+ All Categories
Home > Documents > Tiger Controls TC500-01

Tiger Controls TC500-01

Date post: 11-Mar-2016
Category:
Upload: amtenco-amtenco
View: 285 times
Download: 9 times
Share this document with a friend
Description:
Tiger Controls TC500-01
6
1 Applic ation Functions 3-position control type TC500-D.../ TC1 000-D... Electric Actuator Used in valves which stroke 20mm. Rating force 500N/ 1000N TC500-D...Series TC1000-D..Series TC500-X24...Series TC1000-X24...Series Datasheet No.: TC500-01 l TC500-D.../ TC1000-D... : 3-position control type l TC500-X24.../ TC1000-X24... : proportional control type l Actual force: 500N~700N/ 1000N~1200N l 24VAC/ 220VAC ±15% can be selected (only 3-position control type) l 2K resistance or SPDT feedback available (only 3-position control type) These actuators used in 2-port, 3-port valve (TF,TL,TW,...series), whose stroke is less than 23 mm . Enviroment tempreture: -10~60℃( 3-position type)/ -10~50℃( proportional typePermissible medium temperature: -25~+130(water valve) / 2~+180℃( steam valve) Notes: 1. If the medium tempreature between 2~+220℃( high tempreature steam valve), 2~+450℃( super-high tempreature steam valve), the actuators bracket should be made more higher, the type should be add "G" in front o f ".12'. For example: change "TC500-D220-S.12" to ""TC500-D220-S G.12". 2. When medium temperature below 0 (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating sheath to avoid frosting and icing. Voltage on terminal 1 and 2: the actuator axes extends, and valve stem retracts Voltage on terminal 1 and 3: the actuator axes retracts, and valve stem extends No voltage interminal 1,2 or 1,3: the actuator axes and valve stem keep its position
Transcript
Page 1: Tiger Controls TC500-01

1

Application

Functions

3-position control

type

TC500-D.../

TC1000-D...

Electric Actuator Used in valves which stroke≦20mm. Rating force 500N/ 1000N

TC500-D...Series TC1000-D..Series TC500-X24...Series TC1000-X24...Series

Datasheet No.: TC500-01

l TC500-D.../ TC1000-D... : 3-position control type

l TC500-X24.../ TC1000-X24... : proportional control type

l Actual force: 500N~700N/ 1000N~1200N

l 24VAC/ 220VAC ±15% can be selected (only 3-position control type)

l 2K resistance or SPDT feedback available (only 3-position control type)

These actuators used in 2-port, 3-port valve (TF,TL,TW,...series), whose stroke is less than 23 mm.

Enviroment tempreture: -10~60℃(3-position type)/ -10~50℃(proportional type)

Permissible medium temperature: -25~+130℃(water valve) / 2~+180℃(steam valve)

Notes:

1. If the medium tempreature between 2~+220℃(high tempreature steam valve), 2~+450℃(super-high tempreature

steam valve), the actuators bracket should be made more higher, the type should be add "G" in front of ".12'. For example: change "TC500-D220-S.12" to ""TC500-D220-S G.12".

2. When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected

by electric heating sheath to avoid frosting and icing.

Voltage on terminal 1 and 2: the actuator axes extends, and valve stem retracts

Voltage on terminal 1 and 3: the actuator axes retracts, and valve stem extends

No voltage interminal 1,2 or 1,3: the actuator axes and valve stem keep its position

Page 2: Tiger Controls TC500-01

2

Proportional control type

( only 24VAC )

TC500-X.../ TC1000-X...

Ordering and

Transportation

Assembly Machine TC500/TC1000...electric actuator can be fitted with 2-port, 3-port TL...,TW...,TF... series valve body .

Engineering Notes

Type Summary

Type DN[mm] PN [Mpa] Datasheet No.

2port

TL...-2V(female threaded water valve)

TL...-2S(female threaded steam valve)

TW...-2V(male threaded water valve)

TW...-2S(male threaded steam valve)

TF...-2V(flanged water valve)

TF...-2S(flanged steam valve)

15...65

15...65

25...65

25...65

15...50

1.6/ 2.5/ 4.0

1.6

1.6

1.6/ 2.5

1.6/ 2.5

1.6/ 2.5/ 4.0

1.6/ 2.5/ 4.0

TL-01

TL-01

TW-01

TW-01

TF-01

TF-01

3-port (control valve with mixing and diverting function)

TL...-3V(female threaded water valve)

TW...-3V(male threaded water valve)

TF...-3V(flanged water valve)

15...65

25...65

15...50

1.6

1.6/ 2.5

1.6/ 2.5/ 4.0

TL-01

TW-01

TF-01

When ordering,please give clear indication on quanlity, products name, type reference and any

accessories required, such as: TC500-D220-S.12.

Actuator and valve body are supplied in separate packages.

l Actuator have long service time without repair

l with limit switch function to protect motor damaged

l Manual device standard

Type Rating Force

Actual Force Operating Voltage Control Signal Manual Running speed

TC500-D24-S.12

500N

500N~700N

AC 24V

3-position

Yes

3.86s/mm (50Hz)

TC1000-D24-S.12

1000N

1000N~1200N

AC 24V

3-position

Yes

3.86s/mm (50Hz)

TC500-D220-S.12

500N

500N~700N

AC 220V

3-position

Yes

3.86s/mm (50Hz)

TC1000-D220-S.12

1000N

1000N~1200N

AC 220V

3-position

Yes

3.86s/mm (50Hz)

TC500-X24-S.12

500N

500N~700N

AC 24V

proportional

Yes

3.86s/mm (50Hz)

TC1000-X24-S.12

1000N

1000N~1200N

AC 24V

proportional

Yes

3.86s/mm (50Hz)

1. 2K feedback function can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF1". For example, change "TC500-D24-S.12" to "TC500-D24-SF1.12".

2. SPDT feedback function also can be selected when actuator is 3-position type, which must be noted when ordering, the type should be changed from"S" to "SF2". For example, change "TC500-D24-S.12" to "TC500-D24-SF2.12".

Control singal at terminal O,E increasing: the actuator axes extends, and valve stem retracts

Control singal at terminal O,E decreasing: the actuator axes retracts, and valve stem extends

Control singal at terminal no changing: the actuator axes and valve stem keep its position

Notes:

This DA mode was made before leaving factory, if RA mode needed , just put the 3rd switch of S2 from OFF to ON.

* DA mode: control singal increasing, the actuator axes retracts

RA mode: control singal increasing, the actuator axes extends

Page 3: Tiger Controls TC500-01

3

Wiring Diagram

Wiring diagram 1: 3-position Wiring diagram 2: 3-position with 2K feedback

TC500-D.../ TC1000-D... TC500-D..-F1/ TC1000-D..-F1

Wiring diagram 3: 3-position with SPDT feedback

TC500-D..-F2/ TC1000-D..-F2

The PCB Figure of Proportional type Actuator

PCB diagram 1:

Proportional type (24VAC)

TC500-X24../ TC1000-X24..

Page 4: Tiger Controls TC500-01

4

The S2 switch setting of Proportional type Actuator

S2 Switch

Function

Description

ON LOG: equal-percentage 1

Flow character OFF LIN: equal-linear

ON 20%:the starting input / output signal is 20% (namely 4~20mA or 2~10V) 2

Starting of input/ output signal OFF 0:the starting input / output signal is 0 (namely 0~20mA or 0~10V)

ON II: input current signal 3

Type of input signal OFF UI: input voltage signaL

ON IO: Output current signaL 4

Type of output signal OFF UO: Output voltage signal

ON DA:DA mode (when input signal is increasing, the actuator axes extends ) 5 Operating mode

OFF RA: RA mode (when input signal is increasing, the actuator axes retracts)

ON DW: When lose input signal (voltage type), the minimum control signal When lose input signal (current type), the minimum control signal

6 Losing input signal mode OFF UP: When lose input signal (voltage type), the maximum control signal

When lose input signal (current type), the minimum control signal

ON DF: when the actuator axes retracts to limit position,output signal will be minimum value when the actuator axes extends to limit position, output signal will be maximum value

7 Output signal

mode OFF RF: when the actuator axes extends to limit position, output signal will be minimum value when the actuator axes retract to limit position, output signal will be maximum value

ON HS: the high sensitivity of input signal ≦1.5% 8 Sensitivity

OFF LS: the low sensitivity of input signal ≦2%

The nominal setting of the S2 switch

Dimensions Mounting Orientation

Chilled/hot water valve body Steam valve body Forbidded downwards Random Orientation suitable

Input signal: 0~10VDC; Output signal: 0~10VDC; DA mode; When lose input signal (voltage type), means the minimum control signal, the actuator axes retracts.

Output signal: 4~20mA; Output signal: 4~20mA; DA mode;

When lose input signal (current type), means the minimum control signal, the actuator axes retracts.

Page 5: Tiger Controls TC500-01

5

Installation Sheet

Manual device operation

Page 6: Tiger Controls TC500-01

6

Technology Data

Power Supply

Function Parameter

Environment

Condition

Material

Weight 1.4 Kg

Electric Motor Operating Voltage TC500-D24.../ TC1000-D24... TC500-D220.../ TC1000-D220... TC500-X24.../ TC1000-X24... Frequency Power consumption TC500-D.../ TC1000-D... TC500-X24.../ TC1000-X24. Up and down dead band Sensitivity Control signal type TC500-D.../ TC1000-D... TC500-X.../ TC1000-X... Input Signal / Output Signal TC500-D.../ TC1000-D... TC500-X.../ TC1000-X... IP degree Permissible medium temperature Running <1> Enviroment tempreture: <2> Enviroment humidity: TCansportation <1> Enviroment tempreture: <2> Enviroment humidity: Stock <1> Enviroment tempreture: <2> Enviroment humidity: Cover Bracket

synchronous motor AC 24V± 15% AC 220V± 15% AC 24V± 15% 50Hz or 60Hz available 7 VA 7 VA ≦2% ≦0.8% 3-position proportional

24VAC/ 220VAC± 15% 0~10VDC, 2-10VDC, 0~20mA, 4~20mA IP54 -25~+130℃(water) 2~+180℃(steam) Notes: 1. If the medium tempreature between 2~+220℃(high tempreature steam valve), 2~+450℃(super-high tempreature

steam valve), the actuators bracket should be made more higher, the type should be add "G" in front of ".12'. For example: change "TC500-D220-S.12" to ""TC500-D220-S G.12".

2. When medium temperature below 0℃ (R12, R22, R134a, R202, glycol), the stem of the valve should be protected by electric heating sheath to avoid frosting and icing. -10~+60℃ (3-position type) -10~+50℃ (proportional type) ≦95% RH -30~+65℃ ≦95% RH -15~+50℃ ≦95% RH ABS engineering plastic aluminum die casting (surface anti-rust process) 1.4 Kg


Recommended