+ All Categories
Home > Documents > TR. OIL _dipen

TR. OIL _dipen

Date post: 03-Apr-2018
Category:
Upload: dipenkhandhediya
View: 216 times
Download: 0 times
Share this document with a friend

of 46

Transcript
  • 7/28/2019 TR. OIL _dipen

    1/46

  • 7/28/2019 TR. OIL _dipen

    2/46

    Transformer Oil Analysis Can

    Be Divided into three groups

    1. Dissolved Gas in oil Analysis.

    2. Transformer Oil Screening Analysis.3. Test for monitoring transformer

    winding condition.

  • 7/28/2019 TR. OIL _dipen

    3/46

    Transformer Dissolve GasAnalysis.

  • 7/28/2019 TR. OIL _dipen

    4/46

    DGA Of Transformer Oil During normal use, slow degradation of the mineral oil generates

    certain gases that collects in the oil.

    When a transformer begins to function abnormally, the oil getsdecomposed/breaksdown and produces the free radicals as shownbelow. These free radicals subsequently recombine and producelow molecular weight hydrocarbon. This process is largelydetermined by temperature, but is also influenced by otherconditions.

    H CH CH2 CH3 etc

    Equilibrium at Fault temperature

    H2 CH4 C2H6 C3H8 .

    C2H4 C3H6 .

    C2H2

  • 7/28/2019 TR. OIL _dipen

    5/46

  • 7/28/2019 TR. OIL _dipen

    6/46

    DGA analysis of Transformer oil. Analyzing these gases and their rate of production is

    a valuable laboratory tool for evaluating the conditionof an operating transformer.

    There are typically nine fault gases which areanalyzed in DGA. Each fault generates certain keygases and a distribution pattern of these gases.

    There are three major types of electrical faults which

    differs in their severity. The least severe is a partialdischarge or corona, localized hot spots are next inseverity, and the most severe is arcing.

  • 7/28/2019 TR. OIL _dipen

    7/46

    Classification of faults. Electrical faults in transformer can be broadly

    classified as following:

    Partial Discharge. Discharge of low energy

    Discharge of high energy

    Over heating less then 3000C.

    Over heating with temp. in between 300 to7000C.

    Overheating above 7000C

  • 7/28/2019 TR. OIL _dipen

    8/46

    Faults in Transformer and its Examples.

    Arcing Corona

    Overheati

    ng of

    Cellulose

    Overheati

    ng of Oil

    1 Causes Arcing Corona Overheating of cellulose X X

    2 Overheating of oil X X

    3 Winding turn-to-turn short-circuit X4 Winding open circuit X X

    5 Operation of build-in LTC X X

    6 Winding distortion or displacement

    7 Lead distortion or displacement

    8 Loose connection to bushing terminals, tap X X X

    leads, terminal boards

    9 Free water or excessive moisture in oil X X

    10 Floating metal particles X X

    11 Loose connection to corona shields X

    12 Loose collars, spacers, core ground straps, X core hold down angle (Braces)

    13 Through fault X

    14 Overloading X X

    15 Damaged yoke bolt insulation X

    16 Rust or other damage on core X

    17 Damaged shunt packs of tank X

    18 Jammed oil circulating path X

    19 Cooling system malfunction X

    Nature of Fault

    Cause of FaultSr

    No

  • 7/28/2019 TR. OIL _dipen

    9/46

    Mineral Oil CnH2n+2

    Hydrogen H - H H2

    Methane CH4

    Ethane C2H6

    Ethylene C2H

    4

    Acetylene H - C- C - H C2H2

    Carbon Dioxide O - C - O CO2

    Carbon

    MonoxideC - O CO

    Oxygen O - O O2

    Nitrogen N - N N2

    Structure of insulating oil and fault gases.Structural Formula of Oil and Fault Gases.

  • 7/28/2019 TR. OIL _dipen

    10/46

    Fault Gas Composition.

    H2 88%

    C02 1

    C0 1CH4 6

    C2H6 1

    C2H4 0.1

    C2H2 0.2

    Corona in Oil

    H2 39%

    C02 2

    C0 4

    CH4 10

    C2H4 6

    C2H2 35

    Arcing in Oil

    H2 16%

    C02 trace

    C0 traceCH4 16

    C2H6 6

    C2H4 41

    C2H2 trace

    Pyrolysis in Oil

    H2 9%

    C02 25

    C0 50

    CH4 8

    C2H4 4

    C2H2 0.3

    Pyrolysis of Cellulose

  • 7/28/2019 TR. OIL _dipen

    11/46

    Gases to be monitored in DGA as per IEC. Hydrogen (H2) Methane (CH4)

    Ethane (C2H6) Ethylene (C2H4) Acetylene (C2H2) Carbon Monoxide (CO)

    Carbon Dioxide (CO2) Nitrogen (N2) Oxygen (O2)

  • 7/28/2019 TR. OIL _dipen

    12/46

    Element Purpose of Test

    Hydrogen (ppm) Key indicator of Corona. Secondary indicator of Arcing and Overheated Oil.

    Methane (ppm) Secondary indicator of Corona, Arcing, and Overheated Oil.

    Ethane (ppm) Secondary indicator of Corona and Overheated Oil.

    Ethylene (ppm) Key indicator of Overheated Oil. Secondary indicator of Corona and Arcing.

    Acetylene (ppm) Key indicator of Arcing. Secondary indicator of severely Overheated Oil

    Carbon Monoxide (ppm) Key indicator of Overheated Cellulose. Secondary indicator of Arcing if the fault involves cellulose.

    Carbon Dioxide (ppm) Secondary indicator of Overheated Cellulose. Secondary indicator of Arcing if the fault involves cellulose.

    Oxygen (ppm) Indicator of system leaks, over-pressurization, or changes in pressure or temperature.

    Nitrogen (ppm) Indicator of system leaks, over-pressurization, or changes in pressure or temperature.

    Significance of Testing of Each Fault Gas

  • 7/28/2019 TR. OIL _dipen

    13/46

    Result Interpretations as per IEC code IEC method looks at the dissolved gas in oil ppm ratio of C2H2 / C2H4,

    CH4 / H2 , C2H2 / C2H4 and assigns a code for each gas pair. Forsome of the code combinations, an analysis/probable cause isdefined.

    IEC Ratio Code

    resulting C2H2 CH4 C2H4

    ratio C2H4 H2 C2H6

    < 0.1 0 1 0

    0.1 -

  • 7/28/2019 TR. OIL _dipen

    14/46

    Result Interpretations as per IEC codeIEC DGA RatiosC2H2 CH4 C2H4

    Case C2H4 H2 C2H60 0 0 0 No Fault, Normal1 0 1 0 Partial discharges of low energy2 1 1 0 Partial discharges of high energy density3 1 0 1 Discharges of low energy, Arcing3 2 0 1 Discharges of low energy, Arcing3 2 0 2 Discharges of low energy, Arcing4 1 0 2 Discharges of high energy, Arcing5 0 0 1 Thermal Fault, 150 C, Conductor Overheating6 0 2 0 Thermal Fault, 150 - 300 C, Oil Overheating, Mild7 0 2 1 Thermal Fault, 300 - 700 C, Oil Overheating, Moderate8 0 2 2 Thermal Fault, 700 C, Oil Overheating, Severe

  • 7/28/2019 TR. OIL _dipen

    15/46

    Transformer Oil ScreeningAnalysis

  • 7/28/2019 TR. OIL _dipen

    16/46

    Transformer oil Filtration: It is a processof removing moisture and mechanical

    impurities form the transformer oil.

    Transformer oil reclamation: It is a

    process of removing chemical impuritiesform the transformer oil.

    Transformer oil Filtration & reclamation

  • 7/28/2019 TR. OIL _dipen

    17/46

    Function Of Transformer Oil.

    1) Provides insulation.

    2) Provides cooling,

    3) Helps in extinguishing arcs.

    4) Dissolves gases generated by oil & winding

    degradation.

  • 7/28/2019 TR. OIL _dipen

    18/46

    Transformer oil Degradation.Oxidation

    Transformer Oil Carboxylic Acids (Acids)+Oil

    New oil contains little or no acidic material. As the acidic materialstart to form, the small amount of acidic material is soluble in oil.

    However, as more of acidic material forms it would reach to aseparation point and further formation would result in separation ofsolid material. This material would settle at the bottom as sludge.

    Acidic material in the oil reacts with various metals present in thetransformer and form salts; another form of sludge, which is also

    insoluble in the insulating oil.

    Effect of the sludge formation on transformer is very detrimentalfor its continued service. It is therefore essential to monitor thisprocess. For Monitoring oil condition following test are to be doneon oil.

  • 7/28/2019 TR. OIL _dipen

    19/46

    Test to be conducted on oil .

    Sr No. Test Name

    ASTM

    Standard Ref.

    No.

    IS

    Standard

    Ref. No.

    1 Dielectric Test ASTM D-877 IS - 6972

    2 Moisture Content ASTM D-4928 IS - 1866

    3 Interfacial Tension ASTM D-2285 IS - 1866

    4 Acidity Test ASTM D-644 IS - 18665 Pow er Factor/Tan Delta Test ASTM D-924 IS - 1866

    6 Test for O2 Inhibitor ASTM D-2268 -- -- -- --

  • 7/28/2019 TR. OIL _dipen

    20/46

    Dielectric Test Of Oil This test measures the ability of the oil to withstand electrical

    stress at power frequencies without failure. A low value for thedielectric-breakdown voltage generally indicates the presence ofcontaminants in the oil.

    Dielectric strength of oil is affected by the presence of moisture,foreign contaminants and particles generated due to oildegradation.

    Significantly oxidized oil may show high dielectric strength inabsence of moisture. It is therefore not advisable to rely solelyon dielectric strength of insulating oil without performing othertest on oil.

    Table -1 specifies limit of dielectric strength of oil for variousclass of transformer (based on operating voltage of transformer).

  • 7/28/2019 TR. OIL _dipen

    21/46

    > 145 KV Min 60 KV Min 50 KV72.5 & < 145 KV Min 50 KV Min 40 KV

    < 72.5 KV Min 40 KV Min 30 KV

    Requirement

    Before Energizing

    Transformer With

    New Oil

    Af ter Energizing

    Transformer and

    in Normal service

    Dielectric Test(Breakdown Voltage)

    in KV (IS:6972:1972)

    Property/Test Method Equipment Voltage

    Table - 1

    Limit of Dielectric Strength

  • 7/28/2019 TR. OIL _dipen

    22/46

    Moisture in Oil. Affects the dielectric properties of the oil.

    Affects winding insulation due to its hygroscopic nature.

    At normal temp. winding insulation absorbs moisture from oil, thus

    affecting its insulation property adversely and may reduce its life.

    At increased transformer temp. winding insulation releases the

    moisture and due to increased solubility of moisture in oil at thistemp, it will absorb the moisture.

    Ageing of oil produces acids, which increases the solubility of water

    in oil. Acid coupled with water further decompose the oil and forms

    more acid and water.

  • 7/28/2019 TR. OIL _dipen

    23/46

    Water solubility V/S Temperature.

  • 7/28/2019 TR. OIL _dipen

    24/46

    Limits of Water Content in oil As Per IS 1866.

    Before EnergizingTransformer With

    New Oil

    AfterEnergizing

    The Transformer

    and in Normal

    Service

    > 145 KV Max 15 ppm Max 25 ppm

    72.5 KV & < 145 KV Max 20 ppm Max 35 ppm< 72.5 KV Max 25 ppm Max 35 ppm

    Requirement

    Equipment Voltage

  • 7/28/2019 TR. OIL _dipen

    25/46

    Interfacial Tension (IFT)

    IFT can be defined as the amount of force required (in N/m) to

    pull a small wire ring upward a distance of 1 centimeter through

    water/ oil.

    The new oil before it is accepted for service shall have IFT valueover 0.040 N/m.

    As oil ages IFT value start decreasing.

    IFT value less then 0.015 N/m indicates sludging.

    IFT value in between 0.015 to 0.022 N/m shows an uncertain

    condition.

    IFT value more then 0.022 N/m indicates no sludging.

    IFT value in between 0.015 to 0.022 N/M should be scheduled

    for reclaiming.

  • 7/28/2019 TR. OIL _dipen

    26/46

    Acidity Test (Acid Number)

    Acid number can be defined as amount of KOH

    required in mg to neutralize the acid in 1 gram of

    transformer oil.

    New insulating oil has acid number less then 0.05.

    An acid number of 0.15 or higher indicates

    accelerated acid formation.

    When acid number reaches to 0.15 then oil should be

    reclaimed.

    An acid number of 0.4 indicates sludging in oil.

  • 7/28/2019 TR. OIL _dipen

    27/46

    Relationship Between IFT and Acid Number.

  • 7/28/2019 TR. OIL _dipen

    28/46

    Power Factor/ Tan Delta Test.

    It is the measure of imperfection of dielectric nature of oil. In an ideal

    dielectric oil, the current flowing through it should lead the voltage by

    90 degrees when sinusoidal AC voltage is applied. But it is not the

    case in reality. The angle by which it is short of 90 degree is calledloss angle. The cosine of the angle (90 - loss angle) is called power

    factor and the tangent of the loss angle is called dissipation factor.

    The loss factor (angle) relates to the inability of molecules in the oil to

    reorient themselves with an alternating electric field. This ability isdependent on the temperature of the sample, the size of the

    molecules involved, and their polarity. It is also dependent on the

    frequency of the alternating field.

  • 7/28/2019 TR. OIL _dipen

    29/46

    Power Factor/ Tan Delta Test.

    The power factor and the tan delta are both affected by the

    molecular size, composition, and relative orientation of

    functional groups within the molecules. In general within a series

    of similar molecules, the tan delta will increase as the molecularweight increases. It is therefore essential to monitor this process

    through either Tan Delta or Power Factor Test.

    IEEE suggested to monitor Power factor of Insulating oil while

    IS-1866 suggest to monitor Tan Delta of Insulating oil. Somerepresentative values are given in the below table.

  • 7/28/2019 TR. OIL _dipen

    30/46

    Before Charging

    (Max)

    After Charging

    (Max)

    < or = 72.5 KV 0.05 1.00

    72.5 - 145 KV 0.05 1.00

    > 145 KV 0.05 0.20

    Type Of Unit

    Tan Delta

    @25 C @100 C

    New Oil max 0.05% max 0.3%

    New oil received in new

    equipment

    < or = 69 KV max 0.15% max 0.15%

    69 288 KV max 0.10% max 0.10%

    >345 KV max 0.05% max 0.30%

    Suggested Limit for oil

    Usedmax 0.10% not specified

    Type of oil/UnitPower Factor

    As per IEC Standard

    As per IS standard

    Limit values of Power Factor and Tan Delta.

  • 7/28/2019 TR. OIL _dipen

    31/46

    Test For Oxygen Inhibitor.

    Formation of acids and sludge is caused by oxidation of oil.

    Prime importance is to be given to the exclusion of oxygen from oil.

    To remove oxygen from the oil, oxygen inhibitor is added. This will act

    like sacrificial electrode. Inhibitor presently used in transformer oil is Ditertiary Butyal

    Peracresol (DBPC).

    The ideal amount of DBPC is 0.3% by total weight of the oil.

    Inhibitor amount falls below 0.08% then oxygen freely attacks the

    transformer insulation system.

    Inhibitor amount less then 0.1% in oil is scheduled for re-inhabitation.

  • 7/28/2019 TR. OIL _dipen

    32/46

    Test for monitoring transformerwinding condition.

  • 7/28/2019 TR. OIL _dipen

    33/46

    Why It Is Required??

    Life of transformer is Life of Solid Insulation.

    Transformer Insulation is made up from Cellulose.

    Cellulose is a polymeric material of Cellobiose,-[C12H14(OH)6]n-, where n is in the

    range of 300 to 700 units.

    Cellobiose it self made up of two glucose units, C6H7O(OH)5 called monomer.

    The number of monomer units in polymer is known as degree of polymerization

    (DP). .

    The new transformer insulation having DP in the range of 1000 to 1400 and at

    the end of life its DP value is less then 200.

    As paper ages or deteriorates due to heat, acids, oxygen and water, will producewater, CO, CO2, furan derivatives and Cellulose with reduce chain length.

    In furan derivatives 2 furaldehyde (FFT) is more stable and often found in oil as

    paper degrades.

  • 7/28/2019 TR. OIL _dipen

    34/46

    How to Monitor Paper Degradationfrom Oil Analysis?

    Paper condition can be monitoring bymonitoring following parameters.

    CO2 and CO concentration in oil.

    CO2/CO ratio.

    FFT level in oil.

  • 7/28/2019 TR. OIL _dipen

    35/46

    Monitoring of CO2 and COconcentration in oil.

    IEEE standard C57.104 Guide for the Interpretation of Gases Generated in Oil-Immersed Transformer gives insulation status condition based on accumulatedvalues of CO2 and CO in oil. Accumulated dissolved gas (CO2 and CO) levelprovides four status condition as listed in following table:

    CO2

    concentration

    in oil in ppm

    CO

    concentration

    in oil in ppmCondition 1 Normal 0 - 2500 0 - 350

    Condition 2 Modest Concern 2500 - 4000 351 - 570

    Condition 3 Major Concern 4001 - 10000 571 - 1400

    Condition 4 Imminent Risk > 10000 > 1400

  • 7/28/2019 TR. OIL _dipen

    36/46

    Monitoring of CO2/CO ratio.

    Calculate CO2/CO ratio from each DGA.

    It has been observed that with normal loading and temperature, the rate of

    generation of CO2 runs 3 to 10 times higher then CO. Normally CO2/CO ratio is around 7.

    CO2/CO ration is less then 3 indicate rapid deterioration of transformerinsulation by electrical fault (Hi-temperature Fault).

    Ratio of CO2/CO around 2 indicates extreme over heating of transformer and itis strongly recommended that transformer should de-energized and internal

    inspection is to be carried out. If ration of CO2/CO is greater then 10 generally indicate thermal fault with

    involvement of cellulose (Low Temperature Thermal Fault Involving Cellulose).

  • 7/28/2019 TR. OIL _dipen

    37/46

  • 7/28/2019 TR. OIL _dipen

    38/46

    Monitoring of FFT Level In Oil.

    As paper ages furan derivatives are produced inoil.

    Some of furan derivatives are stable and some

    are highly unstable in oil. In furan derivatives 2 -Furaldehyde (FFA) is most stable and often foundin oil due to degradation of paper.

    FFA measurement in transformer oil gives theaverage decay integrates over the entire volume

    of the transformer insulation. In healthy transformer, there are no detectable

    furans in oil, or they are less then 100 ppb.

  • 7/28/2019 TR. OIL _dipen

    39/46

    Monitoring of FFT Level In Oil.

    When transformer ageing starts or significantdamage to paper insulation from heat occurs,furan levels in oil can go up to at least 1000 ppb

    and maximum to 70000 ppb. Table -2 can be used for the assessment of

    insulation condition in which First column in tableis used for the transformer with non-thermallyupgraded paper and second column is for the

    transformer with thermally upgraded paper. From furan analysis & from the table-2 it is easy

    to identify the insulation condition and estimatethe residual life of the transformer.

  • 7/28/2019 TR. OIL _dipen

    40/46

    2-Furaldehyde Furans (ppb) Estimated Estimated % of

    (ppb) Thermally DP Remaining Life

    Non thermal Paper upgreaded paper

    58 51 800 100130 100 700 90

    292 195 600 79

    654 381 500 66

    1464 745 400 50

    1720 852 380 46

    2021 974 360 42

    2374 1113 340 382789 1273 320 33

    3277 1455 300 29

    3851 1664 280 24

    4524 1902 260 19

    5315 2175 240 13

    6245 2487 220 7

    7337 2843 200 0

    End of Expected Life of

    Paper Insulation and of

    The Transformer

    Interpretation

    Normal Aging Rate

    Accelerated Aging

    Rate

    Excessive Aging

    Danger Zone

    High Risk Of Failure

    Table -2- Furans, DP, Percentage of life Used, of paper insulation.

  • 7/28/2019 TR. OIL _dipen

    41/46

    EHV TRANSFORMERS/REACTORS (132 KV AND

    ABOVE BUT INCLUDING UNIT AUXILIARY

    TRANSFORMERS):-

    DGA, BDV and Moisture in oil to be done once in sixmonth.

    Acidity, IFT, PF/Tan Delta and Furan analysis to be done

    once in year.

    Test for oxygen inhibitor to be done in once in two year.

    If possible metal particle analysis also to be done once in

    year.

    Contd.

    Recommended Test

  • 7/28/2019 TR. OIL _dipen

    42/46

    Transformer Below 132 KV ...

    DGA, BDV and Moisture analysis in oil to be done

    once in year.

    Acidity, IFT, PF/Tan Delta and Furan analysis tobe done once in year.

    Test for oxygen inhibitor to be done in once in

    three year.

  • 7/28/2019 TR. OIL _dipen

    43/46

    Some Examples

    Case I 2/27/75

    Hydrogen 231 ppm

    Oxygen 1043

    Carbon Dioxide 2194

    Ethylene 5584*

    Ethane 1726*

    Acetylene 0

    Nitrogen 71,154

    Methane 3997*

    Carbon Monoxide 0

    Conclusion : Thermal Fault, 700 C, Oil Overheating, Severe

    not involving cellulose.

    Ratio Value IEC Ratio code

    C2H2/C2H4 0 0

    CH/H2 17.3 2

    C2H4/C2H6 3.2 2

  • 7/28/2019 TR. OIL _dipen

    44/46

    Some Examples

    Case II 7/23/74

    Hydrogen 127 ppm

    Oxygen 1947

    Carbon Dioxide 2024

    Ethylene 32

    Ethane 1

    Acetylene 81*

    Nitrogen 78,887

    Methane 24

    Carbon Monoxide 0

    Ratio Value IEC Ratio code

    C2H2/C2H4 2.5 1

    CH/H2 0.18 0

    C2H4/C2H6 32 2

    Conclusion: Discharges of high energy, Arcing not

    involving cellulose.

  • 7/28/2019 TR. OIL _dipen

    45/46

    Limitations of Oil Analysis.

    No homogeneous condition with in thetransformer due to which system is

    never at true equilibrium. Pinpointing of problem is not possible.

    Extremely difficult to reach on any

    conclusion based on single Analysis. When fault is detected other techniques

    are also required for assistance.

  • 7/28/2019 TR. OIL _dipen

    46/46

    Thank you


Recommended