IM 05P03D21-11EN page 1/8 Contents 1. Safety Precautions 2. Model and Suffix Codes 3. How to Install 4. Hardware Specifications 5. How to Connect Wires 6. Terminal Wiring Diagrams Introduction Thank you for purchasing the UM33A Digital Indicator with Alarms. This operation guide describes the basic operations of the UM33A. The guide should be provided to the end user of this product. Be sure to read this operation guide before using the product in order to ensure correct operation. For details of each function, refer to the electronic manual. Before using the product, refer to the table of Model and Suffix Codes to make sure that the delivered product is consistent with the model and suffix codes you ordered. Also make sure that the following items are included in the package. • Digital Indicator with Alarms (the model you ordered) ............................x1 • Set of Brackets ........................................................................................x1 • Unit Label (L4502VZ) ..............................................................................x1 • Tag Label (L4502VE) (Only when ordered.) ...........................................x1 • Operation Guide (this document) ............................................................x4 (A3 size) (Installation and Wiring, Initial Settings, Operations, and Parameters) l Target Readers This guide is intended for the following personnel; • Engineers responsible for installation, wiring, and maintenance of the equipment. • Personnel responsible for normal daily operation of the equipment. 1. Safety Precautions The following symbol is used on the instrument. It indicates the possibility of injury to the user or damage to the instrument, and signifies that the user must refer to the user’s manual for special instructions. The same symbol is used in the user’s manual on pages that the user needs to refer to, together with the term “WARNING” or “CAUTION.” WARNING Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences. CAUTION Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre- cautions that should be taken to prevent such occurrences. AC AC/DC The equipment wholly protected by double insulation or reinforced insulation. Functional grounding terminals (Do not use this terminal as a protective grounding terminal). Note Identifies important information required to operate the instrument. Warning and Disclaimer (1) YOKOGAWA makes no warranties regarding the product except those stated in the WARRANTY that is provided separately. (2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to any person or entity for any loss or damage, direct or indirect, arising from the use of the product or from any unpredictable defect of the product. Safety, Protection, and Modification of the Product (1) In order to protect the system controlled by this product and the product itself, and to ensure safe operation, observe the safety precautions described in the user’s manual. Use of the instrument in a manner not prescribed herein may compromise the product's functions and the protection features inherent in the device. We assume no liability for safety, or responsibility for the product's quality, performance or functionality should users fail to observe these instructions when operating the product. (2) Installation of protection and/or safety circuits with respect to a lightning protector; protective equipment for the system controlled by the product and the product itself; foolproof or failsafe design of a process or line using the system controlled by the product or the product itself; and/or the design and installation of other protective and safety circuits are to be appropriately implemented as the customer deems necessary. (3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts or consumables. (4) This product is not designed or manufactured to be used in critical applications that directly affect or threaten human lives. Such applications include nuclear power equipment, devices using radioactivity, railway facilities, aviation equipment, air navigation facilities, aviation facilities, and medical equipment. If so used, it is the user’s responsibility to include in the system additional equipment and devices that ensure personnel safety. (5) Modification of the product is strictly prohibited. (6) This product is intended to be handled by skilled/trained personnel for electric devices. (7) This product is UL Recognized Component. In order to comply with UL standards, end-products are necessary to be designed by those who have knowledge of the requirements. WARNING l Power Supply Ensure that the instrument’s supply voltage matches the voltage of the power supply before turning ON the power. l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H 2 S, SO X , etc.) for extended periods of time may cause a failure. l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself. l Damage to the Protective Construction Operation of the instrument in a manner not specified in the user’s manual may damage its protective construction. CAUTION This instrument is an EMC class A product. In a domestic environ- ment this product may cause radio interference in which case the user needs to take adequate measures. 2. Model and Suffix Codes UM33A Model Suffix code Optional suffix code Description UM33A Digital Indicator with Alarms (Power supply: 100-240 V AC) (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) Type 1: Basic -0 Standard type -S UM33A Digital Indicator with Alarms (SENCOM HMI Type) (please see the Operation Guide IM 05P09D21-11EN.) Type 2: Functions 0 None 1 1 additional DO (c-contact relay), RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*1) 2 1 additional DO (c-contact relay) 3 6 additional DOs (c-contact relay: 1 point, open collector: 5 points) Type 3: Open networks 0 None 3 CC-Link communication (with Modbus master function) (*2) Display language (*3) -1 English (Default. Can be switched to other language by the setting.) -2 German (Default. Can be switched to other language by the setting.) -3 French (Default. Can be switched to other language by the setting.) -4 Spanish (Default. Can be switched to other language by the setting.) Case color 0 White (Light gray) 1 Black (Light charcoal gray) Optional suffix codes /LP 24 V DC loop power supply (*4) /DC Power supply 24 V AC/DC /CT Coating (*5) /CV Terminal cover *1: When /LP option is specified, the RS-485 communication of the Type 2 code “1” is 2-wire system. *2: Type 3 code “3” can be specified only when the Type 2 code is “0” or “2”. *3: English, German, French, and Spanish are available for the guide display. *4: The /LP option can be specified only when the code for Type 2 code is any of “0”, “1” or “2”, and the Type 3 code is “0”. *5: When the /CT option is specified, the UM33A does not conform to the safety standards (UL and CSA) and CE marking (Products with /CT option are not intended for countries which require CE marking.). Accessories (sold separately) The following is an accessory sold separately. • LL50A Parameter Setting Software Model Suffix code Description LL50A -00 Parameter Setting Software • External Precision Resistor Model Suffix code Description X010 See the General Specifications (GS X010-01EN) (*) Resistance Module *: Necessary to input the current signal to the voltage input terminal. • Terminal Cover For UM33A: Model UTAP002 • User’s Manual (A4 size) Note: User’s Manual can be downloaded from a website. • Brackets Part number: L4502TP (2 pcs for upper and lower sides) • Areas close to flammable articles Absolutely do not place the instrument directly on flam- mable surfaces. If such a circumstance is unavoidable and the instrument must be placed close to a flammable item, provide a shield for it made of 1.43 mm thick plated steel or 1.6 mm thick unplated steel with a space of at least 150 mm between it and the instrument on the top, bottom, and sides. • Areas subject to being splashed with water WARNING Be sure to turn OFF the power supply to the indicator before install- ing it on the panel to avoid an electric shock. Mounting the Instrument Main Unit Provide an instrumented panel steel sheet of 1 to 10 mm thickness. After opening the mounting hole on the panel, follow the procedures below to install the indicator: 1) Insert the indicator into the opening from the front of the panel so that the terminal board on the rear is at the far side. 2) Set the brackets in place on the right and left of the indicator as shown in the figure below, then tighten the screws of the brackets. Take care not to overtighten them. Direction to insert the indicator Insert the indicator into the opening at the front of the panel. Panel Bracket (side mounting hardware) Bracket (side mounting hardware) Terminal board Insert a screwdriver into the brackets to tighten the screws. Appropriate tightening torque: 0.25 Nm CAUTION Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage. Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes. External Dimensions and Panel Cutout Dimensions UM33A Unit: mm (approx. inch) Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2 96 (3.78) 48 (1.89) Bracket 20 (0.79) 65 (2.56) 11 (0.43) Terminal cover Bracket 94.6 (3.72) 91.6 (3.61) 105.2 (4.14) 1 to 10 (0.04 to 0.39) (panel thickness) (25) (0.98) (53) (2.09) • General mounting 145 (5.71)min. +0.03 0 (3.62 ) +0.6 0 45 +0.02 0 (1.77 ) +0.8 0 92 70 (2.76) min. 150 mm 150 mm 150 mm 150 mm Operation Guide IM 05P03D21-11EN UM33A Digital Indicator with Alarms Operation Guide This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation. 7th Edition : Dec. 2018 Installation and Wiring For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL. Functional Enhancement http://www.yokogawa.com/ns/ut/im/ www.yokogawa.com/ns YOKOGAWA ELECTRIC CORPORATION Network Solutions Business Division 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN YOKOGAWA CORPORATION OF AMERICA Head office and for product sales 2 Dart Road, Newnan, Georgia 30265, USA YOKOGAWA EUROPE B.V. Headquarters Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation Protection of Environment Waste Electrical and Electronic Equipment (WEEE), Directive This is an explanation of how to dispose of this product based on Waste Electrical and Electronic Equipment (WEEE), Directive. This directive is only valid in the EU. Marking This product complies with the WEEE Directive marking requirement. This marking indicates that you must not discard this electrical/electronic product in domestic household waste. Product Category With reference to the equipment types in the WEEE directive, this product is classified as a “Small equipment” product. Do not dispose in domestic household waste. When disposing products in the EU, contact your local Yokogawa Europe B.V. office. 3. How to Install Installation Location The instrument should be installed in indoor locations meeting the following conditions: • Instrumented panel This instrument is designed to be mounted in an instrumented panel. Mount the instrument in a location where its terminals will not inadvertently be touched. • Well ventilated locations Mount the instrument in well ventilated locations to prevent the instrument’s inter- nal temperature from rising. However, make sure that the terminal portions are not exposed to wind. Exposure to wind may cause the temperature sensor accuracy to deteriorate. To mount mul- tiple indicators, see the external dimensions/panel cutout dimensions which follow. If mounting other instruments adjacent to the instrument, comply with these panel cut- out dimensions to provide sufficient clearance between the instruments. • Locations with little mechanical vibration Install the instrument in a location subject to little mechanical vibration. • Horizontal location Mount the instrument horizontally and ensure that it is level, with no inclination to the right or left. Front panel of the indicator 30° Keep this angle within 30° Note If the instrument is moved from a location with low temperature and low humidity to a place with high temperature and high humidity, or if the temperature changes rapidly, condensation will result. Moreover, in the case of thermocouple inputs, measurement errors will result. To avoid such a situation, leave the instrument in the new environment under ambient conditions for more than 1 hour prior to using it. Do not mount the instrument in the following locations: • Outdoors • Locations subject to direct sunlight or close to a heater Install the instrument in a location with stable temperatures that remain close to an average temperature of 23°C. Do not mount it in locations subject to direct sunlight or close to a heater. Doing so adversely affects the instrument. • Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely affects the instrument. Do not mount the instrument in locations subject to any of these substances. • Areas near electromagnetic field generating sources Do not place magnets or tools that generate magnetism near the instrument. If the instrument is used in locations close to a strong electromagnetic field generating source, the magnetic field may cause measurement errors. • Locations where the display is difficult to see The instrument uses an LCD for the display unit, and this can be difficult to see from extremely oblique angles. Mount the instrument in a location where it can be seen as much as possible from the front. ■ Customized Product For customized product, the product is identified by the option code of /S# (where ‘#’ is a number). Contact your supplier in case your instrument has option /S#, and you are not in the possession of FX1-[Model code]-S# or IM [Model code]-S# (where [Model code] means, for example, UT55A).
Transcript
Page 1: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 1/8

Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams

IntroductionThankyouforpurchasingtheUM33ADigitalIndicatorwithAlarms.ThisoperationguidedescribesthebasicoperationsoftheUM33A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrect operation. For details of each function, refer to the electronic manual. Before usingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproduct isconsistentwith themodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.

•DigitalIndicatorwithAlarms(themodelyouordered) ............................x1• Set of Brackets ........................................................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE)(Onlywhenordered.) ...........................................x1•OperationGuide(thisdocument) ............................................................x4(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)

lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.

1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer totheuser’smanual forspecial instructions.Thesamesymbol isused in theuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”

WARNING

Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.

AC

AC/DC

Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.

Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).

NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.

Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin

theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto

anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.

Safety,Protection,andModificationoftheProduct(1) Inordertoprotectthesystemcontrolledbythisproductandtheproductitself,andto

ensuresafeoperation,observethesafetyprecautionsdescribedintheuser’smanual.Useoftheinstrumentinamannernotprescribedhereinmaycompromisetheproduct'sfunctionsandtheprotectionfeaturesinherentinthedevice.Weassumenoliabilityforsafety,or responsibility for theproduct'squality,performanceor functionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.

(2) Installationofprotectionand/orsafetycircuitswith respect toa lightningprotector;protectiveequipment for thesystemcontrolledbytheproductandtheproduct itself;foolproofor failsafedesignofaprocessor lineusing thesystemcontrolledby theproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomerdeemsnecessary.

(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.

(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.

(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)This product isULRecognizedComponent. In order to complywithUL

standards,end-productsarenecessary tobedesignedby thosewhohaveknowledgeoftherequirements.

WARNING

lPower Supply Ensure that the instrument’s supply voltage matches the voltage

of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible

or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.

l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than

YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.

l Damage to the Protective Construction Operation of the instrument in a manner not specified in the

user’s manual may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.

2. ModelandSuffixCodes UM33A

Model SuffixcodeOptional suffixcode

Description

UM33ADigitalIndicatorwithAlarms(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)

Type1:Basic

-0 Standard type

-SUM33ADigitalIndicatorwithAlarms(SENCOMHMIType)(pleaseseetheOperationGuideIM05P09D21-11EN.)

Type2:Functions

0 None

1 1additionalDO(c-contactrelay),RS-485communication(Max.38.4kbps,2-wire/4-wire)(*1)

2 1additionalDO(c-contactrelay)

3 6additionalDOs(c-contactrelay:1point,opencollector:5points)

Type3:Opennetworks

0 None3 CC-Linkcommunication(withModbusmasterfunction)(*2)

Displaylanguage(*3)

-1 English(Default.Canbeswitchedtootherlanguagebythesetting.)-2 German(Default.Canbeswitchedtootherlanguagebythesetting.)-3 French(Default.Canbeswitchedtootherlanguagebythesetting.)-4 Spanish(Default.Canbeswitchedtootherlanguagebythesetting.)

Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)

Optionalsuffixcodes

/LP 24VDClooppowersupply(*4)/DC Powersupply24VAC/DC/CT Coating(*5)/CV Terminalcover

*1: When/LPoptionisspecified,theRS-485communicationoftheType2code“1”is2-wiresystem.*2: Type3code“3”canbespecifiedonlywhentheType2codeis“0”or“2”.*3: English,German,French,andSpanishareavailablefortheguidedisplay.*4: The/LPoptioncanbespecifiedonlywhenthecodeforType2codeisanyof“0”,“1”or“2”,

andtheType3codeis“0”.*5: Whenthe/CToptionisspecified,theUM33Adoesnotconformtothesafetystandards(UL

andCSA)andCEmarking(Productswith/CToptionarenotintendedforcountrieswhichrequireCEmarking.).

Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware

Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware

• ExternalPrecisionResistorModel Suffixcode Description

X010 SeetheGeneralSpecifications(GSX010-01EN)(*)

ResistanceModule

*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover ForUM33A:ModelUTAP002• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)

• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.

• Areas subject to being splashed with water

WARNING

Be sure to turn OFF the power supply to the indicator before install-ing it on the panel to avoid an electric shock.

Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstalltheindicator:1) Insert the indicator into theopening from the frontof thepanelso that the

terminalboardontherearisatthefarside.2) Set thebrackets inplaceontherightand leftof the indicatorasshownin the

figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.

Direction to insert theindicatorInsert the indicatorinto the opening atthe front of the panel.

Panel

Bracket(side mounting hardware)

Bracket(side mounting hardware)

Terminal boardInsert a screwdriver into thebrackets to tighten the screws.

Appropriatetightening torque:0.25 N•m

CAUTION

• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.

• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.

External Dimensions and Panel Cutout DimensionsUM33A Unit: mm (approx. inch)

Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2

96 (3.78)

48 (1

.89)

Bracket

20 (

0.79

)65

(2.5

6)11

(0.4

3)

Terminal cover

Bracket

94.6 (3.72)91.6 (3.61)

105.2 (4.14)

1 to 10 (0.04 to 0.39)

(panel thickness)(25) (0.98)

(53)

(2.09)

• General mounting145 (5.71)min.

+0.030(3.62 )

+0.6045

+0.020(1.77 ) +0.8

092

70 (2.76) min.

150 mm150 mm

150 mm

150 mm

OperationGuideIM 05P03D21-11EN

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation.

7th Edition : Dec. 2018

Installation and Wiring

For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA

Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

Protection of Environment Waste Electrical and Electronic Equipment (WEEE), Directive

ThisisanexplanationofhowtodisposeofthisproductbasedonWasteElectricalandElectronicEquipment(WEEE),Directive.ThisdirectiveisonlyvalidintheEU.

MarkingThis product complieswith theWEEEDirectivemarkingrequirement.Thismarkingindicatesthatyoumustnotdiscardthis electrical/electronic product in domestic household waste.

ProductCategoryWithreferencetotheequipmenttypesintheWEEEdirective,thisproductisclassifiedasa“Smallequipment”product.Donotdispose indomestichouseholdwaste.Whendisposingproducts in theEU, contact your localYokogawaEuropeB.V.office.

3. How to Install Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.

• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.

However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tipleindicators,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcut-outdimensionstoprovidesufficientclearancebetweentheinstruments.

• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.

Front panelof the indicator

30°

Keep this anglewithin 30°

NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.

Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases

Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.

• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.

• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.

CustomizedProduct Forcustomizedproduct,theproductisidentifiedbytheoptioncodeof/S#(where‘#’isanumber).

Contactyoursupplier incaseyour instrumenthasoption /S#,andyouarenotin thepossessionofFX1-[Modelcode]-S#or IM[Modelcode]-S#(where[Modelcode]means,forexample,UT55A).

Page 2: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 2/8

4. HardwareSpecifications

WARNING

This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IVCable

III TO( I )

II

Category IEC/EN/CSA/UL 61010-1 EN 61010-2-030 Remarks

No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-

lyconnectedtoMAINS.

No.2 Measurement CategoryII

Measurement CategoryII

For measurements performed on circuits directly connectedtothelow-voltageinstallation.

No.3 Measurement CategoryIII

Measurement CategoryIII

Formeasurementsperformedinthebuildinginstal-lation.

No.4 Measurement CategoryIV

Measurement CategoryIV

For measurements performed at the source of the low-voltageinstallation.

InputSpecifications

UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,

Input Type Instrument Range

AccuracyºC ºF

Thermo-couple

K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor

0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT

-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF

J -200.0to1200.0ºC -300.0to2300.0ºF

T-270.0to400.0ºC -450.0to750.0ºF

0.0to400.0ºC -200.0to750.0ºF

B 0.0to1800.0ºC 32to3300ºF

±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C

S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit

R 0.0to1700.0ºC 32to3100ºF

N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C

E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.

L -200.0to900.0ºC -300.0to1600.0ºF

U-200.0to400.0ºC -300.0to750.0ºF

0.0to400.0ºC -200.0to1000.0ºF

W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)

Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit

PR20-40 0.0to1900.0ºC 32to3400ºF

±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.

W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit

RTD

JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit

(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit

Standardsignal0.400to2.000V

±0.1%ofinstrumentrange±1digit

1.000to5.000V4.00to20.00mA

DCvoltage/current

0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.

Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.

Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988

•Inputsamplingperiod:50,100,200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.

•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω

•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)

Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.

For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD

ContactInputSpecifications• Numberofinputs:2points• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Inputsamplingperiod+50ms• Use:Eventinput

RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Alarm-1to-3output:contactpoint1a;3points(commonisindependent) Alarm-4output:contactpoint1c;1point• Contactrating: Contactpoint1a(Alarm-1to-3output):240VAC,1Aor30VDC,1A(resistanceload) Contactpoint1c(Alarm-4output):250VAC,3Aor30VDC,3A(resistanceload)• Use:Alarmoutput,FAILoutput,etc.Note:Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.

TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.50ms• Use:Alarmoutput,FAILoutput,etc.

RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppower

supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)

Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof

transmission output itself.

15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)

StepResponseTimeSpecificationsWithin500ms(whentheinputsamplingperiodis50msor100ms)Within1s(whentheinputsamplingperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)

24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)

SafetyandEMCStandards• Safety: CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.

Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-

1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.

• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2, EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe

rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-

ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave

protection standard compliance

Construction,Installation,andWiring• Dust-proofanddrip-proof:IP66(forfrontpanel)• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×48(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeachforrightand leftmounting

• Panelcutoutdimensions(mm):92+0.8/0(W)×45+0.6/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)

PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)

*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC

• Isolationspecifications

PV (universal ) input terminals

Alarm-1 relay (contact point a) output terminals

Alarm-2 relay (contact point a) output terminals

Alarm-3 relay (contact point a) output terminals

Contact input terminals (all)RS-485 communication terminals

24 V DC loop power supply terminals

Contact output (transistor) terminals

Retransmission (analog) output terminals(not isolated between the analog output terminals)

Internal

circuits

Power

supply

CC-Link communication terminals

The circuits divided by lines are insulated mutually.

Alarm-4 relay (contact point c) output terminals

EnvironmentalConditions

Normal Operating Conditions• Ambienttemperature:-10to50ºC IftheCC-Linkoptionisspecified,0to40°CforUM33A.• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections

Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections

• Short-periodvibration:14.7m/s2, 15 seconds or less• Shock:98m/s2 or less, 11 ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.

TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.

Transportation and Storage Conditions• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)

EffectsofOperatingConditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)

Page 3: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 3/8

5. How to Connect Wires

WARNING

• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.

• Be sure to turn OFF the power supply to the indicator before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.

• For the wiring cable, the temperature rating is 75 °C or more.• As a safety measure, always install a circuit breaker (an IEC

60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.

• Install the power cable keeping a distance of more than 1 cm from other signal wires.

• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.

• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.

• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)

This product

Functional insulation

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A safety voltage circuit

A safety voltage circuit

This product

Reinforced insulation

Reinforced insulation

Functional insulation

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

A hazardous voltage circuit

CAUTION

• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.

• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.

CAUTION

• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.

• If there is a risk of external lightning surges, use a lightning arrester etc.

• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.

• Since the alarm output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.

• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.

• After completing the wiring, the terminal cover is recommended to use for the instrument.

RecommendedCrimp-onTerminalLugs

(A)

(F)

(ød)

5.5 3.3

Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2

CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer

Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2

Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2 is recommended. If the cross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.

RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresCC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)

Recommendedtighteningtorque:0.5to0.6N·m

DC Relay Wiring

R

External DC power supplyRelayUM33A

UM’s contact

Diode(Mount it directlyto the relay coilterminal (socket).)

Relay(Use one with a relay coil rating

less than the UM’s contact rating.)

AC Relay Wiring

UM33A

R

UM’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)

External AC power supply

Relay(Use one with a relay coilrating less than the UM’s

contact rating.)

Transistor Output Wiring

power+ –

UMDO

LoadCOM

6. Terminal Wiring Diagrams

CAUTION

• Do not use an unassigned terminal as the relay terminal.• Do not use a 100-240 V AC power supply for the 24 V AC/DC

model; otherwise, the instrument will malfunction.

UM33A

301-312

201-212

101-112

212 211 210 208 207 204 203

112 111 110 109 106 105 104108 107 103

202 201

102 101

306 305 304 303 302 301312 311 310 309 308 307

E1-terminal area

PVPV input (Equippedas standard)

TC input

+

-

202

203

RTD input

A

B

b

201

202

203

Voltage (mV, V) input

+

-

202

203

Current (mA) input

+

- 203

204

Factory default: PV input type is undefined.

RETRetransmission output (Equipped as standard)Retransmission output

4-20 mA DC or0-20 mA DC

+

-

Default: 4-20 mA DC

Default: PV retransmission

Load resistance 600 Ω or less

207

208

15 V DC loop power supply

14.5-18.0 V DC(Max. 21 mA DC)

+

-

207

208

Can be used for 15 V DC loop power supply when not used for retransmission output.

ALM (Equipped as standard)Contact output

External contact output (relay)

AL3

AL2

AL1

Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)

Alarm-3 output(PV high limit)

Alarm-2 output( PV low limit)

Alarm-1 outputPV high limit

Common

Common

Common

UM104

105

106

107

108

109

ALM4Contact output

Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)

AL4

(24 V AC/DC power supply: Optional suffix code /DC)

Power supply

Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared

100-240 V AC power supply

N

L

110

111

112

24 V AC/DC power supply

-

+

110

111

112

N

L

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

-

24 V DC loop power supply

(Suffix code: Type 2=0 or 2 and with optional suffix code /LP)

305

306

LPS24RS-485

SDB(+)

SDA(-)

RDB(+)

RDA(-)

SG

RS-485 communication

301

302

303

304

305

RS485(Suffix code: Type 2=1 and without optional suffix code /LP)

(Suffix code: Type 2=3)Contact outputExternal contact output

DO14

DO15

DO13

DO12

DO11

COMCommon

UM301

302

303

304

305

306

DO

Transistor contact rating: 24 V DC, 50 mA

The function of each contact output can be changed.

Alarm-6 output( PV low limit)

Alarm-5 output(PV high limit)

Alarm-8 output( PV low limit)

FAIL

Alarm-7 output(PV high limit)

DI (Equipped as standard)Contact input

Contact rating: 12 V DC, 10 mA or more

External contact input

DI2

DI1

COMCommon

DI2

DI1

COM

+5V

+5V

No-voltagecontact

Transistor contactUM UM

210

211

212

210

211

212

The function of each contact input can be changed.

DI1=ON: PV peak and bottom values reset

OFF → ON: Latch release

101

102

Relay contact output

103

NC

NO

COM

Alarm-4 output

( PV low limit)

AL4

CC-Link communication (with Modbus master)

(Suffix code: Type 3=3)FG: Flame ground

SLD: Shield

DG: TX/RX signal ground

DB: RX/TX signal - signal

DA: RX/TX signal + signal

CHK(red)(Lit: User profile error/Adress error, Unlit: Normal)

L ERR(red)(Lit: Communication failure(CRC error), Unlit: Normal)

L RUN(green)(Lit: Normal, Unlit: No carrier detected/Communication timeout)

Not used

301

302

303

304

305

306

307

308

309

RS-485

RSB(+)

RSA(-)

SG

310

311

312

DB

DA

110Ω

CC-LIf the UM is located at the end of a segment for the CC-Link communication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)

RS-485

RSB(+)

RSA(-)

SG

RS-485 communication/24 V DC loop power supply

+

24 V DC loop power supply

21.6-28.0 V DC(Max. 30 mA DC)

-

301

302

303

305

306

RS485/LPS24(Suffix code: Type 2=1 and with optional suffix code /LP)

(Suffix code: Type 2=1, 2 or 3)

Page 4: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 4/8

Intentionallyblank Intentionallyblank

Page 5: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 5/8

Contents1. NamesandFunctionsofDisplayParts2. QuickSettingFunction(SettingofInputandOutput)3. SettingAlarmType

1. Names and Functions of Display Parts

(1)

(2)

(3)(4)

(5)

(11)

(8)(6)(7)

(13)

(12)

(10)

(9)

No.infigure Name Description

(1) PVdisplay (whiteorred)

DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.

(2) Groupdisplay(green) Displaysagroupnumber.(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.

(5) Eventindicator (orange)

Litwhenthealarms1to8occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.

(6) Keynavigationindica-tor(green)

LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.

(7) Parameterdisplaylevelindicator(green)

Displaysthesettingconditionsoftheparameterdisplaylevelfunction.

Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit

(8) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.

No.infigure Name Description

(9) DISPkey

UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedSELECTDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.

(10) PARAkey

Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).

(11)SET/ENTERkeyUp/Down/Left/Rightarrow keys

SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthe setpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/DownarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode (setpointisblinking)tomovebetweendigitsaccordingtotheparameter.

(12) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.

(13) Userfunctionkeys Fnkey.Theusercanassignafunctiontothekey.Thefunctionissetbytheparameter.

Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareison the side of the unit.

2. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionoftheindicator.TurnontheindicatortostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysettheinput,andquicklystartthealarmaction.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)

Afterturningontheindicator,firstdecidewhetherornottousetheQuicksettingfunction.

Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.

MakingSettingsUsingQuickSettingFunctionExample: Setting to thermocouple type K (range of 0.0 to 500.00C).Forthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.

(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).(3)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(4)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(5)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(6)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto

completethesetup.OperationDisplayappears.

FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.

8

1.

2.

3.

4.

5.

6.

8.

9.

10.

11.

7.

8

8

8

8

Power-on

Quick setting starts

The PV input type parameter (IN) is displayed.Initial value: OFF

OFF blinks.Blinking allows you to change the setting.

K1 is displayed.

K1 has been registered.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) has been changed to 500.0.

The setpoint for the parameter RH has been registered.

The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)

Select NO with the Down arrow key and press the SET/ENTER key.

Press the SET/ENTER key while YES is displayed to start the Quick setting.

[YES][NO]

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up arrow key.

Select NO to return to the Operation Display.

Press the Down arrow key.

Press the Down arrow key.

Press the Down arrow key.

The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.

Operation Display

Displays the measured input value (PV).

Follow the same procedure to set RL.

OperationGuide

Initial Settings

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes basic settings and operations of the UM33A.For details of each function, see User’s manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key. For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

3. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm(setpoint:02).

1.

2.

3.

4.

5.

6.

8

AL menu is displayed.

ALRM menu is displayed.

Show the Operation Display.

Hold down the key for 3 seconds.

Press the Right arrow key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter AL1 (alarm-1 type) is displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

The alarm-1 type setpoint 02 (PV low limit) is registered. After the setup is completed, press the DISP key once to return to the Operation Display.

To change the alarm type, change the last 2 digits of the 5-digit value.

Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)

For the latch action, see User ’s Manual.

Symbol Stand-by actionEnergized/De-energizedLatch action

- -No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

PV low limit (02)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint) Alarm Action (Energized)

Hysteresis

Alarm setpoint PV

Closed (lit)

Open (unlit)

Alarm setpoint

Hysteresis

PV

Closed (lit)

Open (unlit)

Hysteresis

Alarm setpoint PV

Open (lit)

Closed (unlit)

Alarm setpoint

Hysteresis

PV

Open (lit)

Closed (unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.

Setting Display of Alarm Type Stand-by Action

Energized (0) / De-energized (1)

Alarm typeWithout (0) or With (1) Stand-by action

Latch action (0/1/2/3/4)See User’s Manual.

PV low limit alarm setpoint

Treatedas normal

ºC

Power-on Time

The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.

Normal Abnormal

The alarm outputturns on.

8

1.

2.

3.

4.

5.

6.

8.

9.

10.

11.

7.

8

8

8

8

Power-on

Quick setting starts

The PV input type parameter (IN) is displayed.Initial value: OFF

OFF blinks.Blinking allows you to change the setting.

K1 is displayed.

K1 has been registered.

The last digit of the upper limit value blinks.

The parameter RH (maximum value of PV input range) has been changed to 500.0.

The setpoint for the parameter RH has been registered.

The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)

Select NO with the Down arrow key and press the SET/ENTER key.

Press the SET/ENTER key while YES is displayed to start the Quick setting.

[YES][NO]

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Up arrow key.

Select NO to return to the Operation Display.

Press the Down arrow key.

Press the Down arrow key.

Press the Down arrow key.

The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.

Operation Display

Displays the measured input value (PV).

Follow the same procedure to set RL.

ParameterstobesetInput Function

Parameter Symbol Name of Parameter Setting Range

IN PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.00to150.000C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

RH MaximumvalueofPVinputrange

Dependsontheinputtype.- For temperature input -Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

RL MinimumvalueofPVinputrange

SDPPVinputscaledecimal point position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces

3:Threedecimalplaces4:Fourdecimalplaces

SH MaximumvalueofPVinputscale

-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof

PVinputscale

Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988

Page 6: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 6/8

Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingAlarmSetpoint3. Troubleshooting

1. Monitoring-purpose Operation Displays Available during Operation

OperationDisplaySwitchingDiagram

8 8

PV Display SELECT Displays (1 to 5)

PresstheDISPkeytoshowSELECTDisplay-1to-5conditionally.FortheregistrationoftheSELECTDisplays,seeUser’sManual.

2. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointto180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochange thealarm type,see“3.SettingAlarmType” in “Initialsettings”of thismanual.

1.

2.

3.

4.

5.

6.

8

8

AL menu is displayed.

Display the parameter that need to be changed.

Blinks during the change.

Show the Operation Display.

Hold down the PARA key for 3 seconds.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.

Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.

OperationGuide

UM33ADigital Indicator with AlarmsOperation Guide

This operation guide describes key entries for operating the UM33A.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISP key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

Operations

For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

1.

2.

3.

4.

5.

6.

8

8

AL menu is displayed.

Display the parameter that need to be changed.

Blinks during the change.

Show the Operation Display.

Hold down the PARA key for 3 seconds.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.

Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .

Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.

The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.

3. Troubleshooting

TroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningontheindicator’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.

RemediesifPowerFailureOccursduringOperations• Instantaneous power failure within 20 ms. Apowerfailureisnotdetected.Normaloperationcontinues.• Power failure for less than about 5 seconds, or for about 5 seconds or more. Affectsthe"settings"and"operationstatus." Fordetails,seeUser'sManual.

NOTEWritedownthesettingsofparametersforarepairrequest.

Is the indicatordefective?

Contact us for repair. Problem solved.

No communicationcapability

Completelyinactive?

Yes

Yes

Yes

No

No

No

Keyoperationfailure?

Yes

No

Yes

Check wiring of thepower terminals.

Check the key locksetting.

Displayfailure?

*Yes

No

Turn off power, andthen turn it on again.

I/O signalfailure?

Yes

No

Check the supply voltage.

Check the specifications and polarity

of connected devices .

Check the communication-related parameters.

Check the specificationsof communication

devices.

Check thecommunication wiring.

Communicationfailure?

No Withcommuni-

cation?

Yes

Yes

Normal?Is the

key locked?

Check the specificationsof the indicator.

Yes

NoCorrect?

Correct the error(s).

Cancel the setting.

Check the I/O specificationsof the indicator.

* The LCD (a liquid crystal display) is used for a display portion of this product.

The LCD has a characteristic that the display action becomes late at the low temperature.

Additionally, the luminance and contrast degradation are caused due to aged deterioration.

However, the function is not affected.

Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.)

PV display (Operation

Display)Setpoint display

(Operation Display)Status indicator

(Operation Display)Parameter that displays error

details Error description Cause and diagnosis Remedy

Indicationoff Indicationoff — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty. Contactusforrepair.

ERR

SYS-----

— System data error System data is corrupted. Faulty. Contactusforrepair.

PAR0004 (foruserdefaultvalueerroronly)

Setupparameter(PA.ER)

User(parameter)defaultvalueerror

Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized

settingparameters.Errorindicationiserased when the power is turned on again.

PAR0010(forsetupparametererroronly) Setup parameter error Setup parameter data is corrupted.

Initializedtouserdefaultvalue.

PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.

Initializedtouserdefaultvalue.

SLOT0001 Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1-terminalarea)

Inconsistence of system data and hardware of extendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1-terminalarea).

Faulty.Contactusforrepair.

Normalindication Normalindication

RightmostdecimalpointonPVdisplayblinks.

Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause

ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint

onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.)

PV display (Operation

Display)Setpoint display

(Operation Display)Status indicator

(Operation Display)Parameter that displays

error details Error description Cause and diagnosis Remedy

AD.ERR Normalindication — Setupparameter(AD1.E) AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.

Contactusforrepair.

RJC.E(DisplaysRJC.EandPValternately.)

Normalindication — Setupparameter(AD1.E) UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror

Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.

B.OUT Normalindication —

Setupparameter(AD1.E) Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout

Checkwiringandsensor.Errorindicationiserasedinnormaloperation.

Setupparameter(PV1.E) PVinputburnouterror BurnoutofanaloginputconnectedtoPV

Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.

OVER-OVER Normalindication — Setupparameter(PV1.E)

PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)

PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.

Checkanaloginputvalueorladderprogram.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Communicationerror(RS-485communication)

FramingparityerrorBufferoverflowInter-character time-out Checksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)

Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.

Normalindication

0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)

— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.

Normalindication Normalindication Rightmostdecimalpointon

Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.

Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.

Page 7: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 7/8

Operation ParametersHolddownthePARAkeyfor3secondstomovefromtheOperationDisplaytotheOp-erationParameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.

Menu

Hold down PARA keyfor 3 sec.

DISP key

SET/ENTER key PARA key

key key key

key key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu Display and Parameter Setting Display are changed in a circular pattern.

Move to the Setup Parameter Setting Display: Hold down the PARA key and the Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.

Alarm Setpoint Setting ParameterMenusymbol: (AL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(A1toA8)

Alarm-1to-8setpoint

SetadisplayvalueofsetpointofPValarmorvelocityalarm. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type

0 Tablebelow EASY

For thealarmsetpointparameter,alarm-1to-8aredisplayedfor thefactorydefault.ThenumberofalarmscanbechangedusingthesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Usethefollowingtabletorecordalarmsetpoints.

Parameter Setpoint Parameter Setpoint

A1 A5

A2 A6

A3 A7

A4 A8

Alarm Function Setting ParameterMenusymbol: (ALRM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(AL1toAL8)

Alarm-1to8typeExample:Alarm-1

Stand-by action

Latch actionEnergized/De-energize

Alarm type

Seta5-digitvalueinthefollowingorder.[Latchaction(0/1/2/3/4)]+[Ener-gized(0)orDe-energized(1)]+[Without(0)orWith(1)Stand-byaction]+[Alarmtype:2digits(seebelow)]Forlatchaction,seeUser'sManual.

AL1,AL3,AL5,AL7:Latch

action(0) Energized

(0) WithoutStand-byaction(0) PVhighlimit(01)

AL2,AL4,AL6,AL8:Latch

action(0) Ener-

gized(0) WithoutStand-byaction(0) PVlowlimit(02)

Tablebelow

EASY

Alarmtype:2digits 00:Disable 01:PVhighlimit 02:PVlowlimit 29:PVvelocity30:Faultdiagnosis31:FAIL

to

(VT1toVT8)

PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00

to

(HY1toHY8)

Alarm-1to-8hysteresis

Setadisplayvalueofsetpointofhysteresis. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".

10

to

(DYN1toDYN8)

Alarm-1to-8On-delaytimer

AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpoint is reached. 0.00to99.59(minute.second)

0.00 STD

Forthealarmfunctionsettingparameter,8alarmsaredisplayedforthefactorydefault.Thenumberofalarmscanbechangedby thesetupparameterALNO. (numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8

ALn

VTn

HYn

DYNn

n:alarmnumber

PV-related Setting ParameterMenusymbol: (PVS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BS)PVinputbias -100.0to100.0%ofPVinputrange

span(EUS)

0.0%ofPVinput rangespan

EASY(FL)PVinputfilter OFF,1to120s OFF

(PEAK)PVpeakvalue

Displayonly (-5.0to105.0%ofPVinputrange(EU))

None

(BOTM)PVbottomvalue None

Setup ParametersHolddownthePARAkeyandLeftarrowkeysimultaneously for3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplayto theSetupPa-rameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.

Menu

DISP key

SET/ENTER key PARA key

key key key

key key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

ParameterEND

Menu

END

Menu END

END

Menu Display and Parameter Setting Display are changed in a circular pattern.

Move to the Operation Parameter Setting Display: Hold down the PARA key for 3 sec.

Hold down PARA key and Left arrow key simultaneously for 3 sec.

Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.

· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.

NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.

Function Setting ParameterMenusymbol: (CTL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(SMP)Inputsamplingperiod 50:50ms,100:100ms,200:200ms 50 STD

PV Input Setting ParameterMenusymbol: (PV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(IN)PVinputtype

OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.0to150.00C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV

OFF EASY

(UNIT)PVinputunit

-:Nounit,C:DegreeCelsius -:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit

C EASY

(RH)MaximumvalueofPVinputrange

Dependsontheinputtype. - For temperature input - Setthetemperaturerangethatisactuallydisplayed.(RL<RH) -Forvoltage/currentinput- Settherangeofavoltage/currentsignalthatisapplied. Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)

Dependson the

input typeEASY

(RL)MinimumvalueofPVinputrange

(SDP)PVinputscaledecimalpoint position

0:Nodecimalplace 1:Onedecimalplace 2:Twodecimalplaces 3:Threedecimalplaces 4:Fourdecimalplaces

Dependson the

input typeEASY

(SH)MaximumvalueofPVinput scale

-19999to30000,(SL<SH),|SH-SL|≤30000

Dependson the

input typeEASY

(SL)MinimumvalueofPVinput scale

(BSL)PVinputburnoutaction

OFF:Disable UP:Upscale DOWN:Downscale

Dependson the

input type

STD(A.BS)

PVanaloginputbias -100.0to100.0%ofPVinputrangespan(EUS)

0.0%ofPVinputrangespan

(A.FL)PVanaloginputfilter OFF,1to120s OFF

W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988WRE:W97Re3-W75Re25

Input Range Setting ParameterMenusymbol: (MPV)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(P.UNI)DisplayPVinputunit

-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit

Same asPVinput unit

STD

(P.DP)DisplayPVinputdecimalpoint position

0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces

1

(P.RH)MaximumvalueofdisplayPVinputrange

-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000

Dependson the

input type

(P.RL)MinimumvalueofdisplayPVinputrange

Output Setting ParameterMenusymbol: (OUT)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(RTS)RetransmissionoutputtypeofRET

OFF:Disable PV1:PV LPS:15VDClooppowersupply

PV1 EASY

(RTH)

Maximumvalueofretransmission output scaleofRET

WhenRTS=PV1RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:When

RTS=PV1,decimalpointpositionissameasthatofPVinput.

WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.

100%ofPVinput range

STD(RTL)

Minimumvalueofretransmission output scaleofRET

0%ofPVinput range

(RET.A)RETcurrentoutputrange

4-20:4to20mA 0-20:0to20mA 20-4:20to4mA 20-0:20to0mA

4-20

OperationGuide

UM33ADigital Indicator with AlarmsOperation Guide

Yokogawa Electric Corporation

Parameters

For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the indicator. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.

Page 8: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by

IM 05P03D21-11EN page 8/8

RS-485 Communication Setting Parameter (E1-terminal Area)Menusymbol: (R485)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PSL)Protocol selection

PCL:PClinkcommunication PCLSM:PClinkcommunication(withchecksum) LADR:Laddercommunication MBASC:Modbus(ASCII) MBRTU:Modbus(RTU)

MBRTU

EASY

(BPS)Baud rate

600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps

19200

(PRI)Parity

NONE:None EVEN:Even ODD:Odd

EVEN

(STP)Stopbit 1:1bit,2:2bits 1

(DLN)Datalength 7:7bits,8:8bits 8

(ADR)Address 1to99 1

CC-Link Communication Setting Parameter (E1-terminal Area)Menusymbol: (CC-L)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(BR)Baud rate

156K:156kbps625K:625kbps2.5K:2.5kbps5M:5Mbps10M:10Mbps

10M

EASY(ADR)Address 1 to 64 1

(BPS)Baud rate

9600:9600bps19200:19.2kbps38400:38.4kbps

38400

(FILE)Profilenumber 0,31to34(0,31:Ver1.10,32to34:

Ver2.00) 0

KeyActionSettingParameterMenusymbol: (KEY)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(Fn)Userfunctionkey-n actionsetting

OFF:DisableLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:Latchrelease(ACK)AL:AlarmsetpointsettingRST:PVpeakandbottomvalues

reset

RST EASY

DisplayFunctionSettingParameterMenusymbol: (DISP)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(PCMD)ActivecolorPVdisplayswitch

0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,

AlarmON:red)3:Linktoalarm1(AlarmOFF:red,

AlarmON:white)4:Linktoalarm1or2(AlarmOFF:

white,AlarmON:red)5:Linktoalarm1or2(AlarmOFF:

red,AlarmON:white)6:PVlimit(Withinrange:white,Out

ofrange:red)7:PVlimit(Withinrange:red,Outof

range:white)10:LinktoDI(ON:red,OFF:white)

0

EASY

(PCH)PVcolorchangehighlimit

SetadisplayvaluewheninPVlimitorSPdeviation. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.

0

(PCL)PVcolorchangelowlimit 0

(GUID)GuidedisplayON/OFF OFF:Non-display,ON:Display ON

STD

(ECO)Economymode

OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)

OFF

(BRI)Brightness (Dark)1to5(Bright) 3 EASY

(MLSD)LeastsignificantdigitalmaskofPVdisplay

OFF:Withleastsignificantdigit ON:Withoutleastsignificantdigit OFF STD

(MKTP)

Methodforleastsignifi-cantdigitalmaskofPVdisplay

0:Rounding,1:Rounding-off 0 STD

SELECTDisplaySettingParameterMenusymbol: (CSEL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

to

(CS1toCS5)

SELECTDisplay-1to-5registration

Registertheoperationparameter(excepttheOperaitonMode)thatisfrequentlymodifiedtodisplayitintheOperationDisplay. OFF,2301to5000 Forthesettingrange,seeCommuni-cationUser'sManual.

OFF STD

UsethefollowingtabletorecordSELECTDsipalysettingvalue.

Parameter n=1 n=2 n=3 n=4 n=5

CSn

KeyLockSettingParameterMenusymbol: (KLOC)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF

STD

(DATA)Front panel parameter data(,)keylock

OFF:Unlock,ON:Lock (AvailableforOperationDisplayonly.) OFF

DIFunctionResistrationParameterMenusymbol: (DI.SL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(RST)PVpeakandbottomvaluesreset

SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.

Standard terminalsDI1:5025,DI2:5026

5025

STD(LAT)

Latchrelease(ACK) 5026

(LCD)LCDbacklightON/OFFswitch OFF

(PVRW)PVred/whiteswitch OFF

AL1-AL4FunctionRegistrationParameterMenusymbol: (ALM)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(AL1.S)AL1functionselection

SetanIrelaynumber.Fortheitemsotherthanbelow,seeUser'sManual.Ex.)Setthenumber4353forAL1.Sto use the alarm 1.Set“OFF”todisablethefunction.

Nofunction:OFFAlarm1:4353Alarm2:4354Alarm3:4355Alarm4:4357Alarm5:4358Alarm6:4359Alarm7:4361Alarm8:4362

FAIL(NormallyON)output:4256

4353

STD

(AL2.S)AL2functionselection 4354

(AL3.S)AL3functionselection 4355

(AL4.S)AL4functionselection 4357

DOSettingParameter(E1-terminalArea)Menusymbol: (DO)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(DO1.S)DO11functionselection

SameasAL1.SSet“OFF”todisablethefunction

4358

STD

(DO2.S)DO12functionselection 4359

(DO3.S)DO13functionselection 4361

(DO4.S)DO14functionselection 4362

(DO5.S)DO15functionselection 4256

SystemSettingParameterMenusymbol: (SYS)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(R.TM)Restarttimer 0to10s. 0 STD

(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO

EASY

(QSM)Quicksettingmode OFF:Disable

ON:Enable ON

(LANG)Guidedisplaylanguage

ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish

Depe-nds on the model and suffixcodes

(PASS)Passwordsetting

0(Nopassword)to65535 Setting“0”means“withoutpasswordprotection.”

0

ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)

Parameter symbol Name of Parameter Status record Display

level

(PA.ER)Parameter error status

EASY

(OP.ER)Optionerrorstatus

(AD1.E)A/Dconvertererrorstatus1

(PV1.E)PVinputerrorstatus

(MCU)MCUversion

(DCU)DCUversion

(ECU1)ECU-1version(E1-terminalarea)

(PARA)Parameterversion

(H.VER)Productversion

(SER1)Serialnumber1

(SER2)Serialnumber2

ParameterDisplayLevelParameterMenusymbol: (LVL)

Parameter symbol Name of Parameter Setting Range Initial

valueUser

settingDisplay

level

(LEVL)Parameterdisplaylevel

EASY:Easysettingmode STD:Standardsettingmode PRO:Professionalsettingmode

STD EASY

*ForProfessionalsettingmode,seeUser’sManual.

Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. CC-Link is a registered trademark of CC-Link Partner Association. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.

• AuthorisedRepresentativeintheEEA YokogawaEuropeBV.(Address:Euroweg2,3825HDAmersfoort,TheNether-lands) istheAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.

• Printed ManualsModel Description

UM33ADigitalIndicatorwithAlarmsOperationGuide IM05P03D21-11ENUM33A-SDigitalIndicatorwithAlarmsOperationGuide IM05P09D21-11ENX010ExternalPrecisionResistor IMX010-01ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN

• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/

Model DescriptionUM33ADigitalIndicatorwithAlarmsOperationGuide IM05P03D21-11ENUM33ADigitalIndicatorwithAlarmsUser’sManual IM05P03D21-01ENUM33A-SDigitalIndicatorwithAlarmsOperationGuide IM05P09D21-11ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENX010ExternalPrecisionResistor IMX010-01ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN

• GeneralSpecificationModel Description

UM33ADigitalIndicatorwithAlarms GS05P03D21-01ENUM33A-SDigitalIndicatorwithAlarms GS05P09D21-01ENLL50AParameterSettingSoftware GS05P05A01-01ENX010ExternalPrecisionResistor GSX010-01EN

* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.