Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers. Michael Milligan & Debbie Lew National Wind Technology Center National Renewable Energy Laboratory Golden, Colorado USA. The Questions. 1. Overview of the Grid. Interconnections, markets, BAs. - PowerPoint PPT Presentation
Popular Tags:
69
Michael Milligan & Debbie Lew National Wind Technology Center National Renewable Energy Laboratory Golden, Colorado USA Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables… and Answers
Transcript
Page 1: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Michael Milligan & Debbie LewNational Wind Technology Center

National Renewable Energy LaboratoryGolden, Colorado USA

Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…

and Answers

Page 2: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

The Questions

1) Overview of the grid (interconnections, markets, BAs, etc) 2) How does the utility schedule their resources? 3) What are reserves? 4) Does a wind plant start or stop very suddenly? 5) Does geographic diversity help? 6) What generation is displaced when the wind blows? (How many kWh of

conventional generation is offset by 1 kWh of wind generation? ) 7) Does wind need backup or storage? 8) Does wind have capacity value? How is it measured and what does it mean? 9) What happens back at the utility when the wind stops blowing? 10) How much does it cost to integrate renewables into the grid? 11) How much does forecasting help? 12) Is there a limit to how much wind can be accommodated on the grid? 13) How do wind, concentrating solar power and PV plants impact the grid? 14) How can more wind be accommodated on the grid? 15) What happened in Texas in Feb ‘08 when they had to cut power to certain loads?

Page 3: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

1. Overview of the Grid

• Interconnections, markets, BAs

Page 4: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

There are 3 interconnections in the U.S.

1 2

3

Page 5: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

There are many control areas (balancing areas) in the East and in the

West

Page 6: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

General Operating Requirements

• The interconnection must be balanced ∑ loads = ∑ generation *

• Implication for individual balancing areas (BAs)∑ loads = ∑ generation + Imports – Exports

* DC ties can span two interconnections, but these are limited

Page 7: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Markets cover part of the U.S.

NPPD is Joining SPP

Page 8: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

2. How does the utility schedule resources?

• Non-market areas (regulated by state PUCs)– Balancing Authority is responsible for

scheduling generation to meet expected loads

– Individual utilities will often provide schedules to BA, based on economics

• Market areas– Similar, except the schedules are induced

by the energy market, not single entity

Page 9: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Economic DispatchLoad Duration Curve

16x103

14

12

10

8

6

4

2

0

MW

80006000400020000Hours

Page 10: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Economic Dispatch16x103

14

12

10

8

6

4

2

0

MW

80006000400020000Hours

Base load generation does not change its output

Intermediate gens change output in response to load

Peaking gens provide capacity, not much energy

Page 11: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Time (hour of day)0 4 8 12 16 20 24

Syst

em L

oad

(MW

)

seconds to minutes

Regulation

tens of minutes to hours

LoadFollowing

day

Scheduling

A Chronological View

Hours to Day ahead: use load forecast to commit units10 minutes to few hours: manually adjust generator set pointsSeconds to minutes: AGC automatically adjusts generator output

Page 12: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

3. What are reserves?There are different kinds of reserves• Contingency reserves

– Extra spinning capacity to guard against sudden loss of generator or transmission

– Contingency event is big and fast (wind does not behave this way)

– Contingency reserves are often shared in reserve pools or groups

– Largest hazard– Expensive

• Regulating Reserves• Operating Reserves

Page 13: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

3. What are reserves?

• Contingency reserves• Regulating reserves

– Capacity that is reserved for small up-down changes in load

• Other operating reserves

Page 14: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

3. What are reserves?• Contingency reserves• Regulating Reserves• Operating Reserves

– Generation that can be used to meet changing or unexpected load conditions

– No universally-accepted, rigorous definition– May be spinning or non-spinning (10-minute availability)– CA study of 33% renewables found increased operating reserves

of 3-7%

Page 15: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

4) Does a wind plant start or stop very suddenly?

• Large wind farms have many individual wind turbines

• The turbines are spread over many miles and do not experience the same wind at the same time

• TX event Feb 24, 2007: drop of 1,500 MW over 2 hours is similar to behavior of load

Total WIND

0

500

1000

1500

2000

2500

2/24/07 9:00 2/24/07 9:28 2/24/07 9:57 2/24/07 10:26 2/24/07 10:55 2/24/07 11:24 2/24/07 11:52 2/24/07 12:21 2/24/07 12:50

Total WIND

2 Hours

Page 16: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers
Page 17: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers
Page 18: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Typical monthly wind-speed state transition matrix

0.0 0.2 0.4 0.6 0.8 1.0

Rel

ativ

e Fr

eque

ncy

0 6 12 18 24 Velocity(t-1)

18 12

6

Wind-speed State Transition MatrixOctober, 1995, Imperial, NE

Velocity(t)

Page 19: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

5. Does Geographic diversity help?

Page 20: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

6. Which generation is displaced when the wind plant generates power?

Page 21: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

0

20

40

60

80

100 P

erce

nt o

f Pea

k

1 3 5 7 9 11 13 15 17 19 21 23Time of Day

Nuclear Other Wind Gas/Oil Hydro CT's

P+: Peakday SimulationUtility U1, High Plains Wind

0

20

40

60

80

100 P

erce

nt o

f Pea

k

1 3 5 7 9 11 13 15 17 19 21 23Time of Day

Nuclear Other Gas/Oil Hydro CT's

P+: Peakday SimulationUtility U1, No Wind

• Wind displaces the most expensive (marginal) generation, absent dispatch or other constraints

• Reduced CT and gas-oil generation in this scenario (your mileage will vary)

Page 22: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Do other generators reduce output by 1kWh when wind/solar produces 1kWh?

• Yes – if not in this balancing area, then another• (unless generation is charging a storage system)• System must be balanced

∑ loads + reserves = ∑ generation

• Unit or combination of units run at reduced output– May be a heat-rate penalty (generators are less efficient at partial

output)– Some units could perhaps be de-committed

• CA study– Mostly combined cycle units were displaced (40% CA and 60%

WECC)– 7500 MW wind and 1900 MW solar reduced NOx ~1500 tons and

SOx ~725 tons

Page 23: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

7. What happens in the control center when the wind stops generating

power?• Operating reserves (other generation) is

deployed– Committed, spinning resource in short time

frame, in merit order subject to ramp constraints

– Units may be started over longer time frame if economic

– Import/export from neighboring Balancing Area

Page 24: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

8. Does wind need backup or storage?• Increased operating reserves may be

necessary, but not dedicated backup• Although new storage has value, it may

not be cost effective• There is typically already storage on the

system– Natural gas in the pipeline or storage

facility– Controllable hydro

• A recent study by Xcel/PSCO found – Using existing pumped storage to offset

variability provided $1.30/MWh reduction in wind integration cost

– Enlarging existing gas storage facility was economic at large wind penetration

Wind Penetration 10% 15% 20% $/ MWH Gas Impact No Storage Benefits $2.17 $2.52 $3.66 $ / MWH Gas Impact With Storage Benefits $1.26 $1.45 $2.10

Page 25: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

9. Does wind have capacity value? How is it measured and what does it

mean?• System Resource Adequacy: is there

enough installed generation to meet load?• Reliability methods applied to power

systems– Loss of load probability (or related metric)– Loss of load expectation (LOLE) and reliability

target such as 1 day/10 years LOLE

Page 26: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Effective Load Carrying Capability (ELCC)

0.12

0.11

0.10

0.09

0.08

0.07

0.06

Loss

of L

oad

Exp

ecta

tion

(day

s/ye

ar)

11.0x10310.510.09.59.08.58.0Load (GW)

Original Reliability Curve Reliability Curve after Adding New Generation Target Reliability Level

<-400 MW->

Each generator added to the system helps increase the load that can be supplied at all reliability levels

Gi Gi+1 Gi+2 Added Generators

Page 27: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

What is ELCC?

• What ELCC is Not – a minimum generation value– a schedule or forecast for wind

• ELCC is– Measure of wind (or other resource’s)

contribution to overall system adequacy– Decomposition of the generator’s

contribution to adequacy

Page 28: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

10. What is wind’s impact on power systems operation, and is there a

cost?• Wind integration studies can help answer this

question• Two primary impacts: variability and

uncertainty• Data requirements

– High fidelity wind power data set– Detailed system specifications (generator

characteristics, loads)• System simulation and statistical analysis

Page 29: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Each relevant time frame for system operations is analyzed to determine

wind’s impact• Evaluate operating

impacts and associated costs– Regulation– Load Following– Unit Commitment

• Evaluate reliability impacts – Effective Load

Carrying Capability/Loss of Load Probability

Time (hour of day)0 4 8 12 16 20 24

Syst

em L

oad

(MW

)

seconds to minutes

Regulation

tens of minutes to hours

LoadFollowing

day

Scheduling

Page 30: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

10. What is wind’s impact on power systems operation, and is there a

cost?

• Minnesota 25% wind energy penetration (by energy) causes an increase in variability that must be met by power system operators and the non-wind generation fleet

14x103

12

10

8

6

4

2

Load

(MW

)

0

5-Minute Periods for Approximately 9 Months

1000500

0-500

-1000

5-m

inut

e ch

ange

s

6,600 Hours of 5-minute Electric Load14x103

12

10

8

6

4

2

Load

(MW

)

0

5-Minute Periods for Approximately 9 Months

-1000

-500

0

500

1000

5-m

inut

e ch

ange

s

6,600 Hours of 5-minute Electric Load and WindLower minimum load with wind

Page 31: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Impact on Uncertainty

• Increase in regulating and operating reserves• Operating reserve will depend on wind generation

in real-time• Change in unit commitment (wind forecasts can

help – more later)

Page 32: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Comparison of Cost-BasedU.S. Operational Impact Studies

* 3-year average; total is non-market cost** highest integration cost of 3 years; 30.7% capacity penetration corresponding to 25% energy penetration; 24.7% capacity penetration at 20% energy penetration*** found $4.37/MWh reduction in UC cost when wind forecasting is used in UC decision

Date Study Wind Capacity Penetra-tion (%)

Regula-tion Cost ($/MWh)

Load Following Cost ($/MWh)

Unit Commit-ment Cost ($/MWh)

GasSupplyCost($/MWh)

Tot Oper. Cost Impact($/MWh)

May ‘03 Xcel-UWIG 3.5 0 0.41 1.44 na 1.85

Sep ‘04 Xcel-MNDOC 15 0.23 na 4.37 na 4.60

June ‘06 CA RPS 4 0.45* trace na na 0.45

Feb ‘07 GE/Pier/CAIAP 20 0-0.69 trace na*** na 0-0.69***

June ‘03 We Energies 4 1.12 0.09 0.69 na 1.90

June ‘03 We Energies 29 1.02 0.15 1.75 na 2.92

2005 PacifiCorp 20 0 1.6 3.0 na 4.60

April ‘06 Xcel-PSCo 10 0.20 na 2.26 1.26 3.72

April ‘06 Xcel-PSCo 15 0.20 na 3.32 1.45 4.97

Dec ‘06 MN 20% 31** 4.41**

Jul ‘07 APS 14.8 0.37 2.65 1.06 na 4.08

Page 33: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

11. How much does wind forecasting help?

• Wind forecasts are derived from weather prediction models

• Wind forecast accuracy is improving

• Several wind forecasting firms in U.S. Courtesy: WindLogics, Inc. St. Paul,

MN

Page 34: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Wind forecasting benefits for NYISO

• 10% penetration, 2005 operating costs with wind forecasts

Page 35: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Forecasting benefits for CAISO

Page 36: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

12. Is there a limit to how much wind can be accommodated on the grid?

• Current studies in the U.S. have analyzed up to 25% of all electric energy from wind

• Based on work done so far, the question is not whether wind can be accommodated at high penetrations, the question is how and at what cost of integration

Page 37: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

International Energy Agency Report: Wind Integration Studies

0102030405060708090

100

W D

enmark

Irelan

d ESBNG UK

Portuga

l

US Minn

esota

2006

Netherl

ands

Spain

2011

Irelan

d ESBNG

Mid Norw

ay S

intef

German

y 201

5 dena

Irelan

d SEI

Sweden

Irelan

d SEI

Nordic

2004

Nordic+

Germany

Gree

nnet

US Minn

esota

2004

US Colo

rado

Finland

2004

US New

York

Perc

ent P

enet

ratio

n

Peak Energy

• Recent International Energy Agency Report: Design and operation of power systems with large amounts of wind power

http://www.uwig.org/IEA_Annex25-State_of_the_Art_Report.pdf

Page 38: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

12. Is there a limit to how much wind can be accommodated on the grid?

Denmark has access to large export marketsLennart Söder,KTH, Sweden, presented at UWIG, Oct 23-25, 2006

Page 39: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

13. How do wind, concentrating solar power, and PV plants impact the grid?

• Investigation in process in Western Wind & Solar Integration Study– 30% Wind, 3.5% CSP, 1.5% PV by

energy in study footprint

• Our prediction:– CSP (with thermal storage) will help

the grid– Wind will have load following

impacts– Distributed PV will have little

impact, but centralized PV could have impacts on regulation and possibly load following

LEGEND

WestConnect LinesCalifornia LinesLADWP LinesDC Lines

Control areas:APSEl PasoNevada PowerPNMSierra PacificSRPTristateTucsonXcelWAPA

Page 40: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Need for Subhourly PV Data and Analysis

Source: Tom Hansen, Tucson Electric Power

Page 41: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Wind power output

Page 42: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

PV and CSP output on sunny dayConfidential Data

Page 43: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Wind output (113 MW Storm Lake, Iowa)

Page 44: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

PV and CSP on a windy cloudy dayConfidential Data

Page 45: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Wind output (113 MW Storm Lake, Iowa)

Page 46: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

PV and CSP on a cloudy day with some windConfidential Data

Page 47: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Wind output (113 MW Storm Lake, Iowa)

Page 48: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

14. How can more wind be accommodated on the grid?

• Utility balancing areas can combine or cooperate – large electricity markets (example: Denmark/Europe)

Page 49: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

14. How can more wind be accommodated on the grid?

• Utility balancing areas can combine or cooperate – large electricity markets

• Example: Ramping, or changing output of generators that can be eliminated with larger balancing areas -1000

-500

0

500

1000

Ram

p (M

W/h

r)

53045298529252865280Hour of Year (one day)

-400-200

0200400

-400

-200

0

200

400

Exce

ss R

ampi

ng a

nd R

amp

Pena

lty (M

W/h

r)

Operating separate balancing areas causes extra ramping compared to combined operations. Blue: up-rampGreen: down-rampYellow: combined ramp

Ramping that could be eliminated by combining operations

Some areas are ramping up nearly 1000 MW/hr while other areas are ramping down nearly 500 MW/hr

Page 50: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

14. How can more wind be accommodated on the grid?

• Power system operations practices and wind farm control/curtailment

• Integration of wind forecasting and real time measurements into control room operations (WindLogics/EnerNex/UWIG/ Xcel study underway in Minnesota)

• Hydro dispatch, pumped hydro• Longer term: other storage

and markets (plug-hybrid electric vehicles, hydrogen)

Page 51: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

14) How can more wind be accommodated on the grid? What

about Storage?• Storage can have

significant benefits to the power system

• Storage may help integrate wind, but storage is not necessary or economic based on results in the U.S. at low-moderate penetrations

Page 52: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

• Event was forecasted but ERCOT’s forecasting system had not yet been integrated into system operations

15. What happened in TX, Feb 2008?

Page 53: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

15. What happened in TX, Feb 2008?• A frequency drop resulted in a call upon reserves including

loads that had voluntarily signed up for a Load-Acting-As-Resource program in which they are paid to curtail.

• There were 3 major contributors:– Wind generation dropped from 2000 to 360 MW in 3.5 hours– A conventional unit with 370 MW capacity tripped offline– The load forecast was wrong

• The wind ramp (500 MW/hour) is not the same as a reliability event with instantaneous loss of gen or transmission. – Conventional contingencies require dedicated, expensive spinning

reserve and immediate response. – Multi-hour wind ramps allow for use of less expensive resources.

Page 54: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Lessons Learned

• Load forecast failed to predict the large ramp up in demand

• The accurate wind energy forecast was not used in scheduling (this has been rectified)

• LAaR was very effective in economically reducing demand

• Wind event was a ramp event, not a contingency event (similar to 2007 event)

Total WIND

0

500

1000

1500

2000

2500

2/24/07 9:00 2/24/07 9:28 2/24/07 9:57 2/24/07 10:26 2/24/07 10:55 2/24/07 11:24 2/24/07 11:52 2/24/07 12:21 2/24/07 12:50

Total WIND

2 Hours

www.osei.noaa.gov

Page 55: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Old stuff below

Page 56: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

10 FAQ’s about Wind

1) How much wind is currently installed in the US?

2) What are the benefits of wind energy to the power system?

3) How can wind’s variability be incorporated into power system operations

4) Does wind plant output start/stop suddenly?

5) Can wind be predicted?

Page 57: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

10 FAQ’s about Wind6) Can the power system be reliably operated

with wind energy?7) Does wind need backup or storage?8) Is there a limit to how much wind can be

accommodated on the grid?9) Can wind power plants be controlled?10) Can wind energy make effective use of

transmission lines?11) Bonus Question: How can more wind be

accommodated on the grid?

Page 58: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

1) How much wind is currently installed in the US?

Page 59: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

1) How much wind is currently installed in the US?

Colorado/Xcel: Approx 20% wind penetration

(wind capacity/system

peak)

Iowa: Approx 16% wind

penetration (wind

capacity/system peak)

Page 60: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

MW Installed End 2006 Installed 2007

End 2007

Total EU-12 419 263 675

Total EU-15 47,651 8,291 55,860

Total EU-27 48,069 8,554 56,535

1b) How much wind is currently installed in Europe?

Page 61: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

2) What are the benefits of wind energy to the power system?

• Wind energy displaces– Fuel– Emissions; carbon

• Wind provides a hedge against rising fuel prices (natural gas, coal)

• Wind is an energy source with limited capacity contribution other generation is also required

• Wind can be cost-competitive with other forms of generation and may reduce electricity cost

Page 62: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

8) Is there a limit to how much wind can be accommodated on the grid?

• Recent International Energy Agency Report:

Design and operation of power systems with large amounts of wind power

http://www.uwig.org/IEA_Annex25-State_of_the_Art_Report.pdf

Page 63: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

9) Can wind power plants be controlled?

• New low-voltage ride-through (LVRT) grid codes in the U.S. will help wind turbines contribute to grid reliability

• Wind turbines can be controlled but not to the extent that conventional generation can be controlled– Ramp rate limits– Up-regulation (operate below potential so that wind output can be

increased if needed)– Curtailment, if necessary and economic, at low-load/high-wind

conditions

Page 64: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

10) Can wind energy make effective use of transmission lines?

• Conditional-firm transmission tariff (recent FERC ruling)

• Wind does not need transmission all of the time

• Most transmission paths have some open capacity most of the time

• Adding wind can result in more efficient usage of existing transmission

Page 65: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Increasing Attention in North America

• IEEE Transactions on Power Systems (2007)

• IEEE Power Engineering Society Magazine, November/December 2005

• Updated in 2007• Wind Power Coordinating

Committee Wind Super-Session, Summer 2008

• Utility Wind Integration Group (UWIG): Operating Impacts and Integration Studies User Group

www.uwig.org

Page 66: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Texas Event Feb 26, 2008

• 15:00 – Wind generation output at 2000 MW and begins a 3.5 hour ramp down to 360 MW at 18:30. The down ramp was 2 hours sooner and somewhat faster (8 MW/minute vs 5 MW/minute) than forecast the day ahead

• 17:10 – Evening load ramp begins, increasing 3800 MW in 90 minutes, (42 MW/minute). The evening load ramp-up began 25 minutes earlier than the short-term hour-ahead load forecast predicted

Page 67: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Texas Event Feb 26, 2008

• 17:44 – 150 MW conventional unit trips offline

18:28 – ERCOT calls on non-spin service to come on-line

18:33 – 328 MW of Responsive (spinning) Reserve deployed

18:41 – ERCOT calls for EECP step 2 18:49 – ERCOT instructs all available

LaaRs to reduce consumption

Page 68: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Texas Event Feb 26, 2008

• 18:59 – 1108 MW of LaaR was reduced within 10 minutes (1200 MW within 12 minutes)

18:56 – Spinning reserve deployment ends

20:08 – ERCOT ends step 2 and enters step 1

21:40 – EECP terminated

Page 69: Top FAQ’s (Frequently Asked Questions) About Utility Integration of Renewables…and Answers

Large Transmission Investments Have Very Small Retail Bill Impacts

Average Monthly Retail Bill $ / 1,000 kWhs

Total $65.75 Total $66.62

Transmission 6%

Generation 74%

Distribution 20%

Impact from $12.6 billion increase

(20%) in Transmission Infrastructure

Source: FERC