+ All Categories
Home > Documents > Transient and Lightning Protection for the Water...

Transient and Lightning Protection for the Water...

Date post: 29-Jun-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
50
5 th ISA Water/Wastewater Automatic Controls Division Symposium (WWAC) August 3-5, Orlando, Florida 1 Mike Nager Phoenix Contact [email protected] Transient and Lightning Protection for the Water Industries
Transcript
Page 1: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium (WWAC)

August 3-5, Orlando, Florida 1

Mike NagerPhoenix [email protected]

Transient and Lightning Protection for the Water Industries

Page 2: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Agenda

• Who are we?• Why protect equipment from

transients?• Likelihood of lightning• Why are water plants so susceptible?• Who is at the greatest risk?• What can be done to prevent damage?

Page 3: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Presenter

• Mike Nager• BS Electronics Engineering• Senior Member ISA, IEEE• Career with industrial control

companies• Published author• Work in Phoenix Contact’s North

American Headquarters responsible for Industry Management

Page 4: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Our surge generator: 200 kA; 200 kV

Page 5: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surge generator

Page 6: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

TT 1654 D 12.04.06

Desktop surge generator: 10 kA, 6 kV

Page 7: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surge suppression in water treatment plants

• Why protect equipment from transients?• Why are plants so susceptible?• Who is at the greatest risk?• What can be done to prevent damage?

Page 8: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Why protect equipment from transients?

• Equipment is expensive• Equipment is sensitive• Labor is expensive• Public demands no mistakes!• A multitude of ROI and non-ROI

drivers

Page 9: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

How sensitive is your equipment?

Page 10: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Transient insurance statistics

Water5.80%

Storm, Flooding, ...0.10%

Misc.2.90%

Surge Voltage22.30%

Human30.80%

Fire5.90%

Technical Failure15.50%

Burglary16,70%

Source: WÜBA Versicherungs-AG, Niederlassung Frankfurt, wd 08. April 2002

Page 11: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Lightning damage (log chart)

1,000,000

10,000

100

060 65 70 75 80 85 90

80

24,755

931

158

indirect strokes

direct strokes

Source: Gugenbauer,A./ Activity report, damage statistics, Linz Fire protection Authority for Upper Austria

Page 12: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Why is this plant at risk?

Page 13: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surface discharge

Page 14: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Why does distance matter?

• Indirect lightning• Lightning remains at

the earth’s surface (skin effect).

• Voltage between front and back hooves kills the cow

7kV 10kV

Page 15: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Why does distance matter?

Page 16: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Flash density

1 sq. km = 247.1 acres

Page 17: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Activated sludge basinCould there be a voltage difference?

Page 18: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Tower height and lightning strikes

From Estimated number of lightning strikes per year based on the number of thunderstorm days in your area and the height of your antenna. Based on information from Living with Lightning, Seminar Notes #ECP-826B Version F, GE Mobile Radio Technical Training, © GE 1985.

Page 19: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surge current laboratory

10/350 10/350 µµss

8/20 8/20 µµss

810 20 t

µs

1,0

0,5

0,00 100 200 300 350

8/208/20µµss "IEEE Scenario I": "IEEE Scenario I": LowLow--energy energy indirecindirect lightning striket lightning strikeSPD:SPD: single 8/20single 8/20µµs varistors varistor

10/35010/350µµss "IEEE Scenario II": "IEEE Scenario II": HighHigh--energy energy direcdirect lightning striket lightning strikeSPD:SPD: 8/208/20µµs varistors in parallel ors varistors in parallel or

10/35010/350µµs spark gaps spark gap

Page 20: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Test house

Source: University of Florida

Lightning current distribution Testing at Camp Blanding, FL

Page 21: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Source: University of Florida

Lightning current distribution Testing at Camp Blanding, FL

Page 22: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Source: University of Florida

Lightning current distribution Testing at Camp Blanding, FL / Findings

Page 23: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Bottom line?

• All outdoor equipment is high risk– Lift stations, motors, tanks, transmitters, sensors

• Also all I/O lines that leave the building– Instrumentation, control lines

Page 24: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

How do I protect equipment?

Now what?

Page 25: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surge suppression basics

A

B

S2 S3

S1

Page 26: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Lightning is load-independent

TT 1681 D 07.06.06

• Lightning currents are like fright trains – you can’t stop them!

• Make sure that you get out of their way!

• Lightning currents have to be redirected so that nobody gets hurt! That’s what lightning protection is about.

Page 27: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Protect all paths!

Power supply

DataTelecommunication

Antenna

Measurement and control

PLC

Page 28: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

“Zone” defense!

A B C

LowEnergy

MediumEnergy

HighEnergy

A Outlets and long branch circuitsAll outlets at more than 30 feet fromCategory BAll outlets at more than 60 feet from Category C

BFeeders and short branch circuitsDistribution panel devicesBus and feeder industrial plantsHeavy appliance outlets with “short”connections to service entranceLighting systems in large buildings

COutside and service entranceService drop from pole to buildingRun between meter and panelOverhead line to detached buildingUnderground line to well pump

Page 29: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Rated impulse voltageof the insulation material

Lightning-current arrester

Main distribution 6.0 kVSubdistribution 4.0 kV

End device 2.5 kV

Special end devices 1.5 kV

L

PEN

kWh

TT 0035 D 20.01.00

Surge-voltage arrester Device protection

Insulation coordination acc. to DIN VDE 0110 Part 1 and IEC 60664-1 for 230/400 V AC and 277/480 V AC

Page 30: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Multi-stage protection

Lightning-currentarrester

EN Type 1IEC Class I

Surge-voltagearrester

EN Type 2IEC Class II

DeviceprotectionEN Type 3

IEC Class III

Page 31: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Requirements• High surge currents from lightning• Long duration surges• Need automatic turn-off• Need failure indication• Sturdy construction

Lightning protection: Service entrance or outdoor equipment

Page 32: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Paralled MOVs or spark-gap technologies

Lightning protection for AC power

Page 33: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Triggered arc gap

Ignition electrode

Spark hornsBaffle plate

Arc-guide plates Quenching

plates

Ignition electronics

TT 0743 D 16.02.07

Page 34: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Lightning protection at lift station

Page 35: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Arc gap applications

Page 36: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Parallel MOV ‘NEMA’ style

Installed adjacent to an electrical panel or directly onto electrical equipment.

Compliant with UL 1449 3rd Edition.

Safety lockouts available

Page 37: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Can be mounted to any panel…

Page 38: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

How about I/O systems?

• Must be robust – Protect against surges with 1000’s of amps not 100’s!

• Need to protect systems on both sides – one surge arrestor cannot protect both transmitter and receiver

• Need compact designs

• Easy serviceability

Page 39: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

How about I/O systems?

Page 40: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Multi-stage transient absorption system

Incomingline transient

Inductorsecond stage

Groundingsystem

Suppressor diode

Metal oxide

varistor

Gasdischarge

arrestor

Inductor first stage

Page 41: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Transmitter protection panel installation

Standard installation

Control room

TT 1721 D 05.02.07

Page 42: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Transmitter protection inline installation

Control room

TT 1721 D 05.02.07

Page 43: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Surge protection inside control room

Examples:

PT 100Digital input/outputS485 etc.0/4 ... 20 mA

PLUGTRAB PT...

TT 1039 D 258.04.06

Page 44: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

power supply

For the bus system

For the

with PLUGTRAB PT...

TT 1723 D 05.02.07

Surge protection for instrumentation

Page 45: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Protection of I/O in control cabinet

Page 46: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Conclusion: Protect against every surge path!

ElectronicsData

CommunicationsAnalog/Digital

Lines

Power Supply

Circle of Protection

Page 47: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Appendix

• Grounding methodology• Florida lightning testing facility

Page 48: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Grounding of SPDs Example I: Wrong

Simplifiedcircuit diagram

IN OUT

Electronics1

2

3

4

TT 061 D 18.04.00

ElectronicsUE

L2 UL2 = 0V

IST

LI

UGDT

ULI

Page 49: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Grounding Example 2: Better

IN OUT

Electronics

UGDT

ULI

UE

L2 UL2

IST

LI

1

2

3

4

L3

UL3

Electronics

TT 062 D 18.04.00

Simplifiedcircuit diagram

Page 50: Transient and Lightning Protection for the Water Industries2015.isawwsymposium.com/wp-content/uploads/2012/01/Nager_Lig… · 5th ISA Water/Wastewater Automatic Controls Division

5th ISA Water/Wastewater Automatic Controls Division Symposium, August 3-5, 2010, Orlando FL

Grounding Example 3: Best practice

IN OUT

ElectronicsUE

IST

1

2

3

4

LI

UL3 = 0V

UGDT

ULI

Electronics

TT 063 D 18.04.00

Simplifiedcircuit diagram


Recommended