Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 1 of 53
TotalSeal MS ™ System
BUILDING PRODUCT TECHNICAL & INSTALLATION MANUAL REF: CODEMARK
BPTIM Doc V4, issued date: June 2018
For New Zealand
NZ Distributor Contact details:
Neptune Pacific LTD, PO Box 185, Albany Village, NZ
B2, 39 Arrenway Drive, Rosedale 0632 New Zealand
Ph: 09 415 4469
Australian Supplier and Distributor Contact details:
Web Site: www.neoferma.com
Ph.: +61 7 5576 4922
e-mail: [email protected]
PO Address: P.O. Box 324, West Burleigh, QLD 4219
HO Street Address: Unit 9, 4 Flagstone Drive, Burleigh, QLD, Australia 4220
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 2 of 53
This page intentionally left blank
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 3 of 53
Table of Contents:
1. General description of the product ……………………………………………….…… P5
a. Product description ……………………………………………………………….… P5
b. Purpose / Use ………………………………………………………………………….. P5
2. Scope of use & limitations ……………………………………………………………….… P6
a. Scope of use ………………………………………………………………………….… P6
b. Limitations …………………………………………………………………………….… P6
3. Compliance with the Building Code ……………………………………………….. P6-7
a. NZBC compliance …………………………………………………………………….. P6
b. B2 Durability ………………………………………………………………………….… P6
c. E2 Weather tightness / External moisture ……………………………. P6-7
d. F2 Hazardous building materials …………………………………………….…P7
4. List of specified components and SDS information ………………………….… P7
a. Membranes …………………………………………………………………………….. P7
b. Ancillary products …………………………………………………………………… P7
c. Features and Benefits …………………………………………………………..… P7
5. Construction Details and Drawings …………………………………………………... P8
a. General installation requirements ………………………………………..… P8
b. Substrate and Backfill …………………………………………………………..… P9
Limitation: Ref Expansion Joints …………………………………………….. P9
c. Construction guidance …………………………………………………………... P10
i. Installation – Soldier Piles ……………………………………………. P10
ii. Installation – Under slab / Horizontal ……………………… P10-11
iii. Installation – Vertical surfaces ………………………………..…… P11
iv. Backfilled Poured in place concrete walls ……………………. P11
v. Metal sheet Piling retention walls ………………………….….… P12
vi. Auger cast concrete retention walls ……………………….….… P12
vii. Pipe penetrations ………………………………………………………… P12
viii. Pile caps ………………………………………………………………………. P13
ix. Wall Floor junctions ………………………………………………….…. P13
x. Shotcrete walls ……………………………………………………….…… P13
xi. Waterstops ……………………………………………………………….…. P13
xii. Construction Joints / Non-movement joints ………………... P13
xiii. Clean up …………………………………………………………………….… P13
6. Maintenance and warranty ……………………………………………………………… P14
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 4 of 53
a. Maintenance …………………………………………………………………………. P14
b. Warranty ..……………………………………………………………………………… P14
7. Quality Management System …………………………………………………………… P14
a. Applicator / Installer Training ………………………………………………… P14
b. Project Checklists and Site Inspections ………………………………….. P15
8. Appendix A: TotalSeal MS™ Technical Data Sheets
a. TotalSeal MS ™ HP…………………..………………………………………….…. P16
b. SwellSeal Bentonite Granules …………………….………………………..… P17
c. Neoferma Seaming Paste …………………………….………………………… P18
d. Neoferma Detail Paste …………………………………..………………………. P19
Appendix B: Sample Warranty Documents for NZ
a. NZ warranty document example ………………………………………. P20-21
Appendix C: Examples of Generic Detail drawings ………………………. P22-39
i. DT001 – Standard Pit Detail (Below water)
ii. DT003 – Standard Pit Detail (Above water)
iii. DT005 – Standard Capping Beam detail (Above Water)
iv. DT006 – Standard Pipe Penetration (Below water)
v. DT007 – Typical Pile Cap Detail
vi. DT008 – Step Down Pile Cap Detail
vii. DT009 – Screw Pile Detail
viii. DT010 – CSM Wall Detail
ix. DT012 – Steel pile Concrete Wall Detail Below Water
x. DT013 – Secant Wall Detail
xi. DT014 – Construction joint Detail (Non moving Above Water)
xii. DT015 – Construction joint Detail (Non moving Below Water)
xiii. DT016 – Construction joint Detail (Non moving Below Water, High pressure)
xiv. DT021 – Pour Strip Detail
xv. DT022 - Masonry Block Foundation Wall Above Water Table
xvi. DT023 - Masonry Block Wall Horizontal Lap Above Water Table
xvii. DT024 - Masonry Block Wall Vertical Lap Above Water Table
xviii. DT025 - Termination Detail
Appendix D: Project checklists / Site Inspection documents
a. Pre-Project start up – IPP008 ……………………………..………………………..….. P40-41
b. Pre-Steel Placement – ITPC 030 V2 …………………..……………………………… P42-45
c. Pre-Concrete Pour – ITPC 031 V1 …………………………………………………….. P46-P47
Appendix E: Safety Data Sheets (SDS) …………………………………………. P48-53
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 5 of 53
1. General description
a. Product description
The TotalSeal MS ™ system is a highly effective, bentonite based, basement
tanking (vertical and horizontal foundation surfaces) waterproofing membrane
system. The membrane is comprised of a geosynthetic clay liner composite
made from high quality polypropylene geotextiles and premium grade sodium
bentonite granules. As part of the system approach the ancillary products;
SwellSeal seaming paste and Detail paste, used with the membrane are also
sodium bentonite based.
TotalSeal MS ™ uses the high swelling and self-sealing properties of Sodium
Bentonite to form a monolithic, low permeability membrane to protect the
structure from water.
Installation is fast and easy, requiring no primers or special tools.
TotalSeal MS ™ can be installed in virtually any weather, including freezing
temperatures and damp conditions.
b. Purpose / Use
Designed for use in below grade / below water table vertical and structural
foundation surfaces. Applications may include structures under continuous or
intermittent hydrostatic pressure. A strong mechanical bond is formed when
concrete is poured against the membrane as the membrane fibres “lock” into
the wet concrete. Upon hydration and when confined under pressure the
sodium bentonite granules swell forming a dense, impervious waterproofing
membrane.
Typical applications include backfilled concrete walls, under structural slabs,
tunnels, earth-covered roofs, and property line construction. Property line
construction applications include metal sheet piling, soldier pile and lagging, and
concrete caisson construction. TotalSeal MS ™ can be installed directly over a
properly prepared soil substrate without a working mud slab. Additionally,
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 6 of 53
TotalSeal MS ™ can be installed on freshly poured concrete walls as soon as the
forms are removed.
Use of TotalSeal MS ™ in areas not specified in the TotalSeal MS ™ Technical
manual (BPTIM Doc V4, issued date: June 2018) are outside the scope of this
certificate.
2. Scope of Use & Limitations
a. Scope of Use
The TotalSeal MS ™ waterproofing system is designed and engineered for use
under reinforced structural concrete slabs of 150mm thick or greater and where
the substrate has been compacted to 85% modified proctor density.
For external waterproof tanking membrane to in-situ concrete, precast
concrete and concrete masonry basement constructions subject to hydrostatic
pressures of up to 2 bar (20 metres); and a damp-proof membrane (DPM) to
slab-on-ground and basement constructions.
b. Limitations
The effectiveness of TotalSeal MS ™ is dependent upon the membrane being
both compacted and confined.
TotalSeal MS ™ is not designed for un-confined, above ground waterproofing
applications or over lightweight insulating concrete or “Besser” type blocks.
TotalSeal MS ™ is not designed for being fully immersed in excessively ponding
water before the geotextile membrane is covered with concrete.
TotalSeal MS ™ is not an expansion joint filler or sealant.
For warranty requirements a manufacturer’s representative should approve
the wall surface(s) prior to installing TotalSeal MS ™.
3. Compliance with the Building Code
A. The TotalSeal MS ™ basement tanking system complies with the following
clauses in the NZ Building Code:
B. B2 Durability: The TotalSeal MS ™ membrane system applied in
accordance with this manual will meet the requirements of NZBC Clause
B2.3.1(a) in terms of 50year longevity.
C. E2 Weather tightness: The TotalSeal MS ™ membrane system applied in
accordance with this manual will meet the requirements of NZBC Clause
E2.3.2 relating to the resistance of water penetration (hydrostatic water
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 7 of 53
resistance, susceptibility to leakage), provided the integrity of the
specified system is maintained.
D. F2 Hazardous building materials: Reference NZBC Clause F2.3.1
regarding Hazardous Building Materials, TotalSeal MS ™ membrane is
non-hazardous. All safety precautions to be adhered to are provided in
this technical manual.
4. List of products within the TotalSeal MS ™ system
Reference: Safety Data Sheet (SDS) provision:
Although all the materials in the basement tanking system mentioned below
are classified as non-hazardous, normal construction industry protocols
regarding the provision of SDS are followed. Current copies of all SDS are kept
on file (both hard copy and electronic) and are provided to customers when
product is shipped, when product is collected from Neoferma facilities and/or
when requested by any relevant site personnel.
a. Membranes
1. TotalSeal MS ™ HP – 1.65mt x 15mt rolls
b. Ancillary Products
1. SwellSeal Granulated Bentonite – 25kg bags
2. Neoferma Seaming Paste – 10kg pails
3. Neoferma Detail Paste -15kg pails
c. Features and Benefits of TotalSeal MS ™ membrane:
1. Purpose made for the construction industry and construction friendly
2. Self-heals if damaged preventing tracking water
3. Has an indefinite life-cycle
4. Can be installed in any weather and as soon as the forms are removed
5. Is easy to handle and install
6. Reinforcing steel can be installed directly on to the membrane
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 8 of 53
5. Construction Details and Drawings
For examples of generic Detail drawings please refer to Appendix C.
a. General Installation Requirements
• Ensure the substrate meets the minimum 85% modified proctor density.
• Install the membrane with the woven side (dark grey) of the geotextile liner facing
the concrete to be waterproofed, in both horizontal and vertical applications.
• Prevent bentonite waterproofing products from being fully immersed in excessively
ponding water before the geotextile membrane is covered with concrete.
• Diagrammatic example of the membrane lapping:
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 9 of 53
b. Substrate and Backfill Requirements:
• Backfill and substrate must be compacted to a minimum 85% Modified Proctor density.
• Substrate materials should be; mud slab, concrete, compacted sand, earth, crushed rock (no larger than 15mm in size.), blue metal or gravel.
• Materials and methodology to be approved in writing by Neoferma Australia prior to commencement.
• Backfill and surfaces should be level, without sharp objects or indentations have a smooth finish, free of debris, oil, grease, laitance, dirt, dust, or other foreign matter which will impair the performance of the waterproofing and drainage system and which do not comply with manufacturer's warranty requirements. TotalSeal MS™ can be installed on green structural concrete as soon as the forms are removed. There is no product limitation regarding a minimum concrete curing time requirement for TotalSeal MS™ to be installed over structural concrete. The Manufacturer recommends obtaining instructions from the project structural engineer regarding any site specific concrete curing time requirement. Do not apply TotalSeal MS™ waterproofing over lightweight insulating concrete or “Besser” type blocks.
• Horizontal deck or roof concrete surfaces should be sloped for proper drainage.
• Remove fins, ridges, and other protrusions to provide a level, smooth finish to match monolithic concrete surface. Completely fill honeycomb, aggregate pockets, holes or other voids with proprietary non-shrink cementitious repair mortar, levelled and smoothly finished to match monolithic concrete surface.
• Closely coordinate TotalSeal MS™ installation with the Backfill operation conducted under Division 2 work. Care should be used during Backfill operation to avoid damage to the waterproofing system. Follow generally accepted practices for backfilling and compaction. Backfill should be added in 150 - 300 mm lifts and compacted to a minimum 85% Modified Proctor density. At grade line and other areas that cannot be fully compacted.
• FLASHING is recommended across the top termination of the membrane.
• Failure to provide substrates to specification will void warranty.
Limitation: Ref Expansion Joints
TotalSeal MS™ waterproofing is not an expansion joint filler or sealant but may be used as
an expansion joint cover over properly installed expansion joint material placed during
substrate preparation.
To use TotalSeal MS™ as a cover for an expansion joint:
• All expansion joints should be cleaned, primed, fitted with the relevant expansion joint product – refer to Expansion joint material manufacturer for details.
• Install a 500 mm wide strip of TotalSeal MS™ centred over the expansion joint. Then place the main course of TotalSeal MS™.
• If movement is expected contact Neoferma for recommendation(s).
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 10 of 53
c. Construction Guidance
Typical generic Detail drawings are provided in Appendix C to assist.
i. Soldier Piles
For warranty requirements, a manufacturer’s representative should approve the wall
surface prior to installing TotalSeal MS™.
• Cut and attach a minimum 200mm strip of TotalSeal MS™ centred over all soldier piles. Prepare surface. Sharp offsets must be filled with Cementitious Repair Mortar. Large projections must be removed and made flush with surface. TotalSeal MS™ will conform to large gradual change in planes (e.g. around caisson column). Wall should be sufficiently planar to provide adequately smooth surface to apply TotalSeal MS™.
• TotalSeal MS™ should extend a minimum 100 mm on both sides of soldier pile.
• Attach TotalSeal MS™ horizontally (dark grey woven geotextile outward facing installer) with washer-head mechanical fasteners 600 mm on centre around the edge. Overlap all seams a minimum of 100 mm. Stagger all vertical overlap seams a minimum of 600 mm.
• Detail around all penetrations and tie-backs with 18 mm cant of Neoferma DETAIL paste. Extend 6 mm Neoferma DETAIL paste over substrate a minimum radius of 50
mm around penetration and tie-backs. Cut TotalSeal MS™ to fit snugly around penetrations and tie-backs.
• Terminate at grade with FLASHING fastened 300 mm on centre. Cover top edge of TotalSeal MS™ with 12 mm thick, 50 mm wide layer of Neoferma DETAIL paste.
• Inspect finished TotalSeal MS™ installation and repair any damaged material prior to concrete placement. Assure that TotalSeal MS™ is not displaced during concrete placement.
ii. Under Slab / Horizontal Installation
• Reinforced structural foundation slabs should be a minimum of 200 mm thick when placed on a working blinding slab. Reinforced concrete slab(s) on compacted grade shall be a minimum of 100 mm thick. When hydrostatic conditions exist, install TotalSeal MS™ under all footings, elevator pits and grade beams.
• No laps are to be directly under a construction or movement joint.
• All construction or movement joints are to have a 500mm wide secondary layer of TotalSeal MS™ membrane located centrally on the construction joint under the main course of membrane.
• Place TotalSeal MS™ directly on properly prepared substrate (dark grey woven geotextile side up facing installer) with adjoining edges overlapped a minimum of 100
mm.
• Stagger sheet end seams a minimum of 600 mm.
• All horizontal laps to be reinforced with a 20mm thick bead of Neoferma Seaming paste.
• All laps are to be staggered a minimum of 300mm to the next adjacent lap.
• When the slab is poured in sections, extend TotalSeal MS™ a minimum 300 mm beyond the slab edge to enable proper overlapping.
• Cut TotalSeal MS™ to fit snugly around penetrations and pile caps. (Do not extend TotalSeal MS™ over pile cap.)
• Around base of penetrations trowel 18 mm thick fillet of Neoferma DETAIL paste and extend the Neoferma DETAIL paste onto TotalSeal MS™.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 11 of 53
• Around base of pile caps trowel 50 mm thick fillet of Neoferma DETAIL paste and extend the Neoferma DETAIL paste onto TotalSeal MS™.
• Provide a minimum of 300 mm overlap between underslab and vertical wall waterproofing by either extending the TotalSeal MS™ beyond the form or turning it up in the form and reinforcing with Neoferma DETAIL paste.
• When laying membrane in trenches, make sure the laps are positioned "outside the trench" (There should be no horizontal lap on the trench wall).
• Any TotalSeal MS™ application in salt or contaminated water MUST BE PRE-HYDRATED with fresh water within a maximum of 24 hours prior to concrete placement.
• In sites with high salt levels refer to Neoferma Australia Pty Ltd.
• Inspect finished TotalSeal MS™ installation and repair any damaged material prior to concrete placement.
• Assure that TotalSeal MS™ is not displaced during concrete placement.
iii. Vertical Surfaces
• All vertical laps to be reinforced with Neoferma Seaming paste (note: the paste is to be placed in the middle of the lap at a bead size of approx 20mm) If the TotalSeal MS™ membrane has a rear PE layer, remove approximately 100 of the PE layer to allow pasting of laps.
• TotalSeal MS™ membrane is to be terminated a minimum 300 mm below grade and is to be secured with an Neoferma approved termination bar.
iv. Vertical / Backfilled Poured-In-Place Concrete Walls
• Place Neoferma DETAIL paste along the wall/footing intersection to form a continuous installation.
• Trowel 18 mm thick Neoferma DETAIL paste fillet at all inside corner transitions.
• Starting at the base of the wall, install TotalSeal MS™ sheet horizontally (dark grey woven geotextile against the wall) covering the Neoferma DETAIL paste and extending onto the footing a minimum of 150 mm.
• For hydrostatic conditions, cover the entire footing and overlap under slab waterproofing a minimum of 150 mm. Attach TotalSeal MS™ using washer-headed mechanical fasteners centred 600 mm around the edge. Stagger all vertical overlap seams a minimum of 600 mm.
• Detail around all penetrations with 18 mm cant of Neoferma DETAIL paste. Extend Neoferma DETAIL paste 60 mm thick over substrate a minimum radius of 150 mm around penetration. Cut TotalSeal MS™ to fit snugly around penetrations (See Detail 5).
• Terminate at grade with FLASHING fastened 300 mm on centre. Cover top edge of TotalSeal MS™ with 12 mm thick, 50 mm wide layer of Neoferma DETAIL paste (See Detail 6).
• Inspect finished TotalSeal MS™ installation and repair any damaged material prior to backfill placement. Assure that TotalSeal MS™ is not displaced during backfill placement or soil compaction.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 12 of 53
v. Vertical / Metal Sheet Piling Retention Walls
• Trowel 18 mm thick layer of Neoferma DETAIL paste along all sheet piling interlocks and over all tie-back plates.
• Attach TotalSeal MS™ directly to sheet piling horizontally (dark grey woven geotextile outward facing installer) with washer-head mechanical fasteners 600 mm on centre around the edge. Overlap all seams a minimum of 100 mm. Stagger all vertical overlap seams a minimum of 600 mm.
• Detail around all penetrations and tie-backs with 18 mm cant of Neoferma DETAIL paste. Extend 6 mm Neoferma DETAIL paste over substrate a minimum radius of 150
mm around penetration and tie-backs. Cut TotalSeal MS™ to fit snugly around penetrations and tie-backs.
• Terminate at grade with FLASHING fastened 300 mm on centre. Cover top edge of TotalSeal MS™ with 12 mm thick, 50 mm wide layer of Neoferma DETAIL paste.
• Inspect finished TotalSeal MS™ installation and repair any damaged material prior to concrete placement. Assure that TotalSeal MS™ is not displaced during concrete placement.
vi. Vertical / Auger Cast and Concrete Retention Walls
• Prepare surface. Sharp offsets must be filled with Cementitious Repair Mortar. Large projections must be removed and made flush with surface. TotalSeal MS™ will conform to large gradual change in planes (e.g. around caisson column). Wall should be sufficiently planar to provide adequately smooth surface to apply TotalSeal MS™. For warranty requirements, a manufacturer’s representative should approve the wall surface prior to installing TotalSeal MS™.
• Attach TotalSeal MS™ horizontally (dark grey woven geotextile outward facing installer) to prepared surface with mechanical fasteners 600 mm on centre around the edge. Overlap all seams a minimum of 100 mm. Stagger all vertical overlap seams a minimum 24" (600 mm).
• Cut TotalSeal MS™ to closely contour caissons and fit snugly around penetrations and tie-back plates. Detail around all penetrations and tie-backs with 18 mm cant of Neoferma DETAIL paste. Extend 6 mm Neoferma DETAIL paste over TotalSeal MS™ a minimum radius of 150 mm around penetration and tie-backs.
• Terminate at grade with FLASHING fastened 300 mm on centre. Cover top edge of TotalSeal MS™ with 12 mm thick, 50 mm wide layer of Neoferma DETAIL paste.
• Inspect finished TotalSeal MS™ installation and repair any damaged material prior to concrete placement.
• Assure that TotalSeal MS™ is not displaced during concrete placement.
vii. Penetrations
• All pipe penetrations to have a 50mm fillet of Neoferma Detail Paste around the base of the pipe in addition to a 300 mm flashing of TotalSeal MS™ membrane, with a 150 mm turn up.
• A single waterstop or equivalent bead of Neoferma XSeal 600 Mastic to be installed around the pipe just prior to the concrete placement. Ensuring that there is sufficient cover as per material manufacturers specification.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 13 of 53
viii. Pile Caps
• At the pile slab junction, lap the TotalSeal MS™ a minimum of 75mm onto the top or side face. Install a minimum of 50mm Neoferma Seaming paste fillet under the TotalSeal MS™ against the pile side or on top of the pile beneath the 75mm lap.
• A minimum of one row of hydrophilic waterstop / Bentonite waterstop or equivalent bead of XSeal 600 Mastic installed strictly as per manufacturers specification.
ix. Wall / Floor Junctions
• At all wall floor junctions, a minimum of 50mm fillet of bentonite powder, granules, Neoferma seaming paste or SwellSeal Hydrobar Tubes is to be placed under the corner junction.
x. Waterstops
• All waterstops are to be placed in a manner that ensures that the bond to the concrete is "firm and continuous". Any void areas beneath the waterstop are to be levelled prior to application.
xi. Construction Joints / Non-Movement Joints.
• All construction joints require a minimum of one row of Neoferma specified hydrophilic or Bentonite based waterstop, installed strictly as per manufacturers specification and must have a minimum of 70 mm concrete cover. On high pressure areas two rows of waterstop are required.
• When installing waterstop to vertical slab construction joints, install a small waterstop or equivalent size bead of XSeal 600 Mastic as per manufacturers specification at five metre intervals running top to bottom of the slab. This is to provide "segmented cells" along the joint. (This is to prevent horizontal tracking of water between installed waterstops that may result from lateral cracks.)
• Waterstops are not recommended in expansion joints unless part of and in conjunction with approved systems for use in expansion or movement joints. Consult Neoferma Australia Pty Ltd for information.
Clean Up
• In areas where adjacent finished surfaces are soiled by work of this Section, consult manufacturer of surfaces for cleaning advice and conform to their recommendations and instructions. Remove all tools, equipment and remaining product on-site. Dispose of section work debris and damaged product following all applicable regulations.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 14 of 53
6. Maintenance & Warranty
a. There is no requirement for on-going maintenance of the membrane
once it has been confined by the concrete pour.
b. Warranty: Neoferma Australia Pty Ltd offers a range of warranty
periods up to 50 years dependent upon levels of certified inspection;
country and client’s requirements.
For examples of the NZ Basement Tanking warranty documents refer to
Appendix B.
To qualify for the TotalSeal MS™ warranty the following steps are required:
1. Warranty request with all relevant information provided, see Appendix B
warranty document for detail of information.
2. Independent Inspection, Distributor or Neoferma Inspection, minimum of 3
site visits during the installation process. See Appendix D for example
documents to be provided.
3. Job photos in conjunction with the site inspections to be on record in the
electronic project folder held by Neoferma Australia Pty Ltd.
7. Quality Management system elements
Key risks related to substrate condition, satisfactory installation and concrete
pour requirements are managed via a Quality Management documentation
system (BPQP manual). See Appendix D for relevant TotalSeal MS™ Technical
Support documents related to Site Inspections.
a. Applicator / Installer Training
Required for entities that have had no experience with the installation of
bentonite membranes.
Neoferma in Australia and Neptune Pacific in New Zealand provide a “hands
on” approach to training with a Product Familiarisation PowerPoint
presentation including required standard procedures. Followed by practical
demonstrations.
A Neoferma Technical Support representative will be present on site to provide
Installation training at the start-up of the project, and during the project life
until satisfied that the Applicator is fully conversant with the products.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 15 of 53
b. Project Checklists & Site Inspections (See Appendix D.)
Notice period required to arrange independent inspections or for a Neoferma or Neptune Technical Support person to visit site:
Minimum notice required: 2 days. At Contractors cost.
Give sufficient notice so that inspections can be made at the following stages:
1. All substrate surfaces prior to the application of the waterproofing system. 2. At completion of installed products, pre-steel placement. 3. Prior to concrete pours to inspect laps and terminations, Pre Hydration of
the membrane. Dependent upon the size of project and number of concrete pours this may entail several visits.
Non approved applicators must disclose to the Head Contractor in writing and
receive an acknowledgement that CodeMark Warranty / QA does not apply,
failure to do so is a prosecutable offence under Australian and New Zealand
law.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 16 of 53
APPENDIX: A
TotalSeal MS™ and Ancillary Products - Technical Data Sheets
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 17 of 53
APPENDIX: A
TotalSeal MS™ and Ancillary Products - Technical Data Sheets
SwellSeal Granular Bentonite
TECHNICAL DATA SHEET
PRODUCT CODE: A15 ISSUE DATE: AUGUST 2017 V1
SWELLSEAL BENTONITE GRANULES
GENERAL Description:
A standard viscosity sodium bentonite with average particle size ranging from
between 0.850 and 0.212mm.
APPLICATIONS:
SwellSeal Bentonite Granules are a general purpose filler and extender for use when
mild thixotropic properties are desirable.
INSTALLATION:
• Neoferma SwellSeal Seaming Paste should be trowel (or hand) applied to approx 50-
75mm width of the top lap edge of the membrane and allowed to “ooze” out from the
lap.
• Smooth off the excess over the lap joint.
Typical Chemical composition (moisture free):
SiO2 31.02% MgO 1.35% Al2O3 11.04% Na2O 1.25%
Fe2O3 1.12% CaO 0.37% FeO 0.13% H2O 53.36%
Trace elements: 0.36%
Purity:
Hydrous aluminium silicate comprised principally of the clay mineral montmorillonite.
Montmorillonite content 90% minimum. Contains small percentage of feldspar,
biotite, selenite, etc.
Moisture Content: Maximum 13% shipped.
Dry particle size: Maximum 20% retained on a 1.18mm sieve.
Maximum 15% passing a 0.212mm sieve.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 18 of 53
APPENDIX: A
TotalSeal MS™ and Ancillary Products - Technical Data Sheets
TECHNICAL DATA SHEET
PRODUCT CODE: A36 ISSUE DATE: JUNE 2018 V2
NEOFERMA SEAMING PASTE
GENERAL Description:
Neoferma Seaming paste is a detailing accessory product for use with TotalSeal MS &
SwellSeal MS bentonite membranes to provide additional waterproofing protection. When
used on all horizontal and vertical membrane laps the seaming paste provides lap integrity
until the concrete pour is completed as the Neoferma Seaming Paste prevents movement
from construction operations or concrete placement.
APPLICATIONS:
Neoferma Seaming Paste is designed to work in conjunction with TotalSeal MS & SwellSeal
MS waterproofing membranes at the horizontal and vertical laps by providing a consistent
application of pre-hydrated sodium bentonite to secure the laps.
Neoferma Seaming Paste can also be used as a fillet for the footing/wall junction of
foundation walls providing additional waterproofing protection at this critical junction.
INSTALLATION:
Neoferma Seaming Paste should be trowel (or hand) applied to approx 50-75mm width of
the top lap edge of the membrane and allowed to “ooze” out from the lap.
• Smooth off the excess over the lap joint.
Typical Analysis:
SiO2 31.02% MgO 1.35%
Al2O3 11.04% Na2O 1.25%
Fe2O3 1.12% CaO 0.37%
FeO 0.13% H2O 53.36%
Trace elements: 0.36%
Packaging: 10kgs plastic pails.
Storage and shelf life: Maximum 12 months in sealed containers stored in a cool dry and
ventilated space.
Once open use immediately, will dry out if lid not replaced after each use.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 19 of 53
APPENDIX: A
TotalSeal MS™ and Ancillary Products - Technical Data Sheets
TECHNICAL DATA SHEET
PRODUCT CODE: A30 ISSUE DATE: JUNE 2018 V2
NEOFERMA DETAIL PASTE
GENERAL Description:
Neoferma Detail paste is a trowel grade, sodium bentonite based, detailing accessory
product for use with TotalSeal MS & Swellseal MS bentonite membranes, gasket and a
variety of surfaces. When used on all horizontal and vertical membrane laps the Detail paste
provides lap integrity until the concrete pour is completed as the DETAIL PASTE prevents
water ingress in the event of movement from construction operations or concrete placement.
APPLICATIONS:
Neoferma Detail paste is designed to work;
- Bonding waterstops to uneven surfaces
- At the horizontal and vertical laps by providing a consistent application of pre-
hydrated sodium bentonite to secure the TotalSeal bentonite membrane laps.
- Around drains and penetrations
- Sealing waterproofing terminations
- As a fillet for the footing/wall junction of foundation walls providing additional
waterproofing protection at this critical junction.
- Pre-cast manhole covers, cable ducts and pipes
- Sealing around precast segments
- Sealing rubber, and / or pvc waterstops
INSTALLATION for basement tanking specifically:
• Neoferma Detail Paste should be trowel (or hand) applied to approx 50-75mm width
of the top lap edge of the membrane and allowed to “ooze” out from the lap. Smooth
off the excess over the lap joint.
Packaging:
15kgs, plastic pails.
Storage and shelf life:
Maximum 12 months in sealed containers stored in a cool dry and ventilated space.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 20 of 53
APPENDIX: B
TotalSeal MS™ – Warranty Document examples
Example: NZ Warranty Template – Page 1
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 21 of 53
APPENDIX: B
TotalSeal MS™ – Warranty Document examples
Example: NZ Warranty Template – Page 2
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 22 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 23 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 24 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 25 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 26 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 27 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 28 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 29 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 30 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 31 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 32 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 33 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 34 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 35 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 36 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 37 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 38 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 39 of 53
APPENDIX: C
EXAMPLES OF GENERIC DETAIL DRAWINGS
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 40 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
IPP 008 – Pre Project Start Up Checklist – Page 1
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 41 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTSIPP 008 – Pre Project
Start Up Checklist – Page 2
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 42 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 030 V2 – Inspection Pre-Steel Placement – Installed products - Page 1
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 43 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 030 V2 – Inspection Pre- Steel Placement – Installed products - Page 2
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 44 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 030 V2 – Inspection Pre Steel Placement – Installed products - Page 3
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 45 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 030 V2 – Inspection Pre Steel Placement – Installed products - Page 4
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 46 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 031 V1 – Inspection Pre-Concrete Pour - Page 1
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 47 of 53
APPENDIX: D
PROJECT CHECKLISTS / SITE INSPECTION DOCUMENTS
ITPC 031 V1 – Inspection Pre-Concrete Pour - Page 2
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 48 of 53
APPENDIX: E
TotalSeal MS™ and Ancillary Products - Safety Data Sheets
Date of Issue: June 2018
Product Name: Neoferma TotalSeal MS™
Geosynthetic Bentonite Membrane Liner PRODUCT CODE: M12 MS5500 HP PLUS
Issued By: Neoferma Australia Pty Ltd.
Not Classified As Hazardous According to Criteria of Worksafe Australia.
This SDS summarizes to the best of our knowledge the health and safety hazard
information of the product and how to safely handle and use the product in the
workplace.
COMPANY DETAILS
Company Name: Neoferma Australia Pty Ltd
Address: PO Box 324, West Burleigh. QLD Australia 4219
Telephone Number: + 61 7 5576 4922
Emergency Number: (M) +61 419 773005 - 24 Hr.
Fax Number: +61 7 5576 4933
Poisons Information Centre: 13 11 26
Identification
Product Name: Neoferma TotalSeal MS™
Product Code: M12 MS5500 HP PLUS
UN Number: None Allocated
Dangerous Goods Class: None Allocated
Hazchem Code: None Allocated
Poisons Schedule: None Allocated
Packaging Group: None Allocated
USE:
Product Use: The Neoferma TotalSeal MS™ bentonite membrane is suitable for waterproofing.
Method of Application: By hand, rolling out prior to concrete pour.
PHYSICAL DESCRIPTION / PROPERTIES
The following information relates to the bentonite layer.
Appearance: odourless, off white to light tan powder
Temperature Working Range: Not applicable
Specific Gravity Not applicable
Flashpoint: Not applicable
Flammability Limits: Not applicable
Solubility in Water: Insoluble, however forms colloidal suspensions
INGREDIENTS:
Typically, bentonite is composed predominantly of the clay mineral Montmorillonite.
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 49 of 53
CAS No: 1302-78-9 80 - 85%
HEALTH HAZARD INFORMATION
HEALTH EFFECTS:
Acute: Bentonite is physiologically inert.
Swallowed: Amounts swallowed during normal handling are not likely to cause
harm. Ingestion of bentonite may cause swelling of a homogenous mass up to 12 times the volume
of the bentonite powder. This may produce intestinal and bowel obstruction.
No serious poisoning hazard expected.
Eye: Mild irritant
Skin: May cause drying and minor irritation.
Inhaled: May cause irritation to the upper respiratory tract.
Chronic: Inhalation of crystalline silica over a long period of time may cause
silicosis
FIRST AID
Swallowed: Wash out mouth with water. Do not induce vomiting. Drink plenty
of water, Keep warm and at rest. Obtain medical attention immediately.
Eye: Wash continuously with water.
Skin: Wash continuously with water.
Inhaled: Remove from exposure. If upper respiratory tract irritation persists
seek medical advice. Show this SDS to the medical practioner.
First Aid Facilities: Provide ready access to running water and first aid kit.
ADVICE TO DOCTOR
Treat symptomatically.
PRECAUTIONS FOR USE
Exposure Limits: N/A
Where natural ventilation is inadequate use local mechanical exhaust ventilation at the point of dust
generation.
PERSONAL PROTECTION
Respiratory Protection: N/A
In confined spaces use air filter dust respirators
complying with AS 1716, or an approved equivalent.
Hand Protection: N/A.
Eye Protection: N/A.
Body Protection: N/A
This information may not be relevant for emergency service situations.
FLAMMABILITY - NOT FLAMMABLE
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 50 of 53
SAFETY SAFE HANDLING INFORMATION
Storage and Transport:
Storage: Not classified as Dangerous Goods for storage.
Avoid contact with water.
Transport: Not classified as Dangerous Goods for transport.
Spills and Disposal:
Spills: Collect spills by vacuum or sweeping. Care should be taken to avoid
slippery surfaces which will occur when bentonite comes into contact with water.
Disposal: Dispose of product in accordance with Local State and Federal
regulations.
Environmental: N/A
Fire/Explosion Hazard:
Dangerous Decomposition: No hazardous decomposition products.
CONTACT POINT
Paul Lyden
Director, Neoferma Australia Pty Ltd
PO Box 324, West Burleigh. Qld. Australia 4219
Tel: (Bus. Hrs) +61 7 5576 4922 24Hr Tel: (M) +61 419 773 005
This data sheet and health, safety and the environmental information it contains is considered to be
accurate at the specified Issue Date. We have reviewed any information contained herein, which we
received from sources outside Neoferma Australia Pty Ltd. However, no warranty or
recommendation, expressed or implied, is made as to the accuracy or completeness of the data and
information contained in this data sheet. Health and safety precautions and environmental advice
noted in this data sheet may not be accurate for all individuals and / or situations. It is the user’s
obligation to evaluate and use this product safely and to comply with all applicable laws and
regulations. No statement made in this data sheet shall be construed as a permission,
recommendation or authorisation given or implied to practise any patented invention without a valid
licence. Neoferma Australia Pty Ltd shall not be responsible for any damage or injury from abnormal
use of the material, for any failure to adhere to recommendations, or from any hazards inherent in
the nature of the material.
Safety Data Sheet updated frequently. Please ensure you have a current copy.
End of SDS Report : July 2013 Reviewed and amended June 2018
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 51 of 53
APPENDIX: E
TotalSeal MS™ and Ancillary Products - Safety Data Sheets
Date of Issue: March 25 2015,
Review date: June 2018 V1
Neoferma Australia Pty Ltd, ABN: 72 094 042
Unit 10, 4 Flagstone Drive, QLD 4220
Tel: +61 7 5576 4922 Email: [email protected]
IDENTIFICATION of the Substance/Preparation and Company name
Product Name: Neoferma Detail Paste
Product Code: A29
Product Use: Waterproofing material.
HAZARDS IDENTIFICATION
Main Hazards: Not classified as hazardous according to Work-safe criteria and NOHSC, but these are
naturally occurring bentonite clays and contain a small amount of crystalline quartz as an impurity.
UN Number: NONE ALLOCATED
Dangerous Goods Class & Subsidiary Risk: NONE ALLOCATED
Hazchem Code: NONE ALLOCATED
Poisons Schedule Number: NONE ALLOCATED
COMPOSITION/INFORMATION on Ingredients
Hazardous ingredients: Mono propylene glycol (CAS number 57–55–7)
Bentonite Clay - Natural Mineral, Montmorillonite (CAS number 1302-78-9)
Non hazardous substances 99 - 100%
FIRST AID MEASURES
INGESTION / Swallowed: No adverse effects expected for normal, incidental ingestion. If large
amounts are swallowed get immediate medical attention.
Skin Contact: No first aid should be needed since this product does not affect the skin. Wash
exposed skin with soap and water before breaks and at the end of the shift.
Eye Content: flush the eyes immediately with large amounts of water, lifting the upper and lower
lids occasionally. If irritation persists or for imbedded foreign body, get immediate medical
attention.
Inhalation: Move immediately to fresh air. If breathing has stopped. Perform artificial respiration. If
breathing is difficult have qualified personnel administer oxygen. Get prompt medical attention.
First Aid facilities: Must ensure eyewash and safety showers area available in close proximity to any
workplace.
FIRE FIGHTING MEASURES
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 52 of 53
Fire Explosion hazard:
Product is combustible if in contact with naked flame.
Thermal decomposition in open flames can generate toxic gases (such as CO, CO2 and possibly
propionaldehyde vapours) as well as hazardous smoke and dust.
Normal extinguishing media is water spray, carbon dioxide, dry chemical or appropriate foam.
When fighting fires ensure use of SCBA units and full protective equipment.
ACCIDENTAL RELEASE MEASURES
Spills and Disposal:
After spills/accidents ensure Australian Standards approved chemical resistant PVC gloves and
protective clothing are worn.
Care must be taken as spillage may be slippery.
Shovel into suitably labelled containers for storage until disposed of via approved landfill. Avoid
contamination of drains and waterways.
Thoroughly wash area with water after spill collected.
HANDLING AND STORAGE
HAZCHEM: Not Applicable
STORAGE AND TRANSPORT
No special precautions required. Ensure containers tightly closed when not in use. Keep dry and
away from heat and open flames. Exercise good housekeeping.
EXPOSURE CONTROLS / PERSONAL PROTECTION
EXPOSURE STANDARDS: None applied by Worksafe Australia
ENGINEERING CONTROLS: Ensure ventilation at the immediate workplace is adequate to avoid
vapours in the immediate vicinity.
PERSONAL PROTECTION: Wear gloves, safety boots and glasses. Avoid skin, eye contact as well as
inhalation of the product. Always wash hands before eating, drinking, smoking or using the toilet.
Wash contaminated clothing and other protective equipment before re-use or storage. Gloves,
safety glasses and boots should comply with the appropriate Australian Standard.
FLAMMABILITY: This product is combustible.
PHYSICAL AND CHEMICAL PROPERTIES
Physical Description/Properties
Appearance: ODOURLESS, BEIGE PASTE
Neoferma Australia Pty Ltd BPT&IM V4 June 2018
Page 53 of 53
Boiling Point/Melting Point: NOT APPLICABLE
Vapour Pressure: (mm Hg.) NOT APPLICABLE
Specific Gravity: (H2o=1) 1.5 approx
Flashpoint: 103 deg C PMCC
Flammability Limits: COMBUSTIBLE-LEL = 2.6% and UEL = 12.5%
Solubility in Water: NEGLIGIBLE
STABILITY AND REACTIVITY
Stability: Stable – hazardous polymerisation will not occur.
TOXICITY
Toxicity: LD 50 (oral) = 21-33 g/kg (Rat)
IARC, NTP or OSHA does not list this product as a carcinogen, mutagen, teratogen or neurotoxin.
HEALTH EFFECTS
Acute Ingestion: No adverse health effects expected however diarrhoea may occur if large
quantities ingested.
Acute Eye: Slight to mild irritation.
Acute skin: May cause drying of skin (dermatitis) and may cause irritation.
Acute Inhalation:
Remove to fresh air. If breathing has stopped. Perform artificial respiration.
If breathing is difficult have qualified personnel administer oxygen.
Get prompt medical attention.
Facilities: No special requirements
Advice to Doctor: Treat symptomatically.
CONTACT POINT
Contact: +61 7 5576 4922 Director: Neoferma Australia Pty Ltd
This SDS summarises to our best knowledge at the date of issue, the chemical health and safety hazards of the material
and general guidance on how to safely handle the material in the workplace, however it shall not constitute a guarantee
for any specific product features and shall not establish a legally valid contractual relationship. Although some hazards are
described herein, we cannot predict that these are the only hazards because we have no knowledge or control over the
user’s working conditions. The user is responsible for the observance of all required statutory provisions. Each user should
read this SDS and consider the information in the context of how the product will be handled and used in the workplace,
including in conjunction with other products.