TR TR 610 top2 TR 612 top2 6100102 6120102 GB TR 610 top2 TR 612 top2 Current connection required for smooth zero-crossing switch operation (see connection diagram)! Assembly and operating instructions Time switch GB E D P 309164 06 MENU OK 1 0 6 12 18 24 2 p o t 0 1 6 R T 2,5mm 2 0,5mm - 2 m m 8 230-240V~ 50-60Hz R 10a - 30T 16(10)A 250V~ C1 1 2 3 MENU OK 1 2 0 6 12 18 24 2 p o t 2 1 6 R T 2,5mm 2 0,5mm - 2 m m 8 230-240V~ 50-60Hz R 10a - 30T C1/C2 16(10)A 250V~ C1 C2 4 5 6 1 2 3
Transcript
Page 1: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

TR TR 610 top2 TR 612 top2

61001026120102

GB

TR 610 top2 TR 612 top2

Current connection required for smooth zero-crossing switch operation (see connection diagram)!

Assembly and operating instructions Time switch

GB E

DP

309164 06

MENU OK

1

0 6 12 18 24

2 p o t 0 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

16(10)A 250V~

C1

MENU OK

1

0 6 12 18 24

2 p o t 1 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

16(10)A 250V~

1 C1 2 3

Ext

MENU OK

1 2

0 6 12 18 24

2 p o t 2 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

C1/C2 16(10)A 250V~

C1

C2

MENU OK

1 2

0 6 12 18 24

2 p o t 2 2 6

R

T

2,5mm 2 0,5mm - 2

230-240V~ 50-60Hz

R 10a - 30T C1/C2 16(10)A 250V~

C1

C2

Ext 2

m m

8

Ext 1

1 2 3

4 5 6

1 2 3

4 5 6

1 3

4 5 6

MENU OK

1

0 6 12 18 24

2,5mm 2 0,5mm - 2

230-240V~ 50-60Hz

R 10a - 30T 16(10)A 250V~

C1

m m

8

1 32

Ext

DCF

L N

TR61

1top2RC

*

MENU OK

1

0 6 12 18 24

2 p o t 0 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

16(10)A 250V~

C1

MENU OK

1

0 6 12 18 24

2 p o t 1 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

16(10)A 250V~

1 C1 2 3

Ext

MENU OK

1 2

0 6 12 18 24

2 p o t 2 1 6

R

T

2,5mm 2 0,5mm - 2

m m 8

230-240V~ 50-60Hz

R 10a - 30T

C1/C2 16(10)A 250V~

C1

C2

MENU OK

1 2

0 6 12 18 24

2 p o t 2 2 6

R

T

2,5mm 2 0,5mm - 2

230-240V~ 50-60Hz

R 10a - 30T C1/C2 16(10)A 250V~

C1

C2

Ext 2

m m

8

Ext 1

1 2 3

4 5 6

1 2 3

4 5 6

1 3

4 5 6

MENU OK

1

0 6 12 18 24

2,5mm 2 0,5mm - 2

230-240V~ 50-60Hz

R 10a - 30T 16(10)A 250V~

C1

m m

8

1 32

Ext

DCF

L N

TR

611top2RC

*

Page 2: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

Contents

Basic advice 3Screen display and keys/Operating principle 4Menu overview 5Connection/assembly 6Initial start-up 7

Menu item PROGRAM Reprogram switching time 8 Change switching time 9

Menu item MANUAL Manual and permanent switching 10

Menu item OPTIONS PIN code 10

Memory card OBELISK top2, RESET 11Technical data 12Service address/Hotline 12

2

Page 3: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

3

Basic advice

• The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715)

• Corresponds to type 1 STU actions in accordance with IEC/EN 60730-2-7

• Power reserve (10 years) is reduced with memory card inserted (in battery mode)

Designated use

• The time switch is used for lighting, air-conditioning, flushing etc. (electronic control)

• For use only in closed, dry rooms

• Do not use on safety devices, e.g. escape route doors, fire safety equipment etc.

Disposal Dispose of equipment in an environmentally-friendly manner

Danger of death through electric shock or fire! Installation should only be carried out by professional electrician!

WARNING

GB

Page 4: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

4

Screen display and keys Operating principle

0 6 12 18 24

Time display

Date display

Channel status C1, C2ON = Ein OFF = Aus

MENU

– Activate display– Open menu– Terminate programme– ESC (Leave menu)

YES Confirmation

OK press

NO Change/ revice

press

OK

– Save selection– Confirm selection

Alternativesare displayed

Days of the week from 1 – 7

Display of active buttons withrelevant function

Programmedswitch times

bbbb

1. Read text line Flashing text/symbol represents question

bbbb

2. Make decision

Page 5: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

Menu overview

19 10 06 C1 OFF C2 OFF

9:4046

PROGRAM

NEW

CHECK

MODIFY

DELETE

END

TIME/DATE MANUAL OPTIONS END

TIME

DATE

SU-WI

WEEK DAY

FORM DATE

FORM TIME

END

CHANNEL C1

OPERATING HOUR

LCD-ILLUMI-NATION

LANGUAGE

PIN

FACTORY SETTINGS

INFO

END

5

MENU

GB

PERM ON

PERM OFF

OVERRIDE ON

HOLIDAY

END

Page 6: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

6

Connection/installation

Connect cable Strip cable by 8 mm (max. 9). Insert cable at 45° in the open terminal (2 cables per terminal is possible). Only for flexible wiring: Press screwdriver downwards to open spring screwless terminal.

Warning, danger of death through electric shock! Must be installed by professional electrician! Disconnect power source. Cover or shield any adjacent live components. Ensure device cannot be switched on! Check power supply is disconnected! Earth and bypass!

WARNING

45° cable

Spring screwlessterminalNC contact

Test tap

Spring screwlessterminal

Page 7: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

7

Initial start-up

Set date, time and summer-/wintertime rule

Press desired button and follow on-screen

instructions.

ENGLISH

YEAR

MONTH

DAY

HOUR

MINUTE

SU-WI EUROPE

SU-WI GB/ IRL/P

SU-WI FIN/ GR/TR

SU-WI CDN

SU-WI USA

SU-WI IRAN

SU-WI FREE RULE

SU-WI FIX DATE

NO SU-WI

ok

19 10 06 C1 OFF C2 OFF

9:4046

GB

Page 8: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

8

same switching time forseveral days = Block

Switchingtime forone day

NEW

CHANNEL C1

MEM FREE 56

C1 On

HOUR

MINUTE

MONDAY

SAVECOPY

ADD TUESD

SAVE

ok

Program switching time

Press MENU.

(see fig.)

There are 56 memory locations available.

PROGRAM

Page 9: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

9

CHANNEL C1

MONDAY

MODIFYHOUR

MODIFY MINUTE

MODIFY SINGLE DAY

MODIFY BLOCK

ok

PROGRAM

NEW

CHECK

MODIFY

DELETE

Change/delete switching time

Press MENU.

(see fig.)

You can either change or delete a block, i.e. a switching time copied for several days (e.g. Mon-Fri) or a single switching time.

GB

Page 10: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

10

Manual and permanent switching

Manual and permanent switching can be selected by using menu option MANUAL or (in the automatic display) via a combination of buttons (see fig.).

Activate manual switching

Quickly press both buttons simultaneously.

Activate permanent switching

Press both buttons simultaneously for 2 sec.

Cancelling manual/permanent switching

Press both buttons simultaneously.

ok

channelC1

channelC2

PIN code

The PIN code is set in the menu underOPTIONS (see fig.).If you lost the PIN call the Theben Hotline.

OPTIONS

WITH PIN

NO PIN

NEW PIN

00 00

OPERATING HOUR

LCD ILLUMI-NATION

LANGUAGE

PIN

FACTORY SETTINGS

INFO

ok

Page 11: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

OBELISK top2 memory card

Using memory card

Insert memory card in the time switch.

Request saved switch timings, read to/from the time switch or start the Obelisk program.

Remove OBELISK top2 memory card (No. 9070404) (optional) after programming etc. and store in cover.

Avoid mechanical over-load or contamination caused by other storage/transport.

11

RESET

Press the 4 buttons simultaneously.

You can choose between RETAIN PROGRAMS

and DELETE PROGRAMS.

COPY OBELISK -> TSWI

COPY TSWI -> OBELISK

RUN OBELISK

CHECK OBELISK

GB

Page 12: TR 610 612 top2 309 164 06 GB - Timeguard€¦ · 3 Basic advice • The device is designed for installation on DIN top hat rails (in accordance with IEC/EN 60715) • Corresponds

12

Technical Data• Rated voltage: 230–240 V AC, +10 %/-15 %• Frequency: 50–60 Hz• Power consumption: max. 6 VA• Switching output: phase-independent zero-crossover switching)• TR 610 top2: suitable for switching SELV (Safe Extra-Low Voltage)• Contact: two way switch• Contact material: AgSnO2

• Switching capacity max.: 16 A, 250 V~, cos ϕ = 1 10 A, 250 V~, cos ϕ = 0,6• Switching capacity min.: 10 mA/230 V AC 100 mA/24 V AC/DC• Incandescent lamp load: 2600 W • Halogen lamp load: 2600 W• Fluorescent lamp load: uncorrected: series corrected: 1000 VA parallel corrected: 730 VA (80 µF)• Compact fluorescent lamps: 22 x 7 W; 18 x 11 W; 16 x 15 W; 16 x 20 W; 14 x 23 W• Permissible ambient temperature: –30 °C ... +55 °C

• Protection class:II in accordance with IEC/EN 60730-1 with designated installation • Protection rating: IP 20 in accordance with IEC/EN 60529• Power reserve: 10 years at +20 °C• Pollution degree: 2• Rated impulse voltage

Service address/HotlineService addressTheben AGHohenbergstr. 3272401 HaigerlochDEUTSCHLANDFon +49 7474 692-0 Fax +49 7474 692-150

HotlineFon +49 7474 692-369Fax +49 7474 [email protected], telephone numbers etc. www.theben.de