circuit conditions, forces in the HV and LV windings can be increased more than 266 times of the normal conditions.

4. Conclusions

In this study, two dimensional finite element analysis has been used for the calculation of the magnetic flux density and short-circuit forces in a 12-pulse multi-winding converter transformer. For this multi-winding transformer, the radial and axial forces computed for three different conditions. For first two conditions single winding was short-circuited and for the third condition both windings were short-circuited. Results show that axial forces were higher during the single winding short circuit as compared to the both short circuited.

Results also show that axial forces exerted during the inrush current are larger than short-circuit forces. It is recommended that during the transformer design stage, inrush current must be considered as one of the main factors because inrush current occurs frequently and sometimes duration of the inrush current is much higher as compared to the short circuit. Due to the higher duration of inrush current, its continuous repetition can damage the transformer and which will be resulted in high financial losses.

5. References

[1] Ahn, H. M. et al, "Finite-element analysis of short-circuit

electromagnetic force in power transformer", IEEE Trans. Ind. Appl., vol. 47, no. 3, pp. 1267-1272, 2011.

[2] Ahn, H. M. et al, "Experimental verification and finite element analysis of short-circuit electromagnetic force for dry-type transformer", IEEE Trans. Magn., vol. 48, no. 2, pp 819-822, 2012.

[3] Steurer M., and Klaus F., "The impact of inrush currents on the mechanical stress of high voltage power transformer coils", IEEE Trans. Power Del, vol. 17, no. 1, pp 155-160, 2002.

[4] Azevedo A. C. et al, "Investigation of Transformer Electromagnetic Forces Caused by External Faults Using FEM" , Transmission & Distribution Conf. and Exposition: Latin America, Caracas, Venezuela, 15-18 August, 2006.

[5] Faiz J. et al, "Computation of static and dynamic axial and radial forces on power transformer windings due to inrush and short circuit currents" , App. Elec. Eng. and Computing Tech. IEEE Conf., Amman, Jordan, 06-08 December, 2011.

[6] S. Güneri et al, "Transformatörde Kısa Devre Kuvvetleri", Eleco 2014, Bursa, Turkey, 27-29 Nov. 2014.

[7] K. Dawood, "Çok sargılı transformatörler için kısa devre empedansı ve sargılara etkiyen kuvvetlerin belirlenmesi için yeni bir yaklaşım", M.S. thesis, Dept. Elect. Eng., Kocaeli Univ., Kocaeli, Turkey, 2017.

[8] Ji T. Y. et al, "Detection of power transformer winding deformation and variation of measurement connections using a hybrid winding model", Electrical Power System Research, vol. 87, no. 1, pp 39–46, 2012.

[9] M. Water, "The short circuit strength of power transformers", Mcdonald & Co Ltd., London, 1966.

[10] Heathcote M., "J & P Transformer book", Newnes, U.K., 2007.

[11] K. Dawood et al., "A new method for the calculation of leakage reactance in power transformers", J. Elect. Eng. Technol., vol. 12, no. 5, 1883-1890, 2017.

[12] K. Dawood et al, "Modelling and Analysis of Transformer using Numerical and Analytical Methods", 18th Int. Symp. ISEF 2017, Lodz, Poland, 14-16 Sept. 2017.

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.50

0.00

2.50

5.00

7.50

10.00

12.50

15.00

Y1 [k

New

ton]

Maxwell2DDesign1HVAUPPER_OUT ANSOFT

Curve Info pk2pk

HVAUPPER_OUT.Force_magSetup1 : Transient 14.6210

HVAUPPER_OUT.Force_xSetup1 : Transient 14.6256

HVAUPPER_OUT.Force_ySetup1 : Transient 0.4045

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

0.00

2.50

5.00

7.50

10.00

12.50

15.00

Y1

[kN

ewto

n]

Maxwell2DDesign1LVALOWER_IN ANSOFT

Curve Info pk2pk

LVALOWER_IN.Force_magSetup1 : Transient 12.8931

LVALOWER_IN.Force_xSetup1 : Transient 12.7150

LVALOWER_IN.Force_ySetup1 : Transient 2.1370

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-15.00

-10.00

-5.00

0.00

5.00

10.00

15.00

Y1

[kN

ew

ton

]

Maxwell2DDesign1LVALOWER_OUT ANSOFT

Curve Info pk2pk

LVALOWER_OUT.Force_magSetup1 : Transient 13.6659

LVALOWER_OUT.Force_xSetup1 : Transient 13.6515

LVALOWER_OUT.Force_ySetup1 : Transient 0.6790

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-2.50

0.00

2.50

5.00

7.50

10.00

12.50

15.00

Y1 [k

New

ton]

Maxwell2DDesign1LVAUPPER_IN ANSOFT

Curve Info pk2pk

LVAUPPER_IN.Force_magSetup1 : Transient 13.8612

LVAUPPER_IN.Force_xSetup1 : Transient 13.6689

LVAUPPER_IN.Force_ySetup1 : Transient

2.3071

0.00 20.00 40.00 60.00 80.00 100.00Time [ms]

-15.00

-10.00

-5.00

0.00

5.00

10.00

15.00

Y1 [k

New

ton]

Maxwell2DDesign1LVAUPPER_OUT ANSOFT

Curve Info pk2pk

LVAUPPER_OUT.Force_magSetup1 : Transient 14.6253

LVAUPPER_OUT.Force_xSetup1 : Transient 14.6225

LVAUPPER_OUT.Force_ySetup1 : Transient 0.4420