  • Engineered for flexibility and performance.TM

    Technical Manual MAC - 2011(60Hz)

    Modular Air Cooled ChillerModels: MAC160A-960A MAC210A-1260ARefrigerantType:R22CoolingCapacity:56/70kW

  • 1Nomenclature..............................................................................................................................2

    Features.......................................................................................................................................3

    Specifications .............................................................................................................................4

    Sound Data ..................................................................................................................................7

    Operating Limit ...........................................................................................................................8

    Performance Data .......................................................................................................................8

    Outlines and Dimensions ........................................................................................................10

    Wiring Diagrams .......................................................................................................................12

    Refrigerant Circuit ....................................................................................................................15

    Equipment Options ..................................................................................................................16

    Troubleshooting .......................................................................................................................20

    Exploded view & Part list .........................................................................................................21

    Contents

    McQuayisaregisteredtrademarkofMcQuayInternational.Allrightsreservedthroughouttheworld.

    2011 McQuay International.2011McQuayInternational.

    BulletinillustrationscoverthegeneralappearanceofMcQuayInternationalproductsatthetimeofpublication.Wereservetherighttochangedesign and construction specifications at any time without notice.

    Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with localcodesandregulations,andexperiencedwiththistypeofequipment.

    Caution: Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.

    Warning: Movingmachineryandelectricalpowerhazardmaycauseseverepersonalinjuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.

    Literature No.: TM-MAC-1101A(60Hz) Supersedes: TM-MAC-1001A(60Hz) Part No.: M08039110006

  • 2Nomenclature

    M AC 160 A ---P XX U

    Export

    Description

    Power Supply P: 208~230/3/60 Q: 460/3/60

    Series

    Nominal Cooling Capacity

    Air Cooled Chiller

    McQuay

  • 3MACunitsarehighthermodynamicengineeringproducts,studiedwithhighaccuracyinbalancingcompressors,condensersandevaporatorsinordertoofferhighperformancesandwidesafetymargins.Thechoiceofthematerialsandtheequipmentadoptedfortheproductshasbeenmadewithoutanycompromis,forthepurposeofhighqualityandlongservicelife.TheproductsmeetISO9001andISO14001requirements,andassurancebeyondanydoubtsofthehighproducingstandardsfollowedbyMcQuay.

    Modular DesignMAC160A,MAC210A,designedasthe2basicmodules,canbecombinedwithfreedomtosatisfydifferentload.Themaximumnumberofcombinationis10modules,howeverit,sstillveryconvenienttotransportandinstalltheseunitsbyseparatingthemintosingleones.

    High FlexiblityTheMACunitsareavailableinsizescoveringarangeofnominalcoolingcapacityfrom56to420kW.Andwithavailability of many accessories, including advanced control and safety devices, the mac units are of high flexibility fortheirinstallationincommercial,residentialandindustrialbuildings.TheycancouplewithdifferenttypesoffancoilorAHU,provingthemselvestobeidealforvariouskindsofareasbymodularcombination.

    Low Installation CostThe units are completely assembled at factory, reducing the cost of installation on site. A firm steel base evenly distributestheweightoftheunittothesupportpointsandallowssimpleinstallationbyaneasyaccesstotheliftingpoints.

    CompressorMcQuay Modular Air Cooled Chiller is equipped with highly efficient, reliable and silent scroll compressor which featuresaninternaloverloadprotection.Thecompressoradoptshermetictypetofurthereliminateoperatingnoiseandvibration.

    Air-cooled CondenserThetwoaircooledcondensercoilswithV-shapedaremadeofstaggeredrowsof3/8"ODseamlesscoppertube,mechanically expanded into slit aluminum fins to ensure optimum heat exchange capability.

    Condenser Fan MotorTo achieve the high air charge requirement, the unit is equipped with the high airflow propeller fan which is made ofacrylstyreneresin.Thefanisdirectdrivenbyweatherproofthree-phasemotortoensureareliablecontinuousoperation.

    EvaporatorTheheatexchangerismadeofstainlesssteelplatescloselyarrangedandbrazedtogethertoensurehighheatexchange efficiency. The complete heat exchanger is insulated with thermal closed cell nitric rubber foam to give optimumthermalinsulation.

    Refrigerant CircuitTherefrigerantcircuitisfactorybrazedandevacuatedbeforeaccuratelychargedwithR22orR407C(optional)to ensure optimum operating requirement. To ensure flawless continuous operation, each refrigerant circuit is equippedwithacarefullysizedthermostaticexpansionvalve,oracapillarytube.

    Additional Safety ProtectionThemodularair-cooledchillersareequippedwithintelligentlydesignedsafetycontroltoensurecontinuoussafeoperation.Highandlowpressureswitchisprovidedtopreventthecompressordamageresultingfrombothabnormal high discharge head pressure and low pressure due to insufficient gas. Inaddition,thermalandcurrentoverloadprotectoraresuppliedwiththeunitsaswellasphasesequencerprotector.

    Features

  • 4Specifications

    MODEL MAC160A MAC320A MAC480A MAC640A MAC800A MAC960A

    NOMINAL CAPACITYBtu/h 191126 382253 573379 764505 955631 1146758

    kW 56 112 168 224 280 336

    NOMINAL TOTAL INPUT POWER kW 22 44 66 88 110 132

    NOMINAL RUNNING CURRENT A 70 140 210 280 350 420

    POWER SOURCE V/Ph/Hz 208~230/3/60,460/3/60

    REFRIGERANT TYPE R22

    CASING

    MATERIAL ELECTRO-GALVANIZEDMILDSTEEL

    FINISH EPOXYPOLYESTERPOWER

    THICKNESS mm/inch 1.2/0.047

    UNIT DIMENSION

    HEIGHT mm/inch 1785/70

    WIDTH mm/inch 1820/72

    DEPTH mm/inch 1000/40 2000/80 3000/120 4000/160 5000/200 6000/240

    PACKING DIMENSION

    HEIGHT mm/inch 1940/76

    WIDTH mm/inch 1930/76

    DEPTH mm/inch 1150/44 2300/88 3450/132 4600/176 5750/220 6900/264NET WEIGHT kg/lb 620/1366 1240/2732 1860/4098 2480/5464 3100/6830 3720/8196GROSS WEIGHT kg/lb 670/1476 1340/2952 2010/4428 2680/5904 3350/7380 4020/8856

    RUNNING WEIGHT kg/lb 640/1410 1280/2820 1920/4230 2560/5640 3200/7050 3840/8460

    NOTES:1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE TESTED AND COMPLY TO ISO 5151.3) NOMINAL COOLING CAPACITY IS BASED ON LEAVING WATER TEMPERATURE 6.7C, AMBIENT TEMPERATURE 35C AND 0.043 L/S

    PER kW WATER FLOW.4) RECOMMENDED NUMBER OF THE UNITS CONNECTED IS 6. IF YOU HAVE TO CONNECT MORE UNITS, PLEASE CONTACT

    SHENZHEN MCQUAY.

    General Data

    MODEL MAC210A MAC420A MAC630A MAC840A MAC1050A MAC1260A

    NOMINAL CAPACITYBtu/h 238908 477816 716724 955631 1194539 1433447

    kW 70 140 210 280 350 420

    NOMINAL TOTAL INPUT POWER kW 24.5 49 73.5 98 122.5 147

    NOMINAL RUNNING CURRENT A 79 158 237 316 395 474

    POWER SOURCE V/Ph/Hz 208~230/3/60,460/3/60

    REFRIGERANT TYPE R22

    CASING

    MATERIAL ELECTRO-GALVANIZEDMILDSTEEL

    FINISH EPOXYPOLYESTERPOWER

    THICKNESS mm/inch 1.2/0.047

    UNIT DIMENSION

    HEIGHT mm/inch 1940/76

    WIDTH mm/inch 1940/76

    DEPTH mm/inch 1140/45 2280/90 3420/135 4560/180 5700/225 6840/270

    PACKING DIMENSION

    HEIGHT mm/inch 2250/92

    WIDTH mm/inch 2140/46

    DEPTH mm/inch 1200/85 2400/170 3600/255 4800/340 6000/425 7200/510

    NET WEIGHT kg/lb 730/1609 1460/3218 2190/4827 2920/6436 3650/8045 4380/9654

    GROSS WEIGHT kg/lb 780/1718 1560/3436 2340/5154 3120/6872 3900/8590 4680/10308

    RUNNING WEIGHT kg/lb 750/1653 1500/3306 2250/4959 3000/6612 3750/8265 4500/9918

  • 5MODEL MAC160A MAC320A MAC480A MAC640A MAC800A MAC960AEVAPORATORTYPE BRAZEDPLATEHEATEXCHANGERPLATEMATERIAL STAINLESSSTEELMODELNAME V25*40*40WATERVOLUME m3/ft3 0.078/2.76 0.156/5.52 0.243/8.28 0.312/10.4 0.39/13.8 4.68/16.56

    NOMINALWATERFLOW m/h/USGPM 9.61/0.71 19.22/1.42 28.84/2.13 38.448/2.84 48.06/3.55 57.67/4.26

    WATERLINE(HYDRAULICKIT)

    PIPINGINSTALLATIONPIPECONNECTION mm/inch 32/1-1/4

    HEAD m 3PIPESIZE mm/inch 73.6/3BPHEWPD kPa/psi 142/20.6 145/21.0 148/21.5 151/21.9 154/22.3 157/22.8CONDENSERCOILTYPE TUBE+FIN

    TUBE

    MATERIAL COPPERTYPE INNERGROOVEWALLTHICKNESS mm/inch 0.36/0.01417OUTERDIAMETER mm/inch 9.52/3/8TUBEHEIGHT TH 36

    FIN

    MATERIAL ALUMINUMTHICKNESS mm/inch 0.11/0.00433ROWS 3FINPERINCH 14

    TOTALFACEAREA m2/ft2 2.75/29.6 5.5/59.2 8.25/88.8 11/118.4 13.75/148 16.5/177.6CONDENSERFANTYPE/DRIVE AXIALBIGVANEANDLOWNOISEBLOWER/DIRECTQUANTITY 2 4 6 8 10 12BLADEMATERIAL GALVANIZEDSTEELBLADEDIAMETER mm/inch 711.2/28POWERSUPPLY V/Ph/Hz 208~230/3/60;460/3/60RATEDRUNNINGCURRENT

    208~230V A 4.5

    460V A 2.2RATEDINPUTPOWER W 1000RATEDOUTPUTPOWER W 850MOTORPOLES 6

    AIRVOLUME CMH/CFM 26000/15058 52000/30116 78000/45174 104000/60232 13000/75290 156000/90348

    COMPRESSORTYPE SCROLLQUANTITY 2 4 6 8 10 12NOSOFCIRCUITS 2 4 6 8 10 12POWERSUPPLY V/Ph/Hz 208~230/3/60;460/3/60RATEDRUNNINGCURRENT

    208~230V A 27

    460V A 13RATEDINPUTPOWER W 7400MAXIMUMSTARTINGCURRENT

    208~230V A 148

    460V A 72PROTECTIONDEVICES H/LPRESSURESWITCH/THERMALANDCURRENTOVERLOADPROTECTORSTAGEOFCAPCITYCONTROL 2 4 6 8 10 12INSULATIONGRADE E

    LOCKEDROTORAMP208~230V A 248460V A 120

    REFRIGERANTTYPE R22CONTROL THERMOSTATICEXPANSIONVALVEANDCAPILLARYREFRIGERANTCHARGE kg/lb 13.1/28.9 26.2/57.8 39.3/86.7 52.4/115.6 65.5/144.5 78.6/173.4

    Components Data

  • 6MODEL MAC210A MAC420A MAC630A MAC840A MAC1050A MAC1260AEVAPORATORTYPE BRAZEDPLATEHEATEXCHANGERPLATEMATERIAL STAINLESSSTEEL

    MODELNAME 208~230V B3-095-84460V B3-095-96

    WATERVOLUME208~230V m3/ft3 0.102/3.60 0.204/7.2 0.306/10.8 0.408/14.4 0.51/18 0.612/21.6460V m3/ft3 0.108/3.81 0.216/7.62 0.324/11.43 0.432/15.24 0.54/19.05 0.648/22.86

    NOMINALWATERFLOW m/h/USGPM 11.88/0.87 23.76/1.74 35.64/2.61 47.52/3.48 59.4/4.35 71.28/5.22

    WATERLINE(HYDRAULICKIT)

    PIPING

    INSTALLATIONPIPECONNECTION

    mm/inch 38/11/2"

    HEAD m 5PIPESIZE mm/inch 125/5"

    BPHEWPD208-230V

    kPa/psi72/10.4 75/10.9 78/11.3 81/11.7 84/12.2 87/12.6

    460V 87/12.6 90/13.1 93/13.5 96/13.9 99/14.4 102/14.8CONDENSERCOILTYPE TUBE+FIN

    TUBE

    MATERIAL COPPERTYPE INNERGROOVEWALLTHICKNESS mm/inch 0.36/0.01417OUTERDIAMETER mm/inch 9.52/3/8

    TUBEHEIGHT TH 40

    FIN

    MATERIAL ALUMINUMTHICKNESS mm/inch 0.11/0.00433ROWS 3FINPERINCH 16

    TOTALFACEAREA m2/ft2 3.50/37.6 7/15.2 10.5 14 17.5 21CONDENSERFANTYPE/DRIVE AXIALBIGVANEANDLOWNOISEBLOWER/DIRECTQUANTITY 2 4 6 8 10 12BLADEMATERIAL GALVANIZEDSTEELBLADEDIAMETER mm/inch 711.2/28POWERSUPPLY V/Ph/Hz 208~230/3/60;460/3/60RATEDRUNNINGCURRENT

    208~230V A 5.2460V A 2.6

    RATEDINPUTPOWER W 1150RATEDOUTPUTPOWER W 840MOTORPOLES 8

    AIRVOLUME CMH/CFM 26000/15058 52000/30116 78000/45174 104000/60232 13000/75290 156000/90348

    COMPRESSORTYPE SCROLLQUANTITY 2 4 6 8 10 12NOSOFCIRCUITS 2 4 6 8 10 12POWERSUPPLY V/Ph/Hz 208~230/3/60;460/3/60RATEDRUNNINGCURRENT

    208~230V A 31460V A 15

    RATEDINPUTPOWER W 8500MAXIMUMSTARTINGCURRENT

    208~230V A 172

    460V A 84

    PROTECTIONDEVICES H/LPRESSURESWITCH/THERMALANDCURRENTOVERLOADPROTECTORSTAGEOFCAPCITYCONTROL 2 4 6 8 10 12INSULATIONGRADE ELOCKEDROTORAMP

    208~230V A 260460V A 125

    REFRIGERANTTYPE R22CONTROL THERMOSTATICEXPANSIONVALVEANDCAPILLARYREFRIGERANTCHARGE kg/lb 13.1/28.9 26.2/57.8 39.3/86.7 52.4/115.6 65.5/144.5 78.6/173.4

  • 7Electric DataMODEL MAC160A-PAAU MAC160A-QAAU MAC210A-PABU MAC210A-QABURATEDTOTALINPUTPOWER(COOLING) W 22000 22000 24500 24500RATEDRUNNINGCURRENT(COOLING) A 70 34 79 38POWERSOURCE V/Ph/Hz 208~230/3/60 460/3/60 208~230/3/60 460/3/60

    POWERSOURCEWIRE

    MAINWIRE SECTIONAREA mm2 25 10 25 10(R/S/T) QTY 3NETURAL SECTIONAREA mm2 6 4 6 4WIRE QTY 1 1 1 1EARTH SECTIONAREA mm2 25 10 25 10WIRE QTY 1CONTROLWIRE RVVP21mm2

    NOTES:1) The above data are based on unit electronic parameter.2) The wires should be well connected.3) Every wire can not contact pipes, compressor, fan motor or other movable parts.

    Safety Devices

    HIGHPRESSURESWITCHOPEN Pa/psi 3000000/406

    CLOSE Pa/psi 2400000/348

    LOWPRESSURESWITCHOPEN Pa/psi 50000/7.25

    CLOSE Pa/psi 150000/21.76

    PHASESEQUENCER Y

    DISCHARGETHERMOSTATSETTING C/F 1255/257.49

    Sound Data

    ACCORDING TO :ISO3744:1994 "ACOUSTICS--DETERMINATION OF SOUND POWER LEVELS OF NOISE SOURCES USING SOUNDPRESSURE--ENGINEERING METHOD IN AN ESSENTIALLY FREE FIELD OVER A REFLECTING PLANE".

    Type1/1OctaveSoundPressureLevel(dB,ref20uPa)

    dB(A)63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ

    MAC160A(208~230V/3Ph/60Hz) 49.0 54.6 58.9 66.2 68.4 63.6 58.5 54.6 71.90

    MAC160A(460V/3Ph/60Hz) 49.3 54.2 57.9 65.6 67.9 63.7 57.3 52.9 71.40

    MAC210A(208~230V/3Ph/60Hz) 50.8 52.7 58.0 64.3 66.4 62.5 57.3 51.0 70.20MAC210A(460V/3Ph/60Hz) 49.4 53.4 57.4 64.4 66.6 61.9 56.8 49.1 70.00

  • 8Performance Data

    COOLING CAPACITY

    Cooling Performance Chart

    0.8025 28 30 35 40 43

    0.820.840.860.880.900.920.940.960.981.001.021.041.061.081.101.121.141.161.18

    Ambient Temperature ()Crrection Factor of Capacity Output Temperature of Cooled Water ()987654

    Operating Limit

    1515

    leaving water temperature ()5 7.5 10 12.5 15 4040Ambient temperature () 20253530 operating limit 20253530Cooling mode548 107.5 1512.5 48

  • 9Water Pressure Drop Chart

    Water Pressure Drop Chart

    04080

    120160200240280320

    Water Flowm3/hPressure DropkPa

    6 7 8 9 10 11 12 13 14 155

    MAC160A-PAA/QAA-E

    COOLING POWER INPUT

    Cooling Power Input Chart

    0.84

    0.86

    0.88

    0.90

    0.92

    0.94

    0.96

    0.98

    1.00

    1.02

    1.04

    1.06

    1.08

    1.10

    Ambient Temperature ()Correction Factor of Power Output Temperature of Cooled Water ()98765425 28 30 35 40 43Correction Factors With Glycol Use

    GLYCOL% COOLINGCAPACITY WATERFLOW PRESSUREDROP

    10 0.99 1.015 1.06

    20 0.98 1.04 1.12

    30 0.97 1.08 1.18

    40 0.965 1.135 1.24

  • 10

    Water Out

    Water In

    Outlines and DimensionsModel: MAC160A

    Model: MAC210A

    Water Out

    Water In

    Water Pressure Drop Chart

    0

    20

    40

    60

    80

    100

    120

    140

    160

    6 17 187 8 9 10 11 12 13 14 15 16

    180

    Water Flowm3/hPressure Drop kP

    aMAC210A-PAB/QAB-E

  • 11

    Models: MAC960A

    91

    3

    3

    AxN=L

    A A A A A A

    232.5

    343

    1820

    335

    1724

    1785

    Intel

    Outel

    Models: MAC1260A

    A A A A A A

    2089

    2193

    2056

    303

    AxN=L110

    3

    3

    335

    456.5

    Intel

    Outel

    Unit:mmmm

    Unit:mmmm

    MODEL NUMBER Single unit size (A) units size (L)MAC160A 1 1000 1000MAC320A 2 1000 2000MAC480A 3 1000 3000MAC640A 4 1000 4000MAC800A 5 1000 5000MAC960A 6 1000 6000

    n (n10) 1000 1000xn

    MODEL NUMBER Single unit size (A) units size (L)MAC210A 1 1030 1030MAC420A 2 1030 2060MAC630A 3 1030 3090MAC840A 4 1030 4120MAC1050A 5 1030 5150MAC1260A 6 1030 6180

    n (n10) 1030 1030xn

  • 12

    Wiring DiagramsEnsurethattheratedvoltageoftheunitcorrespondstothatofthenameplatebeforegeneralprecautions.Provideapoweroutlettobeusedexclusivelyforeachunit.Apowersupplydisconnectsandacircuitbreakerforover-currentprotectionshouldbeprovidedintheexclusiveline.Themodularair-cooledchillersmustbewellgrounded.Itabsolutelycannotbeconnectedwithgas-pipe,waterpipeandtelephoneline.

    With MCH03B Controller 208-230V/3Ph/60Hz

    HEATER

    24 25

    T

    KM1

    S

    R

    KM2

    FAN2FAN1

    OL3 OL4

    L1

    2.1A

    OL3

    2.1A

    OL4

    PCB

    MCH03BCN6

    A B

    CN4

    HT/EV1

    LIVE

    NEUTRAL

    COMP1

    L2

    TH1

    COMP2

    TH2 TH3

    EV2

    4WV-1

    TH5TH4

    4WV-2

    A-HA

    T

    KM3 KM4

    1 2

    KM1 KM2

    AL-OUT

    M/FA

    N2

    HP2

    HP1

    OL3

    BA JP5

    CN5

    JP8

    JP4

    JP3

    SET/SFJP1

    JP2LP1

    HP1

    23

    22

    AL-IN

    PUMP

    H/FAN1

    JP6

    L/HE

    AT

    OV-COMP2

    OV-COMP1

    OV-FAN

    OV-PUMP

    16

    FLOW

    FREZ/LP2

    OVHT/HP2

    EN-SAVE

    N-COM

    13

    14

    12

    L2

    LP1

    OL417

    DPS

    LP2

    5 6 7

    KM5 KM3 KM4

    19

    21

    TC1

    TC2

    SYMBOL

    OL3-4

    HP1-2

    LP1-2

    CRANKCASE HEATERHEATERCRANKCASE

    DESCRIPTION

    COMPRESSOR

    DESCRIPTION:

    COMP1-2

    KM1-4

    FAN1-2

    SYMBOL

    SYMBOL

    FAN MOTOR

    CONTACTOR TEMPERATURE SWITCHDISCHARGE

    OVERLOAD PROTECTOR

    TC1-2

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH

    PHASE PROTECTOR

    DESCRIPTION

    FU

    SYMBOL

    FUSE

    OVERLOAD PROTECTOR SETTING:

    ENVI

    RONM

    ENT T

    HERM

    OST

    AT

    LEAV

    ING

    WAT

    ER TH

    ERM

    OST

    AT

    ENTE

    RING

    WAT

    ER TH

    ERM

    OST

    AT

    25

    1518

    L2

    L3

    28

    RM4-TG20

    L1

    JP3

    OPEN CLOSE

    JP1 JP2 JP7JP5JP4 JP6 JP8

    CLOSE OPENCLOSE OPENOPEN OPEN

    JUMPPER SETTING:

    COMP1

    CRANKCASE

    ~

    COMP2

    ~

    CRANKCASEHEATER

    M M~ ~M M

    JP7

    MODEL: MAC160/210A(SLAVE UNIT)

    PRESSURE SWITCHDPS

    FU1

    FU2

    208~230V/3~/60Hz

    RM4-TG20

    TO LAST SLAVE UNIT TO NEXT SLAVE UNIT

    IF UNIT IS FINAL SLAVE UNIT, JP8 JUMPER IS CLOSEFACTORY WIRINGFIELD WIRING1:

    3:2:

    NOTE:

    JP3

    OPEN CLOSE

    JP1 JP2 JP7JP5JP4 JP6 JP8

    HEATER

    24 25

    T

    KM1

    S

    R

    KM2

    FAN2FAN1

    OL3 OL4

    L1

    2.1A

    OL3

    2.1A

    OL4

    PCBMCH03B

    CN6A B

    CN4

    HT/EV

    1

    LIVE

    NEUTRAL

    COMP

    1

    L2

    TH1

    COMP

    2

    TH2 TH3

    EV2

    4WV-1

    TH5TH4

    4WV-2 A-HA

    T

    KM3 KM4

    1 2

    KM1 KM2

    AL-OUT

    M/FA

    N2

    HP2

    HP1

    OL3

    BA JP5

    CN5

    JP8

    JP4

    JP3

    SET/SFJP1

    JP2LP1

    HP1

    23

    22

    POWER

    CN4

    AL-IN

    CN3

    CN2

    CN1

    PUMP

    H/FA

    N1

    JP6

    LCD DISP WINDOW

    L/HEA

    T

    OV-COMP2

    OV-COMP1

    OV-FAN

    OV-PUMP

    16

    15

    FLOW

    FREZ/LP2

    OVHT/HP2

    EN-SAVE

    N-COM

    13

    14

    12

    11

    L2

    LP1

    OL417

    DPS

    LP2

    5 6 7

    KM5 KM3 KM4

    109

    19

    21

    TC1

    TC2

    SYMBOL

    OL3-4

    HP1-2

    LP1-2

    CRANKCASE HEATERHEATERCRANKCASE

    DESCRIPTION

    COMPRESSOR

    DESCRIPTION:

    COMP1-2

    KM1-4

    FAN1-2

    SYMBOL

    SYMBOL

    FAN MOTOR

    CONTACTOR TEMPERATURE SWITCHDISCHARGE

    OVERLOAD PROTECTOR

    TC1-2

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH

    PHASE PROTECTOR

    DESCRIPTION

    FU

    SYMBOL

    FUSE

    CLOSE CLOSECLOSE CLOSEOPEN OPEN

    JUMPPER SETTING:

    OVERLOAD PROTECTOR SETTING:

    ENVI

    RONM

    ENT

    THER

    MOS

    TAT

    LEAV

    ING

    WAT

    ER T

    HERM

    OSTA

    T

    ENTE

    RING

    WAT

    ER T

    HERM

    OSTA

    T

    25

    1518L2

    L3

    28

    RM4-TG20L1

    COMP1

    CRANKCASE

    ~

    COMP2

    ~

    CRANKCASEHEATER

    M M~ ~M M

    JP7

    AC/DC

    ALARM INDICATOR LIGHT AC/DC POWER

    2-WAY VALVE INTERLOCKING

    PUMP OVERLOAD PROTECTORSC302B CONTROLLER

    POWERADAPTER

    PUMP CONTACTOR

    NOTE:

    4:

    1:

    3:2:

    FIELD WIRINGFACTORY WIRING

    KM5IF 2-WAY VALVE INTERLOCKING FUNCTION IS PERMITED , JP6 JUMPER IS OPEN .OTHERWISE IS CLOSE(FACTORY SETTING)

    TO SLAVE UNIT

    PRESSURE SWITCHDPS

    FU1

    FU2

    208~230V/3~/60Hz

    RM4-TG20

    MODEL: MAC160/210A(MASTER UNIT)

  • 13

    460V/3Ph/60Hz

    JP3

    OPEN CLOSE

    JP1 JP2 JP7JP5JP4 JP6 JP8

    HEATER

    24 25

    T

    KM1

    S

    R

    KM2

    FAN2FAN1

    OL3 OL4

    L1

    2.1A

    OL3

    2.1A

    OL4

    PCBMCH03B

    CN6A B

    CN4

    HT/EV

    1

    LIVE

    NEUTRAL

    COMP

    1

    L2

    TH1

    COMP

    2

    TH2 TH3

    EV2

    4WV-1

    TH5TH4

    4WV-2 A-HA

    T

    KM3 KM4

    1 2

    KM1 KM2

    AL-OUT

    M/FA

    N2

    HP2

    HP1

    OL3

    BA JP5

    CN5

    JP8

    JP4

    JP3

    SET/SFJP1

    JP2LP1

    HP1

    23

    22

    POWER

    CN4

    AL-IN

    CN3

    CN2

    CN1

    PUMP

    H/FA

    N1

    JP6

    LCD DISP WINDOW

    L/HEA

    T

    OV-COMP2

    OV-COMP1

    OV-FAN

    OV-PUMP

    16

    15

    FLOW

    FREZ/LP2

    OVHT/HP2

    EN-SAVE

    N-COM

    13

    14

    12

    11

    L2

    LP1

    OL417

    DPS

    LP2

    5 6 7

    KM5 KM3 KM4

    109

    19

    21

    TC1

    TC2

    SYMBOL

    OL3-4

    HP1-2

    LP1-2

    CRANKCASE HEATERHEATERCRANKCASE

    DESCRIPTION

    COMPRESSOR

    DESCRIPTION:

    COMP1-2

    KM1-4

    FAN1-2

    SYMBOL

    SYMBOL

    FAN MOTOR

    CONTACTOR TEMPERATURE SWITCHDISCHARGE

    OVERLOAD PROTECTOR

    TC1-2

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH

    PHASE PROTECTOR

    DESCRIPTION

    FU

    SYMBOL

    FUSE

    CLOSE CLOSECLOSE CLOSEOPEN OPEN

    JUMPPER SETTING:

    OVERLOAD PROTECTOR SETTING:EN

    VIRO

    NMEN

    T TH

    ERM

    OSTA

    T

    LEAV

    ING

    WAT

    ER T

    HERM

    OSTA

    T

    ENTE

    RING

    WAT

    ER T

    HERM

    OSTA

    T

    PUMP CONTACTOR

    NOTE:

    4:

    1:

    3:2:

    FIELD WIRINGFACTORY WIRING

    KM5IF 2-WAY VALVE INTERLOCKING FUNCTION IS PERMITED , JP6 JUMPER IS OPEN .OTHERWISE IS CLOSE(FACTORY SETTING)

    25

    1518L2

    L3

    28

    RM4-TG20L1

    COMP1

    CRANKCASE

    ~

    COMP2

    ~

    CRANKCASEHEATER

    M M~ ~M M

    JP7

    AC/DC

    MODEL: MAC160/210A(MASTER UNIT)

    ALARM INDICATOR LIGHT AC/DC POWER

    2-WAY VALVE INTERLOCKING

    PUMP OVERLOAD PROTECTORSC302B CONTROLLER

    POWERADAPTER

    TO SLAVE UNIT

    PRESSURE SWITCHDPS

    RM4-TG20

    460V

    230V

    FU1

    TF

    FU2

    460V/3~/60Hz

    TRANSFORMERTR

    JP3

    OPEN CLOSE

    JP1 JP2 JP7JP5JP4 JP6 JP8

    HEATER

    24 25

    T

    KM1

    S

    R

    KM2

    FAN2FAN1

    OL3 OL4

    L1

    2.1A

    OL3

    2.1A

    OL4

    PCBMCH03B

    CN6A B

    CN4

    HT/EV

    1

    LIVE

    NEUTRAL

    COMP

    1

    L2

    TH1

    COMP

    2

    TH2 TH3

    EV2

    4WV-1

    TH5TH4

    4WV-2 A-HA

    T

    KM3 KM4

    1 2

    KM1 KM2

    AL-O

    UT

    M/FA

    N2

    HP2

    HP1

    OL3

    BA JP5

    CN5

    JP8

    JP4

    JP3

    SET/SFJP1

    JP2LP1

    HP1

    23

    22

    AL-IN

    PUMP

    H/FA

    N1

    JP6

    L/HEA

    T

    OV-COMP2

    OV-COMP1

    OV-FAN

    OV-PUMP

    16

    FLOW

    FREZ/LP2

    OVHT/HP2

    EN-SAVE

    N-COM

    13

    14

    12

    L2

    LP1

    OL417

    DPS

    LP2

    5 6 7

    KM5 KM3 KM4

    19

    21

    TC1

    TC2

    SYMBOL

    OL3-4

    HP1-2

    LP1-2

    CRANKCASE HEATERHEATERCRANKCASE

    DESCRIPTION

    COMPRESSOR

    DESCRIPTION:

    COMP1-2

    KM1-4

    FAN1-2

    SYMBOL

    SYMBOL

    FAN MOTOR

    CONTACTOR TEMPERATURE SWITCHDISCHARGE

    OVERLOAD PROTECTOR

    TC1-2

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH

    PHASE PROTECTOR

    DESCRIPTION

    FU

    SYMBOL

    FUSE

    CLOSE OPENCLOSE OPENOPEN OPEN

    JUMPPER SETTING:

    OVERLOAD PROTECTOR SETTING:

    ENVI

    RONM

    ENT

    THER

    MOS

    TAT

    LEAV

    ING

    WAT

    ER T

    HERM

    OSTA

    T

    ENTE

    RING

    WAT

    ER T

    HERM

    OSTA

    T

    L3 15

    RM4-TG20L1

    L2 2518

    28

    TR TRANSFORMER

    COMP1

    CRANKCASE

    ~

    COMP2

    ~

    CRANKCASEHEATER

    M M~ ~M M

    JP7

    MODEL: MAC160/210A(SLAVE UNIT)

    PRESSURE SWITCHDPS

    RM4-TG20

    TO LAST SLAVE UNIT TO NEXT SLAVE UNIT

    IF UNIT IS FINAL SLAVE UNIT, JP8 JUMPER IS CLOSEFACTORY WIRINGFIELD WIRING1:

    3:2:

    NOTE:

    TF230V

    460V

    FU1 FU2

    460V/3~/60Hz

  • 14

    With MC01 (OYLM) Chiller Panel Controller 208-230V/3Ph/60Hz

    JH1

    JUMPPER SETTING:

    OPEN

    OL4

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH PHASE PROTECTOR

    DESCRIPTION

    NOTE:

    CONTACTOR

    COMPRESSORCOMP

    KM

    SYMBOL

    RM4-TG20HP

    LP

    SYMBOL

    HEATER

    DESCRIPTION

    FUSEOVERLOAD PROTECTOR FUOL

    SYMBOL

    FAN1 FAN2

    208-230V/3~/60Hz

    KM1

    25

    T

    R

    S

    26

    KM2 KM4

    CLOSE

    JH2 2:

    NOTE:

    1:FACTORY WIRING.FIELD INSTALLATION.

    ENTERING WATER TEMPERATURE

    OUTDOOR AMBENT SENSORLEAVING WATER TEMPERATURE

    N

    LIVE

    COM2

    1 2

    COM1

    BOILE

    R

    KM1KM2

    W-P

    UMP

    OUT-F

    AN2

    OUT-F

    AN1

    4WV1

    4WV2

    5 7

    A-FR

    EEZE

    ALM-

    OUT

    11

    KM3KM4

    AC/DC SUPPLY

    ALM-

    IN

    12

    ALARM

    MAC160A

    TOLERANCE SETTING:

    MODEL

    5.3A

    OL3

    5.3A

    OL4

    LCD DISP WINDOW

    12V LP2

    F02 F01

    LP1

    HP2

    HP1

    CO2

    CO1

    FLOW

    PO AL-M DE2

    DE1

    C/H

    ON/O

    FF

    WI

    WO

    OA CD1 CD

    2DF

    1DF

    2

    OL5

    OL3

    OL4

    JH1

    JH2

    3

    1813 14 15 16 17 19 22

    COMPRESSOR DISCHARGE SENSOR 1COMPRESSOR DISCHARGE SENSOR 2

    USER PANEL

    N

    FAN FAN MOTOR

    24

    OL3

    KM3

    DPSQS SWITCH

    KM6 KM7

    27 28

    WATER PUMP, BOILER AND ANTIFREEZE CONTROL CONTACTOR .KM5, KM6, KM73:

    KM5

    4

    DPS

    23

    QS

    18L3 15

    RM4-TG20

    2825

    L1

    L2

    7.2A7.2AMAC210A

    OL1 OL2

    OL2OL1

    42.0A47.0A 47.0A

    42.0A

    OL1

    OL2

    20 21

    CRANKCASE

    COMP1

    ~M

    COMP2

    CRANKCASEHEATER

    ~M

    ~M

    MODEL: MAC160/210A

    LP2

    LP1

    HP2

    HP1

    PCB BOARD

    M~

    FU2

    FU1

    DIFFERENTIAL PRESSURE SWITCH

    JH1

    JUMPPER SETTING:

    OPEN

    OL4

    DESCRIPTION

    LOW PRESSURE SWITCH

    HIGH PRESSURE SWITCH PHASE PROTECTOR

    DESCRIPTION

    NOTE:

    CONTACTOR

    COMPRESSORCOMP

    KM

    SYMBOL

    RM4-TG20HP

    LP

    SYMBOL

    HEATER

    DESCRIPTION

    FUSEOVERLOAD PROTECTOR FUOL

    SYMBOL

    FAN1 FAN2

    460V/3~/60Hz

    KM1

    25

    T

    R

    S

    26

    KM2 KM4

    CLOSE

    JH2 2:

    NOTE:

    1:FACTORY WIRING.FIELD INSTALLATION.

    ENTERING WATER TEMPERATURE

    OUTDOOR AMBENT SENSORLEAVING WATER TEMPERATURE

    N

    LIVE

    COM2

    1 2

    COM1

    BOILE

    R

    KM1KM2

    W-P

    UMP

    OUT-

    FAN2

    OUT-

    FAN1

    4WV1

    4WV2

    5 7

    A-FR

    EEZE

    ALM-

    OUT

    11

    KM3KM4

    AC/DC SUPPLY

    ALM-

    IN

    12

    ALARM

    MAC160A

    TOLERANCE SETTING:

    MODEL

    2.5A

    OL3

    2.5A

    OL4

    LCD DISP WINDOW

    12V LP2

    F02 F01

    LP1

    HP2

    HP1

    CO2

    CO1

    FLOW

    PO AL-M

    DE2

    DE1

    C/H

    ON/O

    FF

    WI

    WO

    OA CD1 CD

    2DF

    1DF

    2

    OL5

    OL3

    OL4

    JH1

    JH2

    3

    1813 14 15 16 17 19 22

    COMPRESSOR DISCHARGE SENSOR 1COMPRESSOR DISCHARGE SENSOR 2

    USER PANEL

    N

    FAN FAN MOTOR

    24

    OL3

    KM3

    DPSQS SWITCH

    KM6 KM7

    27 28

    WATER PUMP, BOILER AND ANTIFREEZE CONTROL CONTACTOR. KM5, KM6, KM7 3:

    KM5

    4

    DPS

    23

    QS

    L3

    RM4-TG20

    L2

    L1

    1518

    2825

    TF TRANSFORMER

    2.9A 2.9AMAC210A

    OL2OL1

    20.0A23.0A 23.0A

    20.0A

    OL2OL1

    CRANKCASE

    COMP1

    ~M

    COMP2

    CRANKCASEHEATER

    ~M

    ~M

    MODEL: MAC160/210A

    LP2

    LP1

    HP2

    HP1

    PCB BOARD

    M~

    FU2

    230V

    TF

    460V

    FU1

    2120

    OL1

    OL2

    DIFFERENTIAL PRESSURE SWITCH

    460V/3Ph/60Hz

  • 15

    Refrigerant CircuitModel: MAC160A

    REFRIGERANTFLOW

    WATERIN

    2

    3

    4

    5

    4

    3

    WATEROUT

    6ACCUMULATOR

    1COMPRESSOR

    4CAPILLARY 5BPHE

    2HEATEXCHANGER 3LIQUIDRECEIVER

    2

    1

    6

    1

    6

    Model: MAC210A

    WATERINLET

    WATEROUTLET

    REFRIGERANTFLOW

    1COMPRESSOR2HEATEXCHARGER3DRY-FILTER

    4TXV 5BPHE 6ACCUMULATOR

    2 34

    2 3 4

    5

    1

    1

    6

    NOTE: THE PICTURE ABOVE IS FOR REFERENCE ONLY

  • 16

    Equipment Options1.INSPECTION

    Allmodularaircooledchillersaretransportedwithpallet.andfullychargedwithrefrigerant.Additionalrefrigerantchargeatsiteisnotnecessary.Allunitsshouldbevisuallyinspectedandmakesureallaccessoriesdeliveredtogetherwithunits.

    2.STORAGEAllunitsshallbestoredatappropriatestorageconditions.DONOTstacktheunits.

    3.INSTALLATIONLOCATION3.1Allunitsshallbeinstalledatappropriatelocations.Improperlyinstalledunitsmayleadtofailureandvoidof

    warranty.3.2 Sufficient clearance in between units and walls shall be provided for easy maintenance and air circulation.3.3Shortcycleofhotcondenserairshallbeavoidatalltime.Adequatespaceandminimumheightclearance

    shallbeprovided.Shortcondenseraircyclemayshortenequipmentlifespan,frequentsystemfailureorequipmentunabletostartup.

    3.4Allobstaclessurroundingtheunitshallberemovedtoensureproperaircirculation.3.5Installationenvironmentshallbenon-hazardousandnon-explosive.Highlyacidicandhighlypolluted

    environmentmayaffectsystemperformanceandleadtocondensercoilchoke,systemfailureandshorterequipmentlife.

    Space between units should be at least 1.5m

    Space between units and the wall should be at least 1.8m

    Space between units and the wall should be at least 1.8m

    The hight of the unit

    3m high space for ventilation

    OBSTACLE

    OBSTACLE BLOCKING AIR INLET

    MODULAR AIR COOLED CHILLERS

    OBSTACLE BLOCKING AIR OUTLET

    OBSTACLE BLOCK AIR INTAKE

  • 17

    3$//(7 7+(&+,//(5%$&.,1*$1*/()25./,)7(5&5$03%$5&$%/(&5$1(

    1.8m

    Min 3m

    AIR DISCHARGE

    4.HANDLING Eachmodularaircooledchillerisskiddedatthefactory.Careshouldbetakenduringhandingtoavoiddamagetotheunitandinternalcomponents.Forklifterorcablecraneshouldbeusedforeasyerection.

    5.LIFTINGMETHOD Liftingropesshallbeusedonthesuspensionplatesontopoftheunit.Duringlifting,specialattentionshouldbepaytothecenterofgravityoftheunit.Specialcareshouldbepaytoliftingropesduringliftingoftheunit.Liftingtoolssuchascrampbarshallbeusedtoprotecttheunit.

  • 18

    7+(/2&$7,212)7+()227%25(

    FOUNDATION BOLT M20(M10)x300Notes: 1. The foundation should be mattess or channel structure which can support at least 400kg/m2.2. 20mm thickness rubber shock pad is needed between the unit and the foundation.3. n is the total number of the module.

    6.INSTALLATIONBASE

    6.1 The unit must be installed on a flat and level concrete foundation. It can be conveniently installed on rooftop, terraceandotherproperplaces.

    6.2Drainpipe

    6.3Strongenough

  • 19

    12

    7(50,1$/'(9,&(43

    5

    1314

    315

    1211

    1110

    WATER INLET

    7

    8

    98

    WATER OUTLETOVERFLOW OUTLET

    6

    7.INSTALLATION

    system1

    7(50,1$/'(9,&( WATER INLET$8;,/,$5

  • 20

    CautionClean water has to be used to avoid corrosion and damage of the system. If the system is operating under harsh atmospheric or water conditions (acidic, corrosive etc.), system is expected to face drop in capacity and might eventually lead to failure.

    TroubleshootingSYMPTOMS POSSIBLECAUSES REMEDIALACTION

    Compressor stops withoutreason.(alarmlampison)

    1.Controlsystemfaulty.2.Compressorfaulty. Contactlocaldealer.

    Noisyandvibrancy1.Dirtordustinfanmotor.2.Compressornoisy.3. Vibrancy noise caused by floor or wall.

    1.Cleanawaydirtordust.2.Contactlocaldealer.3.Checktheinstallation.

    Fanmotorceaserunning. 1.Circuitfaulty.2.Overheatrelaystarting.1.Checkthecircuitandrepairwhennecessary.2.Contactlocaldealer.

    Insufficient cooling/heating.

    1.Compressorfaulty.2.Contaminationinhydraulicsystem.3.Cloggedcondensercoil.4.Lowrefrigerantcharge.

    1.Contactlocaldealer.2.Cleanhydraulicsystem.3.Cleanthecoil.4.Addrefrigerant.

    Cyclingwaterpumpdoesnotstart.

    1.Nopowersupply.2.Waterpumpmotorfaulty.3.waterpump

    1.Checkpowersystem.2.Checkwaterpumporchangeifnecessary.3.Trytorunthewatervaneorchangewaterpumpit

    necessary.

    Watercyclingfaulty. 1.Gasincyclingsystem.2.Depositordirtintheheatexchanger.1.Dischargethegas.2.Backwashheatexchanger.

    Unitdoesnotstart. 1. Water flow switch faulty.2.Pressureswitchfaulty.1. Check water flow.2.Checksystempressure.

  • 21

    Exploded view & Part list

  • 22

    NO. PartNumber Description Quantity

    1 M01014300958 FANGUARD 2

    2 M03019000807 FANBLADE,89MMTFE710C-89XINCHANG 2

    3 M50014300883 PANEL,OUTFLOW 2

    4 M03039001528 MOTOR,YDK1000-6BCYONGAN 2

    5 M50014300882 FANSUPPORT 2

    6 M50024301859 ASSY,RIGHTCOIL 2

    7 M50024301858 ASSY,LEFTCOIL 2

    8 ASSY,METALSTRUCTURE 1

    9 M01014300932 PANEL,LEFTSURFACE 2

    10 M04109010636 PRESSURESWITCH2.4/2.8MPa 1

    11 A50054009748 ASSY,ACCESSVALVE1/4SP2200 4

    12 M04109010637 PRESSURESWITCH0.05/0.15MPa 1

    13 M50049305803 CONTROLBOXASSY 1

    14 A02169000502 FILTERDRIER,BFK-085SALCO 2

    15 M02089321002 CAPILLARY 4

    16 M01014300930 PANEL,FRONTSURFACEA 1

    17 M01014300931 PANEL,FRONTSURFACEB 1

    18 M0419010625 COMPRESSOR,ZR125KC-TF5-522(WITHHEATER) 2

    19 M02119012953 ACCUMULATOR,QFQ5.2-A-016.0LTONGLI 2

    20 ASSY,COPPERTUBE 1

    21 M01014300929 PANEL,FRONTANDBACKSURFACE 3

    22 havenothispart

    23 M04064305407 DIFFERENCEPRESSURE5/9KPa 1

    24 M02209000726 HEATEXCHANGER,BRAZEDPLATEV25*40*40SWEP 1

    25 M02069005115 STRIANER,WATERCUPN25(11/4")ITALYOR

    26 M50104303801 WATERPIPE,INLET(PPR) 1

    27 M50104303806 WATERPIPE,OUTLET(PPR) 1

    28 M50014300880 ASSY,BASEPAN 1

    TERMINAL BOX M50044304010

    1 A04119003779 TERMINALBLOCK,ET3501-3P-1 1

    2 M04119003708 TERMINALBLOCK,HP-T3021-18P

    3 M04039003178 CONTACTOR,LC1-D6511MTCT.E. 2

    4 M04039003169 CONTACTOR,LC1-D0910M7CT.E. 2

    5 M04169003904 FUSELINKRT14-4AWITHBASEDELIXI 1

    6 M04199011980 PHASEPROTECTORDB3A01A 1

    7 M04089011195 CONTROLMODULE,MCH03BEC(B4.3) 1

    8 M04089900249 CONTROLLERSC302B(MCQUAY,CHINESE) 1

    9 M04179003990 OVERLOADPROTECTOR,LR2-D1307N1.6-2.5A) 2

    MAC160A-PAA-E

  • 23

    NO. PartNumber Description Quantity

    1 M01014300958 FANGUARD 2

    2 M03019000807 FANBLADE,89MMTFE710C-89XINCHANG 2

    3 M50014300883 PANEL,OUTFLOW 2

    4 M03039001527 MOTOR,YDK1000-6ACYONGAN 2

    5 M50014300882 FANSUPPORT 2

    6 M50024301859 ASSY,RIGHTCOIL 2

    7 M50024301858 ASSY,LEFTCOIL 2

    8 ASSY,METALSTRUCTURE 1

    9 M01014300932 PANEL,LEFTSURFACE 2

    10 M04109010636 PRESSURESWITCH2.4/2.8MPa 1

    11 A50054009748 ASSY,ACCESSVALVE1/4SP2200 4

    12 M04109010637 PRESSURESWITCH0.05/0.15MPa 1

    13 M50049305803 CONTROLBOXASSY 1

    14 A02169000502 FILTERDRIER,BFK-085SALCO 2

    15 M02089321002 CAPILLARY 4

    16 M01014300930 PANEL,FRONTSURFACEA 1

    17 M01014300931 PANEL,FRONTSURFACEB 1

    18 A050049004677 COMPRESSOR,ZR125KC-TFD-522(WITHHEATER) 2

    19 M02119012953 ACCUMULATOR,QFQ5.2-A-016.0LTONGLI 2

    20 ASSY,COPPERTUBE 1

    21 M01014300929 PANEL,FRONTANDBACKSURFACE 3

    22 havenothispart

    23 M04064305407 DIFFERENCEPRESSURE5/9KPa 1

    24 M02209000726 HEATEXCHANGER,BRAZEDPLATEV25*40*40SWEP 1

    25 M02069005115 STRIANER,WATERCUPN25(11/4"ITALYOR

    26 M50104303801 WATERPIPE,INLET(PPR) 1

    27 M50104303806 WATERPIPE,OUTLET(PPR) 1

    28 M50014300880 ASSY,BASEPAN 1

    TERMINAL BOX M50044304010

    1 A04119003779 TERMINALBLOCK,ET2501-3P-1 1

    2 M04119003708 TERMINALBLOCK,HP-T3021-18P

    3 M04039003178 CONTACTOR,LC1-D6511MTCT.E. 2

    4 M04039003151 CONTACTOR,LC1-2501M7C 2

    5 M04169003904 FUSELINKRT14-4AWITHBASEDELIXI 1

    6 M04199362000 PHASEPROTECTORRM4-TG20T.E. 1

    7 M04089012294 CONTROLMODULE,MC01ECMC2.02CP 1

    8 M04089900249 CONTROLLERSC302B(MCQUAY,CHINESE) 1

    9 M04179003990 OVERLOADPROTECTOR,LR2-D1307N1.6-2.5A) 2

    MAC160A-QAA-E

  • 24

  • 25

    MAC210A-PAB-E

    NO. PartNumber Description Quantity

    1 M01014302202 OUTERNOZZLE810mm 2

    2 M03019000809 FANBLADE,240MMDBF7A-240XINCHANG 2

    3 M01014303266 PANEL,OUTFLOW 2

    4 M03039001148 MOTOR,YDK1000-8A9,YONGAN 2

    5 M01014300567 SUPPORTMOTOR 2

    6 M50024304050 ASSY,RIGHECOIL 2

    7 M50024304049 ASSY,LEFTCOIL 2

    8 ASSY,METALSTRUCTURE 1

    9 M01014300103 PANEL,UNDERSURFACE 4

    10 M04109003655 PRESSURESWITCHH20PS3.0/2.4MPa 1

    11 A50054009748 ASSY,ACCESSVALVE1/4SP2200 4

    12 M04109010639 LOWPRESSURESWITCH0.05/0.15MPa 1

    13 M50049304037 TERMINALBOX 1

    14 A02169000508 FILTERDRIER,EK-085SALCO 2

    15 M05019010949 VALVE,TXVTDEBX115/8*7/8DANFOSS 2

    16 M01014300104 PANEL,UNDERSURFACE5 1

    17 M01014300105 PANEL,UNDERSURFACE5 1

    18 M04019002899 COMPRESSOR,ZR144KC-TF5(WITHHEATER)COPELAND 2

    19 M02119012953 ACCUMULATOR,QFQ5.2-A-016.0LTONGLI 2

    20 ASSY,COPPERTUBE 1

    21 M01014300106 PANEL,UNDERSURFACE 1

    22 M05014302007 VALVE,CONNECTSENSOR 2

    23 M04064305407 SWITCH,DIFFERENCEPRESSURE5/9KPa 1

    24 M02204302010 BPHE,B3-095-84QINBAO 1

    25 M05029004269 JOINT,FLEXIBLERUBBERKST-40 2

    26 M05014013017 VALVE,BALLQ11F-20T 2

    27 M02069005116 STRAINER,WATERCUPN25(11/2)ITALYOR 1

    28 M50104303215 ASSY,WATERPIPE(INLET) 1

    29 M50104303216 ASSY,WATERPIPE(OUTLET) 1

    30 M50014303234 ASSYBASEPAN 1

    TERMINALBOX1 M04119003708 TERMINALBLOCK,HP-T3021-18P 1

    2 M04119003779 TERMINALBLOCK,ET3501-3P-1 1

    3 M04039003178 CONTACTOR,LC1-D6511MTCT.E. 2

    4 M04039003169 CONTACTOR,LC1-D0910M7CT.E. 2

    5 M04169003904 FUSELINKRT14-4AWITHBASEDELIXI 1

    6 M04199362000 PHASEPROTECTOR,RM4-TG20T.E. 1

    7 M04089012294 CONTROLMODULE,MC01ECMC2.0 1

    8 M04089900247 CONTROLLERSC302B(MCQUAY,ENGLISH) 1

    9 M04179003986 OVERLOADPROTECTOR,LR2-D3357C 2

  • 26

    NO. PartNumber Description Quantity

    1 M01014302202 OUTERNOZZLE810mm 2

    2 M03019000809 FANBLADE,240MMDBF7A-240XINCHANG 2

    3 M01014303266 PANEL,OUTFLOW 2

    4 M03039013480 MOTOR,YT160-1000-8A4 2

    5 M01014300567 SUPPORTMOTOR 2

    6 M50024304050 ASSY,RIGHECOIL 2

    7 M50024304049 ASSY,LEFTCOIL 2

    8 ASSY,METALSTRUCTURE 1

    9 M01014300103 PANEL,UNDERSURFACE 4

    10 M04109003655 PRESSURESWITCHH20PS3.0/2.4MPa 1

    11 A50054009748 ASSY,ACCESSVALVE1/4SP2200 4

    12 M04109010639 LOWPRESSURESWITCH0.05/0.15MPa 1

    13 M50049304038 TERMINALBOX 1

    14 A02169000508 FILTERDRIER,EK-085SALCO 2

    15 M05019010949 VALVE,TXVTDEBX115/8*7/8DANFOSS 2

    16 M01014300104 PANEL,UNDERSURFACE5 1

    17 M01014300105 PANEL,UNDERSURFACE5 1

    18 M04019002837 COMPRESSOR,ZR144KC-TFD-522(WITHHEATER)COPELAND2

    19 M02119012953 ACCUMULATOR,QFQ5.2-A-016.0LTONGLI 2

    20 ASSY,COPPERTUBE 1

    21 M01014300106 PANEL,UNDERSURFACE 1

    22 M05014302007 VALVE,CONNECTSENSOR 2

    23 M04064305407 SWITCH,DIFFERENCEPRESSURE5/9KPa 1

    24 M02204302010 BPHE,B3-095-84QINBAO 1

    25 M05029004269 JOINT,FLEXIBLERUBBERKST-40 2

    26 M05014013017 VALVE,BALLQ11F-20T 2

    27 M02069005116 STRAINER,WATERCUPN25(11/2)ITALYOR 1

    28 M50104303215 ASSY,WATERPIPE(INLET) 1

    29 M50104303216 ASSY,WATERPIPE(OUTLET) 1

    30 M50014303234 ASSYBASEPAN 1

    TERMINAL BOX

    1 M041190026708 TERMINALBLOCK,HP-T24021-18P 1

    2 M04119003777 TERMINALBLOCK,ET2501-3P-1 1

    3 M04039003168 CONTACTOR,LC1-3201M7CT.E. 2

    4 M04039003169 CONTACTOR,LC1-D0910M7CT.E. 2

    5 M04169003901 FUSE,RT14-10A,BOLTIN10A022M04010-001 1

    6 M041992662000 PHASEPROTECTOR,RM4-TG20T.E. 1

    7 M04089012294 CONTROLMODULE,MC01ECMC2.0 1

    8 M04089900247 CONTROLLERSC302B(MCQUAY,ENGLISH) 1

    9 M0417003957 OVERLOADPROTECTOR,LRD22KN(16-24A)T.E. 2

    MAC210A-QAB-E

  • 2011McQuayInternational+1(800)432-1342www.mcquay.com

    Wedoourutmosteffortstoensurealldetailsarecorrectandaccurateduringthetimeofpublication.However, McQuay reserves the right to discontinue and/or alter the specifications and designs any time

    withoutnoticeandincurringobligations.Specifications may change to suit local conditions and some models are not available for certain countries.

    ISO9001Certificate No.: 9601019

    BS-OHSAS18001Certificate No.: 7644

    ISO14001Certificate No.: EMS 80362


Recommended