The Value of the
PI System at PJM
Interconnection
Thomas Keyser
Transmission System Operator
© Copyr i gh t 2014 OSIso f t , LLC.
Agenda
• Who is PJM
• Background of PI System at PJM
• Control Room displays
• PMU data in PI System
• Wind generation and PI System
• PI System and GIS
• Performance Compliance uses for PI System
2
© Copyr i gh t 2014 OSIso f t , LLC.
Regional Transmission Organizations
3
© Copyr i gh t 2014 OSIso f t , LLC.
PJM Territory
4
© Copyr i gh t 2014 OSIso f t , LLC.
About PJM
• Responsible for the reliable operation of the high-voltage electric grid
in all or parts of 13 states and Washington DC.
• Balancing Authority – responsible for balancing supply and demand
• Operate world’s largest wholesale electricity market.
• Peak Demand - 163,000 MW
• Territory includes 6,000 substations
• 62,000 miles of transmission lines in PJM territory (69-765KV)
• Dispatch 1,300+ generators
5
© Copyr i gh t 2014 OSIso f t , LLC.
Control room software vendors
• EMS – Siemens Spectrum EMS
- Dual hot control centers at two different sites
• Market System – Alstom-Energy Market Systems
• Day ahead and real-time market
• Visualization – OSIsoft
- The PI System
6
© Copyr i gh t 2014 OSIso f t , LLC.
Visualization Challenges
7
• Situation Awareness for large geographical area
• Tracking of 1300 generators- unit status, MW and MVAR output, unit reserves
• Tracking system voltages throughout 13 state territory
• Viewing transmission zone overviews for a large grid
• Keeping track of wind generation output and forecast
• Track MW transfers into PJM and across the transmission system
• Consistent displays in each control room
© Copyr i gh t 2014 OSIso f t , LLC.
Visualization Solutions
• PI ProcessBook displays used throughout control room
on video walls and desktop monitors.
• Use combination of bar charts, trends, and one-line
overviews
• Use Multi-States with different colors to distinguish
between normal/abnormal values
8
© Copyr i gh t 2014 OSIso f t , LLC.
PI Client Overview
• PI ProcessBook displays for dispatcher real-time
monitoring, training and during simulations and
restoration drills
• PI ProcessBook displays for after event analysis
• PI DataLink for engineering analysis and
reporting
• PI Coresight for ad-hoc analysis
9
© Copyr i gh t 2014 OSIso f t , LLC.
Data Collected in PI System
• Real-time SCADA data – voltages, MW, MVAR, loads, Circuit Breaker Status, MW reserves
• State Estimator data
• Market data – Generator bid information, Dispatch rates
• PMU data (synchrophasor)
• Line and transformer outage data
• All PI System data stored for 7 years except for phasor data which is stored for 90 days.
10
© Copyr i gh t 2014 OSIso f t , LLC.
Control Room Displays
• Voltages
• Frequency
• Generation (steam units, CTs, wind and hydro)
• Transmission zonal loads
• Tie-lines between transmission companies
• One-line area overviews
• MW Reserves, MVAR reserves
11
© Copyr i gh t 2014 OSIso f t , LLC. 12
View of control room video walls
© Copyr i gh t 2014 OSIso f t , LLC.
Situational awareness in control room
13
© Copyr i gh t 2014 OSIso f t , LLC.
Transmission flows and voltages
14
© Copyr i gh t 2014 OSIso f t , LLC. 15
Scheduled and Actual MW flows between PJM and neighbors
© Copyr i gh t 2014 OSIso f t , LLC.
Generation outputs
16
© Copyr i gh t 2014 OSIso f t , LLC. 17
Generation Video Wall
© Copyr i gh t 2014 OSIso f t , LLC. 18
Desk Top Displays Load Picker Display
© Copyr i gh t 2014 OSIso f t , LLC. 19
Transmission Zone Overview Example
© Copyr i gh t 2014 OSIso f t , LLC. 20
Zoomed in after search
© Copyr i gh t 2014 OSIso f t , LLC. 21
Generator Unit details
© Copyr i gh t 2014 OSIso f t , LLC. 22
Actual & Forecasted Loads
© Copyr i gh t 2014 OSIso f t , LLC.
Situation awareness improved in
control room.
Operators are all looking at same
information
Solution Results and Benefits Business Challenge
Being able to visualize large
amounts of data is not
possible with desktop PCs.
Desktop monitors too small
for one-line overviews of large
transmission systems.
Create PI ProcessBook
displays for generation and
transmission data that can be
visible to all operators in the
control room.
PJM is using PI ProcessBook displays on
the large video walls and desktops in the
control room for the operators to view
generation outputs of over 1300
generators, and various transmission
related displays.
23
Situational Awareness Benefits with PI System
© Copyr i gh t 2014 OSIso f t , LLC.
Synchrophasor Data at PJM
• 360 PMUs installed in 90 substations
• Approx 4500 PI Tags collecting data
• Estimated 1TB data per month collected
• Phasor PI Tags used for alarming in Intelligent Event
Processor tool.
• Phasor data used for after event analysis
24
© Copyr i gh t 2014 OSIso f t , LLC.
PMU Deployment
25
© Copyr i gh t 2014 OSIso f t , LLC. 26
Phasor data example during switching event
SCADA MW / calculated MW using PMU data
MW swings on hydro units
MW swinging on 1 unit but not
the other 2 at same station
Frequency change PMUs
Frequency change
© Copyr i gh t 2014 OSIso f t , LLC.
Performance Compliance
department is currently using PMU
data for analysis of system
disturbances.
Engineers are using PMU data for
stability analysis.
Solution Results and Benefits Business Challenge
Be able to capture instability
on the transmission system
that happens in cycles which
normally wouldn’t be picked
up in SCADA data
Install PMU at all major
substations and capture the
data in PI System so
displays can be built for real-
time monitoring and post
mortem analysis.
SCADA data is received every 2-4
seconds. PMU data is received at much
faster scan rates and can pick up small
changes in frequency and voltages that
can be missed with SCADA data.
27
PMUs and The PI System
© Copyr i gh t 2014 OSIso f t , LLC.
Renewable integration into Operations
Wind Display
28
Wind Unit
© Copyr i gh t 2014 OSIso f t , LLC. 29
Future data is combined with historical and real-time data
Wind Power Forecasting
© Copyr i gh t 2014 OSIso f t , LLC.
Dispatchers can view the real-
time outputs of individual wind
farms and view the forecast MW.
Results in better situational
awareness in the control room.
Solution Results and Benefits Business Challenge
Balance generation supply
with load can be challenging
with wind outputs that can
quickly increase or decrease
Build PI ProcessBook displays
with Wind Farm outputs and
trends with real-time MW and
forecasted MW.
With the increasing amount of wind
generation on the system, there is a need
to display the output of each wind farm due
to the volatility nature of wind generation.
30
Renewable Integration into Operations
© Copyr i gh t 2014 OSIso f t , LLC.
Future PI System data uses - ARC GIS
31
© Copyr i gh t 2014 OSIso f t , LLC.
Transmission system overview
32
© Copyr i gh t 2014 OSIso f t , LLC.
Radar data added
33
© Copyr i gh t 2014 OSIso f t , LLC.
Temperatures and clouds added
34
© Copyr i gh t 2014 OSIso f t , LLC.
Ongoing project – PI System
integration into dynamic map
slated for 2015 timeframe.
Solution Results and Benefits Business Challenge
The need exists for a dynamic
map that covers the PJM
system and can display
weather information along
with transmission and
generation data.
Combine Esri and OSIsoft
products to visualize power
flows on the PJM grid.
With a control area spanning 13 states, PJM
needs a tool to view a wide area picture of
the transmission system.
35
GIS and PI System
© Copyr i gh t 2014 OSIso f t , LLC. 36
PI System uses for Operations and Performance Compliance
Equipment Outage Tracker HTML and ASP.net
© Copyr i gh t 2014 OSIso f t , LLC. 37
Outage Tracker Report – PI AF SDK
© Copyr i gh t 2014 OSIso f t , LLC. 38
Order No. 794 approved by the FERC
on January 16th, 2014
Applicable to Balancing Authorities
Effective April 1st, 2016
Each … Balancing Authority … shall
achieve an annual Frequency Response
that is equal to or more negative than its
Frequency Response Obligation
Responding to new FERC orders
© Copyr i gh t 2014 OSIso f t , LLC. 39
Typical Interconnection Frequency Responses for 2011
© Copyr i gh t 2014 OSIso f t , LLC. 40
Frequency Response Unit Event Performance Tool
© Copyr i gh t 2014 OSIso f t , LLC. 41
Unit responded as expected
© Copyr i gh t 2014 OSIso f t , LLC. 42
Frequency Response Unit Summary Performance
© Copyr i gh t 2014 OSIso f t , LLC. 43
59.9
59.92
59.94
59.96
59.98
60
60.02
60.04
21:1
2:47
21:1
2:48
21:1
2:49
21:1
2:50
21:1
2:51
21:1
2:52
21:1
2:53
21:1
2:54
21:1
2:55
21:1
2:56
21:1
2:57
21:1
2:58
21:1
2:59
21:1
3:00
21:1
3:01
21:1
3:02
21:1
3:03
21:1
3:04
21:1
3:05
21:1
3:06
21:1
3:07
21:1
3:08
21:1
3:09
21:1
3:10
21:1
3:11
21:1
3:12
Salem 1
AEP - Baker CE - Zion RECO - S Mawa DOM - N Anna PL - Susq 2 EMS Freq
4/13/2014 21:12:52Frequency (Hz)
Unit loss – SCADA data vs Phasor data
© Copyr i gh t 2014 OSIso f t , LLC. 44
59.9
59.91
59.92
59.93
59.94
59.95
59.96
59.97
59.98
59.99
21:2
5:23
21:2
5:24
21:2
5:25
21:2
5:26
21:2
5:27
21:2
5:28
21:2
5:29
21:2
5:30
21:2
5:31
21:2
5:32
21:2
5:33
21:2
5:34
21:2
5:35
21:2
5:36
21:2
5:37
21:2
5:38
21:2
5:39
21:2
5:40
21:2
5:41
21:2
5:42
21:2
5:43
21:2
5:44
21:2
5:45
21:2
5:46
21:2
5:47
21:2
5:48
Calvert Cliffs 1&2
AEP - Baker CE - Zion RECO - S Mawa DOM - N Anna PL - Susq 2 EMS Freq
1/21/2014 21:25:28Frequency (Hz)Two unit loss - 9 seconds apart
© Copyr i gh t 2014 OSIso f t , LLC.
Displays built without the need of
vendors.
Displays built without requiring
code changes in the EMS.
Solution Results and Benefits Business Challenge
Being able to develop
displays in a timely manner
without disruption to EMS.
PI ProcessBook and PI DataLink
have been utilized to create new
displays.
Effective April 1st, 2016
Each … Balancing Authority … shall achieve an annual Frequency Response that is equal to or more negative than its Frequency Response Obligation
45
Meeting new requirements
© Copyr i gh t 2014 OSIso f t , LLC.
Thomas Keyser
• Transmission Dispatcher
• PJM Interconnection
46
© Copyr i gh t 2014 OSIso f t , LLC. 47
Questions
Please wait for
the microphone
before asking
your questions
State your
name &
company
© Copyr i gh t 2014 OSIso f t , LLC.