Three-Phase A.C. Circuits Chapter 3 Learning Outcomes This chapter introduces the concepts and principles of the three-phase electrical supply, and the corresponding circuits. On completion you should be able to: 1 Describe the reasons for, and the generation of the three-phase supply. 2 Distinguish between star (3 and 4-wire) and delta connections. 3 State the relative advantages of three-phase systems compared with single-phase-systems. 4 Solve three-phase circuits in terms of phase and line quantities, and the power developed in three-phase balanced loads. 5 Measure power dissipation in both balanced and unbalanced three-phase loads, using the 1, 2 and 3-wattmeter methods, and hence determine load power factor. 6 Calculate the neutral current in a simple unbalanced 4-wire system. 85 3.1 Generation of a Three-Phase Supply In order to understand the reasons for, and the method of generating a three-phase supply, let us firstly consider the generation of a single- phase supply. Alternating voltage is provided by an a.c. generator, more commonly called an alternator. The basic principle was outlined in Fundamental Electrical and Electronic Principles, Chapter 5. It was shown that when a coil of wire, wound on to a rectangular former, is rotated in a magnetic field, an alternating (sinusoidal) voltage is induced into the coil. You should also be aware that for electromagnetic induction to take place, it is the relative movement between conductor and magnetic flux that matters. Thus, it matters not whether the field is static and the conductor moves, or vice versa. For a practical alternator it is found to be more convenient to rotate the magnetic field, and to keep the conductors (coil or winding) stationary.
Transcript

Three-Phase A.C. Circuits

Chapter 3

Learning Outcomes

This chapter introduces the concepts and principles of the three-phase electrical supply, and the corresponding circuits. On completion you should be able to: 1 Describe the reasons for, and the generation of the three-phase supply. 2 Distinguish between star (3 and 4-wire) and delta connections. 3 State the relative advantages of three-phase systems compared with single-phase-systems. 4 Solve three-phase circuits in terms of phase and line quantities, and the power developed in

three-phase balanced loads. 5 Measure power dissipation in both balanced and unbalanced three-phase loads, using the

1, 2 and 3-wattmeter methods, and hence determine load power factor. 6 Calculate the neutral current in a simple unbalanced 4-wire system.

85

3.1 Generation of a Three-Phase Supply

In order to understand the reasons for, and the method of generating a three-phase supply, let us fi rstly consider the generation of a single-phase supply. Alternating voltage is provided by an a.c. generator, more commonly called an alternator. The basic principle was outlined in Fundamental Electrical and Electronic Principles, Chapter 5. It was shown that when a coil of wire, wound on to a rectangular former, is rotated in a magnetic fi eld, an alternating (sinusoidal) voltage is induced into the coil. You should also be aware that for electromagnetic induction to take place, it is the relative movement between conductor and magnetic fl ux that matters. Thus, it matters not whether the fi eld is static and the conductor moves, or vice versa.

For a practical alternator it is found to be more convenient to rotate the magnetic fi eld, and to keep the conductors (coil or winding) stationary.

CH003-H8747.indd 85CH003-H8747.indd 85 4/10/2008 3:24:46 PM4/10/2008 3:24:46 PM

86 Further Electrical and Electronic Principles

In any rotating a.c. machine, the rotating part is called the rotor, and the stationary part is called the stator. Thus, in an alternator, the fi eld system is contained in the rotor. The winding in which the emf is generated is contained in the stator. The reasons for this are as follows:

In this context, the term fi eld refers to the magnetic fi eld. This fi eld is normally produced by passing d.c. current through the rotor winding. Since the winding is rotated, the current is passed to it via copper slip-rings on the shaft. The external d.c. supply is connected to the slip-rings by a pair of carbon brushes.

(a) When large voltages are generated, heavy insulation is necessary. If this extra mass has to be rotated, the driving device has to develop extra power. This will then reduce the overall effi ciency of the machine. Incorporating the winding in the stator allows the insulation to be as heavy as necessary, without adversely affecting the effi ciency.

(b) The contact resistance between the brushes and slip-rings is very small. However, if the alternator provided high current output (in hundreds of ampere), the I 2 R power loss would be signifi cant. The d.c. current (excitation current) for the fi eld system is normally only a few amps or tens of amps. Thus, supplying the fi eld current via the slip-rings produces minimal power loss. The stator winding is simply connected to terminals on the outside of the stator casing.

(c) For very small alternators, the rotor would contain permanent magnets to provide the rotating fi eld system. This then altogether eliminates the need for any slip-rings. This arrangement is referred to as a brushless machine.

The basic construction for a single-phase alternator is illustrated in Fig. 3.1 . The conductors of the stator winding are placed in slots

GJ

L

B

D

FH

S

N

rotor

stator

K

M

A

C

E

Fig. 3.1

CH003-H8747.indd 86CH003-H8747.indd 86 4/10/2008 3:24:50 PM4/10/2008 3:24:50 PM

Three-Phase A.C. Circuits 87

around the inner periphery of the stator. The two ends of this winding are then led out to a terminal block on the casing. The rotor winding is also mounted in slots, around the circumference of the rotor. This fi gure is used to illustrate the principle. A practical machine would have many more conductors and slots.

Since the conductors of the stator winding are spread around the whole of the slots, it is known as a distributed winding. As the rotor fi eld sweeps past these conductors an emf is induced in each of them in turn. These individual emfs reach their maximum values only at the instant that the rotating fi eld ‘ cuts ’ them at 90°. Also, since the slots have an angular displacement between them, then the conductor emfs will be out of phase with each other by this same angle. In Fig. 3.1 there are a total of twelve conductors, so this phase difference must be 30°. The total stator winding emf will therefore not be the arithmetic sum of the conductor emfs, but will be the phasor sum, as shown in Fig. 3.2 . The ratio of the phasor sum to the arithmetic sum is called the distribution factor. For the case shown (a fully distributed winding) the distribution factor is 0.644.

30

EF

GH

LK

M

JD

CB

A

AB, CD etc. are conductor (coil) emfs.AM is the phasor sum

Fig. 3.2

Now, if all of the stator conductors could be placed into a single pair of slots, opposite to each other, then the induced emfs would all be in phase. Hence the phasor and arithmetic sums would be the same, yielding a distribution factor of unity. This is not a practical solution. However, if the conductors are concentrated so as to occupy only one third of the available stator slots, then the distribution factor becomes 0.966. In a practical single-phase alternator, the stator winding is distributed over two thirds of the slots.

Let us return to the option of using only one third of the slots. We will now have the space to put two more identical windings into the stator. Each of the three windings could be kept electrically separate, with their own pairs of terminals. We would then have three separate single-phase alternators in the same space as the original. Each of these would

CH003-H8747.indd 87CH003-H8747.indd 87 4/10/2008 3:24:50 PM4/10/2008 3:24:50 PM

88 Further Electrical and Electronic Principles

also have a good distribution factor of 0.966. The three winding emfs will of course be mutually out of phase with each other by 120°, since each whole winding will occupy 120° of stator space. What we now have is the basis of a three-phase alternator.

The term three-phase alternator is in some ways slightly misleading. What we have, in effect, are three identical single-phase alternators contained in the one machine. The three stator windings are brought out to their own separate pairs of terminals on the stator casing. These stator windings are referred to as phase windings, or phases. They are identifi ed by the colours red, yellow and blue. Thus we have the red, yellow and blue phases. The circuit representation for the stator winding of such a machine is shown in Fig. 3.3 . In this fi gure, the three phase windings are shown connected, each one to its own separate load. This arrangement is known as a three-phase, six-wire system. However, three-phase alternators are rarely connected in this way.

LOAD 2

LOAD 1

LOAD 3

Fig. 3.3

voltageVR

0180 360 θ (deg)

VY VB

Fig. 3.4

Since the three generated voltages are sinewaves of the same frequency, mutually out-of-phase by 120°, then they may be represented both on a waveform diagram using the same angular or time axis, and as phasors. The corresponding waveform and phasor diagrams are shown in Figs. 3.4 and 3.5 respectively. In either case,

CH003-H8747.indd 88CH003-H8747.indd 88 4/10/2008 3:24:51 PM4/10/2008 3:24:51 PM

Three-Phase A.C. Circuits 89

we need to select a reference phasor. By convention, the reference is always taken to be the red phase voltage. The yellow phase lags the red by 120°, and the blue lags the red by 240° (or, if you prefer, leads the red by 120°). The windings are arranged so that when the rotor is driven in the chosen direction, the phase sequence is red, yellow, blue. If, for any reason, the rotor was driven in the opposite direction, then the phase sequence would be reversed, i.e. red, blue, yellow. We shall assume that the normal sequence of R, Y, B applies at all times.

It may be seen from the waveform diagram that at any point along the horizontal axis, the sum of the three voltages is zero. This fact becomes even more apparent if the phasor diagram is redrawn as in Fig. 3.6 . In this diagram, the three phasors have been treated as any other vector quantity. The sum of the vectors may be determined by drawing them to scale, as in Fig. 3.6 , and the resultant found by measuring the distance and angle from the beginning point of the fi rst vector to the arrowhead of the last one. If, as in Fig. 3.6 , the fi rst and last vectors meet in a closed fi gure, the resultant must be zero.

VR

VY

VB

Fig. 3.5

VR

VB VY

Fig. 3.6

3.2 Three-Phase, Four-Wire System

It is not necessary to have six wires from the three phase windings to the three loads, provided there is a common ‘ return ’ line. Each winding will have a ‘ start ’ (S) and a ‘ fi nish ’ (F) end. The common connection mentioned above is achieved by connecting the corresponding ends

CH003-H8747.indd 89CH003-H8747.indd 89 4/10/2008 3:24:51 PM4/10/2008 3:24:51 PM

90 Further Electrical and Electronic Principles

of the three phases together. For example, either the three ‘ F ’ ends or the three ‘ S ’ ends are commoned. This form of connection is shown in Fig. 3.7 , and is known as a star or Y connection. With the resulting 4-wire system, the three loads also are connected in star confi guration. The three outer wires are called the lines, and the common wire in the centre is called the neutral.

S

F

SS

F

F

Fig. 3.7

If the three loads were identical in every way (same impedance and phase angle), then the currents fl owing in the three lines would be identical. If the waveform and/or phasor diagrams for these currents were drawn, they would be identical in form to Figs. 3.4 and 3.5 . These three currents meet at the star point of the load. The resultant current returning down the neutral wire would therefore be zero. The load in this case is known as a balanced load, and the neutral is not strictly necessary. However it is diffi cult, in practice, to ensure that each of the three loads are exactly balanced. For this reason the neutral is left in place. Also, since it has to carry only the relatively small ‘ out-of-balance ’ current, it is made half the cross-sectional area of the lines.

Let us now consider one of the advantages of this system compared with both a single-phase system, and the three-phase 6-wire system. Suppose that three identical loads are to be supplied with 200 A each. The two lines from a single-phase alternator would have to carry the total 600 A required. If a 3-phase, 6-wire system was used, then each line would have to carry only 200 A. Thus, the conductor csa would only need to be 1/3 that for the single-phase system, but of course, being six lines would entail using the same total amount of conductor material. If a 4-wire, 3-phase system is used there will be a saving on conductor costs in the ratio of 3.5:6 (the 0.5 being due to the neutral). If the power has to be sent over long transmission lines, such as the National Grid System, then the 3-phase, 4-wire system yields an enormous saving in cable costs. This is one of the reasons why the power generating companies use three-phase, star-connected generators to supply the grid system.

CH003-H8747.indd 90CH003-H8747.indd 90 4/10/2008 3:24:51 PM4/10/2008 3:24:51 PM

Three-Phase A.C. Circuits 91

3.3 Relationship between Line and Phase Quantities in a Star-connected System

Consider Fig. 3.8 , which represents the stator of a 3-phase alternator connected to a 3-phase balanced load. The voltage generated by each of the three phases is developed between the appropriate line and the neutral. These are called the phase voltages, and may be referred to in general terms as V ph , or specifi cally as V RN , V YN and V BN respectively. However, there will also be a difference of potential between any pair of lines. This is called a line voltage, which may be generally referred to as V L , or specifi cally as V RY , V YB arid V BR respectively.

IL

VLIN

IL

Vph

Vph

Vph

VL

VL

Iph

Iph

Iph

R

N

B

Y

Fig. 3.8

VYN

VBN

VYN C

B

0 AVRN

30

30

Fig. 3.9

A line voltage is the phasor difference between the appropriate pair of phase voltages. Thus, V RY is the phasor difference between V RN and V YN . In terms of a phasor diagram, the simplest way to subtract one phasor from another is to reverse one of them, and then fi nd the resulting phasor sum. This is, mathematically, the same process as saying that a b a ( b). The corresponding phasor diagram is shown in Fig. 3.9 .

CH003-H8747.indd 91CH003-H8747.indd 91 4/10/2008 3:24:51 PM4/10/2008 3:24:51 PM

92 Further Electrical and Electronic Principles

Note : If V YN is reversed, it is denoted either as V YN or as V NY . We shall use the fi rst of these.

The phasor difference between V RN and V YN is simply the phasor sum of V RN ( V YN ). Geometrically this is obtained by completing the parallelogram as shown in Fig. 3.9 . This parallelogram consists of two isosceles triangles, such as OCA. Another property of a parallelogram is that its diagonals bisect each other at right angles. Thus, triangle OCA consists of two equal right-angled triangles, OAB and ABC. This is illustrated in Fig. 3.10 . Since triangle OAB is a 30°, 60°, 90° triangle, then the ratios of its sides AB:OA:OB will be 1:2:3

– respectively.

B

30° 60°

O A

C

Fig. 3.10

Hence, OB

OA

so OBOA

but OC OB OA

and since OC ,

3

2

3

22 3

.

.

VRY and OA

then

V

V VRN

RY RN3

Using the same technique, it can be shown that:

V V V VYB YN BR BN 3 3 and

Thus, in star configuration, V VL ph 3

(3.1)

The complete phasor diagram for the line and phase voltages for a star connection is shown in Fig. 3.11 . Also, considering the circuit diagram of Fig. 3.8 , the line and phase currents must be the same.

Hence, in star configuration, I IL ph (3.2)

We now have another advantage of a 3-phase system compared with single-phase. The star-connected system provides two alternative voltage outputs from a single machine. For this reason, the stators of all alternators used in electricity power stations are connected in star confi guration. These machines normally generate a line voltage

CH003-H8747.indd 92CH003-H8747.indd 92 4/10/2008 3:24:52 PM4/10/2008 3:24:52 PM

Three-Phase A.C. Circuits 93

of about 25 kV. By means of transformers, this voltage is stepped up to 400 kV for long distance transmission over the National Grid. For more localised distribution, transformers are used to step down the line voltage to 132 kV, 33 kV, 11 kV, and 415 V. The last three of these voltages are supplied to various industrial users. The phase voltage derived from the 415 V lines is 240 V, and is used to supply both commercial premises and households.

Worked Example 3.1

Q A 415 V, 50 Hz, 3-phase supply is connected to a star-connected balanced load. Each phase of the load consists of a resistance of 25 and inductance 0.1 H, connected in series. Calculate (a) phase voltage, (b) the line current drawn from the supply, and (c) the power dissipated.

A

Whenever a three-phase supply is specifi ed, the voltage quoted is always the line voltage. Also, since we are dealing with a balanced load, then it is necessary only to calculate values for one phase of the load. The fi gures for the other two phases and lines will be identical to these.

V L 415 V; f 50 Hz; R ph 25 ; L ph 0.1 H

IL Iph

VL 0.1 H

Vph

25 Ω

Fig. 3.12

VBN

VRN

VRYVBR

VYN

VYB

30°

30°

30°

Fig. 3.11

CH003-H8747.indd 93CH003-H8747.indd 93 4/10/2008 3:24:52 PM4/10/2008 3:24:52 PM

94 Further Electrical and Electronic Principles

(a)

VV

V

phL

ph

34 5

3240

1

so V Ans

(b) Since it is possible to determine the impedance of a phase of the load, andwe now know the phase voltage, then the phase current may be calculated:

X fL

X

Z R X

L

L

ph ph L

2 2 50 0

3 42

25 32 2 2

ohm

hence

ohm

.

.

1

1

11

1

1

.

.

.

.

42

40 5

24040 5

5 98

2

Z

V

Z

ph

phph

ph

ph

I

I

amp

so A

In a star-connected circuit, I L I Ph therefore I L 5.98 A Ans

The power in one phase, wattP R

P

ph ph ph

ph

I 2

25 98 25

893 2

.

. 99 W

and since there are three phases, then the total power is:

P P

Pph

3 3 893 29

2 68

watt

hence kW

.

. Ans

3.4 Delta or Mesh Connection

If the start end of one winding is connected to the fi nish end of the next, and so on until all three windings are interconnected, the result is the delta or mesh connection. This connection is shown in Fig. 3.13 . The delta connection is not reserved for machine windings only, since a 3-phase load may also be connected in this way.

IL

IL

VL

Iph

Iph Iph

IL

SF

F

F

S

S

Fig. 3.13

CH003-H8747.indd 94CH003-H8747.indd 94 4/10/2008 3:24:53 PM4/10/2008 3:24:53 PM

Three-Phase A.C. Circuits 95

3.5 Relationship between Line and Phase Quantities in a Delta-connected System

It is apparent from Fig. 3.13 that each pair of lines is connected across a phase winding. Thus, for the delta connection:

V VL ph

(3.3)

It is also apparent that the current along each line is the phasor difference of a pair of phase currents. The three phase currents are mutually displaced by 120°, and the phasor diagram for these is shown in Fig. 3.14 . Using exactly the same geometrical technique as that for the phase and line voltages in the star connection, it can be shown that:

I IL ph 3

(3.4)

IB(ph)

IY(ph)

IR(ph)120°

120°120°

Fig. 3.14

The phasor diagram for the phase and line currents in delta connection is as in Fig. 3.15 . Note that the provision of a neutral wire is not applicable with a delta connection. However, provided that the load

IL

IL

IL

Iph

Iph

Iph

30°

30°

30°

Fig. 3.15

CH003-H8747.indd 95CH003-H8747.indd 95 4/10/2008 3:24:53 PM4/10/2008 3:24:53 PM

96 Further Electrical and Electronic Principles

is balanced, there is no requirement for one. Under balanced load conditions the three phase currents will be equal, as will be the three line currents. If the load is unbalanced, then these equalities do not exist, and each phase or line current would have to be calculated separately. This technique is beyond the scope of the syllabus you are now studying.

Worked Example 3.2

Q A balanced load of phase impedance 120 is connected in delta. When this load is connected to a 600 V, 50 Hz, 3-phase supply, determine (a) the phase current, and (b) the line current drawn.

A

Z ph 120 ; V L 600 V; f 50 Hz

The circuit diagram is shown in Fig. 3.16 .

IL

Iph

VL Vph 600 V

Z 120 Ω

Fig. 3.16

(a)

In delta, V

amp

so, A

V V

V

Z

ph L

phph

ph

ph

600

60020

5

I

I

1

Ans

(b)

in delta, amp

therefore A

I I

IL ph

L

3 3 5

8 66. Ans

3.6 Power Dissipation in Star and Delta-connected Loads

We have seen in Example 3.1 that the power in a 3-phase balanced load is obtained by multiplying the power in one phase by 3. In many practical situations, it is more convenient to work with line quantities.

P ph V ph I ph cos φ watt

where cos φ is the phase power factor.

total power,

cos watt.............

P P

V Iph

ph ph

3

3 1φ [ ]

CH003-H8747.indd 96CH003-H8747.indd 96 4/10/2008 3:24:54 PM4/10/2008 3:24:54 PM

Three-Phase A.C. Circuits 97

Considering a STAR-connected load,

V

VI Iph

Lph L

3, and

Substituting for V ph and I ph in eqn [1]:

P

VIL

L 33

cos φ

therefore cos wattP V IL L 3 φ (3.5)

For a delta-connected load,

V V I

Iph L ph

ph and

3

and substituting these values into eqn [1] will yield the same result as shown in (3.5) above. Thus, the equation for determining power dissipation, in both star and delta-connected loads is exactly the same. However, the value of power dissipated by a given load when connected in star is not the same as when it is connected in delta. This is demonstrated in the following example.

Worked Example 3.3

Q A balanced load of phase impedance 100 and power factor 0.8 is connected (a) in star, and (b) in delta, to a 400 V, 3-phase supply. Calculate the power dissipation in each case.

A

Z ph 100 ; cos φ 0.8; V L 400 V

(a) the circuit diagram is shown in Fig. 3.17

VL 400 V

Z 100 ΩVph

IL Iph

Fig. 3.17

CH003-H8747.indd 97CH003-H8747.indd 97 4/10/2008 3:24:54 PM4/10/2008 3:24:54 PM

98 Further Electrical and Electronic Principles

VV

V

V

Z

phL

ph

L phph

ph

L

3400

323

2300

volt

so V

amp

and

1

1

1I I

I

2 3

3 3 400 2 3 0 8

28

.

. .

.

1

1

1

A

cos watt

therefore kW

P V

PL LI φ

Ans

(b) The circuit diagram is shown in Fig. 3.18 .

IL

Iph

VL Vph 400 V

Z 100 Ω

Fig. 3.18

V V

V

Z

ph L

phph

ph

ph

L ph

400

40000

4

3 3 4

V

amp

so A

but

so

I

I

I I

1

A

cos watt

therefore

I

I

L

L LP V

P

6 93

3 3 400 6 93 0 8

3 8

.

. .

.

φ

44 kW Ans

Comparing the two answers for the power dissipation in the above example, it may be seen that:

Power in a delta-connected load is that when i

three timestt is connected in star configuration.

(3.6)

Worked Example 3.4

Q A balanced star-connected load is fed from a 400 V, 50 Hz, three-phase supply. The resistance in each phase of the load is 10 and the load draws a total power of 15 kW. Calculate (a) the line current drawn, (b) the load power factor, and (c) the load inductance.

A

V L 400 V; f 50 Hz; R 10 ; P 15 000 W

CH003-H8747.indd 98CH003-H8747.indd 98 4/10/2008 3:24:54 PM4/10/2008 3:24:54 PM

Three-Phase A.C. Circuits 99

(a) The power in one phase will be one third of the total power, so

PP

P R

P

R

ph

ph ph

L phph

35 000

35

2

watt

kW

but, watt

so,

1

I

I I55000

022 36

1

IL . A Ans

(b)

P V

PV

L L

L L

3

35 000

3 400 22 36

I

I

cos watt

so, cos p.f.

φ

φ1

.

hhence, p.f. 0 968. Ans

(c)

φ

φ

cos

tan

so,

1 1

1

1 1

0 968 4 47

0 258

0 0 258 2

. .

.

.

X

R

X

ph

ph

ph ..

.

.

58

22 58100

8 22

1

1L

Xf

L

L

ohm

and mH Ans

400 VVL

R

L

10 Ω

Fig. 3.19

φ

Zph

Xph

Rph

Fig. 3.20

CH003-H8747.indd 99CH003-H8747.indd 99 4/10/2008 3:24:55 PM4/10/2008 3:24:55 PM

100 Further Electrical and Electronic Principles

Worked Example 3.5

Q A balanced delta-connected load takes a phase current of 15 A at a power factor of 0.7 lagging when connected to a 115 V, 50 Hz, three-phase supply. Calculate (a) the power drawn from the supply, and (b) the resistance in each phase of the load.

A

V L V ph 115 V; f 50 Hz; I ph 15 A; cos φ 0.7

(a)

I I

I

I

L ph

L

L LP V

3 3 5

25 98

3 3 5 25 98 0

amp

A

cos watt

1

11

.

. .φ 773622 5so W P . Ans

(b)

PP

P R

RP

ph

ph ph

ph

ph

33622 5

3207 5

2

2

..1

1

W

and watt

so ohm

I

I

2207 55

5 37

2

.

.

1

R Ans

3.7 Star/Delta Supplies and Loads

As explained in Section 3.3, the distribution of 3-phase supplies is normally at a much higher line voltage than that required for many users. Hence, 3-phase transformers are used to step the voltage down to the appropriate value. A three-phase transformer is basically three single-phase transformers interconnected. The three primary windings may be connected either in star or delta, as can the three secondary windings. Similarly, the load connected to the transformer secondary windings may be connected in either confi guration. One important point to bear in mind is that the transformation ratio (voltage or turns ratio) refers to the ratio between the primary phase to the secondary phase winding. The method of solution of this type of problem is illustrated in the following worked example.

115 VVL Vph

R

L

IL

Iph15 A

Fig. 3.21

CH003-H8747.indd 100CH003-H8747.indd 100 4/10/2008 3:24:55 PM4/10/2008 3:24:55 PM

Three-Phase A.C. Circuits 101

Worked Example 3.6 Q Figure 3.22 shows a balanced, star-connected load of phase impedance 25 and power factor

0.75, supplied from the delta-connected secondary of a 3-phase transformer. The turns ratio of the transformer is 20:1, and the star-connected primary is supplied at 11 kV. Determine (a) the voltages V 2 , V 3 and V 4 , (b) the currents I1, I 2 , and I 3 , and (c) the power drawn from the supply.

I1

I2

I3

V3

V4Z25Ωcosφ0.75

V2

20:1

V111 kV

Fig. 3.22

A

V 1 11 000 V; N p /N s 20/1; Z ph 25 ; cos φ 0.75

(a)

VV

V

VV

NN

VN VN

s

p

s

p

21

2

3

2

32

311 000

36 351

635

kV

so volt

. Ans

1120

317 45

3317 45

3183 3

3

43

4

hence V

and V

V

VV

V

.

.

.

Ans

Ans

(b) In order to calculate the currents, we shall have to start with the load, and work ‘ back ’ through the circuit to the primary of the transformer:

I

I

II

I

I

34

3

23

2

83 325

7 33

37 33

34 23

VZ ph

amp

A

A

1

1

.

.

.

.

Ans

Ans

II

II

I

2

2 4 2320

0 2 2

NN

NN

s

p

s

pso amp

hence A

1

1 1

.

. Ans

CH003-H8747.indd 101CH003-H8747.indd 101 4/10/2008 3:24:55 PM4/10/2008 3:24:55 PM

102 Further Electrical and Electronic Principles

(c)

P V

P

3

3 0 0 2 2 0 75

3 02

3

cos watt

therefore kW

1 1

11 1 1

I φ

. .

. AAns

Worked Example 3.7

Q The star-connected stator of a three-phase, 50 Hz alternator supplies a balanced delta-connected load. Each phase of the load consists of a coil of resistance 15 and inductance 36 mH, and the phase voltage generated by the alternator is 231 V. Calculate (a) the phase and line currents, (b) the load power factor, and (c) the power delivered to the load.

A

f 50 Hz; R 15 ; L 36 mH; V ph 231 V

R

L

I2I1

V2

36 mH

15 Ω

V1

231 V

Fig. 3.23

(a)

For the alternator:

V V

V V V

V

ph

L ph

ph L

1

1

1

23 V

V2

2

3

400

I I I

For the load:

V V V

X fL

X

Z R X

L ph

L

L

ph L

2

3

2

2 00 36 0

3

400 V

ohm

1 1

11 1.

22 2 2

2

2

5 3

8 79

4008 79

2

ohm

amp

1 11 1

1

1

1

.

.

.

Z

V

Z

ph

phph

ph

I I

I ..

.

.

29

3 3 2 29

36 882

A

A

Ans

Ans

I I I

IL

1

1

1

(b)

p.f. cos

p.f. lagging

φRZ

1

1

58 79

0 8.

. Ans

CH003-H8747.indd 102CH003-H8747.indd 102 4/10/2008 3:24:56 PM4/10/2008 3:24:56 PM

Three-Phase A.C. Circuits 103

(c)

P VP

L L

3 3 400 36 88 0 820 4

I cos wattkW

Alternativel

φ . .. Ans

yy, watt

kW

P P R

P

ph

3 3

3 2 29 520 4

22

2

I

1 1.. Ans

3.8 Measurement of Three-phase Power

In an a.c. circuit the true power may only be measured directly by means of a wattmeter. The principle of operation of this instrument is described in Fundamental Electrical and Electronic Principles, Chapter 5. As a brief reminder, the instrument has a fi xed coil through which the load current fl ows, and a moving voltage coil (or pressure coil) connected in parallel with the load. The defl ection of the pointer, carried by the moving coil, automatically takes into account the phase angle (or power factor) of the load. Thus the wattmeter reading indicates the true power, P VI cos φ watt.

If a three-phase load is balanced, then it is necessary only to measure the power taken by one phase. The total power of the load is then obtained by multiplying this fi gure by three. This technique can be very simply applied to a balanced, star-connected system, where the star point and/or the neutral line are easily accessible. This is illustrated in Fig. 3.24 .

R

N

B

Y

W1

Fig. 3.24

In the situation where the star point is not accessible, then an artifi cial star point needs to be created. This is illustrated in Fig. 3.25 , where the value of the two additional resistors is equal to the resistance of the wattmeter voltage coil.

In the case of an unbalanced star-connected load, one or other of the above procedures would have to be repeated for each phase in turn. The total power P P 1 P 2 P 3 , where P 1 , P 2 and P 3 represent the three separate readings.

CH003-H8747.indd 103CH003-H8747.indd 103 4/10/2008 3:24:56 PM4/10/2008 3:24:56 PM

104 Further Electrical and Electronic Principles

For a delta-connected load, the procedure is not quite so simple. The reason is that the phase current is not the same as the line current. Thus, if possible, one of the phases must be disconnected to allow the connection of the wattmeter current coil. This is shown in Fig. 3.26 . Again, if the load was unbalanced, this process would have to be repeated for each phase.

W1R

B

Y

R R

Fig. 3.25

W1R

B

Y

Fig. 3.26

3.9 The Two-Wattmeter Method

The measurement of three-phase power using the above methods can be very awkward and time-consuming. In practical circuits, the power is usually measured by using two wattmeters simultaneously, as shown in Fig. 3.27 .

The advantages of this method are:

(a) Access to the star point is not required. (b) The power dissipated in both balanced and unbalanced loads is

obtained, without any modifi cation to the connections. (c) For balanced loads, the power factor may be determined.

CH003-H8747.indd 104CH003-H8747.indd 104 4/10/2008 3:24:57 PM4/10/2008 3:24:57 PM

Three-Phase A.C. Circuits 105

Considering Fig. 3.27 , the following statements apply:

Instantaneous power for wattand for ,

1

2 2

W p v i

W p vRB R

YB

, 1

ii

p p

v i v i

Y

RB R YB Y

watttotal instantaneous power

]

1 2

1………[

Now, any line voltage is the phasor difference between the appropriate pair of phase voltages, hence:

v v v v v vRB RN BN YB YN BN and

and substituting these into eqn [1] yields:

p p i v v i v v

v i v i v i i

i

R RN BN Y YN BN

RN R YN Y BN R Y

1 2

( ) ( )

( )

but, RR Y Bi i

i.e. the phasor sum of three equal currents is zero.

therefore p p v i v i v iRN R YN Y BN B1 2

The instantaneous sum of the powers measured by the two wattmeters is equal to the sum of instantaneous power in the three phases.

Hence, total power,

P P P P P PR Y B 1 2 watt (3.7)

Consider now the phasor diagram for a resistive-inductive balanced load, with the two wattmeters connected as in Fig. 3.27 . This phasor diagram appears as Fig. 3.28 , below.

W1

W2

IB

IY

VRB

VYB

IRR

B

Y

Fig. 3.27

CH003-H8747.indd 105CH003-H8747.indd 105 4/10/2008 3:24:57 PM4/10/2008 3:24:57 PM

106 Further Electrical and Electronic Principles

The power indicated by W 1 ,

P V IL L1 cos (30 )φ (3.8)

and that for W 2 ,

P V IL L2 cos (30 )φ (3.9)

From these results, and using Fig. 3.29 , the following points should be noted:

IB

φ

φ

φ

VBRVBN VR

VRN

VRBVYN

VYB

IY

IR(30° φ)

(30° φ)

Fig. 3.28

wattmeterreadings

90 30 30 90 150 (30° φ)

Fig. 3.29

1 If the load p.f. 0.5 (i.e. φ 60°); both meters will give a positive reading.

2 If the load p.f. 0.5 (i.e. φ 60°); W 1 indicates the total power, and W 2 indicates zero.

3 If the load p.f. 0.5 (i.e. φ 60°); W 2 attempts to indicate a negative reading. In this case, the connections to the voltage coil

CH003-H8747.indd 106CH003-H8747.indd 106 4/10/2008 3:24:57 PM4/10/2008 3:24:57 PM

Three-Phase A.C. Circuits 107

of W 2 need to be reversed, and the resulting reading recorded as a negative value. Under these circumstances, the total load power will be P P 1 P 2 .

4 The load power factor may be determined from the two wattmeter readings from the equation:

φ

tan 1 2 1

2 1

3P P

P P

⎝⎜⎜⎜⎜

⎠⎟⎟⎟⎟

(3.10)

hence, power factor, cos φ can be determined.

Worked Example 3.8

Q The power in a 3-phase balanced load was measured, using the two-wattmeter method. The recorded readings were 3.2 kW and 5 kW respectively. Determine the load power and power factor .

A

P PP P PP

1

1

3 2 53 2

8 2

2

2

..

.

kW; kW watt ( 5) kW

therefore, kW AAns

φ

tan

tan

1 1

1

1

3

35 3 25 3 2

2

2

P PP P

⎝⎜⎜⎜⎜

⎠⎟⎟⎟⎟⎟

⎛⎝⎜⎜⎜

⎞.. ⎠⎠

⎟⎟⎟⎟

hence, and p.f. cos

φφ

20 820 935

.. Ans

Worked Example 3.9

Q A 3-phase balanced load takes a line current of 24 A at a lagging power factor of 0.42, when connected to a 415 V, 50 Hz supply. If the power dissipation is measured using the two-wattmeter method, determine the two wattmeter readings, and the value of power dissipated. Comment on the results.

A

I L 24 A; cos φ 0.42; V L 415 V

φφ

cos cos (30 ) watt

cos (

1

1

1

1

0 42 65 7

4 5 24

. .P VL LI

335 78 42

302

..

111

)therefore, kW

cos ( ) watt

PP VL L

AnsI φ

44 5 24 95 7896 72

2

1 1

1

cos ( )therefore, W

watt

..P

P P PAns

88 42 896 77 244

1

( )hence, kW

..P Ans

To obtain the negative reading on W 2 , the connections to its voltage coil must have been reversed.

CH003-H8747.indd 107CH003-H8747.indd 107 4/10/2008 3:24:58 PM4/10/2008 3:24:58 PM

108 Further Electrical and Electronic Principles

Worked Example 3.10

Q A delta-connected load has a phase impedance of 100 at a phase angle of 55°, and is connected to a 415 V three-phase supply. The total power consumed is measured using the two-wattmeter method. Determine the readings on the two meters and hence calculate the power consumed .

A

Z ph 100 ; φ 55°; V L 415 V V ph

VL 415 V

VL 415 V

IL

ILW1

W2

Zph

100 Ω

Fig. 3.30

I

I I

I

phph

ph

L ph

L L

V

Z

P V

amp A

A

c

4 500

4 5

3 3 4 5 7 9

1

11

1 1

1

.

. .

oos ( ) watt cos

kW

cos

30 4 5 7 9 25

2 704

2

φ 1 1

1

.

.P

P VL L

Ans

I ( ) watt cos 85

W

watt

30 4 5 7 9

260

2702

2

φ 1 1

1

.

P

P P P

Ans

44 2602 964

P . kW Ans

3.10 Neutral Current in an Unbalanced Three-phase Load

We have seen that the neutral current for a balanced load is zero. This is because the phasor sum of three equal currents, mutually displaced by 120°, is zero. If the load is unbalanced, then the three line (and phase) currents will be unequal. In this case, the neutral has to carry the resulting out-of-balance current. This current is simply obtained by calculating the phasor sum of the line currents. The technique is basically the same as that used previously, by resolving the phasors into horizontal and vertical components, and applying Pythagoras ’ theorem. The only additional fact to bear in mind is that both horizontal and vertical components can have negative values. This is illustrated by the following example.

CH003-H8747.indd 108CH003-H8747.indd 108 4/10/2008 3:24:58 PM4/10/2008 3:24:58 PM

Three-Phase A.C. Circuits 109

Worked Example 3.11

Q An unbalanced, star-connected load is supplied from a 3-phase, 415 V source. The three phase loads are purely resistive. These loads are 25 , 30 and 40 , and are connected in the red, yellow and blue phases respectively. Determine the value of the neutral current, and its phase angle relative to the red phase current.

A

V L 415 V; R R 25 ; R Y 30 ; R B 40

The circuit diagram is shown in Fig. 3.31.

Vph

VL

IR

IY

IB

IN

R

Y

B

30 Ω

40 Ω

25 Ω

Fig. 3.31

VV

V

R

V

R

V

R

phL

Rph

RY

ph

YB

ph

B

34 5

3240 volt V

amp; amp;

1

I I I amp

A A A

24025

24030

24040

9 6 8 6I I IR Y B.

The corresponding phasor diagrams are shown in Fig. 3.32 .

IB

IY

IR

INV.C.

H.C.

φ

60 °

60 °

Fig. 3.32

CH003-H8747.indd 109CH003-H8747.indd 109 4/10/2008 3:24:58 PM4/10/2008 3:24:58 PM

110 Further Electrical and Electronic Principles

Horizontal components, H.C. cos cos

(

I I IR Y B60 60

9 6. 88 0 5 6 0 5

2 6

. .

.

) ( )

so, H.C. A

Vertical components, V.C. IB ssin sin

( ) ( )

so V.C. A

The

60 60

6 0 866 8 0 866

732

IY

. .

.1

neutral current, V.C. H.C. amp

hence,

I

I

N

2 2

2 2732 2 61. .

NN

3 24

7322 6

33

.

..

.

1

11 1

A

tanV.C.H.C.

tan

hence,

Ans

φ

φ 667 relative to IR Ans

3.11 Advantages of Three-phase Systems

In previous sections, some of the advantages of three-phase systems, compared with single-phase systems, have been outlined. These advantages, together with others not yet described, are listed below. The advantages may be split into two distinct groups: those concerned with the generation and distribution of power, and those concerning a.c. motors. The last four of the advantages listed refer to the second group, and their signifi cance will be appreciated when you have completed Chapter 5, which deals with a.c. machines.

1 The whole of the stator of a three-phase machine is utilised. A single phase alternator utilises only two thirds of the stator slots.

2 A three-phase alternator has a better distribution factor. 3 A three-phase, four-wire system provides considerable savings

in cable costs, for the distribution of an equivalent amount of power.

4 A three-phase, four-wire system provides alternative voltages for industrial and domestic users.

5 For a given machine frame size, the power output from a three-phase machine is greater than that from a single-phase machine.

6 A three-phase supply produces a rotating magnetic fi eld; whereas a single-phase supply produces only a pulsating fi eld.

7 Three-phase motors are inherently self-starting; whereas single-phase motors are not.

8 The torque produced by a three-phase motor is smooth; whereas that produced by a single-phase motor is pulsating.

CH003-H8747.indd 110CH003-H8747.indd 110 4/10/2008 3:24:59 PM4/10/2008 3:24:59 PM

111

Summary of Equations

Phase and line quantities: In star, I L I ph ; V L 3Vph

In delta , V L V ph ; I L 3I ph

Power dissipation: P V IL L 3 cos wattφ

P P V I I Rph ph ph ph ph 3 3 3 2 cos wattφ

and for the same load, P (delta) 3 P (star)

Power measurement: For two wattmeter method: P P 1 P 2 watt

Load phase angle, tanφ

1 2 1

2 1

3P P

P P

⎝⎜⎜⎜⎜

⎠⎟⎟⎟⎟

Three-Phase A.C. Circuits

CH003-H8747.indd 111CH003-H8747.indd 111 4/10/2008 3:24:59 PM4/10/2008 3:24:59 PM

112 Fundamental Electrical and Electronic PrinciplesFurther Electrical and Electronic Prinicples

1 A three-phase load is connected in star to a 400 V, 50 Hz supply. Each phase of the load consists of a coil, having inductance 0.2 H and resistance 40 . Calculate the line current.

2 If the load specifi ed in Question 1 above is now connected in delta, determine the values for phase and line currents.

3 A star-connected alternator stator generates 300 V in each of its stator windings. (a) Sketch the waveform and phasor diagrams for the phase voltages, and (b) calculate the p.d. between any pair of lines.

4 A balanced three-phase, delta-connected load consists of the stator windings of an a.c. motor. Each winding has a resistance of 3.5 and inductance 0.015 H. If this machine is connected to a 415 V, 50 Hz supply, calculate (a) the stator phase current, (b) the line current drawn from the supply, and (c) the total power dissipated.

5 Repeat the calculations for Question 4, when the stator windings are connected in star confi guration.

6 Three identical coils, connected in star, take a total power of 1.8 kW at a power factor of 0.35, from a 415 V, 50 Hz supply. Determine the resistance and inductance of each coil.

7 Three inductors, each of resistance 12 and inductance 0.02 H, are connected in delta to a 400 V, 50 Hz, three-phase supply. Calculate (a) the line current, (b) the power factor, and (c) the power consumed.

8 The star-connected secondary of a three-phase transformer supplies a delta-connected motor, which takes a power of 80 kW, at a lagging power factor of 0.85. If the line voltage is 600 V, calculate (a) the current in the transformer secondary windings, and (b) the current in the motor windings.

9 A star-connected load, each phase of which has an inductive reactance of 40 and resistance of 25 , is fed from the secondary of a three-phase, delta-connected transformer.

If the transformer phase voltage is 600 V, calculate (a) the p.d. across each phase of the load, (b) the load phase current, (c) the current in the transformer secondary windings, and (d) the power and power factor.

10 Three coils are connected in delta to a 415 V, 50 Hz, three-phase supply, and take a line current of 4.8 A at a lagging power factor of 0.9. Determine (a) the resistance and inductance of each coil, and (b) the power consumed.

11 The power taken by a three-phase motor was measured using the two-wattmeter method. The readings were 850 W and 260 W respectively. Determine (a) the power consumption and, (b) the power factor of the motor.

12 Two wattmeters, connected to measure the power in a three-phase system, supplying a balanced load, indicate 10.6 kW and 2.4 kW respectively. Calculate (a) the total power consumed, and (b) the load phase angle and power factor. State the signifi cance of the negative reading recorded.

13 Using the two-wattmeter method, the power in a three-phase system was measured. The meter readings were 120 W and 60 W respectively. Calculate (a) the power, and (b) the power factor.

14 Each branch of a three-phase, star-connected load, consists of a coil of resistance 4 and reactance 5 . This load is connected to a 400 V, 50 Hz supply. The power consumed is measured using the two-wattmeter method. Sketch a circuit diagram showing the wattmeter connections, and calculate the reading indicated by each meter.

15 A three-phase, 415 V, 50 Hz supply is connected to an unbalanced, star-connected load, having a power factor of 0.8 lagging in each phase. The currents are 40 A in the red phase, 55 A in the yellow phase, and 62 A in the blue phase. Determine (a) the value of the neutral current, and (b) the total power dissipated.

Assignment Questions

112

CH003-H8747.indd 112CH003-H8747.indd 112 4/10/2008 3:24:59 PM4/10/2008 3:24:59 PM

Fundamental Electrical and Electronic Principles 113 Fundamental Electrical and Electronic Principles 113 Three-Phase A.C. Circuits

Suggested Practical Assignments

Assignment 1 To determine the relationship between line and phase quantities in three-phase systems.

Apparatus: Low voltage, 50 Hz, three-phase supply 3 1 k rheostats 3 ammeters 3 voltmeters (preferably DMM)

Method:

1 Using a digital meter, adjust each rheostat to exactly the same value (1 k ). 2 Connect the rheostats, in star confi guration, to the three-phase supply. 3 Measure the three line voltages and the corresponding phase voltages, and

record your results in Table 1. 4 Measure the three line currents, and record these in Table 1. 5 Check that the neutral current is zero. 6 Carefully unbalance the load by altering the resistance value of one or two

of the rheostats. ENSURE that you do not exceed the current ratings of the rheostats.

7 Measure and record the values of the three line currents and the neutral current, in Table 2.

8 Switch off the three-phase supply, and disconnect the circuit. 9 Carefully reset the three rheostats to their original settings, as in paragraph

1 of the Method. 10 Connect the rheostats, in delta confi guration, to the three-phase supply,

with an ammeter in each line. 11 Switch on the supply, and measure the line voltages and line currents.

Record your values in Table 3. 12 Switch off the supply, and connect the three ammeters in the three phases

of the load, i.e. an ammeter in series with each rheostat. This will involve opening each phase and inserting each ammeter.

13 Switch on and record the values of the three phase currents. Record values in Table 3.

14 From your tabulated readings, determine the relationship between line and phase quantities for both star and delta connections.

15 From your readings in Table 2, calculate the neutral current, and compare this result with the measured value.

16 Write an assignment report. Include all circuit and phasor diagrams, and calculations. State whether the line and phase relationships measured conform to those expected (allowing for experimental error).

Assignment 2 To measure the power in three-phase systems, using both single and two-wattmeter methods.

Apparatus: Low voltage, 50 Hz, three-phase supply 3 1 k rheostats 2 wattmeters 1 DMM

113

CH003-H8747.indd 113CH003-H8747.indd 113 4/10/2008 3:24:59 PM4/10/2008 3:24:59 PM

114

Method:

1 As for Assignment 1, carefully adjust the three rheostats to the same value (1 k ) .

2 Connect the circuit shown in Fig. 3.33 , and measure the power in the red and yellow phases.

W1

W2

R

N

Y

B

Fig. 3.33

W1

W2

R

B

Y

Fig. 3.34

3 Transfer one of the wattmeters to the blue phase, and measure that power. 4 Add the three wattmeter readings to give the total power dissipation. Check

to see whether this is three times the individual phase power. 5 Switch off the power supply, and reconnect as in Fig. 3.34.

6 Record the two wattmeter readings, and check whether their sum is equal to the total power recorded from paragraph 4 above.

7 Switch off the power supply and reconnect the circuit as in Fig. 3.35 . 8 Record the two wattmeter readings. 9 Switch off the supply, and transfer one of the wattmeters to the third phase. 10 Record this reading. Add the three readings to give the total power, and

check that this is three times the phase power. 11 Switch off the supply and connect the circuit of Fig. 3.36 . 12 Record the two wattmeter readings, and check that their sum equals the

total power obtained from paragraph 10 above.

114 Further Electrical and Electronic Principles

CH003-H8747.indd 114CH003-H8747.indd 114 4/10/2008 3:25:00 PM4/10/2008 3:25:00 PM

W1

W2

R

B

Y

Fig. 3.35

W1

W2

R

B

Y

Fig. 3.36

Assignment 3 Show how the two-wattmeter method of power measurement can be accomplished by means of a single wattmeter, together with a suitable switching arrangement. You may either devise your own system, or discover an existing system through library research.