Page 1 TK C21P (RTU A01P) TK C21S (RTU A11) Installation Manual
Transcript
Page 1: TK C21S (RTU A11) - Honeywell

Page 1

TK C21P (RTU A01P)

TK C21S (RTU A11)

Installation Manual

Page 2: TK C21S (RTU A11) - Honeywell

Notice This document contains Honeywell proprietary information. Information contained herein is to be used solely for the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express permission of Honeywell Europe. This document and the data in it shall not be duplicated, used or disclosed to others for procurement or manufacturing, except as authorized by and with the written permission of Temaline, Inc. The information contained in this document or in the product itself is the exclusive property and trade secrets of Temaline, Inc. Copyright laws of the United States protect all information in this document or in the software product itself. While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer. In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The information and specifications in this document are subject to change without notice.

Trademarks Tema-Voyager TM is a trademark of Honeywell International Inc. MIFARE® is a registered trademark of Philips Electronics N.V. HID is a trademark or registered trademark of HID Global Corporation. LonWorks® is a registered trademark of Echelon Corporation. Any other trademarks that appear in this document are used only to the benefit of the trademark owner, with no intention of trademark infringement.

Compliance To obtain applicable EU compliance Declaration of Conformities for this product, please refer to our website, https://extranet.honeywell.com. For any additional information regarding the compliance of this product to any EU-specific requirements, please send email to [email protected]

Single contact point and Support Manufacturer’s single point of contact: Honeywell S.r.l. Via Philips, 12 20052 Monza ITALY For technical assistance, call your nearest Honeywell office.

Document Release Issue Date 800-22711 1.3 E November 2017

Page 3: TK C21S (RTU A11) - Honeywell

CONTENTS

PRELIMINARY OPERATIONS ........................ 1

Mounting and Cabling Instructions ............................................. 1 Electrical Connections .............................................................. 2

INSTALLATION ........................................... 4

Hooking Up the Unit ................................................................. 4 Connecting the Cables .............................................................. 5

Connecting to Supervised Contacts ..................................... 5 Connecting to Sensors ....................................................... 7 Connecting to load ............................................................. 9 LON and Power connection ............................................... 12 Anti-Removal Tamper Option.............................................. 13

Elemental Detail ..................................................................... 15 Jumpers ............................................................................... 16 Harsh environment ................................................................. 17 Closing the Unit ..................................................................... 18

TECHNICAL SPECIFICATIONS .................... 19

TemaKey TK C21P (RTU-A01P code 1500163xx) ....................... 19

REGULATIONS COMPLIANCE ..................... 21

CE Compliance ....................................................................... 21 Canadian and United States UL Listed ..................................... 21 FCC Compliance ..................................................................... 21 RoHS compliance ................................................................... 22 WEEE compliance ................................................................... 22 China RoHS declaration .......................................................... 22

ACTIVATION ............................................ 23

Identification via the Service Pin .............................................. 23 Identification via Bar Code ....................................................... 24 Identification Form ................................................................. 25 Spare Parts .......................................................................... 26

MEANING OF GRAPHICAL SYMBOLS USED 27

Page 4: TK C21S (RTU A11) - Honeywell

Page left intentionally blank

Page 5: TK C21S (RTU A11) - Honeywell

PRELIMINARY OPERATIONS Page 1

PRELIMINARY OPERATIONS

Mounting and Cabling Instructions

The cables are attached to an encased box or frame with a DIN rail on which the RTU-A01P unit will be mounted. Figure 1 indicates the minimum size of the panel. If you need to install additional RTU-A01P modules, you can use a larger panel; however, make sure that you allow sufficient space for accessing the cables.

120mm min.

150m

m m

in.

80mm min.interior depth

DIN RAIL

CABLE ENTRY POINT

45m

m m

in.

Figure 1. Box with DIN/Ω Rail

Page 6: TK C21S (RTU A11) - Honeywell

Page 2 PRELIMINARY OPERATIONS

Electrical Connections

You must connect the following cables to the RTU-A01P unit:

– 12V power cable.

– LONWORKS1 twisted-pair cable.

– I/O cables from the contacts/sensors.

Make sure that the 12V cable corresponds in size to the norms indicated in the table below; the size of the 12V cable can be calculated using the following table (maximum voltage drop on the cable = 0.5V):

Cable length (m) = 0.5V / (I[A] load x 2 x (res [Ohm/km] /1000))

Type of cable Length (m) in relation to base loadAWG mm2 Ohm/Km 100 [mA] 200 [mA] 500 [mA] 1 [A] 2 [A] 5 [A]

10 5,25 3,41 733 367 147 73 37 1512 3,3 5,7 439 219 88 44 22 914 2 8,8 284 142 57 28 14 616 1,3 14 179 89 36 18 9 418 0,9 21 119 60 24 12 6 220 0,6 34 74 37 15 7 4 122 0,35 52 48 24 10 5 2 1

• The LONWORKS1 data cable must be twisted-pair.

• In a free-topology configuration, the sum total of the sections must not exceed 500m.

• In a bus configuration, the sum total of the sections must not exceed 2700m.

• In a free-topology configuration, activate the 50ohm terminator by placing the appropriate jumper on the FTT10A plug-in of the TemaServer.

• In a bus configuration, place two terminators (with resistance values of 100ohm 1% ½W) at the two ends of the bus.

• Check that the length of the LONWORKS1 data cable corresponds to the norms indicated in Table 1.

1LONWORKS® is a trademark of the Echelon Corporation

Page 7: TK C21S (RTU A11) - Honeywell

PRELIMINARY OPERATIONS Page 3

Type of cable Length [m] in relation to cable capacity AWG mm2 ohm/Km 50nF/Km 100nF/Km 200nF/Km 500nF/Km 1uF/Km

12 3,3 5,7 2676 1892 1338 846 598 14 2 8,8 2153 1523 1077 681 482 16 1,3 14 1707 1207 854 540 382 18 0,9 21 1394 986 697 441 312 20 0,6 34 1096 775 548 346 245 22 0,35 52 886 626 443 280 198 24 0,2 85 693 490 346 219 155

Table 1. Length/Capacity of LONWORKS Data Cables

• The FTT10A Echelon v1.2 User Guide recommends the cables indicated in Table 2.

Producer and Model AWG Connection to bus -maximum total length [m]

Connection in free topology –maximum node-node length max. [m]

Connection in free topology –maximum total wire length. [m]

Belden 85102 16 2700 500 500 Belden 8471 16 2700 400 500 Level IV (twisted-pair, typically solid and unshielded)

22 1400 400 500

JY (St) 2x2x0.8 (4-wire helical twist, solid shielded)

20 900 320 500

TIA Cat5 / 900 250 450

Table 2. Recommended LONWORKS Cables

Page 8: TK C21S (RTU A11) - Honeywell

Page 4 INSTALLATION

INSTALLATION

Hooking Up the Unit

To hook up the unit, follow these steps:

1. Rest the upper panel of the RTU-A01P on the rail.

2. Press until you hear the tongue click into position on the rail (see Figure 2).

TONGUE

ROTATE

Figure 2. Hooking Up the Unit to the DIN Rail

Page 9: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 5

Connecting the Cables

Connecting to Supervised Contacts

Connect the contact cables to each of the 4 available inputs. Each contact must be fitted with the appropriate balancing resistors supplied with the kit. Place the resistors next to the contacts themselves, as illustrated in Figure 3.

contact 3In -V

contact 4

white

In -V

contact 2

In -V

contact 1

In -V+V +V +V +Vout

out

out

out

white white white

yellow yellow yellow yellow

JP3

JP2

SW1

J4 J5 J4 J3

J1 J2LED1

SW1

J3 J2 J1

Figure 3. Connecting the Supervised Contact Cables

Yellow resistor: 1210 Ohm 1%

White resistor: 392 Ohm 1%

Close contact resistance: 296 Ohm

Open contact resistance: 1210 Ohm

Page 10: TK C21S (RTU A11) - Honeywell

Page 6 INSTALLATION

When the cables go outdoor is mandatory to use shielded cables. The cables’ shielding must be connected to the respective ground connectors (-V).

For internal wiring without shielded cables is recommended an electrical environment where the cables are well separated, even at short runs, especially to the power cables or external cables which can be essentially subjected to interference or lighting.

Use a twisted-pair cable for the contact cables. Make sure that the cables correspond in size to the norms indicated in.

Max contact resistance = 25 Ohm

Cable type Lenght

AWG mm2 ohm/Km [m]12 3,3 5,7 219314 2 8,8 142016 1,3 14 89318 0,9 21 59520 0,6 34 36822 0,35 52 24024 0,2 85 147

Table 3. Length of Contact Cables

Page 11: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 7

Connecting to Sensors

Connect each sensor as illustrated in Figure 4, using the appropriate balancing resistors supplied with the kit.

tampercontact

SENSOR

blackyellow

white

pow

er s

uppl

y

xscl

usio

n

+-

(idem) (idem) (idem)+-InOut

JP3

JP2

J5 J4 J3J1J2J3J4

Figure 4. Connecting the Sensor Cables

Yellow resistor: 1210 Ohm 1%; White resistor: 392 Ohm 1%; Black resistor=3920 Ohm 1%

Close contact resistance: 296 Ohm; Open contact resistance: 1210 Ohm;

Tamper contact resistance: 3920 + 296 Ohm or 3920 + 1210 Ohm

Page 12: TK C21S (RTU A11) - Honeywell

Page 8 INSTALLATION

When the cables go outdoor is mandatory to use shielded cables. The cables’ shielding must be connected to the respective ground connectors (-V).

For internal wiring without shielded cables is recommended an electrical environment where the cables are well separated, even at short runs, especially to the power cables or external cables which can be essentially subjected to interference or lighting.

Use 4-wire (or 5-wire, if the sensor is provided with input disable) cables for the connections to the sensors. Make sure that the cables correspond in size to the norms indicated in Table 4 (maximum voltage drop on the cable = 0.1V):

Cable length(m) = 0.1V / (I[A] load x 2 x (res [Ohm/km] /1000))

I load max for each sensor = 100mA (400mA overall)

Length (m)Type of cable in relation to current absorbed by sensor

AWG mm2 ohm/Km 20 [mA] 50 [mA] 100 [mA] 200 [mA] 500 [mA]12 3,3 5,7 439 175 88 44 1814 2 8,8 284 114 57 28 1116 1,3 14 179 71 36 18 718 0,9 21 119 48 24 12 520 0,6 34 74 29 15 7 322 0,35 52 48 19 10 5 224 0,2 85 29 12 6 3 1

Table 4. Sensor Cable Length

Page 13: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 9

Connecting to load

Connect each of the cables from the load to one of the 4 available output connectors, as shown in Figure 7. Internally, all of the output lines are provided with Power Mosfet that can drive to ground:

1,2A 30V continuous

5A 30V (0,5 sec) peak current for inductive loads

When the cables go outdoor is mandatory to use shielded cables. The cables’ shielding must be connected to the respective ground connectors (-V).

For internal wiring without shielded cables is recommended an electrical environment where the cables are well separated, even at short runs, especially to the power cables or external cables which can be essentially subjected to interference or lighting.

In -V +Vout

In -V +Vout

In -V +Vout

In -V +Vout

JP3

JP2

SW1

J4 J5 J4 J3

J5 J2LED1

SW1

J3 J2 J1

AC IN

DC OUT

IsolatedPower supplyG

ND

GN

D

GN

D

GN

D

10-30VDC

LOA

D 1

LOA

D 2

LOA

D 3

LOA

D 4

Figure 5: Connecting to resistive loads

Page 14: TK C21S (RTU A11) - Honeywell

Page 10 INSTALLATION

In -V +Vout

In -V +Vout

In -V +Vout

In -V +Vout

JP3

JP2

SW1

J4 J5 J4 J3

J5 J2LED1

SW1

J3 J2 J1

AC IN

DC OUT

IsolatedPower supplyG

ND

GN

D

GN

D

GN

D

10-30VDC

LOA

D 1

LOA

D 2

LOA

D 3

LOA

D 4

1N40

04

1N40

04

1N40

04

1N40

04

Figure 6: Connecting to inductive loads with an external isolated power supply

Note for inductive loads

• In this case is mandatory use the 1N4004 diodes as in figure. Four (4) Diodes are included in the product

• The external power supply have to be isolated

Page 15: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 11

Relay 4

In -V +Vout

Relay 3

In -V +Vout

Relay 2

In -V +Vout

Relay 1

In -V +Vout

JP3

JP2

SW1

J4 J5 J4 J3

J5 J2LED1

SW1

J3 J2 J1

1N40041N40041N40041N4004

Figure 7. Connecting the Relays

Notes:

• Use 12VDC relay - max coil current = 100mA each.

• In this case is mandatory use the 1N4004 diodes as in figure.

Page 16: TK C21S (RTU A11) - Honeywell

Page 12 INSTALLATION

LON and Power connection

Connect the LONWORKS® data cable and the two power cables to connector J5, as illustrated in Figure 8.

+ - LON+12

LONWORKS

POWER SUPPLY 12VDC+-

SW1J5 J2

LED1

SW1

Figure 8. LON and power Connection

Page 17: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 13

Anti-Removal Tamper Option

The anti-removal option consists of two optional microswitches. To mount this option, follow these steps:

1. Mount the first microswitch (an anti-removal tamper) onto the bottom panel of the box, so that it presses against the wall.

2. Mount the second microswitch (an anti-opening tamper) so that the lid of the box presses against it.

NOTES

• In this configuration, there is no need to place the safety cover on the RTU-A01P unit. The anti-opening tamper on the box protects all the contents (the unit itself, the cables, and the anti-removal tamper).

• If the box contains several RTU-A01P units, it is only necessary to mount the anti-removal option on one of them.

3. Connect the anti-removal and the anti-opening tampers to their respective jumpers (JP2 and JP3) on the RTU-A01P unit (see Figure 9).

4. Connect the tampers so that they are left in the “open” position.

5. Use a Mascon CE100F24-2 Connector with AWG24 wires (no polarity)

ANTI-REMOVALTAMPER

ANTI-OPENINGTAMPER

SW1

J5 J4 J3

J2

JP2

JP3

Page 18: TK C21S (RTU A11) - Honeywell

Page 14 INSTALLATION

Figure 9. Anti-Removal Tamper Option

Page 19: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 15

Elemental Detail

Figure 10 provides a detailed representation of the electronic card, including the main connectors, and jumpers.

JP3

JP2

SW1

J4 J5 J4 J3

J5LED1

SW1

servicebutton

serviceLED

tamperswitch

I/O1I/O2I/O3I/O4

+ - LON

+-InOut+-InOut+-InOut+-InOut

1 2 3 4

26 27 28 29 30 31 32 3318 19 20 21 22 23 24 25

J3 J2 J1

Tamper JumpersJP2 = NOJP3 = NC

Figure 10. Elemental Detail

Page 20: TK C21S (RTU A11) - Honeywell

Page 16 INSTALLATION

Jumpers

For normal operation, configure the jumpers on the main board as specified in Table 5.

Jumper Function Default State

JP2 anti-opening tamper open

JP3 anti-removal tamper inserted

Table 5. Configuration of Jumpers

If the anti-opening and anti-removal tampers are present on the board, connect the corresponding cables to JP2 and JP3, respectively. In this situation, the internal tamper does not serve any purpose, and there is no need to replace the upper safety cover of the unit (which can therefore be left open).

Page 21: TK C21S (RTU A11) - Honeywell

INSTALLATION Page 17

Harsh environment

In the harsh environment where the electromagnetic noise is very High the connections have to be:

- LON cable = unshielded or shielded with the shield connected to Earth in an only point and separate to the internal Ground

- Power input cable = shielded with the shield connected to Earth in an only point and separate to the internal Ground

- Inputs cable = shielded as in the Figure 3

- Output = use direct outs only if the load is at a distance less than 3 mt with an unshielded cable well separate to others cables.

If the load distance is more than 3 mt use the external relays to mount close to the RTUA01P at a distance less than 3 mt, connected with an unshielded cable well separate to others cables. See Figure 7

Page 22: TK C21S (RTU A11) - Honeywell

Page 18 INSTALLATION

Closing the Unit

To close the unit, follow these steps (see Figure 11):

1. Place the safety cover onto the lower part of the unit.

2. Screw down the safety cover, using the 4 self-tapping screws (you will need a ∅ 3mm Philips screwdriver).

Honeywell

RTUA01P

Figure 11. Closing the Unit

Page 23: TK C21S (RTU A11) - Honeywell

TECHNICAL SPECIFICATIONS Page 19

TECHNICAL SPECIFICATIONS

TemaKey TK C21P (RTU-A01P code 1500163xx)

Parameter Value

Power Supply 12V +/-15% [18V internal PTC protection] 50mA [nominal], 450mA Max [including loads]

Weight 0.2 Kg Dimensions (LxWxH) 105x93x61 mm Mounting Support Standard DIN/omega rail 35 Environmental temperature

-20°C to 60°C

LONWORKS® Connection

Unshielded twisted-pair cable in free topology (Echelon FT3120E4 RoHS chip)

Outputs Number 4 Type Power Open drain (MOSFET) Current 1,2A continuous 5A (0,5sec) impulsive Voltage 10V...+14V (internal Power supply) Voltage (absolute max) 10V...+30V (from external Power supply). Current 1,2A [5A / 0,5sec peak max – inductive load] Normality NO or NC via software setting Wire length connection: it depends on cable diameter, load current sink and load min power supply On state resistance = typical 20 mOhm Load 1A = 0.02 V

Inputs Number 4

Page 24: TK C21S (RTU A11) - Honeywell

Page 20 TECHNICAL SPECIFICATIONS

Type Supervised Current 0-3mA for each input (internal reference) Voltage +14V max. 0V min Min detection time: 250 msec

Power Output for external devices

12V +/-15% 300mA Max. (overall) [internal PTC protection]

Page 25: TK C21S (RTU A11) - Honeywell

REGULATIONS COMPLIANCE Page 21

REGULATIONS COMPLIANCE

CE Compliance Company name: Honeywell S.r.l. Via Philips, 12 20052 Monza Italy Product name: TKC21P (RTU A01P) Is in conformity with the European Union following harmonization legislation: Directives: Electromagnetic Compatibility Directive (2014/30/EU) General Product Safety Directive (2001/95/EC) RoHS EU Directive ( 2011/65/EU) Standards: EN 55032:2012 + AC:2013 EN 50130-4:2011+A1:2014 EN 60950-1:2006+A11:2009 +A1:2010 +A12:2011+A2:2013 EN 50581:2012

Canadian and United States UL Listed UL60950 Reference File: E221152. UL's investigation of your product has been completed under the above Reference Number and the product was determined to comply with the applicable requirements.

FCC Compliance

CFR 47 FCC Part 15 subpart B, 2014

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, this is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by tuning the equipment off and on, the user is encouraged to try to correct the interference by one or more the following measures: • Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

• Consult the dealer or an experienced radio/TV technician for help.

Page 26: TK C21S (RTU A11) - Honeywell

Page 22 REGULATIONS COMPLIANCE

RoHS compliance 2011/65/EU The device is compliant with the European Parliament and Council Directive on the restriction on the use of certain Hazardous Substances in electrical and electronic equipment devices and with the Waste Electrical and Electronic Equipment Directive

WEEE compliance 2012/19/EU In application of directive 2012/19/EU regarding waste electrical and electronic apparatus (WEEE), effective beginning 14 February 2014, Honeywell commits, when requested by the customer, to the collection, treatment, recovery, and disposal of apparatus produced. Customers in European Union are advised to dispose this product, at the end of its useful life, as per applicable local laws, regulations and procedures

China RoHS declaration This product contains toxic and hazardous substances or elements over the defined maximum concentration values defined by the regulation. The product can be used safely during its environmental protection use period (15 years) and needs to enter into the recycling system when this period is over.

Page 27: TK C21S (RTU A11) - Honeywell

ACTIVATION Page 23

ACTIVATION

Identification via the Service Pin

To identify the node, you can activate the service pin by means of a reed sensor located inside the unit (see Figure 12). This procedure consists of the following steps:

1. Place a magnet in front of the service reed sensor (see Figure 14).

2. The TemaServer then sends a wink command in response to the service pin, which makes yellow LED flash for 2 seconds. This allows you to verify that communication to and from the TemaServer is working.

3. Check that the service LED remains off after you have completed this operation.

SERVICE LEDSERVICEREED SENSOR M

AG

NET

Honeywell

RTUA01P

Figure 12. Service Elements

Page 28: TK C21S (RTU A11) - Honeywell

Page 24 ACTIVATION

Identification via Bar Code

The components enclosed in the packaging include a bar code label. The person responsible for installing the terminal must apply this label to the corresponding identification form, and indicate the location of the terminal in the appropriate box (see example in Table 6).

Description of location

Office entrance area, first floor - staircase E

Description of TemaServer

Panel 2 entrance area, first floor – staircase E

RTU-A01P

Input 1 Contact at entrance to offices Output 1 X Input 2 Contact at staircase entrance Output 2 X Input 3 Microwave sensor - entrance to offices Output 3 “ ” “ Input 4 Infra-red sensor - entrance to offices Output 4 “ ” “

Table 6. Example of Completed Identification Form

Bar code label with Neuron ID

Page 29: TK C21S (RTU A11) - Honeywell

ACTIVATION Page 25

Identification Form

Description of location

Description of TemaServer

RTU-A01P

Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 4 Output 4

Notes:

Bar code label with Neuron ID

Page 30: TK C21S (RTU A11) - Honeywell

Page 26 ACTIVATION

Spare Parts

Yellow resistor Code 1651067 Black resistor Code 1651068 White resistor Code 1651069 Resistor kit Code 1584927

Page 31: TK C21S (RTU A11) - Honeywell

MEANING OF GRAPHICAL SYMBOLS USED Page 27

MEANING OF GRAPHICAL SYMBOLS USED

In compliance with “EN60950 Amendment 2 – Information Technology – Safety, General Requirements” this appendix shows the list of graphical symbols used in the product and their meanings.

Symbol Meaning Located on

Keep away from rain To indicate that the transport package shall be kept away from rain and in dry conditions.

Carton Box

Fragile; handle with care To indicate that the contents of the transport package are fragile and the package shall be handled with care.

Carton Box

This way up To indicate correct upright position of the transport package.

Carton Box

Conformité Européenne To indicate the manufacturer declares that the product meets the requirements of the applicable EC directives

Label

Canadian and United States UL Listed To indicate that the product meets the requirements of the UL60950 regulation

Label

Page 32: TK C21S (RTU A11) - Honeywell

Page 28 MEANING OF GRAPHICAL SYMBOLS USED

Recycling To indicate compliance with EC directive regarding waste electrical and electronic apparatus.

Label

China RoHS environmental protection use period Indicates the environmental protection use period of the product.

Label