2
x 8 72B1 72B2 52R INV Controller Serial port RS-232C PC PLC LCD Panel Communication Unit . Modbus-TCP . Ethernet(Socket) . RS-485 SOLAR WARE 630 PVL-L630E x 8 90 91 92 93 94 95 96 97 98 99 0 20 40 60 80 100 Load(%) Efficiency(%) SOLAR WARE 630 Performance 550V-50Hz Advanced Multilevel Inverter -56% of switching loss reduction SOLAR WARE 630 redefines the PV utility scale solar inverter solution in reliability, efficiency and productivity. TMEIC sets the standard of Utility scale installation with its own proprietary design resulting the most advanced multilevel inverter system by reducing the switching loss by 56%. Grid Connection Features TMEIC developed the grid connection features working with Japanese power companies. All of TMEIC’s utility scale inverters include the latest interconnection technology. These features include: Power factor control Reactive/Active power control Fault ride through - Voltage ride through (low voltage ride through) - Frequency ride through TMEIC’s proprietary anti-islanding technique utilizes a slip mode frequency shift method Featuring compact footprint This advanced inverter design significantly reduces size, achieving the smallest 630 kW inverter. Advanced multilevel Inverter system Maximum 98.6% efficiency High voltage MPPT window: up to 950V Featuring compact footprint: 1.33 m 2
Transcript
Page 1: TMEIC manual

x 8

72B1

72B2

52RINV

ControllerSerialport

RS-232CPC

PLC

LCD Panel

Communication Unit .Modbus-TCP .Ethernet(Socket) .RS-485

SOLAR WARE 630 PVL-L630E

x 8

90

91

92

93

94

95

96

97

98

99

0 20 40 60 80 100Load(%)

Effi

cien

cy(%

)

SOLAR WARE 630 Performance

550V-50Hz

Advanced Multilevel Inverter-56% of switching loss reductionSOLAR WARE 630 redefi nes the PV utility scale solar inverter solution in reliability, effi ciency and productivity. TMEIC sets the standard of Utility scale installation with its own proprietary design resulting the most advanced multilevel inverter system by reducing the switching loss by 56%.

Grid Connection FeaturesTMEIC developed the grid connection features working with Japanese power companies. All of TMEIC’s utility scale inverters include the latest interconnection technology. These features include:• Power factor control• Reactive/Active power control• Fault ride through

- Voltage ride through (low voltage ride through)

- Frequency ride through• TMEIC’s proprietary anti-islanding technique

utilizes a slip mode frequency shift method

Featuring compact footprintThis advanced inverter design signifi cantly reduces size, achieving the smallest 630 kW inverter.

Advanced multilevel Inverter system

Maximum 98.6% effi ciency

High voltage MPPT window: up to 950V

Featuring compact footprint: 1.33 m2

Page 2: TMEIC manual

C-0039-1110-D(*)

TOSHIBA MITSUBISHI-ELECTRIC INDUSTRIAL SYSTEMS CORPORATIONPower Electronics Systems Division, Photovoltaic System CenterEmail: [email protected] • www.tmeic.co.jp

TMEIC Corporation • Roanoke, Virginia • Email: [email protected] • www.tmeic.comContents subject to change without notice

Input Side(DC)

Output Side(AC)

EnvironmentalConditions

ProtectiveFunctions

User Interface

Compliance

Cooling MethodInverter Dimensions (H x W x D)Unit Weight

Maximum DC PowerMaximum DC Voltage

MPPT Operating RangeMaximum DC Current

Maximum Number of InputNominal AC Output PowerNominal AC VoltageNominal AC FrequencyNominal AC CurrenctPower Factor

Harmonic Distortion of AC CurrentMaximum Efficiency

European EfficiencyEnclosure Protection Ratings

Relative HumidityAmbient Temperature RangeMax. Altitude Above Sea LevelInput (DC) SideGrid (AC) SideGrid AssistanceLocal Control PanelCommunications

Fault Analysis

771kW

540~950V *11000V

1403A

630kW380V 3-phase, 3-wire system

957A>0.99 (Rated Power)

< 5% (Rated Power)

98.6%98.3%

IP2X (Indoors)15% to 95% (not condensating)-20 oC to + 50 oC *2

2000m(-4F to 122F)

Ground Fault, DC Reverse Current, Over Voltage, Over CurrentAnti-islanding, Over/Under Voltage, Over/Under Frequency, Over CurrentReactive/Active Power Control, Fault Ride Through, Power Factor Control

LCD (3.8inch, QVGA) with Touch-Screen, Emergency Shut-off ButtonEthernet (Socket / Modbus TCP), Serial (RS485 / RS232C)

16

50 / 60Hz

1300kg (2866lbs)

2075mm x 1900mm x 700mm (81.7” x 74.8” x 28.7”)Forced air cooling

Low Voltage Directive: 2006/95/EC (EN50178)EMC Directive: 2004/108/EC (EN61000-6-2, EN55011)

PVL-L0630EType

Fault Event Log, Waveform Acquisition via SD card

Note): *1:Transition mode between MPPT and constant DC voltage operation from 540 to 550V *2: Need optional heater below -10 oC(14F) , Power de-rating over +40 oC(104F)

AIR FLOW

AIR FLOW

FLOOR LEVEL

MAINTENANCE SPACE

VENTILATIONAIR FILTER

INVERTERDC INTERFACE AC INTERFACE

EMERGENCYSTOP BUTON

FRONT VIEW RIGHT SIDE VIEW

1900mm74.8”

900mm35.4”

500mm19.7”

500mm19.7”

1900mm74.8”

75mm3.0”

100mm3.9”

2075mm81.7”

600mm23.6”

30mm1.2”

29.5mm1.2”

300mm11.8”

2300mm90.5”

700mm27.6”

730mm28.7”


Recommended