SAI Global Certification Services Kevin Goodwin General manager Technical Services SAI Global Assurance Daniel Darakas – Unrestricted Building Certifier Date of issue: 25/03/2019 Date of expiry: 25/03/2022 Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 1 of 6 Certification Body: SAI Global Certification Services Pty Limited (ACN 108 716 669) Trading as “SAI Global” JAS-ANZ Accreditation No. Z1440295AS Address: 680 George St, Sydney, NSW 2000 Website: www.saiglobal.com Certificate Holder: Kingspan Insulation Pty Ltd 266 Beringarra Avenue, Malaga, WA 6090 Tel: 1300 247 235 Fax: 1300 247 329 [email protected] Certificate number: CM20201 THIS TO CERTIFY THAT Kooltherm® K10 FM G2 Soffit Board and K10 FM G2W White Soffit Board Type and/or use of product: Kingspan Kooltherm® K10 FM G2 & K10 FM G2W Soffit Boards are a super high performance thermal insulation board for use as soffit board, being installed to the underside of concrete soffits. Description of product: Kingspan Kooltherm® K10 FM G2 & K10 FM G2W soffit boards are fibre-free rigid thermoset, closed cell phenolic insulation core, sandwiched between an upper tissue-based facing and a lower facing of aluminium foil autohesively bonded to the insulation core during manufacture. K10 FM G2 has a lower facing of highly reflective aluminium foil. K10 FM G2W has a lower facing of white aluminium foil. COMPLIES WITH THE FOLLOWING BCA PROVISIONS AND STATE OR TERRITORY VARIATION(S) BCA 2016 Amdt. 1 Volume One Volume Two Performance Requirement(s) N/A N/A N/A N/A Deemed-to-Satisfy Provision(s): C1.10(a)(ii) interalia Spec C1.10 Clause 4 and Clause 7 J1.2 (such that it is able to be used as part of a system in Fire Hazard Properties Wall and ceiling linings Other materials Thermal Construction – general 3.12.1.1 3.12.1.2 3.12.1.5 Building Fabric – Building fabric thermal insulation Building Fabric – Roof Building Fabric – Floor
Transcript
Page 1: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

SAI Global Certification Services

Kevin Goodwin General manager Technical Services SAI Global Assurance

Daniel Darakas – Unrestricted Building Certifier

Date of issue: 25/03/2019

Date of expiry: 25/03/2022

Certificate number: CM20201

This certificate is only valid when reproduced in its entirety.

Page 1 of 6

Certification Body:

SAI Global Certification Services Pty Limited

(ACN 108 716 669) Trading as “SAI Global”

JAS-ANZ Accreditation No. Z1440295AS

Address: 680 George St, Sydney, NSW 2000

Website: www.saiglobal.com

Certificate Holder:

Kingspan Insulation Pty Ltd

266 Beringarra Avenue, Malaga, WA 6090

Tel: 1300 247 235 Fax: 1300 247 329

[email protected]

Certificate number: CM20201

THIS TO CERTIFY THAT

Kooltherm® K10 FM G2 Soffit Board and K10 FM G2W White Soffit Board

Type and/or use of product: Kingspan Kooltherm® K10 FM G2 & K10 FM G2W Soffit Boards are a super high performance thermal insulation board for use as soffit board, being installed to the underside of concrete soffits.

Description of product: Kingspan Kooltherm® K10 FM G2 & K10 FM G2W soffit boards are fibre-free rigid thermoset, closed cell phenolic insulation core, sandwiched between an upper tissue-based facing and a lower facing of aluminium foil autohesively bonded to the insulation core during manufacture. K10 FM G2 has a lower facing of highly reflective aluminium foil. K10 FM G2W has a lower facing of white aluminium foil.

COMPLIES WITH THE FOLLOWING BCA PROVISIONS AND STATE OR TERRITORY VARIATION(S) BCA 2016 Amdt. 1

Volume One Volume Two

Performance Requirement(s) N/A N/A N/A N/A

Deemed-to-Satisfy Provision(s):

C1.10(a)(ii) interalia Spec C1.10 Clause 4 and Clause 7 J1.2 (such that it is able to be used as part of a system in

Fire Hazard Properties Wall and ceiling linings Other materials Thermal Construction – general

3.12.1.1

3.12.1.2

3.12.1.5

Building Fabric – Building fabric thermal insulation

Building Fabric – Roof

Building Fabric – Floor

Page 2: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 2 of 6

clauses J1.3 & J1.6)

State or territory variation(s): NSW Spec C1.10 NSW Clause 7

NSW Section J

NT Section J

QLD Section J

SA J1.3

Fire Resistance – Fire Hazard Properties Other Materials

Replace Section J with NSW Section J as follows: NSW Subsection J(A) Energy Efficiency – Class 2 buildings and Class 4 parts NSW Subsection J(B) Energy Efficiency – Class 3 and Class 5 to 9 buildings

Replace Section J with NT Section J Energy Efficiency For a Class 2 building and a Class 4 part of a building, Section j is replaced with Section J of BCA 2009 Section J does not apply to Class 3 and Class 5 to 9 buildings.

For Class 2 buildings, Section J is replaced with Section J of BCA 2009.

Insert SA J1.3(e) Energy Efficiency - Roof and ceiling construction

NSW Part 3.12

NT 3.12

SA 3.12

ENERGY EFFICIENCY ACCEPTABLE CONSTRUCTION Delete Part 3.12 & substitute with NSW Part 3.12 BASIX applies

Part 3.12 is replaced with BCA 2009 Part 3.12

Class 10a buildings must comply with 3.12.1.6

Page 3: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 3 of 6

SUBJECT TO THE FOLLOWING LIMITATIONS AND CONDITIONS AND THE PRODUCT TECHNICAL DATA IN APPENDIX A AND EVALUATION STATEMENTS IN APPENDIX B

Limitations and conditions:

1. The product to be used for Class 2 to Class 9 NCC Classifications in all states and territories, except for parts of the building as noted below:

• Class 3 and class 9a accommodation for the aged, people with disability, children and health-care building public corridors, unless sprinkler protection is provided within the building.

• Class 9b, and Class 9c Public Corridors, unless sprinkler protections are provided within the building. • Within fire-isolated exits and fire control rooms.

2. This product has been tested to AS/ISO 9705-2003 and achieved a Group 2 material under BCA Specification C1.10. 3. The K10 FM G2W White Soffit Board is to be installed in accordance with the Kooltherm® K10 FM G2W White Soffit

Board (K10MG2W AW2420 Issue 4 Jan 2019) 4. The K10 FM G2 Soffit Board is to be installed in accordance with the Kooltherm® K10 FM G2 Soffit Board (K10MG2

AW2421 Issue 4 Jan 2019)

Building classification/s:

Class 2 to 9 buildings

Class 1 & Class 10a

Scope of certification: The CodeMark Scheme is a building product certification scheme. The rules of the Scheme are available at the ABCB website www.abcb.gov.au. This Certificate of Conformity is to confirm

that the relevant requirements of the Building Code of Australia (BCA) as claimed against have been met. The responsibility for the product performance and its fitness for the intended use remain with the

certificate holder. The certification is not transferrable to a manufacturer not listed on Appendix A of this certificate.

Disclaimer: The Scheme Owner, Scheme Administrator and Scheme Accreditation Body do not make any representations, warranties or guarantees, and accept no legal liability whatsoever arising from or

connected to, the accuracy, reliability, currency or completeness of any material contained within this certificate; and the Scheme Owner, Scheme Administrator and Scheme Accreditation Body disclaim to the

extent permitted by law, all liability (including negligence) for claims of losses, expenses, damages and costs arising as a result of the use of the product(s) referred to in this certificate.

Page 4: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 4 of 6

APPENDIX A – PRODUCT TECHNICAL DATA

A1 Type and intended use of product

Refer to Page 1 of this certificate.

A2 Description of product

Refer to Page 1 of this certificate.

A3 Product specification

Refer to product manuals for total R-values for various thicknesses (25, 30, 40, 50, 60, 70, 80 & 90mm thick) of Kooltherm® K10 FM G2 Soffit Board and Kooltherm® K10 FM G2W White Soffit

Board.

A4 Manufacturer and manufacturing plant(s)

Kingspan Insulation Pty Ltd. – Manufactured in Somerton

25 O’Herns Road, Somerton, VIC, 3062, Australia

A5 Installation requirements

Refer to Page 2 of this certificate and the following;

• Kooltherm® K10 FM G2W White Soffit Board (K10MG2W AW2420 Issue 4 Jan 2019)

• Kooltherm® K10 FM G2 Soffit Board (K10MG2 AW2421 Issue 4 Jan 2019).

A6 Other relevant technical data

Refer to Report documented below (B2 Reports) and the following:

Kooltherm K10 FM G2W Soffit Board:

o Ignitability Index 0

o Spread of Flame Index 0

o Heat Evolved Index 0

o Smoke Developed Index 2

Page 5: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 5 of 6

Kingspan Kooltherm K10 G2 Soffit Board

o Ignitability Index 0

o Spread of Flame Index 0

o Heat Evolved Index 0

o Smoke Developed Index 1

Page 6: THIS TO CERTIFY THAT ® K10 FM G2 Soffit Board and K10 …

Certificate number: CM20201 This certificate is only valid when reproduced in its entirety. Page 6 of 6

APPENDIX B – EVALUATION STATEMENTS

B1 Evaluation methods

The system has been assessed as complying with the identified Performance Requirements of the BCA 2016. This involved a review of product specifications, test reports, installation

manuals, and associated documentation.

1. Fire Resistance Assessment – Volume 1; A0.5(a)/A2.2(a)(iv) and Volume 2; 1.0.5(a)/1.2.2(a)(i) – Report from a Registered Testing Authority (NATA accreditation No. 3277); and

Volume 1; A0.5(a)/A2.2(a)(v) and Volume 2; 1.0.5(a)/1.2.2(a)(iii) – Report from an appropriately qualified person.

2. Energy Efficiency Assessment – Volume 1; A0.5(a)/A2.2(a)(iv) and Volume 2; 1.0.5(a)/1.2.2(a)(i) – Report from a Registered Testing Authority (NATA accreditation No. 1356); and

Volume 1; A0.5(a)/A2.2(a)(v) and Volume 2; 1.0.5(a)/1.2.2(a)(iii) – Report from an appropriately qualified person.

B2 Reports

1. Exova Warrington fire Test Report EWFA Report No. 47288200.1 dated 20 April 2017 (NATA accreditation No. 3277)

This report provides the testing results for Group Rating for the fire test of a room lined with Kingspan Kooltherm® K10G2 panels, tested in accordance with AS ISO 9705-2003 & AS

5637.1:2015.

2. Exova Warrington fire Test Report EWFA Report No. 56093400.3 dated 14 August 2018 (NATA accreditation No. 3277)

This report provides the testing results for Group Rating for the fire test of a room lined with Kingspan K10 FM G2W White Soffit Board, tested in accordance with AS ISO 9705-2003

R2016 & AS 5637.1:2015

3. AWTA Product Testing -Test Report (Test Number 18-006414) for Kingspan Kooltherm® K10 FM G2W Soffit Board dated 22 November 2018 (NATA accreditation No. 1356)

This report provides the testing results for ‘Early Fire Hazard Indices’ for the Kooltherm® K10 External White Soffit Board when tested to AS/NZS 1530.3-1999.

4. AWTA Product Testing -Test Report (Test Number 18-000915) for Kingspan Kooltherm® K10 G2 Soffit Board dated 07 March 2018 (NATA accreditation No. 1356)

This report provides the testing results for ‘Early Fire Hazard Indices’ for the Kooltherm® K10 G2 Soffit Board, when tested to AS/NZS 1530.3-1999.

5. AWTA Product Testing -Test Report (Test Number 18-000773) for Kingspan Kooltherm® K10 G2 Soffit Board dated 22 February 2018 (NATA accreditation No. 1356)

This report provides the testing results for measured heat flux and thermal conductivity of 90mm Kooltherm® K10 G2 Soffit Board, when tested to ASTM C518-2017

6. Acronem Consulting Australia Pty Ltd letter issued by Dr Cameron Chick dated 01 August 2018

This report provides verification from a professional engineer for the Kooltherm® K10 G2 Soffit and Kooltherm® K10 Soffit insulation Board when tested to achieve the noted

Insulation R-Values in the product brochures.