Date post: | 15-Oct-2015 |
Category: |
Documents |
Upload: | adiel-camarillo-narvaez |
View: | 162 times |
Download: | 9 times |
of 47
5/26/2018 Transformer Failure Modes 20130820
1/47
ABB Inc. 2013
Craig L. Stiegemeier; ABB TRES Transformer Remanufacturing & Engineering Services; August 20, 2013
ABB Red TIE Series - PomonaTransformer failure modes
5/26/2018 Transformer Failure Modes 20130820
2/47
ABB Inc. 2013
Slide 2
Transformer Failure ModesAgenda
Definition of a transformer
Primary Causes of Transformer Failure
Balancing the three leg stool Thermal degradation
Dielectric withstand
Mechanical performance
Causes of insulation system degradation
Identification of failure vulnerabilities including keytransformer components
5/26/2018 Transformer Failure Modes 20130820
3/47
ABB Inc. 2013
Slide 3
Transformer Failure ModesDefinition of a transformer
IEC 60076-1
A Static piece of apparatus with two or more windings
which, by electromagnetic induction, transformers asystem of alternating voltage and current into another
system of voltage and current usually of different values
and at the same frequency for the purpose of
transmitting electrical power.
IEEE C57.12.80
A static device consisting of a winding, or two or more
coupled windings with or without a magnetic core forintroducing mutual coupling between electrical circuits.
5/26/2018 Transformer Failure Modes 20130820
4/47
ABB Inc. 2013
Slide 4
Transformer Failure ModesFundamental laws of a transformer
Maxwell 2nd Law (No 2 - induction law )
Ui = - N d / dt or converted to
Ui = 4.44 f N B AFe or U1 / U2 = N1 / N2
where:
Ui r.m.s value of the induced voltage [ v ]
f frequency [ Hz ]
N number of turns
B peak value of the magnetic induction [ T ]
AFe section of the iron core [ m2 ]
5/26/2018 Transformer Failure Modes 20130820
5/47
ABB Inc. 2013
Slide 5
Transformer Failure ModesGeneral fundamental of a transformer
HV Winding
LV Winding
Electrical Voltage applied to
the HV winding
Magnetizes the Core
And the voltage is inducedinto the LV winding
5/26/2018 Transformer Failure Modes 20130820
6/47
ABB Inc. 2013
Slide 6
Transformer Failure ModesMagnetic Coupling between coils and secondary EMF
5/26/2018 Transformer Failure Modes 20130820
7/47
Transformer Failure ModesCore Form Transformer
ABB Inc. 2013
Slide 7
5/26/2018 Transformer Failure Modes 20130820
8/47
ABB Inc. 2013
Slide 8
Transformer Failure ModesStresses Acting on Power Transformers
Mechanical Stresses
Between conductors, leads and windings due to
overcurrents or fault currents caused by short circuits andinrush currents
Thermal Stresses
Due to local overheating, overload currents and leakagefluxes when loading above nameplate ratings; malfunction
of cooling equipment
Dielectric Stresses
Due to system overvoltages, transient impulse conditions
or internal resonance of windings
5/26/2018 Transformer Failure Modes 20130820
9/47
ABB Inc. 2013
Slide 9
The fault current is
governed by:
Open-circuit voltage
Source impedance
Instant of fault onset
Displacement of current
Transformer Failure ModesMechanical Stresses in Power Transformers
In the case of externalshort-circuits, the firstpeak of the fault currentthrough the transformer
will increase to amultiple of the ratedcurrent
5/26/2018 Transformer Failure Modes 20130820
10/47
Transformer Failure ModesMagnetic field lines
ABB Inc. 2013
Slide 10
5/26/2018 Transformer Failure Modes 20130820
11/47
ABB Inc. 2013
Slide 11
Transformer Failure ModesMechanical Stresses in Power Transformers
A short circuit gives rise to:
Mechanical forces
Temperature rise The transformer must be designed so
that permanent damage does not takeplace
Electromagnetic forces tend to increase
the volume of high flux Inner winding to reduced radius
Outer winding towards increasedradius
Winding height reduction
5/26/2018 Transformer Failure Modes 20130820
12/47
ABB Inc. 2013
Slide 12
Inner
winding
Outer
winding
Radial forces inwards
compressive stress
Radial forces outwards
tensile stress
Fmean
Transformer Failure ModesMechanical Stresses in Power TransformersEffect of the radial forces on windings
5/26/2018 Transformer Failure Modes 20130820
13/47
ABB Inc. 2013
Slide 13
Inner
winding
Outer
winding
Transformer Failure ModesMechanical Stresses in Power Transformers
Radial forces result in:
Buckling for inner windings
Increased radius for outer windings Spiraling of end turns in helical winding
5/26/2018 Transformer Failure Modes 20130820
14/47
ABB Inc. 2013
Slide 14
Axial short circuit forces accumulate towards winding mid-height
The radial
component of
the leakage
flux createsforces in axial
direction
Transformer Failure ModesMechanical Stresses in Power TransformersEffect of the axial forces on windings
5/26/2018 Transformer Failure Modes 20130820
15/47
ABB Inc. 2013
Slide 15
B B Fax Fax
B B Fax Fax
Axial imbalance
will create extraaxial forces
The forces tend
to increase the
imbalance
Transformer Failure ModesMechanical Stresses in Power Transformers Axial
5/26/2018 Transformer Failure Modes 20130820
16/47
ABB Inc. 2013
Slide 16
Failure mode Spiraling:
Characteristic failure mode for
inner and outer winding
Failure mode Buckling:
Characteristic failure
mode for inner winding
Transformer Failure ModesMechanical Stresses in Power Transformers - Radial
5/26/2018 Transformer Failure Modes 20130820
17/47
ABB Inc. 2013
Slide 17
Transformer Failure ModesMechanical Stresses in Power Transformers
Two examples showing buckling of inner windings
5/26/2018 Transformer Failure Modes 20130820
18/47
Transformer Failure ModesMechanical Stresses in Power Transformers
Another example of buckling of the inner windings
ABB Inc. 2013
Slide 18
5/26/2018 Transformer Failure Modes 20130820
19/47
ABB Inc. 2013
Slide 19
Axial force failure modes:
Collapse of winding end support
Tilting of winding conductors
Telescoping of windings
Bending of cables between spacers Damage of conductor insulation
Transformer Failure ModesMechanical Stresses in Power Transformers
5/26/2018 Transformer Failure Modes 20130820
20/47
ABB Inc. 2013
Slide 20
Failure mode
Conductor tilting
Failure mode
Bending of cables
Failure mode
Collapse of end support
Transformer Failure ModesMechanical Stresses in Power Transformers
5/26/2018 Transformer Failure Modes 20130820
21/47
ABB Inc. 2013
Slide 21
Transformer Failure ModesMechanical Stresses in Power Transformers
Axial forces cause:
Mechanical withstand of insulation material
Risk for tilting
5/26/2018 Transformer Failure Modes 20130820
22/47
Transformer Failure ModesMechanical Stresses in Power Transformers
Example for axial forces
ABB Inc. 2013
Slide 22
5/26/2018 Transformer Failure Modes 20130820
23/47
ABB Inc. 2013
Slide 23
Transformer Failure ModesShort-Circuit Failure
Unit Auxiliary Test Transformer FailureInternal High Speed Film Camera Footage
ABB Inc.
Originally taken by The General Electric Company atPittsfield, Massachusetts
5/26/2018 Transformer Failure Modes 20130820
24/47
ABB Inc. 2013 - Slide 24
Movies should be screened in thegrey area as featured here, sizeproportion 4:3. No titles should beused.
5/26/2018 Transformer Failure Modes 20130820
25/47
ABB Inc. 2013
Slide 25
Transformer Failure ModesRisk: Short Circuit Forces & Stresses
Through faults are often the cause oftransformer failures
Many older designs have insufficient
margin for todays fault currents Loose coils due to aging can cause
failures
Normal aging can cause brittle
insulation and increased failures Even brief overloading may cause
significant aging
Oxygen in the oil can double theaging rate
Moisture in the insulation increasesaging rate 2-5 times depending onthe amount of moisture
5/26/2018 Transformer Failure Modes 20130820
26/47
ABB Inc. 2013
Slide 26
Transformer Failure ModesMechanical Risk: Short Circuit Forces & Stresses
Figure 3. Results of the Short-Circuit Strength Design Analysis used in a Life Assessment Study
HV Radial
(Hoop)
HV Axial
(tipping or
crushing)
LV Radial
(Buckling)
LV Axial
(tipping or
crushing)
LTC
Winding
Radial
(Buckling)
LTC
Winding
Axial
(tipping)
Design #1
Design #2
Design #3
Design #4
Little Risk of Failure
Slight Risk of Failure
High Risk of FailureDesi
gnMargin
5/26/2018 Transformer Failure Modes 20130820
27/47
ABB Inc. 2013
Slide 27
Transformer Failure ModesThermal Stresses in Power Transformers
Loading is primarily limited by highest permissible temperatures inthe transformer, especially within the windings
Temperature limits are based on:
Expected lifetime The risk for oil vaporization
Permissible temperatures are generally expressed as temperaturerises above ambient
Ambient temperature is in turn defined by current standards 24 hour ambient temperature average 30 C
Maximum ambient 40 C
In accordance to Standards:
Winding temperature rise 65 K Top oil temperature rise 65 K
Hot spot temperature rise 80 K
5/26/2018 Transformer Failure Modes 20130820
28/47
ABB Inc. 2013
Slide 28
Winding hot spot
Top oil rise
hot spot factor
Winding average rise
Copper over winding oil gradient
AmbientWinding
Temperature
Bottom oil
Copper over tank oil gradient
Transformer Failure ModesWinding Temperature Rise and HS Calculation
5/26/2018 Transformer Failure Modes 20130820
29/47
ABB Inc. 2013
Slide 29
Transformer Failure ModesThermal Risk: Intensive aging
T f F il M d
5/26/2018 Transformer Failure Modes 20130820
30/47
ABB Inc. 2013
Slide 30
Transformer Failure ModesThermal Risk: Intensive aging
T f F il M d
5/26/2018 Transformer Failure Modes 20130820
31/47
ABB Inc. 2013
Slide 31
Transformer Failure ModesDegree of Polymerization - DP
Degree of polymerization is a measure of the number ofintact chains in a cellulose fiber. It provides an indication ofthe ability of the transformer insulation to withstand
mechanical force (due to through-faults, etc).Cellulose Fiber Chain
T f F il M d
5/26/2018 Transformer Failure Modes 20130820
32/47
ABB Inc. 2013
Slide 32
Transformer Failure ModesFactors affecting DP and Measurement Method
The DP of the insulation is affected by the followingconditions:
Moisture content
Acidity of the oil
Oxygen content
Temperature
The DP is measured by viscosity measurements according
an ASTM method after dissolving the paper samples incupriethylene diamine solvent.
Paper samples must be taken from enough differentareas in a transformer in order to get a profile ofdeterioration of the cellulose
When combined with detailed design knowledge,measurements in one area of the transformer can giveinformation on the condition of paper in inaccessibleareas of the windings.
T f F il M d
5/26/2018 Transformer Failure Modes 20130820
33/47
ABB Inc. 2013
Slide 33
0.1
1.0
10.0
100.0
1000.0
10000.0
50 60 70 80 90 100 110 120 130 140 150
Temperature [oC]
L
ife
E
xp
ect
an
cy
(years)
Dry & Clean (Insuldur)
Acidic Oil (Insuldur)
1% Water Content (Insuldur)
3-4% Water Content (Insuldur)
Transformer Failure ModesLife Expectancy Based on DP and Other Factors
It is assumed that the DP of transformer insulation is approx. 1,000 at the start of life and approx.200 at the end of life. This graph shows the expected life of thermally upgraded insulation(Insuldur) under various conditions:
For long insulation life expectancy, it is important to keep the insulation dry, keep acidity
and oxygen concentration of oil low and provide good cooling for insulation
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
34/47
ABB Inc. 2013
Slide 34
Transformer Failure ModesThermal Stresses in Power Transformers
Life Expectancy Based on DP and Other Factors
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
35/47
ABB Inc. 2013
Slide 35
Transformer Failure ModesDielectric Stresses in Power Transformers
Overvoltage integrity
Overvoltages can be divided into two classes:
Continuous
Transitory
Continuous overvoltage is related to the core and itsmagnetization (normal 50Hz or 60 Hz stresses)
Transitory overvoltage refers to intermittent stressesplaced on the insulation system, usually at much higherlevels than the power frequency stresses
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
36/47
ABB Inc. 2013
Slide 36
Lightning and switching impulse
surges are called Transients
because their duration is short. The frequencies are much higher
than the power frequency (60 Hz
here) operation frequency.
Transient calculations are used to
find the time dependent distribution
of transient voltages, applied on the
line terminals, over the windings.
Transformer Failure ModesDielectric Stresses in Power Transformers
Transient Voltages
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
37/47
ABB Inc. 2013
Slide 37
Winding
Win-
dinglength
Voltage
Winding oscillation
Transformer Failure ModesDielectric Stresses in Power Transformers
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
38/47
ABB Inc. 2013
Slide 38
2 D field plotscan be used to
check thedesign of themain insulation
2 D Field Plot
Transformer Failure ModesDielectric stresses - Main insulation design
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
39/47
Transformer Failure ModesDielectric stresses failure - Main insulation design
ABB Inc. 2013
Slide 39
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
40/47
ABB Inc. 2013
Slide 40
Field distribution over the barriers andHV-LV windings
CAD-model
FLC evaluation
Transformer Failure ModesAnalysis of Bushing Failure
525 kV unit assumed bushing failure
Simulation showed electric stress was greatest on the paperinsulation around the shield ring
Used simulation to redesign insulation barriers
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
41/47
ABB Inc. 2013
Slide 41
Transformer Failure ModesWhat we know
Top transformer failures (78%) (from Doble):
43% winding insulation
19% bushings
16% tap changers
Other areas of concern:
Pollution, dust & debris affecting bushings &cooling systems
Cooling System inefficiency
COPS Tank elevation
Specific issues:
Streaming Electrification
Nitrogen Gas Bubble Evolution
Blocking / GE Mark II Clamping
Shell Form Rewedging
GE Type U Bushings
Transformer Failure Modes
5/26/2018 Transformer Failure Modes 20130820
42/47
Transformer Failure ModesDe-energized tap changer
ABB Inc. 2013
Slide 42
Transformer Failure Modes, grounding of the active part
5/26/2018 Transformer Failure Modes 20130820
43/47
Transformer Failure Modes, grounding of the active partHot metals gassing
ABB Inc. 2013
Slide 43
Core Clamp grounding point
Core clamp grounding totank
Transformer Failure Modes - Thermal Scan Value
5/26/2018 Transformer Failure Modes 20130820
44/47
Loose Bushing Terminal Connection
When there is a loose connection at the terminal from thebushing to the bus work, it will lead to overheating of thebushing top terminal when under load.
The thermograph will show the bushing terminal as hot, whilethe body of the porcelain will show normal temperatures.
ABB Inc. 2013
Slide 44
Transformer Failure Modes - Thermal Scan Value
5/26/2018 Transformer Failure Modes 20130820
45/47
Blocked Oil Flow in Radiators
In case of a malfunction that stops or restricts the flow of oilthrough a radiator, this will show up on an infrared scan.
The image will reveal dim areas where the oil flow is restricted
and brighter areas where normal oil flow is taking place
ABB Inc. 2013
Slide 45
Transformer Failure Modes / Diagnostic Techniques
5/26/2018 Transformer Failure Modes 20130820
46/47
ABB Inc. 2013
Slide 46
g qHighly Effective On-line Actions are Best
PROBLEMS DIAGNOSTIC TECHNIQUESSERVICE CONDITIONS
OF THE EQUIPMENT[1]
PROVEN
EFFECTIVENESS[2]
MECHANICAL
1. Excitation Current2. Low-voltage impulse3. Frequency response analysis4. Leakage inductance measurement5. Capacitance
OFF-SOFF-SOFF-SOFF-SOFF-S
MLH
M/HH
THERMAL
GAS-IN-OIL ANALYSIS6. Gas chromatography7. Equivalent Hydrogen method
ONON
HM
OIL-PAPER DETERIORATION8. Liquid chromatography-DP method9. Furan Analysis
ONON
M/HM/H
HOTSPOT DETECTION10. Invasive sensors11. Infrared thermography
ONON
LH
DIELECTRIC
OIL ANALYSIS12. Moisture, electric strength, resistivity, etc.
ON M
13. Turns ratio OFF-S L
PD MEASUREMENT14. Ultrasonic method15. Electr ical method
ONON
M/HM/H
16. Power Factor and Capacitance17. Dielectric Frequency Response
OFF-SOFF-S
HH
ABB Service Handbook for Transformers, Table 3-1, Page 72
[1] OFF-S = equipment out of service at site, OFF-L = equipment out of service in laboratory, ON = equipment in service[2] H=High, M=Medium, L=Low
5/26/2018 Transformer Failure Modes 20130820
47/47