Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water Water-Source Heat Pumps Installation, Operation & Maintenance Instructions 97B0099N01 Revised: August 21, 2018 Model Nomenclature 3 General Information 4-5 Storage 5 Pre-Installation 5 Physical Data 6 Dimensional Data 7 Water Connection Installation 8 Ground Loop Applications 9-10 Water Quality Standards 11 Load Plumbing Installation 12 Hot Water Generator 13-15 Electrical - Line Voltage 16 Electrical - Low Voltage Wiring 16-17 Electrical Wiring Diagrams 18-19 DXM Controls 20-21 Safety Features - DXM Controls 22-23 Unit Commissioning and Operating Conditions 24 Unit and System Checkout 25 Start Up Procedure 26-27 Operating Pressures 28-29 Preventive Maintenance 30 Troubleshooting Form 31 Warranty 32 Revision History 36 Table of Contents
Transcript
Page 1: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Tranquility®

Brazed PlateGeothermal Closed Loop

Water-to-Water (TBW) Series

Residential EarthPure® Water-to-Water

Water-Source Heat PumpsInstallation, Operation &Maintenance Instructions

97B0099N01Revised: August 21, 2018

Model Nomenclature 3

General Information 4-5

Storage 5

Pre-Installation 5

Physical Data 6

Dimensional Data 7

Water Connection Installation 8

Ground Loop Applications 9-10

Water Quality Standards 11

Load Plumbing Installation 12

Hot Water Generator 13-15

Electrical - Line Voltage 16

Electrical - Low Voltage Wiring 16-17

Electrical Wiring Diagrams 18-19

DXM Controls 20-21

Safety Features - DXM Controls 22-23

Unit Commissioning and Operating Conditions 24

Unit and System Checkout 25

Start Up Procedure 26-27

Operating Pressures 28-29

Preventive Maintenance 30

Troubleshooting Form 31

Warranty 32

Revision History 36

Table of Contents

Page 2: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

This page was intentionally left blank.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

2 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 3: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

ClimateMaster Geothermal Heat Pump Systems

Model Nomenclature

� WARNING! �WARNING! TBW is for GROUND LOOP INSTALLATIONS ONLY. Installing TBW on open loop system will void warranty and unit will not be eligible for federal tax credit.

3

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

T B W A0 3 6 DG 0 0 B 0 B S1 3 6 7 8 9 10 11 12 13

SERIES

W = WATER TO WATER HEAT PUMPCONFIGURATION

UNIT SIZE036, 060, 120

REVISION LEVEL

TB= Tranquility Closed Loop

VOLTAGE

CONTROLS

0 = RESIDENTIALCABINET INSULATION

HOT WATER GENERATOR OPTIONS

B=BRAZED PLATESOURCE WATER COIL OPTIONS

B=BRAZED PLATELOAD WATER COIL OPTIONS

S = STANDARD

0 = NONE

FUTURE OPTIONS0 = NONE

1 = HWG w/INTERNAL PUMP

D = DXM

G = 208-230/60/1 - HFC-410A

2 4 5 14 15

Rev = A

Page 4: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

General Information

� WARNING! �

� WARNING! �

� CAUTION! �

WARNING! To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.

WARNING! All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.

CAUTION! To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and filters can quickly become clogged with construction dirt and debris, which may cause system damage and void product warranty.

SafetyWarnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any installation, service, or troubleshooting of the equipment.

DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury. DANGER labels on unit access panels must be observed.

WARNING: Indicates a potentially hazardous situation, which if not avoided could result in death or serious injury.

CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.

NOTICE: Notification of installation, operation or maintenance information, which is important, but which is not hazard-related.

� WARNING! �WARNING! This product can expose you to chemicals including Carbon Black, which is known to the State of California to cause cancer and Methanol, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

The following warning complies with State of California law, Proposition 65.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

4 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 5: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

General Information

� CAUTION! �

� CAUTION! �

CAUTION! DO NOT store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move and store units in an upright position. Tilting units on their sides may cause equipment damage.

CAUTION! CUT HAZARD - Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.

5

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

InspectionUpon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. Assure the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not filed within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to file all necessary claims with the carrier. Notify the ClimateMaster Traffic Department of all damage within fifteen (15) days of shipment.

StorageEquipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times. The stack limit for TBW036, 060 and 120 is three.

Unit ProtectionCover units on the job site with either shipping packaging, vinyl film, or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.

Examine all pipes, fittings, and valves before installing any of the system components. Remove any dirt or trash found in or on these components.

Pre-InstallationInstallation, Operation, and Maintenance instructions are provided with each unit.. The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation.Prepare units for installation as follows:1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the correct unit has been shipped.

2. Keep the cabinet covered with the shipping packaging until installation is complete and all plastering, painting, etc. is finished.

3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.

4. Inspect all electrical connections. Connections must be clean and tight at the terminals.

Page 6: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Unit Physical Data

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

6 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Model 036 060 120Compressor (qty) Scroll (1) Scroll (2)

Factory Charge HFC-410A (oz) [kg] Per Circuit 50 [1.41] 68 [1.93] 68 [1.93]

Water Connection SizeSource/Load 1" Swivel 1-1/2 FPT

HWG (in) 1" Swivel 1/2" FPT

WeightWeight - Operating (lbs) [kg] 295 [134] 268 [122] 541 [245]

Weight - Packaged (lbs) [kg] 320 [145] 293 [133] 585 [265]

Water Volume (Source)Gallons (Liters) 0.56 [2.1] 0.7 [2.7] 1.4 [5.3]

Dual isolated compressor mountingBalanced port expansion valve (TXV)Insulated Source and Load Water Coils standardInsulated Refrigerant Circuit standardCompressor on (green) and fault (red) light

Unit Maximum Water Working Pressure PSIG (kPa)Unit 145 [100]

Maximum Water Flow Through Unit GAL (L) 036 25 [94.6]

060, 120 35 [132.5]

Page 7: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

B

C

A

M

LK

1.0(2.5 cm)

1

2

3

4

5 6

JH

GF

E

D

1

2

3

4

5

6

RequiredService AccessOptional

Service Access

RequiredService Access

OptionalService Access

B

C

A

1.8(4.6 cm)

1.3(3.3 cm)

2.7(6.9 cm)

(18.3 cm)

(4.3 cm)

1.0(2.5 cm)

7.2

1.7

3 Ft

3 Ft

Notes 1 & 2 3 FtNotes 1 & 2

Notes 1 & 2 3 FtNotes 1 & 2

(7.4 cm)2.9

(10.1 cm)4.0

B

C

A

M

LK

1.0(2.5 cm)

1

2

3

4

5 6

JH

GF

E

D

1

2

3

4

5

6

RequiredService AccessOptional

Service Access

RequiredService Access

OptionalService Access

B

C

A

1.8(4.6 cm)

1.3(3.3 cm)

2.7(6.9 cm)

(18.3 cm)

(4.3 cm)

1.0(2.5 cm)

7.2

1.7

3 Ft

3 Ft

Notes 1 & 2 3 FtNotes 1 & 2

Notes 1 & 2 3 FtNotes 1 & 2

(7.4 cm)2.9

(10.1 cm)4.0

Notes:1. 3 feet front access is required, both sides ac-

cess is optional preferred for service access. However, all components may be serviced from the front access panel if side access is not available.

2. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field services.

Water to Water

Overall CabinetWater Connections

Electric Access Plugs1 2 3 4 5 6

ADepth

BWidth

CHeight

DSource

(Outdoor) Water In

E Source

(Outdoor) Water Out

FLoad

(Indoor) Water In

G Load

(Indoor) Water Out

H HWG

Water In

J HWG Water Out

K Low

Voltage

L External

Pump

M Power Supply

036-060in. 30.6 25.4 33 2.7 9.4 19.4 24.5 27.9 30.4 20.9 22.9 30.9

cm. 77.8 64.5 83.8 6.9 23.9 49.3 62.2 70.9 77.2 53.1 58.2 78.5

120in. 30.6 52.9 37 25.2 25.2 30.1 30.1 34.9 34.9 29.9 31.9 34.4

cm. 77.8 134.4 94 64.0 64.0 76.5 76.5 88.6 88.6 75.9 81.0 87.4

7

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

TBW036 - 120Unit Dimensional Data

Page 8: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Unit Installation

Residential models using swivel piping fittings for water connections are rated for 450 psi (3101 kPa) operating pressure. The connections have a rubber gasket seal similar to a garden hose gasket, which when mated to the flush end of most 1” threaded male pipe fittings provides a leak-free seal without the need for thread sealing tape or joint compound. Insure that the rubber seal is in the swivel connector prior to attempting any connection (rubber seals are shipped attached to the swivel connector). DO NOT OVER TIGHTEN or leaks may occur.

Unit is shipped with load and source strainers for field instal-lation outside unit.

FPT Connections (Size 120)Pipe joint compound is not necessary when Teflon threaded tape is pre-applied to hose assemblies or when flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint. Note: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed.

Maximum allowable torque for brass fittings is 30 ft-lbs [41 N-m]. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary.

WATER CONNECTION INSTALLATION

Unit LocationThese units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs.

The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the Installing Contractor to determine

and comply with ALL applicable codes and regulations.Locate the unit in an indoor area that allows easy removal of access panels, and has enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water and electrical connections. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. These units are not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate in areas subject to freezing or where humidity levels can cause cabinet condensation.

Gasket

Swivel Nut

Stainless steel snap ring

Brass Adaptor

Hand Tighten Only!

Do Not Overtighten!

The female locking ring is threaded onto the pipe threads which holds the male pipe end against the rubber gasket, and seals the joint. HAND TIGHTEN ONLY! DO NOT OVERTIGHTEN!

WARNING! Polyolester Oil, commonly known as POE oil, is a synthetic oil used in many refrigeration systems including those with HFC-410A refrigerant. POE oil, if it ever comes in contact with PVC or CPVC piping, may cause failure of the PVC/CPVC. PVC/CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC-410A as system failures and property damage may result.

� WARNING! �

WARNING! Must use strainer on both load and source sides. 20 mesh minimum. Failure to use strainers will void your warranty.

� WARNING! �

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

8 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 9: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Unit Installation

� CAUTION! �

Ground-Loop Heat Pump Applications

Pre-InstallationPrior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.

Piping InstallationAll earth loop piping materials should be limited to polyethylene fusion only for in-ground sections of the loop. Galvanized or steel fittings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fittings should be avoided due to their potential to leak in earth coupled applications. A flanged fitting should be substituted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat exchanger. Earth loop temperatures can range between 25 and 110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to 3.23 l/m per kW] of cooling capacity is recommended in these applications.

Test individual horizontal loop circuits before backfilling. Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled.

Flushing the Earth LoopOnce piping is completed between the unit, the flow controller and the ground loop (Figure 1), the loop is ready for final purging and charging. A flush cart with at least a 1.5 hp [1.1 kW] pump is required to achieve enough fluid velocity in the loop piping system to purge air and dirt particles. An antifreeze solution is used in most areas to prevent freezing. All air and debris must be removed from the earth loop piping before operation. Flush the loop with a high volume of water at a minimum velocity of 2 fps (0.6 m/s) in all piping. The steps below must be followed for proper flushing. 1. Fill loop with water from a garden hose through the

flush cart before using the flush cart pump to insure an even fill.

2. Once full, the flushing process can begin. Do not allow the water level in the flush cart tank to drop below the pump inlet line to avoid air being pumped back out to the earth loop.

3. Try to maintain a fluid level in the tank above the return tee so that air cannot be continuously mixed back into the fluid. Surges of 50 psi (345 kPa) can be used to help purge air pockets by simply shutting off the return valve going into the flush cart reservoir. This “dead heads” the pump to 50 psi (345 kPa). To purge, dead head the pump until maximum pumping pressure is reached. Open the return valve and a pressure surge will be sent through the loop to help purge air pockets from the piping system.

4. Notice the drop in fluid level in the flush cart tank when the return valve is shut off. If air is adequately purged from the system, the level will drop only 1-2 inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC flush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop fluid. Perform the “dead head” procedure a number of times.Note: This fluid level drop is your only indication of air in the loop.

Antifreeze may be added before, during or after the flushing procedure. However, depending upon which time is chosen, antifreeze could be wasted when emptying the flush cart tank. See antifreeze section for more details.

Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for a number of minutes to condition the loop to a homogenous temperature. This is a good time for tool cleanup, piping insulation, etc. Then, perform final flush and pressurize the loop to a static pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer). After pressurization, be sure to loosen the plug at the end of the Grundfos loop pump motor(s) to allow trapped air to be discharged and to insure the motor housing has been flooded. This is not required for Taco circulators. Insure that the Flow Controller provides adequate flow through the unit by checking pressure drop across the heat exchanger and compare to the pressure drop tables at the back of the manual.

AntifreezeIn areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area. Low temperature protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the

CAUTION! The following instructions represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

9

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 10: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

leaving loop temperature would be 25 to 22°F [-4 to -6°C] and low temperature protection should be at 15°F [-10°C]. Calculation is as follows:30°F - 15°F = 15°F [-1°C - 9°C = -10°C].

All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. Calculate the total volume of fluid in the piping system using Table 1. Then use the percentage by volume shown in Table 2 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity.

Table 2: Antifreeze Percentages by Volume

Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe

Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)Pipe Size Volume (gal) [liters]

Copper

1” 4.1 [15.3]

1.25” 6.4 [23.8]

2.5” 9.2 [34.3]

Rubber Hose 1” 3.9 [14.6]

Polyethylene

3/4” IPS SDR11 2.8 [10.4]

1” iPS SDR11 4.5 [16.7]

1.25” IPS SDR11 8.0 [29.8]

1.5” IPS SDR11 10.9 [40.7]

2” IPS SDR11 18.0 [67.0]

1.25” IPS SCH40 8.3 [30.9]

1.5” IPS SCH40 10.9 [40.7]

2” IPS SCH40 17.0 [63.4]

Unit Heat Exchanger Typical 1.0 [3.8]

Flush Cart Tank 10” Dia x 3ft tall [254mm x 91.4cm tall] 10 [37.9]

Ground-Loop Heat Pump Applications

Figure 1: Typical Ground-Loop Application Source Side

Air Pad

From Load

Shutoffswith P/T Plugs

Strainer(20 Mesh)

Strainer(20 Mesh)

Low Water Temperature Cutout Setting - DXM ControlWhen antifreeze is selected, the FP1 jumper (JW3) should be clipped to select the low temperature (antifreeze 10°F [-12.2°C]) set point and avoid nuisance faults (see “Low Water Temperature Cutout Selection” in this manual).

Type

Minimum Temperature for Low Temperature Protection

10°F [-12.2°C]

15°F [-9.4°C]

20°F [-6.7°C]

25°F [-3.9°C]

MethanolPropylene GlycolEthanol*

21%29%23%

17%24%20%

13%18%16%

8%12%11%

* Must not be denatured with any petroleum based product

� CAUTION �Do not exceed 25 GPM [94.6L] when flushing system. Damage to flow switch will occur.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

10 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 11: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Water Quality Standards

Table 3: Water Quality Requirements for TBWThis guide is an attempt to give a picture of the resistance of the unit heat exchanger in water to corrosion by some important chemical factors. However, corrosion is actually a very complex process influenced by many different factors in combination. This table is therfore a considerable simplification, and its value should not be overestimated.

Water Containing Concentration (mg/l or ppm) Resistance Explanations: + Good resistance under normal conditions

0 Corrosion problems possible, particularly when there are other factors rated 0

− Use is not recommended

Alkalinity (HCO3¯)< 70 +

70-300 +> 300 +

Sulfate (SO4²¯)< 70 +

70-300 +> 300 0

HCO3¯ / SO4²¯> 1.0 +< 1.0 +

Electrical Conductivity< 10 μS/cm +

10-500 μS/cm +> 500 μS/cm +

pH

< 6.0 06-7.5 0/+

7.5-9.0 +> 9.0 +

Ammonia (NH3)< 2 +

2-20 +> 20 +

Chlorides (CL¯) (140°F maximum) < 300 +

Free Chlorine (CL2)< 1 +1-5 +> 5 0/+

Hydrogen Sulfide< 0.05 +> 0.05 +

Free (aggressive) Carbon Dioxide (CO2)

< 5 +5-20 +> 20 +

Total Hardness (°dH) 4.0-8.5 +

Nitrate (NO3)< 100 +> 100 +

Iron (Fe)< 0.2 +> 0.2 +

Aluminum (Al)< 0.2 +> 0.2 +

Manganese (Mn)< 0.1 +> 0.1 +

11

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 12: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Load Side Plumbing Installation

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

12 G e o t h e r m a l H e a t i n g a n d C o o l i n g

TBW Unit Load PlumbingThe applications are too varied to describe in this document. However, some basic guidelines will be presented. Much of the discussions on water loop applications would be valid for the load plumbing discussion as well. Buffer tanks should be used to prevent short cycling of unit. All plumbing should conform to local codes with the following considerations:

Wide temperature variation applications such as heating/cooling coils: - Employ piping materials that are rated for the maximum

temperature and pressure combination. This excludes PVC for most heating applications.

- Insure that load water flow in high temperature heating applications is at least 3 gpm per ton [3.9 l/m per kW] to improve performance and reduce nuisance high pressure faults.

- DO NOT employ plastic to metal threaded joints- Utilize a pressure tank and air separator vent system to

equalize pressure and remove air..

Swimming Pool/Hot Tub Applications:- Load side should be isolated with secondary heat

exchanger constructed of anti-corrosion material in all chlorine/bromine fluid applications.

Potable Water Applications:- Load side should always be isolated with secondary

heat exchanger for use in potable water systems.- Insure load water flow in high temperature heating

applications is at least 3 gpm per ton to improve performance and reduce nuissance to high pressure faults.

Note: The manufacturer strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any finishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system. The manufacturer will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.

Page 13: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Hot Water Generator

The HWG (Hot Water Generator) or desuperheater option provides considerable operating cost savings by utilizing excess heat energy from the heat pump to help satisfy domestic hot water requirements. The HWG is active throughout the year, providing virtually free hot water when the heat pump operates in the cooling mode or hot water at the COP of the heat pump during operation in the heating mode.

Heat pumps equipped with the HWG option include a built-in water to refrigerant heat exchanger that eliminates the need to tie into the heat pump refrigerant circuit in the field. The control circuit and HWG pump are also built in and factory wired for residential equipment. Figure 3 shows a typical example of HWG water piping connections on a unit with built-in pump. This piping layout minimizes scaling potential.

Electric water heaters are recommended. If a gas, propane, or oil water heater is used, a second preheat tank should be considered (Figure 4). Also, if the electric water heater has only a single center element, the dual tank system is recommended to insure a usable entering water temperature for the HWG.

Hot Outletto House

PoweredWaterHeater

Upperelement to120 - 130°F[49 - 54°C]

Lowerelement to100 - 110°F[38 - 43°C]

Cold Inlet fromDomestic supply

Shut-offValve #4

Shut-offValve #1

Insulated water lines - 5/8” OD, 50 ft maximum (one way) meters [16mm OD, 15 meters maximum]

Shut Off Valve #2

Shut-offValve #3

InOut

Typically a single tank of at least 52 gallons (235 liters) is used to limit installation costs and space. However, a dual tank, as shown in Figure 4, is the most efficient system, providing the maximum storage and temperate source water to the HWG.

It is always advisable to use water softening equipment on domestic water systems to reduce the scaling potential and lengthen equipment life. In extreme water conditions, it may be necessary to avoid the use of the HWG option since the potential cost of frequent maintenance may offset or exceed any savings.

HFC-410A systems inherently have a lower hot gas temperature than R-22 systems because the equipment is more efficient (i.e. less waste heat is available). It is possible that energy could be transferred from the water heater to the hot gas line instead of from the hot gas line to the water heater during certain times of the year. To prevent this from occurring, a temperature switch will deactivate the pump at those conditions that typically occur in the cooling mode with low entering water temperatures.

Figure 3: Typical HWG Installation

Insulated water lines - 5/8” OD, 50 ft maximum (one way)[16mm OD, 15 meters maximum]

Upper element to 130°F [54°C](or owner preference)

Cold Inlet

Hot Outlet tohouse

PoweredWater Heater

Cold Inlet fromDomestic supply

Hot Outlet

UnpoweredWater Heater

Field Supplied 3/4” brass nipple and “T”

Lower element to 120°F [49°C]

Shut-offValve #1

Shut-offValve #4

Shut-offValve #3

Shut Off Valve #2

InOut

Figure 4: HWG Double Tank Installation

13

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 14: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Hot Water Generator

InstallationThe HWG has two temperature sensors factory connected to HWG circuit board at PI. NEVER DISCONNECT, RELOCATE OR REMOVE SENSORS! HWT is located on the HWG heat exchanger “Water In” line. If the HWG is connected incorrectly or if circulation is reversed, the HWG will not operate. Full load conditions could drive hot water tank temperatures far above safe temperature levels if the sensors have been disconnected or removed.

The heat pump, water piping, pump, and hot water tank must be located where the ambient temperature is not subject to freezing. Keep water piping lengths at a minimum. DO NOT use a one way length greater than 50 ft. [15 m].

All installations must be in accordance with local codes. The installer is responsible for knowing the local requirements, and for performing the installation accordingly. DO NOT connect the pump wiring until “Initial Start-Up” section, below. Powering the pump before all installation steps are completed may damage the pump.

Water Tank Preparation1. Turn off power or fuel supply to the hot water tank.2. Connect hose to the drain valve on the water tank.3. Shut off the cold water supply to the water tank.4. Open the drain valve and open the pressure relief

valve or a hot water faucet to drain tank.5. When using an existing tank, it should be flushed

with cold water after it is drained until the water leaving the drain hose is clear and free of sediment.

6. Close all valves and remove the drain hose.7. Install HWG water piping.

HWG Water Piping1. Using at least 5/8” O.D. copper, route and install

the water piping, valves and air vent as shown in Figures 3 or 4. An appropriate method must be employed to purge air from the HWG piping. This may be accomplished by flushing water through the HWG (as In Figures 3 or 4).

2. Insulate all HWG water piping with no less than 3/8” [10mm] wall closed cell insulation.

3. Open both shut off valves and make sure the tank drain valve is closed.

Water Tank Refill1. Close valve #4. Ensure that the HWG valves

(valves #2 and #3) are open. Open the cold water supply (valve #1) to fill the tank through the HWG piping. This will purge air from the HWG piping.

2. Open a hot water faucet to vent air from the sys-tem until water flows from faucet; turn off faucet. Open valve #4.

3. Depress the hot water tank pressure relief valve handle to ensure that there is no air remaining in the tank.

4. Inspect all work for leaks.5. Before restoring power or fuel supply to the water

heater, adjust the temperature setting on the tank thermostat(s) to insure maximum utilization of the heat available from the refrigeration system and conserve the most energy. On tanks with both up-per and lower elements and thermostats, the lower element should be turned down to 100°F [38°C] or the lowest setting; the upper element should be adjusted to 120-130°F [49-54°C]. Depending upon the specific needs of the customer, you may want to adjust the upper element differently. On tanks with a single thermostat, a preheat tank should be used (Fig 4).

6. Replace access cover(s) and restore power or fuel supply.

� CAUTION! �CAUTION! Use only copper piping for HWG piping due to the potential of high water temperatures for water that has been in the HWG heat exchanger during periods of no-flow conditions (HWG pump not energized). Piping other than copper may rupture due to high water temperature and potable water pressure.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

14 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 15: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Hot Water Generator

Initial Start-Up (After unit checkout and start-up procedure is complete)

1. Make sure all valves in the HWG water circuit are fully open.

2 Energize the HWG by flipping DIP switch 12 to "off" position.

Logic - For pump to operate, Hot Water Temperature (HWT) must be ≤ 125°F (52°C), Compressor Discharge Temperature (CDT) must be ≥ 125°F (52°C), both conditions are needed for PR relay contacts to close and pump to run.

3. Turn on the heat pump and allow it to run for 10-15 minutes.

4. The HWG pump should not run if the compressor is not running.

5. The temperature difference between the water entering and leaving the HWG coil should be approximately 5-10°F [3-6°C].

6. Allow the unit to operate for 20 to 30 minutes to insure that it is functioning properly.

15

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 16: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

All field installed wiring, including electrical ground, must comply with the National Electrical Code as well as all applicable local codes.

Refer to the unit wiring diagrams and electrical data table (Table 4) for fuse sizes and a schematic of the field connections which must be made by the installing (or electrical) contractor.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. All final electrical connections must be made with a length of flexible conduit to minimize vibration and sound transmission to the building.

General Line Voltage WiringBe sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.

Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the power distribution block, or compressor contactor, refer to unit wiring diagram. Consult the electrical data table (Table 4) for correct fuse size.

TransformerThe units are factory wired for 230 Volt. If supply voltage is 208V, transformer must be rewired by installer as illustrated on the wiring diagram by switching the Red (208V) and the Orange (230V) at the contactor terminal L1.

Load and Source PumpsWire pumps to unit per unit wire diagram.

� WARNING! �To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

� CAUTION! �Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors.

� WARNING! �Disconnect electrical power source to prevent injury or death from electrical shock.

Electrical - Line Voltage

Model VoltageCode Voltage Min/Max

VoltageCompressor HWG

PumpFLA

EXT LoopPumpFLA

Total Unit FLA

Min Circuit Amps

Max Fuse/ HACRRLA LRA QTY

036 3 208/230/60/1 197/252 16.7 79.0 1 0.5 4.0 21.2 25.3 40

060 3 208/230/60/1 197/252 26.3 134.0 1 0.5 4.0 30.8 37.3 60

120 3 208/230/60/1 197/252 26.3 134.0 2 0.5 4.0 57.1 63.6 80

HACR circuit breaker in USA onlyResidential units come standard with 75VA transformer, and optional HWG pump.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

16 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Table 4: TBW Electrical Data

Page 17: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Electrical - Low Voltage Wiring

Figure 5: AVM Valve Wiring

CC

Termostato

Y

12

3Y

AVMTaco VálvulaCalentador Interruptor

Unidad Empacada

CC

Aquastat

Y1

12

3

Y1

AVMTaco ValveHeater Switch

DXM2

Figure 6: Taco SBV Valve Wiring

Unit is typically controlled by field installed and wired aquastat and mode changeover switch (R to O is cooling mode). Wire to DXM P1 terminals, use minimum 18GA Class II wire.

Note: Do not close up unit until checkout is completed.

Low Voltage Wiring

A-Stat DXM

C C

Y1 Y1

End Switch

TACO VALVE

LED

CW/Y

Water Solenoid Valves An external solenoid valve(s) (with end switch so valve is fully open before compressor starts) should be used. Valve should also be normally closed type so water flows through only when unit is operating. A slow closing valve may be required to help reduce water hammer. Typical wiring for a 24VAC external solenoid valve. Figures 5 or 6 illustrate typical slow closing water control valve wiring for Taco zone sentry series (ClimateMaster P/N AMV…) and Taco SBV series valves. Slow closing valves take approximately 60 seconds to open (very little water will flow before 45 seconds). Once fully open, an end switch closure allows the compressor to be energized. When wired as shown, the slow closing valve will operate properly with the following notations:

1. The valve will remain open during a unit lockout.2. The valve will draw approximately 25-35 VA through the

“Y” signal of the aquastat

17

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 18: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

18 G e o t h e r m a l H e a t i n g a n d C o o l i n g

TBW036 & TBW060 Electrical Wiring Diagram - 96B0223N10

Page 19: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

19

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

TBW120 Electrical Wiring Diagram - 96B0225N10

Page 20: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

DXM Control - For detailed control information, see the DXM AOM (part #97B0003N13)

-Slow Flash = 1 flash every 2 seconds-Fast Flash = 2 flashes every 1 second-Flash code 2 = 2 quick flashes, 10 second pause, 2 quick flashes, 10 second pause, etc.-On pulse 1/3 second; off pulse 1/3 second

Field Selectable Inputs - Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the DXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will flash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds.Retry mode: If the control is attempting a retry of a fault, the status LED will slow flash (slow flash = one flash every 2 seconds) to indicate the control is in the process of retrying.

Field Configuration Options - Note: In the following field configuration options, jumper wires should be clipped ONLY when power is removed from the DXM control. LT1 and LT2 sensors are on the refrigerant lines; LT1 is between source HX and TXV; LT2 is between TXV and Load HX. Both sense refrigerant temperature, not water, which is a better indication of how water flow and temperature is affecting the refrigeration circuit.

Source Water low temperature limit setting: Jumper 3 (JW3-LT1 Low Temp) provides field selection of temperature limit setting for LT1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].Must use antifreeze if clipped.

Load Water low temperature limit setting: Jumper 2 (JW2-LT2 Low Temp) provides field selection of temperature limit setting for LT2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature).

Note: This jumper should only be clipped under extenuating circumstances, as recommended by ClimateMaster technical services.Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C]. Must use antifreeze if clipped.

Alarm relay setting: Jumper 4 (JW4-AL2 Dry) provides field selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection). Not Clipped = AL2 connected to R.Clipped = AL2 dry contact (no connection).

Low pressure normally open: Jumper 1 (JW1-LP norm open) provides field selection

for low pressure input to be normally closed or normally open.Not Clipped = LP normally closed. Clipped = LP normally open.

DIP Switches - Note: In the following field configuration options, DIP switches should only be changed when power is removed from the DXM control.

DIP Package #1 (S1) - DIP Package #1 has 8 switches and provides the following setup selections:1.1 - Unit Performance Sentinel (UPS) disable: DIP Switch 1.1 provides field selection to disable the UPS feature. On = Enabled. Off = Disabled.1.2 - Compressor relay staging operation: DIP 1.2 provides selection of compressor relay staging operation. The compressor relay can be selected to turn on with a stage 1 or stage 2 call from the thermostat. This is used with dual stage units (2 compressors where 2 DXM controls are being used) or with master/slave applications. In master/slave applications, each compressor and fan will stage according to its appropriate DIP 1.2 setting. If set to stage 2, the compressor will have a 3 second on-delay before energizing during a Stage 2 demand. Also, if set for stage 2, the alarm relay will NOT cycle during test mode.On = Stage 1. Off = Stage 2.

Description ofOperation

Status LED(green)

Test LED(yellow)

Fault LED (red) Alarm Relay

Normal mode On - Off Open

Normal mode with UPS On - Flashing Code 8 Cycle (closed 5 sec,open 25 sec)

DXM is non-functional Off Off Off OpenFault Retry Slow Flash - Flashing fault code OpenLockout Fast Flash - Flashing fault code ClosedTest Mode - On - -Night Setback Flashing Code 2 - - -ESD Flashing Code 3 - - -

HP Fault Slow Flash - Flashing Code 2 OpenLP Fault Slow Flash - Flashing Code 3 OpenLT1 Fault Slow Flash - Flashing Code 4 OpenLT2 Fault Slow Flash - Flashing Code 5 OpenCO Fault Slow Flash - Flashing Code 6 Open

Over/Under Voltages Slow Flash - Flashing Code 7 Open (closed after 15minutes)

Notes:a) Codes will be displayed with a 10 second LED off period.

For example: Code 3= flash 3 times, off for 10 seconds, flash 3 times, off for 10 seconds, etc…b) Slow flash will be 1 flash per every 2 seconds.c) Fast flash will be 2 flashes per every 1 second (same as currently is).

Invalid T-stat Inputs Flashing Code 4 - - -

Table 3b: DXM LED And Alarm Relay Operations

DXM Board

(Source) JW3 LT1(Load) JW2 LT2

Low Water Temperature Cutouts

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

20 G e o t h e r m a l H e a t i n g a n d C o o l i n g

DXM CONTROLS

Page 21: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

DXM Controls

1.3 - Thermostat type (heat pump or heat/cool): DIP 1.3 provides selection of thermostat type. Heat pump or heat/cool thermostats can be selected. When in heat/cool mode, Y1 is the input call for cooling stage 1; Y2 is the input call for cooling stage 2; W1 is the input call for heating stage 1; and O/W2 is the input call for heating stage 2. In heat pump mode, Y1 is the input call for compressor stage 1; Y2 is the input call for compressor stage 2; W1 is the input call for heating stage 3 or emergency heat; and O/W2 is the input call for reversing valve (heating or cooling, depending upon DIP 1.4).On = Heat Pump. Off = Heat/Cool.1.4 - Thermostat type (O/B): DIP 1.4 provides selection of thermostat type for reversing valve activation. Heat pump thermostats with “O” output (reversing valve energized for cooling) or “B” output (reversing valve energized for heating) can be selected with DIP 1.4. On = HP stat with “O” output for cooling. Off = HP stat with “B” output for heating.1.5 - Dehumidification mode: DIP 1.5 provides selection of normal or dehumidification fan mode. In dehumidification mode, the fan speed relay will remain off during cooling stage 2. In normal mode, the fan speed relay will turn on during cooling stage 2.On = Normal fan mode. Off = Dehumidification mode.1.6 - DDC output at EH2: DIP 1.6 provides selection for DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output.On = EH2 Normal. Off = DDC Output at EH2.1.7 - Boilerless operation: DIP 1.7 provides selection of boilerless operation. In boilerless mode, the compressor is only used for heating when LT1 is above the temperature specified by the setting of DIP 1.8. Below DIP 1.8 setting, the compressor is not used and the control goes into emergency heat mode, staging on EH1 and EH2 to provide heating. On = normal. Off = Boilerless operation.1.8 - Boilerless changeover temperature: DIP 1.8 provides selection of boilerless changeover temperature set point. Note that the LT1 thermistor is sensing refrigerant temperature between the source heat exchanger and the expansion device (TXV or cap tube). Therefore, the 50°F [10°C] setting is not 50°F [10°C] water, but approximately 60°F [16°C] EWT.On = 50°F [10°C]. Off = 40°F [16°C].

DIP Package #2 (S2) - DIP Package #2 has 8 switches and provides the following setup selections:2.1 - Accessory1 relay personality: DIP 2.1 provides selection of ACC1 relay personality (relay operation/characteristics). See table 6c for description of functionality. 2.2 - Accessory1 relay personality: DIP 2.2 provides selection of ACC 1 relay personality (relay operation/characteristics). See table 6c for description of functionality.2.3 - Accessory1 relay personality: DIP 2.3 provides selection of ACC 1 relay options. See table 6c for description of functionality.2.4 - Accessory2 relay personality: DIP 2.4 provides selection of ACC 2 relay personality (relay operation/characteristics). See table 6c for description of functionality. 2.5 - Accessory2 relay personality: DIP 2.5 provides selection of ACC 2 relay personality (relay operation/characteristics). See table 6c for description of functionality.2.6 - Accessory2 relay personality: DIP 2.6 provides selection of ACC 2 relay options. See table 6c for description of functionality.2.7 - Auto dehumidification fan mode or high fan mode: DIP 2.7 provides selection of auto dehumidification fan mode or high fan mode. In auto dehumidification mode, the fan speed relay will remain off during cooling stage 2 IF the H input is active. In high fan mode, the fan enable and fan speed relays will turn on when the H input is active. On = Auto dehumidification mode. Off = High fan mode.2.8 - Special factory selection: DIP 2.8 provides special factory selection. Normal position is “On” Do not change selection unless instructed to do so by the factory.

DIP 2.1 DIP 2.2 DIP 2.3 ACC1 Relay OptionOn On On Cycle with fan

Off On On Digital NSB

On Off On Water Valve - slow opening

On On Off OAD

Off Off Off Reheat Option - Humidistat

Off On Off Reheat Option - Dehumidistat

DIP 2.4 DIP 2.5 DIP 2.6 ACC2 Relay OptionOn On On Cycle with compressor

Off On On Digital NSB

On Off On Water Valve - slow opening

On On Off OAD

All other DIP combinations are invalid

Table 3c: Accessory DIP Switch Settings

21

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 22: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Safety Features - DXM Controls

Safety Features – DXM Control - The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor.Note: The 5 minute anti-short cycle also occurs at power up.Random start: The control features a random start upon power up of 5-80 seconds.Fault Retry: In Fault Retry mode, the Status LED begins slowly flashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed at the “fault” LED (DXM board). Note: LT1/LT2 faults are factory set at only one try.Lockout: In lockout mode, the status LED will begin fast flashing. The compressor relay is turned off immediately. Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset (disconnecting power to the control) resets the control and erases fault memory.Lockout with emergency heat: If DXM is configured for heat pump thermostat type (DIP 1.3), emergency heat will become active if O/W2 is energized.High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor).High pressure lockout code = 2Example: 2 quick flashes, 10 sec pause, 2 quick flashes, 10 sec. pause, etc.Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The low pressure switch input is bypassed for the initial 120 seconds of a compressor run cycle.Low pressure lockout code = 3

Source water low temperature (LT1): The LT1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT1 fault. The LT1 input is bypassed for the initial 120 seconds of a compressor run cycle. LT1 is set at the factory for one try. Therefore, the control will go into lockout mode once the LT1 fault has occurred.LT1 lockout code = 4Load water low temperature (LT2): The LT2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a LT2 fault. The LT2 input is bypassed for the initial 60 seconds of a compressor run cycle. LT2 is set at the factory for one try. Therefore, the control will go into lockout mode once the LT2 fault has occurred.LT2 lockout code = 5Condensate overflow: The condensate overflow sensor must sense overflow level for 30 continuous seconds to be recognized as a CO fault. Condensate overflow will be monitored at all times.CO lockout code = 6Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 19VAC to 30VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the DXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close.Over/under voltage shut down code = 7Unit Performance Sentinel-UPS (patent pending): The UPS feature indicates when the heat pump is operating inefficiently. A UPS condition exists when:

a. In heating mode with compressor energized, LT2 is greater than 125°F [52°C] for 30 continuous seconds, or:

b. In cooling mode with compressor energized, LT1 is greater than 125°F [52°C] for 30 continuous seconds, or:

c. In cooling mode with compressor energized, LT2 is less than 40°F [4.5°C] for 30 continuous seconds.

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

22 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 23: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Safety Features - DXM Controls

If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc.UPS warning code = 8

Swapped LT1/LT2 thermistors: During test mode, the control monitors to see if the LT1 and LT2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout with code 9 after 30 seconds if:

a. The compressor is on in the cooling mode and the LT1 sensor is colder than the LT2 sensor, or:

b. The compressor is on in the heating mode and the LT2 sensor is colder than the LT1 sensor.

Swapped LT1/LT2 thermistor code = 9.

ESD (DXM only): The ESD (Emergency Shut Down) mode can be enabled from an external common signal to terminal ESD to shut down the unit. The green status light will flash code 3 when the unit is in ESD mode. ESD mode = code 3 (green “status” LED)

DXM CONTROLS

Diagnostic Features - The LED on the DXM board advises the technician of the current status of the control. The LED can display either the current mode or the last fault in memory if in test mode. If there is no fault in memory, the LED will flash Code 1 (when in test mode).

The green status LED and red fault LED on the DXM board advise the technician of the current status of the DXM control. The status LED will indicate the current mode that the DXM control is in. The fault LED will ALWAYS flash a code representing the LAST fault in memory. If there is no fault in memory, the fault LED will flash Code 1. The yellow test LED will turn on when in test mode.

DXM Control Start-up Operation - The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The first time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized. On all subsequent compressor calls, the random start delay is omitted.

23

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 24: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Safety Features

Unit Commissioning & Operating Conditions

Environment – This unit is designed for indoor installation only. Do not install in an area subject to freezing or where humidity levels can cause cabinet condensation.Power Supply – A voltage variation of +/- 10% of nameplate utilization voltage is acceptable.

Operation and performance is primarily dependent upon water temperatures, water flow rates and ambient air temperature. This water to water heat pump is capable of operating over a wide temperature range and with flow rates of between 1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however usually no more than one of these factors may be at a minimum or maximum level at a time.

The commissioning table indicates water temperatures which are suitable for initial unit commissioning in an environment where the flow rate and water temperature is not yet stable and to avoid nuisance shut down of the units freeze and refrigerant pressure safeties.

The operating table indicates the maximum and minimum ranges of the unit.

For more specific unit performance reference the product catalog, the submittal data sheets or contact your supplier for assistance.

BUILDING COMMISSIONING

Cooling Heating

Unit Size 036 060/120 036 060/120

Source Min/Max 50/110˚ F10/43˚ C

50/120˚ F10/49˚ C

30/80˚ F-1/27˚ C

30/80˚ F-1/27˚ C

Load Min/Max 60/80˚ F16/27˚ C

60/90˚ F16/32˚ C

60/120˚ F16/49˚ C

60/120˚ F16/49˚ C

Ambient Min/Max 45/110˚ F7/43˚ C

39/85˚ F4/29˚ C

BUILDING OPERATING

COOLING HEATING

Unit Size 036 060/120 036 060/120

Source Min/Max 50/120˚ F10/49˚ C

50/120˚ F10/49˚ C

20/80-7/27˚ C

20/80-7/27˚ C

Load Min/Max 50/90˚ F10/32˚ C

50/90˚ F10/32˚ C

60/130˚ F16/54˚ C

60/130˚ F16/54˚ C

Ambient Min/Max 45/110˚ F7/43˚ C

39/85˚ F4/29˚ C

Table 6

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

24 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 25: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

UNIT CHECKOUTq Balancing/Shutoff Valves: Ensure all isolation

valves are open, water control valves wired and open, and flow switch (load and source) are operational* or brazed plates may burst.

q Line Voltage and Wiring: Ensure Voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Low voltage wiring is complete.

q Unit Control Transformer: Ensure transformer has properly selected control voltage tap. 208-230V units are factory wired for 230 operation unless specified otherwise.

q Entering Water: Ensure entering water temperatures are within operating limits of Table 6.

q Low Water Temperature Cutout: Verify low water temperature cut-out on DXM is properly set.

q Water Flow Balancing: Verify inlet and outlet water temperatures on both Load and source are recorded for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water flows that can erode heat exchangers.

q Unit Controls: Verify DXM settings are proper and complete.

* Water flow switches are normal open (no flow) contacts. TBW036 switch contacts close at 2.2 GPM flow. TBW060 and TBW120 switch contacts close at 3.3 GPM flow.

BEFORE POWERING SYSTEM, please check the following: SYSTEM CHECKOUTq System Water Temperature: Check load and

source water temperature for proper range and also verify heating and cooling setpoints for proper operation.

q System pH: System water pH is 6 - 8.5. Proper pH promotes longevity of hoses and fittings.

q System Flushing: Verify all hoses are connected end to end when flushing to ensure debris bypasses unit heat exchanger and water valves etc. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Verify all air is purged from the system. Air in the system can cause poor operation or system corrosion.

q Cooling Tower/Boiler: Check equipment for proper setpoints and operation.

q Standby Pumps: Verify the standby pump is properly installed and in operating condition.

q System Controls: Verify system controls function and operate in the proper sequence.

q Low Water Temperature Cutout: Verify low water temperature cut-out controls are provided for the outdoor portion of the loop or operating problems will occur.

q System Control Center: Verify control center and alarm panel for proper setpoints and operation.

q Strainers: Verify 20 mesh (841 micron) [0.84mm] strainers are installed in load and source water piping. Confirm maintenance schedule for strainers.

q Units with HWG: Confirm hot water tank(s) and piping have been filled and air has been purged. HWG is de-engerized (DIB-Switch 12 is "On") unit unit start up.

q Miscellaneous: Note any questionable aspects of the installation.

� WARNING! �Verify ALL water controls are open and allow water flow prior to engaging the compressor. Freezing of the heat exchanger or water lines can permanently damage the heat pump.

� WARNING! �To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze.

Unit & System Checkout

Note: The manufacturer strongly recommends all piping connections, both internal and external to the unit, be pressure tested by an appropriate method prior to any finishing of the interior space or before access to all connections is limited. Test pressure may not exceed the maximum allowable pressure for the unit and all components within the water system. The manufacturer will not be responsible or liable for damages from water leaks due to inadequate or lack of a pressurized leak test, or damages caused by exceeding the maximum pressure rating during installation.

25

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 26: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Table 7: Water Temperature Change Through Source Heat Exchanger

Note: Units have a five minute time delay in the control circuit that can be eliminated on the DXM PCB as shown in Figure 8. See controls description for detailed features of the control.

� WARNING! �When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment.

Water Flow, gpm [l/m] Rise, Cooling °F, [°C]

Drop, Heating°F, [°C]

For Closed Loop: Ground Source or Closed Loop Systems at 3 gpm

per ton [3.9 l/m per kW]

9 - 12[5 - 6.7]

4 - 8[2.2 - 4.4]

Unit Start Up Procedure

Model GPMPressure Drop PSI

30°F 50°F 70°F 90°FSource/Outdoor Brazed Plate

0364.56.89.0

1.74.17.1

1.33.46.0

1.02.85.1

0.82.44.5

0607.511.315.0

1.54.06.9

1.33.46.2

1.13.05.5

0.92.75.0

12015.022.530.0

1.74.47.6

1.43.86.8

1.23.36.1

0.92.75.0

Load/Indoor Brazed Plate

0364.56.89.0

0.61.42.6

0.51.32.4

0.31.12.2

0607.511.315.0

1.43.56.2

1.33.25.8

1.23.05.5

12015.022.530.0

1.63.86.8

1.43.56.4

1.33.36.0

Must use antifreeze if operation falls in grey area Operation not recommdedMultiply PSI x 2.31 to determine ft of hd

1. Adjust all valves to their full open position. Turn on the line power to all heat pump units.

2. Source and Load water temperatures should be within the minimum-maximum ranges of Table 6.

3. It is recommended that water-to-water units be first started in the heating mode, when possible. This will allow liquid refrigerant to flow through the filter-drier before entering the TXV, allowing the filter-drier to catch any debris that might be in the system before it reaches the TXV.

4. Four factors determine the operating limits of water source heat pumps, (a) source entering water temperature, (b) source entering water flow rate, (c) load entering water temperature, and (d) load entering water flow rate. When any one of these factors is at a minimum or maximum level, the other factors must be at normal levels to ensure proper unit operation.a. Place the mode switch (if applicable) in the

"HEAT" position. Adjust the unit aquastat to the lowest setting.

b. Slowly raise the aquastat setting to a higher temperature until the compressor activates.

c. Check for warm load water delivery within a few minutes after the unit has begun to operate.

d. Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Table 8. Refer to Table 7. Check the temperature of both entering and leaving source water. If the temperature drop is within range, proceed with the test. If the temperature drop is outside of the operating range, check refrigerant pressures and compare to Tables 9 and 10. Heat of extraction (HE) can be calculated for the source and compared to submittal data capacity pages. The formula for HE for systems with water is as follows:

HE = TD x GPM x 500, where TD is the temperature difference between the entering and leaving source water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Table 8.

JW3JW2JW1

Test

Off On

LT1LT2LP

DXM Board Short test pins together to enter Test Mode and speed-up timing and delays for 20 minutes.

Figure 8: Test Pins

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

26 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Table 8: Water Pressure Drop TBW036-120

Page 27: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

e. Heating capacity, also known as heat of rejection (HR), can be calculated and compared to submittal data capacity pages. The formula for HR for systems with water is as follows:

HR = TD X GPM X 500, where TD is the tem-perature difference between the entering and leaving load water, and GPM is the flow rate in U.S. GPM, determined by comparing the pres-sure drop across the heat exchanger to Table 8.

f. Check for vibration, noise, and water leaks.

5. Allow five (5) minutes between tests for pressure to equalize before beginning cooling test.a. Place the mode switch (if applicable) in the

"COOL" position. Adjust the unit aquastat to the highest setting.

b. Slowly lower the aquastat setting to a lower temperature until the compressor activates.

c. Check for cool load water delivery within a few minutes after the unit has begun to operate.

d. Verify correct water flow by comparing unit pressure drop across the heat exchanger ver-sus the data in Table 8. Refer to Table 7. Check the temperature of both entering and leaving source water. If the temperature rise is within range, proceed with the test. If the temperature rise is outside of the operating range, check refrigerant pressures and compare Tables 9 and 10. Heat of rejection (HR) can be calculated for the source and compared to submittal data capacity pages. The formula for HR for systems with water is as follows:

HR = TD X GPM X 500, where TD is the temperature difference between the entering and leaving source water, and GPM is the flow rate in U.S. GPM, determined by comparing the pressure drop across the heat exchanger to Table 8.

e. Cooling capacity, also known as heat of extrac-tion (HE), can be calculated and compared to submittal data capacity pages. The formula for HE for systems with water is as follows:

HE = TD X GPM X 500, where TD is the tem-perature difference between the entering and leaving load water, and GPM is the flow rate in U.S. GPM, determined by comparing the pres-

Unit Start Up Procedure

sure drop across the heat exchanger to Table 8.f. Check for vibration, noise, and water leaks.

6. If unit fails to operate, perform troubleshooting analysis (see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to ensure proper diagnosis and repair of the equipment.

7. When testing is complete, set system to maintain desired comfort level.

8. BE CERTAIN TO FILL OUT AND RETURN ALL WARRANTY REGISTRATION PAPERWORK.

� WARNING! �Verify ALL water controls are open and allow water flow prior to engaging the compressor. Freezing of the heat exchanger or water lines can permanently damage the heat pump.

27

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 28: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

TBW036-120 (TBW120 Per Circuit) (60 Hz I-P Units)

Source Entering

Water Temp °F

Source Water Flow

GPM/ton

Cooling

Load EWT °F @ 1.5-3.0

GPM/ton

Suction Pressure

PSIG

Discharge Pressure

PSIG

Super-heat°F

Sub-cooling°F

Water Temp

Rise °F Source

Water Temp

Drop °F Load

50

1.5

50 99-106 230-234 11-18 18-25

20-28

7-15

60 111-122 241-243 11-18 18-25 8-17

70 122-137 251-253 17-25 18-25 8-19

80 126-145 254-258 26-35 18-25 9-20

2.3

50 98-105 212-214 18-23 14-20

13-18

7-15

60 106-117 218-220 18-23 14-20 8-17

70 114-129 225-227 24-32 14-20 9-19

80 117-135 228-230 32-41 14-20 9-20

3.0

50 87-101 199-203 12-18 12-18

9-12

8-16

60 91-113 203-207 12-18 12-18 8-17

70 95-124 204-216 16-34 12-18 9-19

80 107-128 212-217 33-35 12-18 9-20

80

1.5

50 104-111 343-348 9-14 18-25

19-28

7-14

60 121-132 355-360 9-14 18-25 7-16

70 138-152 367-373 9-14 18-25 8-18

80 148-161 377-381 12-23 18-25 9-20

2.3

50 103-111 320-325 8-14 14-21

13-18

7-14

60 118.-129 328-334 8-14 14-21 8-16

70 132-147 336-344 12-20 14-21 8-18

80 140-172 343-353 19-29 14-21 9-20

3.0

50 94-110 305-314 9-13 12-18

8-12

7-15

60 112-121 313-319 9-13 12-18 8-16

70 121-146 317-329 12-20 12-18 9-18

80 131-151 324-333 18-27 12-18 9-20

110

1.5

50 109-116 483-497 9-13 17-23

18-26

5-11

60 128-135 494-511 9-13 17-23 6-13

70 147-154 505-525 9-13 17-23 7-15

2.3

50 109-116 459-473 9-13 15-20

14-17

5-11

60 127-135 466-484 9-13 15-20 6-13

70 153-159 473-495 9-13 15-20 7-15

3.0

50 100-112 444-431 9-14 12-17

8-13

5-12

60 120-130 449-467 9-14 12-17 6-14

70 131-152 454-474 9-14 12-17 7-15

80 153-164 463-479 13-21 12-17 8-17

Table 9

Operating Pressures

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

28 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 29: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Operating Pressures

TBW036-120 (TBW120 Per Circuit) (60 Hz I-P Units)

Source Entering

Water Temp °F

Source Water Flow

GPM/ton

Heating

Load EWT °F @ 1.5-3.0

GPM/ton

Suction Pressure

PSIG

Discharge Pressure

PSIG

Super-heat°F

Sub-cooling°F

Water Temp

Drop °F Source

Water Temp

Rise °F Load

20 3.0

60 56-63 199-228 4-14 6-14

2-6

5-1480 58-65 286-297 4-14 6-14 5-1490 59-66 310-344 4-14 6-14 4-14

100 61-65 360-385 4-14 6-14 4-14120 64-69 459-510 4-14 6-14 4-13

50

1.5

60 85-95 212-224 6-11 7-11

9-16

6-1780 91-99 290-310 6-11 7-11 6-1790 92-101 326-338 6-11 7-11 6-17

100 96-103 381-399 6-11 7-11 5-17120 100-108 474-488 6-11 7-11 4-16

2.3

60 95-102 215-228 6-13 7-11

6-12

7-1880 98-106 299-313 6-13 7-11 6-1890 99-108 329-341 6-13 7-11 6-18

100 102-110 384-401 6-13 7-11 6-17120 106-114 475-491 6-13 7-11 5-17

3.0

60 95-107 215-256 6-14 7-15

5-9

7-1980 101-110 310-326 6-14 7-15 7-1990 103-112 329-376 6-14 7-15 6-19

100 105-114 399-414 6-14 7-15 6-18120 108-118 476-524 6-14 7-15 5-17

80

1.5

60 109-129 225-237 14-26 5-14

15-21

8-1880 123-138 314-327 14-26 5-14 8-1990 130-142 343-357 10-15 5-14 7-19

100 137-147 402-415 10-15 5-14 7-19120 150-157 493-504 10-15 5-14 6-20

2.3

60 111-132 227-239 14-38 6-15

10-15

8-2080 135-147 315-330 14-38 6-15 8-2090 143-152 344-360 10-16 6-15 8-20

100 145-154 405-418 10-16 6-15 7-20120 156-163 494-507 10-16 6-15 6-20

3.0

60 110-149 227-279 19-44 6-18

7-12

9-2180 135-150 286-332 19-44 6-18 8-2190 145-166 345-408 13-23 6-18 8-21

100 148-158 405-420 13-23 6-18 8-21

Table 10

29

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 30: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Water Coil Maintenance Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treatment and mineral buildup through water use can also contribute to higher maintenance. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. However, flow rates over 3 gpm per ton (3.9 l/m per kW) can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.

StrainersFor proper water flow strainers must be cleaned regularly.

Hot Water Generator CoilsSee water coil maintenance for ground water units. If the potable water is hard or not chemically softened, the high temperatures of the desuperheater will tend to scale even quicker than the water coil and may need more frequent inspections. In areas with extremely hard water, a HWG is not recommended.

CompressorsConduct annual amperage checks to ensure amp draw is no more than 10% greater than that indicated by serial plate data.

CabinetDo not allow water to stay in contact with the cabinet for long periods of time to prevent corrosion of the cabinet sheet metal. Generally cabinets are set up from the floor a few inches for prevention. The cabinet can be cleaned using a mild detergent.

Refrigerant System To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Reference the operating chart for pressure and temperatures. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.

If the refrigerant circuit is opened for any reason, a new liquid line filter-drier must be installed.

Preventative Maintenance

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

30 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 31: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

TBW Troubleshooting Form

:etaD putratS:epyT pooL:remotsuC

Model #: :% & epyT ezeerfitnA:# laireS

Complaint:

VoltageCompressor Amps

1 Suction Temp2 Suction Press

2a Saturation Temp2b Superheat3 Discharge Temp4 Discharge Press

4a Saturation Temp4b Subcooling5 Liquid Line Temp6 Source Water In Tmp7 Source Water Out Tmp8 Source Water In Pres9 Source Water Out Pres

9a Press Drop9b Flow Rate GPM [l/s]10 Load Water In Temp 11 Load Water Out Temp12 Load Water In Pres13 Load Water Out Pres

13a Press Drop13b Flow Rate GPM [l/s]

Heat of Extraction (Absorption) or Heat of Rejection:

HE or HR =

Flow Rate x Temp. Diff x Fluid Factor

setoNnoitpircseD

H Temp Diff. =

H Temp Diff. = C Temp Diff. =

C Temp Diff. =

Heating Cooling

Refrigeration Troubleshooting FormWater-to-Water Units

COMPRESSOR

DISCHARGE

SUCTION

HWG**

EXPANSIONVALVE FILTER

DRIER

REVERSINGVALVE

HEATING POSITION COOLING POSITION

1

5

1210

1311

9

7

8

6

4

3

2

LT2:HEATINGLIQUIDLINE

5 LT1:COOLINGLIQUIDLINE

CONDENSER (HTG)EVAPORATOR (CLG)

CONDENSER (COOLING)EVAPORATOR (HEATING)

**Turn off HWG before troubleshooting.

REFRIG FLOW - HEATING REFRIG FLOW - COOLING

REFRIGERANT: HFC-410A

OPERATING MODE: HEATING COOLING

Fluid Factor: (for Btuh)500 (Water); 485 (Antifreeze)

Source

BrazedPlateHX

Load

Fluid Factor: (for kW)4.18 (Water); 4.05 (Antifreeze)

BrazedPlateHX

31

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 32: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

WarrantyC

LIM

ATE

MA

STE

R, IN

C.

LIM

ITE

D E

XPR

ESS W

AR

RA

NT

Y A

ND

LIM

ITATIO

N O

F LIA

BIL

ITY

AN

D

RE

ME

DIE

S FOR

RE

SIDE

NT

IAL C

LA

SS PRO

DU

CT

S WIT

H L

AB

OR

AL

LO

WA

NC

E

This L

imited E

xpress Warranty A

nd Lim

itation Of L

iability And R

emedies A

ffects Your Legal R

ights And Should B

e Read C

arefully In Its Entirety.Subject to the term

s and conditions below, C

limate M

aster, Inc. (“CM

”) extends a limited w

arranty (“Limited W

arranty”) for Residential Class heating and cooling equipm

ent manufactured or sold by C

M (“Products”), that w

as purchased on or after May 1, 2010 (this w

ould generally include C

M U

nits with serial num

bers beginning with “N

118” and higher), and installed in a one or two fam

ily residential dwelling, for personal, household or fam

ily purposes in the United States of A

merica or C

anada, (“Application”), to be free from

defects and workm

anship under normal use and

maintenance. If you are unsure if this Lim

ited Warranty applies to a Product you have purchased, contact C

M at the phone num

ber or address reflected below.This Lim

ited Warranty D

OES N

OT cover com

mercial applications of the Products. C

omm

ercial applications include any application other than installation in a one or two fam

ily residential dwelling for personal, household or fam

ily purposes. Refer to Clim

ateMaster C

omm

ercial Limited Express

Warranty for details. Full copies are available for dow

nload at Clim

ateMaster.com

.This Lim

ited Warranty provides a com

plete statement of C

M’s responsibilities to purchasers of the Products. N

o oral or written statem

ent made by C

M, any person or entity associated w

ith CM

or by any person or entity claiming to be associated w

ith CM

, including but not limited to statem

ents m

ade in sales literature, catalogs, or agreements to purchase or install the Products, is intended to provide an express or im

plied warranty of any kind and does not form

a part of the basis of the bargain. Further, no such statement shall operate to extend, alter or m

odify the scope or terms of this

Limited W

arranty.E

XC

EPT A

S SPEC

IFICA

LLY

SET FOR

TH

HE

RE

IN, T

HE

RE IS N

O E

XPR

ESS W

AR

RA

NT

Y A

S TO A

NY

OF C

M’S PR

OD

UC

TS. C

M M

AK

ES N

O W

AR

RA

NT

Y A

GA

INST L

AT

EN

T DE

FEC

TS, O

F ME

RC

HA

NTA

BILIT

Y O

F TH

E PRO

DU

CT

S OR

OF T

HE PR

OD

UC

TS

FOR

AN

Y PA

RT

ICU

LA

R PU

RPO

SE.

TE

RM

: This Limited W

arranty shall comm

ence on the earliest to occur of the following dates: (i) proof of date of first occupancy; (ii) proof of date of start-up of the Product by a qualified and trained H

VAC contractor; or (iii) six (6) m

onths from the shipm

ent date of the Product from C

M if item

s (i) or (ii) are not available (“W

arranty Inception Date”). The Lim

ited Warranty shall extend as follow

s:C

osts of Repair or R

eplacement of C

overed Product Parts

(1) Ten (10) years from the W

arranty Inception date for air conditioning, heating and/or heat pump units built or sold by C

M (“C

M U

nits”);

(2) Ten (10) years from the W

arranty Inception Date for therm

ostats, auxiliary electric heaters, water storage tanks, and geotherm

al pumping m

odules built or sold by CM

, when installed w

ith CM

Units;

(3) O

ne (1) year from the date of shipm

ent from C

M for any other accessories or parts built or sold by C

M, w

hen installed with C

M U

nits; and

(4) Ninety (90) days from

the date of shipment from

CM

for all repair or replacement parts that are not supplied under this w

arranty.C

osts of Labor to Install R

epaired or Replaced C

overed Product Parts

(1) Five (5) years from the W

arranty Inception Date for C

M U

nits;

(2) Five years from the W

arranty Inception Date for therm

ostats, auxiliary electric heaters, water storage tanks, and geotherm

al pumping m

odules built or sold by CM

, when installed w

ith CM

Units

This Lim

ited Warranty does not cover labor costs for installation of other accessories or parts built or sold by C

M or any repaired or replacem

ent parts that are not supplied under this Limited W

arranty.W

HO

IS CO

VE

RE

D: This Lim

ited Warranty is provided only to the original ow

ner of the one or two fam

ily residential dwelling in w

hich the Products are first installed. This Limited W

arranty is not transferrable. CM

reserves the right to request any documentation necessary in its sole discretion

to determine the date of purchase and occupancy of the residential dw

elling or the date of installation and start-up of the Product(s). For the avoidance of any doubt, this Limited W

arranty shall not extend to, and shall provide no remedies w

hatsoever for, any distributor or installer of the Products.C

LA

IM PR

OC

ESS: To m

ake a claim under this w

arranty, the Product or parts must be returned to C

M in O

klahoma City, O

klahoma, freight prepaid, no later than ninety (90) days after the date of the failure of the part. If C

M determ

ines the Product or part to be defective and covered by this Lim

ited Warranty, C

M w

ill either repair or replace the Product or part and send it to a CM

-recognized distributor, dealer or service organization, F.O.B. C

M, O

klahoma City, O

klahoma, freight prepaid. The Lim

ited Warranty on any Product or part repaired or replaced under this Lim

ited Warranty

extends only through the original warranty period.

WH

AT IS C

OV

ER

ED

: Subject to the Term, this Lim

ited Express Warranty covers the: (i) the cost of repair or replacem

ent of any covered Product or Product parts; and (ii) the cost of labor incurred by CM

authorized service personnel in connection with the installation of a repaired or replaced

covered Product or Product part.If a Product part is not available, C

M w

ill, at its option, provide a free suitable substitute part or provide a credit in the amount of the then factory selling price for a new

suitable substitute part to be used by the claimant tow

ards the retail purchase price of a new C

M product. A

ll labor costs are subject and lim

ited to amounts specifically set forth in the then existing labor allow

ance\ schedule provided by CM

’s Warranty D

epartment. A

ctual labor costs are not covered by this Limited W

arranty to the extent they: (i) exceed the amount allow

ed under the allowance schedule; (ii) are not

specifically provided for in the allowance schedule; (iii) are not perform

ed by CM

authorized service personnel; (iv) are incurred in connection installation of a part not covered by this Limited W

arranty; or (v) are incurred outside the Term.

WH

AT IS N

OT C

OV

ER

ED

: This Limited W

arranty does not cover and does not apply to: (1) air filters, fuses, refrigerant, fluids, oil; (2) Products relocated after initial installation; (3) any portion or component of any system

that is not supplied by CM

, regardless of the cause of the failure of such portion or com

ponent; (4) Products on which the unit identification tags or labels, or rating labels, have been rem

oved or defaced; (5) Products on which paym

ent to CM

, or to the owner’s seller or installing contractor, is in default; (6) Products w

hich have not been installed and maintained by

a qualified and trained HVA

C contractor; (7) Products installed in violation of applicable building codes or regulations including but not limited to w

iring or voltage conditions; (8) Products subjected to accident, misuse, negligence, abuse, fire, flood, freezing, lightning, unauthorized alteration,

misapplication, contam

inated or corrosive air or liquid supply, operation at abnormal air or liquid tem

peratures or flow rates, or opening of the refrigerant circuit by unqualified personnel; (9) m

old, fungus or bacteria damages; (10) corrosion or abrasion of the Product; (11) products supplied by

others; (12) Products that have been operated in a manner contrary to C

M’s printed instructions; (13) Products w

hich have insufficient performance as a result of im

proper system design, sizing or the im

proper application, installation, or use of CM

’s products; (14) electricity or fuel costs, or any increases or unrealized savings in sam

e, for any reason whatsoever; or (15) operating any w

ater storage tanks when they are em

pty or partially empty (i.e. dry firing), at tem

peratures exceeding the maxim

um setting of the operating or high lim

it controls, at pressures greater than those shown on the

rating label, with non-potable w

ater, with alterations or attachm

ents (including energy savings devises) not specifically authorized in writing by C

M, or w

ithout the free circulation of water. C

M m

ay request written docum

entation showing com

pliance with the above lim

itations.In connection w

ith repair or replacement of covered Product parts, C

M is not responsible for: (1) the costs of any fluids, refrigerant or system

components supplied by others, or associated labor to repair or replace the sam

e, which is incurred as a result of repair or replacem

ent of a covered Product part; (2) the costs of labor, refrigerant, m

aterials or service incurred in diagnosis and removal of a covered Product part subject to repair or replacem

ent under this Limited W

arranty; (3) shipping costs incurred in sending a claimed defective part from

the installation site to CM

; (4) shipping costs to return a claim

ed defective part from C

M to the installation site if the part is not covered by this Lim

ited Warranty; (5) rem

oval or disposal costs associated with the repair or replacem

ent of covered Product Parts; or (6) the costs of normal m

aintenance.O

TH

ER

WA

RR

AN

TY

LIM

ITAT

ION

: This Limited W

arranty is given in lieu of all other warranties express or im

plied, in law or in fact. If, notw

ithstanding the disclaimers contained herein, it is determ

ined that other warranties apply, any such w

arranty, including without lim

itation any express w

arranties or any implied w

arranties of fitness for particular purpose and merchantability, shall be lim

ited in time to the Term

of this Limited W

arrantyL

IMITA

TIO

N O

F RE

ME

DIE

S: In the event of a breach of the Limited W

arranty, a claimant’s rem

edies will be lim

ited to repair or replacement of a part or unit, or to furnish a new

or rebuilt part or unit in exchange for the part or unit which has failed. If after w

ritten notice to CM

’s factory in O

klahoma City, O

klahoma of each defect, m

alfunction or other failure, and a reasonable number of attem

pts by CM

to correct the defect, malfunction or other failure, the rem

edy fails of its essential purpose, CM

shall refund the purchase price paid to CM

in exchange for the return of the sold good(s). Said refund shall be the m

aximum

liability of CM

. THIS R

EMED

Y IS TH

E SOLE A

ND

EXC

LUSIV

E REM

EDY

OF TH

E BUY

ER OR TH

EIR PURC

HA

SER AG

AIN

ST CM

FOR A

NY

AC

TION

FOR BR

EAC

H O

F CO

NTR

AC

T, BREA

CH

OF A

NY

WA

RR

AN

TY, PATEN

T IN

FRIN

GEM

ENT, O

R FOR C

M’S N

EGLIG

ENC

E OR IN

STRIC

T LIABILITY. N

O A

CTIO

N A

RISIN

G O

UT O

F AN

Y C

LAIM

ED BR

EAC

H O

F THIS LIM

ITED W

AR

RA

NTY

MA

Y BE BRO

UG

HT M

OR

E THA

N O

NE (1) Y

EAR A

FTER THE CA

USE O

F AC

TION

HA

S AR

ISEN.

LIM

ITAT

ION

OF L

IABIL

ITY: C

M shall have no liability for any dam

ages if CM

’s performance is delayed for any reason or is prevented to any extent by any event such as, but not lim

ited to: any war, civil unrest, governm

ent restrictions or restraints, strikes, or work stoppages, fire, flood,

accident, shortages of transportation, fuel, material, or labor, acts of G

od or any other reason beyond the sole control of CM

. C

M EX

PRESSLY

DISC

LAIM

S AN

D EX

CLU

DES A

NY

LIABILITY

FOR C

ON

SEQU

ENTIA

L, INC

IDEN

TAL, SPEC

IAL A

ND

/OR PU

NITIV

E DA

MA

GES BA

SED O

N A

NY

THEO

RY IN

CO

NTR

AC

T, BREA

CH

OF A

NY

EXPR

ESS OR IM

PLIED W

AR

RA

NTY, PA

TENT

INFR

ING

EMEN

T, OR IN

TORT, W

HETH

ER FOR C

M’s N

EGLIG

ENC

E OR A

S STRIC

T LIABILITY

AN

D R

EGA

RD

LESS OF W

HETH

ER CM

IS AD

VISED

OF TH

E POSSIBILITY

OF SU

CH

DA

MA

GES.

OBTA

ININ

G W

AR

RA

NT

Y PE

RFO

RM

AN

CE: N

ormally, the dealer or service organization w

ho installed the products will provide w

arranty performance for the ow

ner. Should the installer be unavailable, contact any CM

recognized distributor, dealer or service organization. If assistance is required in obtaining w

arranty performance, w

rite or call:C

limate M

aster, Inc. • Custom

er Service • 7300 SW 44th Street • O

klahoma City, O

klahoma 73179 • (405) 745-6000 • e-service@

climatem

aster.comN

OTE: Som

e states or Canadian provinces do not allow

the exclusion or limitation of im

plied warranties or the lim

itation of incidental or consequential damages for certain products supplied to consum

ers, or the limitation of liability for personal injury, so the above lim

itations and exclusions m

ay be limited in their application to you. W

hen the implied w

arranties are not allowed to be excluded in their entirety, they w

ill be limited to the duration of the applicable w

ritten warranty. This w

arranty gives you specific legal rights, which m

ay vary depending on local law. IF AN

Y PRO

DU

CT

TO W

HIC

H TH

IS LIMITED

WA

RR

AN

TY A

PPLIES IS DETER

MIN

ED TO

BE A “C

ON

SUM

ER PROD

UC

T” UN

DER TH

E MA

GN

USO

N-M

OSS W

AR

RA

NTY

AC

T (15 U.S.C

.A. §2301, ET SEQ

.) OR O

THER A

PPLICABLE LAW

, THE FO

REG

OIN

G D

ISCLA

IMER O

F IMPLIED

W

AR

RA

NTIES SH

ALL N

OT A

PPLY TO

YO

U, A

ND

ALL IM

PLIED W

AR

RA

NTIES O

N TH

IS PROD

UC

T, INC

LUD

ING

WA

RR

AN

TIES OF M

ERCH

AN

TABILITY

AN

D FITN

ESS FOR TH

E PARTIC

ULA

R PUR

POSE, SH

ALL A

PPLY FO

R THE SA

ME TER

M SET FO

RTH A

BO

VE

(ON

E YEA

R) AS PRO

VID

ED U

ND

ER APPLICA

BLE LAW. The portions of this Lim

ited Warranty and lim

itation of liability shall be considered fully severable, and all portions which are not disallow

ed by applicable law shall rem

ain in full force and effect. This w

arranty gives you specific legal rights, and you may also have other rights w

hich vary from state to state and from

Canadian province to C

anadian province. Refer to your local laws for your specific rights under this Lim

ited Warranty.

Please refer to the CM

Installation, Operation and M

aintenance Manual for operating and m

aintenance instructions.R

ev.: 3/20Part N

o.: RP851

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

32 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 33: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Notes

33

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 34: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Notes

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

34 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Page 35: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Notes

35

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

c l i m a t e m a s t e r. c o m

Page 36: Tranquility Brazed Plate Water-to-Water Table of Contents ......Tranquility ® Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series Residential EarthPure ® Water-to-Water

Revision History

97B0099N01

ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warran-ties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products.

Engineered and Assembled in the USA

© ClimateMaster, Inc. 2015

*97B0099N01*

7300 S.W. 44th StreetOklahoma City, OK 73179

Phone: 405-745-6000Fax: 405-745-6058climatemaster.com

R e s i d e n t i a l Tr a n q u i l i t y Wa t e r- t o - Wa t e r ( T B W ) S e r i e s - H F C - 4 1 0 AR e v i s e d : A u g u s t 2 1 , 2 0 1 8

36 G e o t h e r m a l H e a t i n g a n d C o o l i n g

Date: Item: Action:

August 21, 2018 Page 4 Added Warning

January 26, 2017 Page 14 Add Caption

January 4, 2016 Pages 6, 10, 25,36 Edits to Strainer chart, update to new AHRI logo

November 20, 2015 All First Published